Chiller Midea PDF
Chiller Midea PDF
Chiller Midea PDF
Contents
I. Product ......................................................................................................................... 3
1. Nomenclature ...........................................................................................................................3
2. Product Line Up .......................................................................................................................3
3. External Appearance………………………………………………………………………………… 4
4. Features…………………………………………………………………………………………………5
5. Specification .............................................................................................................................8
6. Operating Range ....................................................................................................................10
7. Outline Dimension .................................................................................................................11
8. Water Flow – Water Drop Pressure Curve ...........................................................................13
II. Installation.................................................................................................................. 15
1. Installation Dimensions& Vibration Isolators………………………………………………… 15
2. Installation Foundation ..........................................................................................................20
3. Installation Spaces.................................................................................................................20
4. Installation of Water Pipeline System ..................................................................................21
III. Electrical Data ............................................................................................................ 26
1. Field Wiring.............................................................................................................................26
2. Electric parameter table ........................................................................................................30
3. Control Flow Chart .................................................................................................................31
4. Control Screen Operation .....................................................................................................33
5. Control Screen Menu Structure ............................................................................................48
6. Introduction of Major Electric Components.........................................................................49
IV. Maintenance and Commissioning ............................................................................ 51
1. Commissioning ......................................................................................................................51
2. Maintenance ...........................................................................................................................61
V. Control Logic ............................................................................................................. 77
1. Start (Stop) Logic ...................................................................................................................77
2. Energy Adjustment Logic ......................................................................................................83
3. Fan Control Logic ..................................................................................................................86
4. Oil heater control Logic .........................................................................................................86
5. EXV operation& wiring ..........................................................................................................87
Appendix 1: R134a saturation temperature - pressure corresponding tables………90
Appendix 2: System working principle map………………………………………………91
Appendix 3: Capacity table…………………………………………………………………...95
Appendix 4: Electrical circuit principle reference map…………………………….….. 99
2
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
I. Product
1. Nomenclature
LS B LG W 380 /C
W: air-cooled condenser
B: semi-hermetic compressor
2. Product Line Up
Model Power Supply Cooling Capacity (kW) Quantity of Compressor Quantity of Fan
3
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
3. External Appearance
LSBLGW1420/C module
4
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
4. Features
Environmental care
R134a refrigerant
Refrigerant of the HFC group with zero ozone depletion potential.
It is environmentally safe and does not have a phase-out date.
5
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Low-noise fans, made of a composite material are now even quieter and do not generate
intrusive low-frequency noise. Rigid fan mounting avoids start-up noise.
Multiple direct drive dynamically balanced propeller fans operate at low tip speeds for maximum
efficiency and minimum noise and vibration. A heavy-gauge vinyl-coated fan guard protects each
fan.
Outstanding reliability
Full factory testing of all the units ensures a trouble free start-up. Extensive test makes certain that
each safety and operating control is properly adjusted, and operates correctly. The unit has passed
full factory test before being delivered to ensure the reliable working on the site.
Transport simulation test in the laboratory on a vibrating table.
The unit can be placed in service after being connected with power supply and water supply during
field installation .Standard flange connection and wire mesh to the electrical panel make the
installation easy and simple.
The sensors related to control and other assemblies are equipped by factory and strictly tested.
Intelligent control:The unit is controlled by micro-controller(PLC) and has the automatic control
functions of fault diagnosis, energy management and anti-freezing monitoring, which ensures the
high-efficiency operation of the unit, and more convenient in use. The unit with RS485 open protocol
communication interface. BMS compatible. The startup and shutdown of each unit is controlled by
the host computer, reducing the running cost to the lowest.
Complete and safe control system: All electrically control elements are designed and selected with
stable quality and reliable function; The unit designed with multiple security measures ensure the
safe and reliable running witch including high and low pressure protection, oil pressure difference
6
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
protection, anti-freezing protection, water flow protection, power protection, overload protection
etc.
The units adopt modular design, which can makes more unit connect together. The unit can
combine 8 modules. Cooling capacity can be within 360kW-7200kW, meanwhile every separate
module can operate as master, also each module can be a slave unit with modules combination,
more convenient for design and installation.
7
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
5. Specification
Single Compressor:
Note:
2) The applicable ambient temperature range of R134a air-cooled screw units is 15℃ ~ 43℃。
8
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Dual Compressors:
Type M shape Heat exchanger, High efficient exchanger tube + aluminum fins
Note:
1) Nominal cooling capacities are based on the following conditions:
2) The applicable ambient temperature range of R134a air-cooled screw units is 15℃ ~ 43℃。
9
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6. Operating Range
10
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
7. Outline Dimension
(1) LSBLGW380/C unit (mm)
11
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
12
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
14
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
II. Installation
15
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
(1) LSBLGW380/C unit (mm)
C ontrol box
F ound ation
U nit bo ttom
F o und ation
b olt M 14
C ontrol b ox
F oundation
U nit bottom
F oundation
bolt M 14
16
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
(3) LSBLGW600/C unit (mm)
C o n tro l b o x
F o u n d a tio n
U n it b o tto m
F o u n d a tio n
b o lt M 1 4
C o n tro l b o x
F o u n d a tio n
U n it b o tto m
F o u n d a tio n
b o lt M 1 4
17
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
(5) LSBLGW880/C unit (mm)
Control box
Unit bottom
Foundation
Foundation bolt M14
Control box
Unit bottom
Foundation
Foundation bolt M14
18
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
(7) LSBLGW1200/C unit (mm)
Control box
Unit bottom
Foundation
Foundation bolt M14
Control box
Unit bottom
Foundation
Foundation bolt M14
19
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2. Installation Foundation
1) The installation foundation shall be designed by professionals according to the site conditions.
2) The installation foundation of the unit must be of a cement or steel structure, and shall bear the
operating weight of the machine, and this face must be horizontal.
3) Please refer to the Diagram for Installation Foundation of Unit, place the steel plate and
anti-vibration bush on the foundation accurately, and execute secondary grouting after
installing the unit and foundation bolts together. The foundation bolts are generally 60 mm
higher than the installation surface .
Bolt
Unit Base (Channel Steel) Installation
Surface Nut
Drain Groove
Washer
Cement Mortar Link Kit
(Secondary Grouting) Anti-vibration
Bush
Steel Plate
Concrete
4) T If the unit will be installed on the top of the building which vibration level should be restricted.
It is recommended to use spring isolators as absorber, please refer to following diagram:
Unit Bottom
Spring Shock
Absorber
Foundation
3. Installation Spaces
1) Reserve the spaces required for unit installation, operation and maintenance.
2) The installation place of the unit shall be free from the effects of fire, inflammables, corrosive
gas or waste gas as much as possible; the ventilation space shall be reserved there; proper
measures shall be taken to reduce noise and vibration whenever possible.
3) When the units are installed on the horizontal plane without obstacles, the longitudinal distance
between the units shall be kept above 1m, the transverse distance between the units shall be
kept above 1.8 m, and such distances shall be as large as possible; if there are obstacles at
both sides of the unit, the distance between the unit and obstacles shall be kept above 1.8 m; if
there are obstacles above the unit, the distance between the unit and obstacles shall be kept
above 2.5 m.
4) The removable post for compressor service access must not be blocked at either side of the unit.
20
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
5) There must be no obstruction under the fans.
Basically, the piping should be designed with a minimum number of bends and changes in elevation
to keep system cost down and performance up.
Single unit:
21
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
1) The water inlet pipeline and drain pipeline shall be connected according to the requirements of
markings on the unit. Generally, the refrigerant pipe side of the evaporator is the chilled water
outlet side.
2) The chilled water pipeline system must be provided with the soft connection, thermometer,
pressure gauge, water filter, electronic scale remover, check valve, target flow controller,
discharge valve, drain valve, stop valve, expansion tank, etc.
3) The water system must be fitted with the water pump with appropriate displacement and head,
so as to ensure normal water supply to the unit. The soft connection shall be used between the
water pump, unit and water system pipelines, and the bracket shall be provided to avoid stress
on the unit. Welding work for installation shall avoid damage to the unit.
(1) Determination of water pump flow:
Flow (m3/h) = (1.1 ~ 1.2) * Unit Cooling Capacity (kW)/5.8
(2) Determination of water pump head:
Head (m) = (Unit Resistance (see product parameters) + Resistance at Maximum End of
Pressure Drop (see product parameters) + Pipeline Resistance (length of the least favorable
loop pipe * 0.05) + Local Resistance (length of the least favorable loop pipe * 0.05 * 0.5)) * (1.1
~ 1.2)
4) The flow switch must be arranged on the drain pipe of the evaporator. The flow switch shall be
interlocked with the input contact in the control cabinet. Its installation requirements are as
22
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
follows:
(1) The flow switch shall be installed on the pipe vertically.
(2) The straight pipe section at each side of the flow switch shall have a length that is at least 5
times the pipe diameter; do not install it near the elbow, orifice plate or valve.
(3) The direction of the arrow on the flow switch must be consistent with the direction of water
flow.
(4) In order to prevent vibration of the flow switch, remove all air in the water system.
(5) Adjust the flow switch to keep it in open state when the flow is lower than the minimum flow
(the minimum flow is 70% of the design flow). When the water flow is satisfied, the flow
switch shall keep in closed state.
5) The water filter must be installed before the water inlet pipeline of the unit, which shall be
provided with a 25-mesh screen. This will aid in preventing foreign material from entering and
decreasing the performance of the evaporator.
23
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6) A strainer should be placed for enough upstream to prevent cavitation at the pump inlet (consult
pump manufacturer for recommendations). The use of a strainer will prolong pump life and help
maintain high system performance levels
7) The flushing and insulation of the water pipelines shall be carried out before it is connected with
the unit, so as to prevent dirt from damaging the unit.
8) The design water pressure of the water chamber is 1.0Mpa. Use of the water chamber shall be
not exceeding this pressure in order to avoid damaging the evaporator.
9) The expansion tank shall be installed 1~1.5m higher than the system, and its capacity accounts
about 1/10 of the water amount in the whole system.
10) The drain connection is arranged on the evaporator cylinder. The drain outlet has been
equipped with a 1/2’’ plug.
11) The auto discharge air valve is arranged between the high point of the pipeline and the
expansion tank.
12) The thermometer and pressure gauge are arranged on the straight pipe sections of the water
inlet pipeline and drain pipeline, and their installation places shall be far away from the elbows.
The pressure gauge installed shall be vertical to the water pipe, and the installation of the
thermometer shall ensure that its temperature probe can be inserted into the water pipe
directly.
13) Each low point shall be fitted with a drain connection so as to drain the remaining water in the
system. Before operating the unit, connect the stop valves to the drain pipeline, respectively
near the water inlet connection and drain connection. The by-pass pipeline shall be provided
between the water inlet pipe and drain pipe of the evaporator, convenient for cleaning and
maintenance. Use of flexible connections can reduce vibration transfer.
14) The chilled water pipeline and expansion tank shall be subjected to insulation treatment, and
the maintenance and operation part shall be reserved on the valve connections.
15) After the air-tightness test is carried out, and the insulation layer is applied on the pipeline, so
as to avoid heat transfer and surface condensation; the insulation layer shall be covered by
moisture-proof seal.
16) Any water piping to the unit must be protected to prevent freezing. There are reserved
terminals for the auxiliary electrical heater. Logic in PLC will transmit ON/OFF signal by
checking the leaving evaporator water temperature.
Note: The unit only supply ON/OFF signal, but not the 220V power. If a separate disconnect is
24
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
used for the 220V supply to the cooler heating cable, it should be clearly marked so that it is not
accidentally shut off during cold seasons
17) If the unit is used as a replacement chiller on a previously existing piping system, the system
should be thoroughly flushed prior to unit installation and then regular chilled water analysis
and chemical water treatment is recommended immediately at equipment start-up.
18) Power on the chilled water pump, and inspect its rotation direction. The correct rotation
direction shall be clockwise; if not, re-inspect the wiring of the pump.
19) Start the chilled water pump to circulate water flow. Inspect the water pipelines for water
leakage and dripping.
20) Commission the chilled water pump. Observe whether the water pressure is stable. Observe
the pressure gauges at the pump inlet and outlet, and the readings of the pressure gauges and
the pressure difference between the inlet and outlet change slightly when the water pressure is
stable. Observe whether the operating current of the pump is within the range of rated
operating current; inspect whether the resistance of the system is too large if the difference
between the operating current and rated value is too big; eliminate the system failures until the
actual operating current is satisfied.
21) Inspect whether the water replenishing device for the expansion tank is smooth, and the auto
discharge air valve in the water system enables auto discharge. If the discharge air valve is a
manual type, open the discharge valve of the chilled water pipeline to discharge all air in the
pipeline.
22) Adjust the flow and inspect whether the water pressure drop of the evaporator meets the
requirement of the unit’s normal operation. The pressure at the chilled water inlet and outlet of
the unit shall be kept at least 0.2MPa.
23) The total water quantity in the system should be sufficient to prevent frequent “on-off” cycling. A
reasonable minimum quantity would allow for a complete water system turnover in not less
than 15 minutes.
25
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
III. Electrical Data
1. Field Wiring
WARNING: In order to prevent any accident of injury and death during the site wiring, the power
supply shall be cut off before the line is connected to the unit.
Wiring must comply with all applicable codes and ordinances. Warranty is voided if wiring is not in
accordance with specifications. An open fuse indicates a short, ground, or overload. Before
replacing a fuse or restarting a compressor or fan motor, the trouble must be found and corrected.
(1) Copper wire is required for all supply lines in field connection to avoid corrosion and overheat at
the connection of terminals. The lines and control cables shall be separately paved and
equipped with protective pipes to avoid intervention of supply line in control cable.
(2) Power section: It is required to connect the power supply cable to the control cabinet of the unit,
when it arrives at the jobsite. The power supply cable is connected to the terminals of L1, L2, L3,
N and PE and the terminals need to be fixed again after 24h running (the minimum allowed
time). Please seal the entering wiring hole after users installed the main power wires, in order to
avoid the dust entering into electric control cabinet.
Caution: it is suggested that to use appropriate tools to make sure there is a enough height to
install the main power wires if the basement is higher than 200 mm.
N
communication interface
PE
Remote Start
Remote Stop
Flow switch
L3 L1
Alarm
Pump
Indication
Multi-units
L2
26
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Remote stop
Water pump
mode indication
communication
2# Alarm
1# Alarm
Multiple
(3) Breaking isolation switches should be added between the power cord of users and the unit. The
capacities of the breaking isolation switches recommended are as follows.
27
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Recommended
Model Recommended Cable Note
breaker
(4) Attention: refrigerant selection: the previous software settings are replaced by the current
hardware settings to avoid the possibility of improper operation of the software leading to
wrongly selected refrigerant and damage to the unit.
(5) Short circuit 1X:35/1X:36 on the wiring terminal 1X in the cabinet and set R22 refrigerant for
the unit, or, R134a is used for the unit.
(6) In order to avoid wrong control in field connection, the liquid control circuit (24 V) shall not be in
the same conduit with the lead wire of the voltage higher than 24 V.
(7) The control circuits of various units are all 220 V, and for the wiring ways of the control circuits,
please refer to the wiring diagrams supplied along with the units.
(8) A unit consists of master compressor and slave compressor communicating via shield wire
protected by sleeve and separated from supply line.
(9) The control output cable to be connected on site shall be AC250V-1mm2, and 0.75mm2 shield
wire (24 V) shall be used for control signal line.
(10) Attentions: Read the electrical wiring principle diagram and connect the wires strictly according
to the wiring terminal diagram. Three-core shield cable (RVVP3×0.75mm2) shall be used for
the connection of the temperature sensor. Common two-core cable (RVV2×0.75mm2) shall be
used for the connection of flow switch to connect to the NO contact of the switch, i.e. the
opening point when waterless. Two buttons can be connected to the external of remote start
and stop.
(11) If the customer desires the linked control of the water pump, connect the water pump as shown
in the diagram, where an intermediate relay is required. If the function of linked control of water
pump is not needed, ensure that the water pump is started before starting the machine.
CAUTION: An independent power supply box needs to be equipped with the power supply of
the water pump.
28
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Pump contactor
Pump motor
(12) The wiring ports for remote start/stop, flow switch, cool/warm switch, water pump linked control,
alarm indication, etc. are reserved in the electrical cabinet of the unit, with the numbers shown
in the diagram below.
1 2 3 4 5 6 7 8 13 14 15 16 17 18 19 20 21 22 23 24
Inside electric
control cabinet
2
Pump intermediate relay
1
Refrigeration lamp
2# alarm lamp
Remote Start
Remote Stop
1# alarm lamp
Flow switch
29
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
large power electrical appliances such as water pump and user electric heating must be
interfaced with a relay, or the PLC might be burned. Other outputs can be directly connected to
indicator lamps or alarms.
Compressor Fan
Max.
Model Start Rated Rated Rate of Rated
running Fan
Quantity current/ current/ power/ fan current/
current/ quantity
A A KW /RPM A
A
LSBLGW380/C 1 586 228 227.4 124 6 940 5.6
30
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2 Compressors 6 to 10 Fans
380VAC Double-Head 14 to 20 Double-Head
3P+N+PE Compressors
Moulded Case M
M
Circuit Breaker ~ M
Moulded Case ~ M
Circuit Breaker ~
~
Phase Sequence
Compressor
Miniature Thermorelay
Compressor
Circuit Fan
Thermorelay Thermorelay
Fan
Breaker
Thermorelay
Compressor
Contactor
Compressor Fan Contactor
Star-Delta Start
Contactor Fan Contactor
星三角启动
Star-Delta Start
Input Output
Module Module
Commu PLC CUP Module
nication
Notes: this module has the important action of compressor protection. The imbalance rate of voltage of
current is usually specified by compressor manufacturers, and burn-down due to overheating will be
resulted from long-time operation under abnormal working voltage.
31
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
protection value;
b) Results of action execution: power-fail of corresponding circuit, failure of start, circuit breaker
switch positioned in the OFF terminal
c) Processing mode: inspect there is burn-down of component(s) or short-circuit between circuits.
If any, please replace the component(s) or modify wiring;
You may attempt to set the circuit breaker to ON terminal, if it immediately trips once again, it indicates
that there is always a condition of short circuit, in this case, inspect the line and components until normal
pull-in is available.
Notes: Before inspection, please switch on the breaker once without electricity. The existence of heavy
current shock may result the damage of the miniature circuit breaker. At this moment, switch-on without
electricity is also impossible. When switch-on is successful, please test with a multimeter whether the
circuit is conducted. If not, you can sure that mechanical mechanism is normal but electric mechanism is
damaged. In such case, please replace the miniature circuit breaker, and inspect the above steps.
3) Fan Thermorelay
a) Protective condition: fans current overload or phase lack;
b) Results of action execution: units stop, display of fans overload on touch screen, thermal
overload relay trip, failure of start.
c) Processing mode: inspect whether there are fans wiring loose. Inspect whether the value of
fans protection is in a proper position. Inspect whether fins are fouled. Please reset the
thermorelay manually, if needed.
Notes: Because the motor and the thermal overload relay have different thermal inertias, the
temperature of motor is still very high while the thermorelay can be reset. Please inspect whether the
temperature of motor is too high when you can’t sure the failure clearly. Immediate resetting is
impossible in the case of overload trip. You have to wait until the thermal effect of the thermorelay is
over.
5) Compressor thermorelay
a) Protective condition: too heavy compressor current or existence of short circuit failure
b) Results of action execution: units stop, display of compressor overload on touch screen,
32
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
thermal overload relay trip, failure of start.
c) Processing mode: inspect whether the compressor part and insulation of loads are normal,
inspect the pressure value when an alarm is given, and balance the pressure if it exceeds the
running range. Please monitor the current of compressors in real time to ensure whether it is
within normal running after the compressor thermorelay is reset.
6) Sensor Failures
Sensor failures include short circuit and open circuit of the temperature sensor and the pressure
sensor (transformer). The current transformer is also included according to the stepless type unit.
a) Protective condition: any sensor failure
b) Results of action execution: stop of units, display of corresponding sensor failure on touch
screen, failure of start.
c) Processing mode: inspect whether the wiring of faulty sensor is proper and firm, and whether
the sensor itself is normal.
2
4 3
【Home Page】
1) Power indicator (yellow), which is on when display is powered on; it is off when powered off.
2) Status indicator (green), which flashes at low frequency when display is normally operative,
33
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
otherwise it is off.
3) Communication indicator (red), which flashes at high frequency when display and PLC
communicate normally, otherwise it is off.
4) PLC and touch screen procedure version: showing the number of PLC and touch screen
procedure version used by the current unit.
4.2 Basic Interface and Operations:
Indicate that
the system is
initializing.
(last about 30
seconds , flash
1/1sencond)
After the system initializing is completed, please clink on button, and the “Password Input”
dialog will be popped up, please input the User Password(58806) or User Manage Password
(40828),and click “ENTER” into the next interface (Mode Setting Page)
34
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Main Page
35
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2 6
3
4
7 8 9 10 11
【Main Page】
1. System Status: Current system status of units is displayed here. The status of system possibly
displayed is as follows:
1) Standby status: in normal condition, displaying “Standby status” after the unit is powered on.
2) Running status: indicating that starting of unit compressors has been finished (entering the running
status after double-head Start of one compressor), and it has entered the process of automatic
energy adjustment from this point.
3) Pause status:The unit enters “Pause” status when the current detection water temperature (chilled
outlet water temperature in single-unit or chilled inlet water temperature in Multi-units) is lower than
the setting temperature of unit pause. The compressor start to run until the current detection
temperature is higher than the setting temperature of compressor start, then the unit enter “Running”
status.
4) Shutting down status: the status display “shutting down” after the unit has been confirmed to
execute shutdown action. After finished, the unit enters “Standby” Status.
5) Protection status: indicating that the unit is in a failure status currently, click on "alarm information" to
see alarm details.
2. Control mode and running mode: the current mode will be displayed here. For example, the current
page displays that the unit is in a “LOCAL MODE”, and the running mode is “PUMP MODE”.
3. Detection Mode: Leaving water control is by default only in the single-unit mode, with entering water
control not allowed; entering water control is by default in the multi-units combination mode, with
setting of leaving water control not allowed。
4. Combination Mode: indicates “Single-unit” when the unit isn’t in the case of multi-combination
control and indicates “Multi-Units” when the unit is in Multi-combination control. (Note: When the
system has only one unit, please don’t set to multi-unit control)
5. This position is the unit alarm display area, and alarm information of failure content will be displayed
here in a mobile mode in case of any failure in units.
6. Functional key area of units. It has the functional keys of “SETTING”, “ALARM”, “STATUS” and
36
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
“Multi-Unit” through which different operating interfaces are accessible. Introduction of their
functions will be detailed hereafter.
7. Start is required upon completion of unit set-up, directly click on “START” button on the lower left,
and the following dialog box will be popped up at this moment: click on “CANCEL” if you don’t
expect to execute the start.
Starting Operation
The system is in pause state when the water pump has been completed to open, but the compressor is
unable to start because some other factors can’t satisfy the condition of compressor starting, the
interface indicates “Failure to start, please check the status”. The starting conditions include oil heating
time 、restart delay、the temperature of compressor starting. In this case, only when all of the conditions
have been meet, the unit starts to operate the compressor, otherwise the sign “Failure to start, please
check the status” will keep displaying in the main page.
Note: Clicking on button is invalid when the unit is in failure. The unit can start normally only
when all of the alarm have been eliminated and reset manually on the touch screen interface.
37
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
When the current ambient temperature is beyond the allowed running range, the below page will be
popped up:
If the current temperature return to the rage, click to the“OK”and the unit will start to run normally.
Click on button , and the “Confirm Shutdown” dialog will be popped up. Click on “Confirm” if
you ensure execution of Shutdown action, the system status indicates “Shutting down”. (Note: The
system status indicates “shutting down” even the requirements of shutting down the compressor are not
meet. The unit will execute shutdown action automatically after all of the requirements have been
satisfied. )
The action of 4 functional keys in main page will be detailed in subsequent sections:
Setting
Click on in main page to enter the password page. Click on the dialog box of password
input, an input keyboard will be popped up in the interface, input user manage password “40828”, then
click on “Enter” in numeric keyboard, the dialog box disappears, click on “ENTER” to enter “User
Parameter Setting Page”.
38
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
“Password Error Page” will be popped up when the password is wrong, click on button to
return “Password Input Interface”, input the password again to enter the next page.
Note:
① “Max” in the upper left indicates the upper limit of the setting parameter; “Min” in the upper right
indicates the lower limit.
② “Automatic On/Off”: Only displaying under Timed mode.
39
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Explanation:
① Target Temp. (Chilled Leaving Water): The target temperature of the chiller leaving water
② Temp. / Compressor start (Chilled Leaving Water): One of the compressor starting conditions
required to be achieved for the chilled leaving water temperature. The compressor can start only at
the current chilled leaving water temperature > the setting value in cooling mode, or the current
chilled leaving water temperature < the setting value in heating mode.
③ Temp. Adjustment Period: The time interval between two temperature detections.
Clock Setting
Manual
input is
allowed
Clock Setting
Click on the numerical box, the numeric keyboard will appear, input the time, click “ENT” to save and
take effect. Click “ESC” to cancel the input value.
Note: Please pay special attention in setting of time and date to the fact that setting of
non-existent date or time is not allowed, and we assume no liability or responsibility for setting
of non-existent date or time and consequence resulting from this setting.
Adjust Screen
User can increase and reduce the brightness and contrast of screen by clicking on “+”and “-” in this
page.
User can also open and close the keypad tone of screen by clicking on “ON” and “OFF”.
User can modify the time of backlight by clicking on the numeric box following the time of backlight.
Electric control capacity displays the battery capacity of PLC whose battery is used for supplying power
for PLC interior time in the case of failure to engage PLC. Reset of PLC interior event will be resulted
40
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
from too long power-fail time of PLC module without battery.
Automatic On/Off
If the automatic on/off function is needed, please switch to “TIMED” mode in control mode (as shown in
Picture 2) firstly, then enter user parameters setting page, click on button to enter
the following page ,and set the starting times and shutdown times.
Manual Input
Is allowed
Inching
switch
on “ to switch to , set the time 0:00 in starting time and 16:00 in shutdown
time on Thursday and click on “ to switch to ,all of the others time buttons are
. Pay attention to that the starting time must be before the shutdown time.
Since system interior time is used for timing start / stop, please draw attention to check whether the time
of the system is correct when you are using this function.
Comm. Setting
engineers to do settings of the unit. After setting well, press the button, it will turn to
, then the number of multi units should be set according to the practical situation.
② “1#comp. on” “2#comp. on”: No.1 or No.2 compressor can be selected to work or not, when the
compressor meet the conditions it will shut down refer to the stop progress if user want to stop one
compressor.
Read serial pot information
Click on to read serial port information when the unit need to be multiple controlled.
Status
Status Information
The upper left in the page display the refrigerant type; the upper right display the station number address,
the station number of master is set to 1.
Note:
To start up, following conditions are required:
① “Restart Delaying” need to display “NO” ,if “YES”, it indicates the delaying period has not achieved.
② ”Water Temp. Allow Compressor Start” need to display “YES”, if “NO”, it indicates the current
temperature is not able to meet the compressor starting condition.
③ “Remaining Oil Heating Time” need to display “0”, if more than 0, it indicates the oil heating is in
process.
42
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
To shut down, the following condition is required:
① ”Min. Running Time Elapsed” need to display “YES”, if ‘NO’, it indicates the shortest running period
has not achieved.
Current Data Display
Please click on button to enter the current data interface, the interface indicates current detection
data. User can enter this interface to query the temperature information when there are alarms such as
temperature too high or too low.
Input Status
“ON” as displayed indicates the input point is closed; “OFF” as displayed indicates the input point is
open.
Note:
① “Remote Start/Stop” is available only under REMOTE mode.
② “Water Switch”: indicating that current water flow status of chilled water system. “OFF” displayed in
no water flow state, otherwise “ON”.
③ “Contactor Protection”: indicating that when the compressor start to run, the contactor act
normally, “OFF” switch to “ON”.
43
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
④ All of protection switch is “ON” in normal condition and “OFF” in failure status.
Output Status
Output
“ON” as displayed indicates the output point is energized; “OFF” as displayed indicates the output point
is de-energized.
Alarm
Click on button and “Fault” in main page disappear, the unit returns to normal. If the warning
message is more, please click on to check. These in red color indicate the alarms which
have not been eliminated; these in white color indicate the alarms which have been eliminated.
Note:
1. High-Pressure Protection is unable to reset in alarm information page, manual reset in the high
pressure switch (installed in the discharge pipe) is needed.
2. Compressor and fan overload protection are unable to reset automatically, please check the
44
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
relevant thermal relay in the control box to reset manually.
History Alarm Information
45
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2#吸气压力变送器故障 2# Suction pressure failure
2#排气压力变送器故障 2# Discharge pressure failure
1#排气温度过高保护 1# High discharge temp. protection
1#翅片温度过高保护 1# High Fin temp. protection
1#压差保护 1# Differential pressure protection
1#吸气压力过低保护 1# Low Suction Pressure protection
1#排气压力过高保护 2# High discharge pressure protection
Multi-Units Status
Click on to enter the next page, it will show the information of all connected units as
following: The communication, alarm information, status, refrigerant type of each unit can be inquired in
the following pages.
Note:
① Max.8 units can achieve combination control, the unconnected unit can access the combination
control system at any time as long as the unit is powered on and connected with the system by
communication cable.
② The “Status” displays “Run” until the unit finish the starting action and enter the process of automatic
energy adjustment, otherwise displayed “shutdown”
47
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
5. Control Screen Menu Structure
Mode Setting
Main Page
48
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6. Introduction of Major Electric Components
Collect all digital quantities and
analog quantities on units as well
as inputs of quantities and touch
Programmable Logic
screen commands, and realize
Controller
different outputs by judgment of
(PLC)
procedures to meet the
requirement or normal and safe
running of units.
Achieve AC220V/DC24V to
provide power supply for touch
Switch Power Supply screen, also for PLC and
intermediate relay in some
tailor-made products.
(for CE )
Transform the electrical system
applied by the user into AC220V
for supplying power to the control
Isolating Transformer circuit. It can isolate harmonic
disturbance between circuits and
increase control accuracy.
50
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
IV. Maintenance and Commissioning
1. Commissioning
1.1 Electrical System Connection Inspection
1) Inspect whether power distribution capacity is compliant with the power of the unit before the first
start-up, and whether the diameter of the selected cable can bear the maximum working current
of the master compressor.
The max economical conveying distance:
<3000h 264
3000~5000h 294
>5000h 331
2) Inspect whether the electric mode is compliant with that of the unit, three-phase five-line (three
phase lines, one zero line and one earth wire, 380V±10%).
3) Inspect whether the maximum phase voltage unbalance is compliant with the requirement, 2%
for the maximum permissible phase voltage unbalance and 5% for the phase current balance.
The machine must not be started up when the phase voltage unbalance exceeds 2%. If the
measured unbalance% is excess, the power supply sector shall be informed of immediately.
The formula for calculation of phase voltage unbalance% based on the maximum deviation
from the average voltage is: voltage unbalance% = maximum deviation from average
voltage/average voltage.
e.g. at nominal voltage 3N~, AC380V, 50Hz, the measured UAB=376V, UAC=379V, UBC=385V.
Average voltage = (376+379+385) 3= 380V
Determined deviation from average voltage:
△UAB=380-376=4V, △UAC=380-379=1V, △UBC=385-380=5V,
Maximum deviation: 5V
5/380=1.3%, the maximum phase voltage unbalance is 1.3%.
4) Inspect whether the supply circuit is the compressor is firmly and properly connected, and
tighten it if there is any looseness. The screws might be loose due to the factors such as
long-distance transport and hoisting of the master compressor. Or, the electrical elements (e.g.
air switch, AC contactor, etc.) in the control cabinet of the master compressor and the
compressor might be damaged.
5) Carefully inspect all the electrical lines with a multimeter, and whether the connections are
properly installed. Carry out measurement in mega ohm and ensure that there is no short circuit
at the shell. Inspect whether the earth wire is properly installed, and whether the insulation
resistance to ground exceeds 2MΩ. And inspect whether the supply line meets the requirement
of capacity.
6) Inspect whether disconnection switch is installed to the supply line of the supply unit.
51
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
7) Carry out complete inspect for all connections of the main circuit in the control cabinet and all
external connections of the control circuit before power connection (e.g. oil heater, compressor
electronic protection, circulatory water temperature sensor, target-type flow switch connection,
water pump linked control, communication line connection, etc.); inspect the bolts of the wiring
terminal for looseness. Inspect whether various electric meters and appliances are properly
installed, complete and available. Inspect the interior and exterior of the electrical cabinet,
especially various wiring ports, for cleanness. If the communication lines of the PLC and control
screen are damaged, refer to the diagram below.
8) After the inspection for all the above items is complete, connect the control cabinet and the
supply indication lamp will light up, indicating that the oil heater is working. Observe whether
the phase loss protection is in normal condition, if it is (green light on), close the single-pole
switch (QF2) in the control cabinet, then the control circuit begins working, and the touch
screen and PLC control are put into operation.
9) Before start up the machine, inspect whether the external system of the unit meets the
conditions for start-up (e.g. whether the water cooling pump of the system is externally
controlled or interlocked with the master compressor, and that the water pump must be started
before starting up the master compressor via external control).
9 needle type D
plug female head
RJ45 crystal head
9
8 8
7 7
6 6
5 5
4 4
3 3
2 2
RJ45 cable 1 1
87654321
RJ45 crystal
head
52
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
1.2 Electrical Elements Parameters Settings Inspection
1) Inspect whether the ports of linked controlled unit are properly connected.
The connection way for linked controlled unit is as below:
11号机组
# unit 22号机组
# unit 88号机组
# unit
Multi-link connection:
The user wiring terminals 9, 10, 11, 12 of each unit are communication line terminals for multi-link.
These terminals can also be used if the upper computer is selected. Attention: either upper
computer or multi-link function can be chosen. The use of both requires application for
customization.
Use 0.5mm2 3-core shield wires to connect the unit.
Double-head unit is considered as one unit. Maximum 8 sets can be connected.
The method of connecting upper computer via Ethernet port:
The connection via Ethernet instead of RS485 serial connection required customization. The
connection way is as below:
Ethernet port,
only if customized
Wire number of
RJ45 crystal head
2) Inspect whether the fan overload protection value is set correctly. The current value for normal
operation fan is 3.5~4A. After a fan overload trouble, press the blue button in the heat relay to
reset.
53
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Protection setting of
fan heat relay
overload value, the
number of which
corresponds to the fan
overload protection
value.
3) Inspect whether the compressor overload protection value, which shall not exceed the
maximum compressor permissible current value indicated in the nameplate on the compressor,
is set correctly. The compressor overload protection value generally equals to the set value of
heat relay (similar to fan heat relay) multiplied by variable ratio of current inductor, which is
(250/5)50 in the following case.
Protection setting of
fan heat relay overload
value, the number of
which corresponds to
the fan overload
protection value.
3) Inspect whether the value of phase loss and reversal protection is set correctly. The
over-/under-voltage protection value shall be ±10% of the rated voltage.
54
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2) Inspect whether moisture content of the system exceeds the limit
Excessive moisture content in the refrigerant system of the unit might cause ice block, copper
plating, etc. that would seriously affect the safety of the unit. Therefore, the dryness of the
refrigerant system of the unit shall be inspected from the sight glass before and during
operation of the unit, purple indicating dry, and pink moist, as shown in the below figure. When
the color turns to red, the filter core in the unit shall be replaced with a dry one.
3) Sufficient lubricating oil in the oil tank (not lower than 1/2 of the oil level in the high oil
immersion lens), and no deterioration (blackness).
Inspect the oil level and quality before start-up for the two factors have direct impact on the
performance and reliability of the unit. There must be sufficient lubricating oil in the unit. And
during the shutdown of the unit, the high oil immersion lens must be full of oil.
When the unit is in stable operation, the oil level in the high oil immersion lens should be at
least above the 1/2 position. And there shall be no deterioration (blackness) of the lubricating oil,
or else, qualified lubricating oil shall be changed before operating the unit.
4) Coil fin cooling fan shall rotate in correct direction without reverse rotation or shutdown.
Before operation of the unit ,Inspect whether the fan networks are deformed under stress,
whether there is friction and collision between the networks and the blades, whether there are
foreign matters in the network, and whether the fin is deformed or damaged caused by collision.
55
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
There should be no
deformation of the
fan guard or foreign
matters in it.
Operate the fans one by one before operating the unit, and inspect whether there is abnormal
noise in the fan caused by poor lubrication of the bearing or friction of foreign matters, and
whether the fan rotates reversely or does not rotate.
5) Inspect whether the directional elements such as one way valve, solenoid valve, electronic
expansion valve, etc. are installed properly. The directions of the one way valve and solenoid
valve are indicated on the valves. As for the thermostatic expansion valve and electronic
expansion valve, if the valves are upward, the direction is generally high-in and low-out.
6) Inspect whether the pressure sensor stop valve, dry filter front/rear angle valve, liquid/air
sampling stop valve and injection stop valve, etc. are all open.
When the unit stops, the high and low voltages shall be almost the same. After the start-up, the
low voltage decreases, and the high voltage increases. If there is no voltage change certain
time after the start-up, inspect whether the liquid/air sampling stop valve is open.
7) After the unit is installed and before connected, it is required to tighten the connections in the
electrical cabinet of the unit one by one.
8) Inspect the bolts of the unit for looseness.
After the unit is transported and installed, it is required to inspect whether the fixing bolts of the
unit (e.g. fixing bolts at compressor base angle, at post and beam of the unit, and at pipe clamp,
etc.) and of the electrical elements (e.g. fixing bolts of PLC and of insulating transformer, and
56
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
connection bolts of upper/lower terminals of AC contactor, etc.) are firmly fixed.
9) Inspect the looseness of the connections in the electrical cabinet, especially the electric part in
the cabinet. The parts connected by bolts might be loose due to transportation. If there is any
looseness, tighten it to avoid burnout of circuit or element caused by poor contact.
Inspect the looseness of the terminals and poor contact caused by vibration and collision during
transportation and installation (especially the electric part; ensure the connection points of all
terminals are firm and reliable before electrification).
Inspect whether there is poor contact and short circuit caused by dust, moisture, etc. in the
electrical cabinet, and whether the values of all temperature sensors are normal. During the
shutdown of the machine, the indicated temperatures of discharge, fin, and the environment
shall be almost the same, and the entering and leaving chilled water temperatures shall be
almost the same.
10) Before the unit leaves the factory, the control cabinet is well connected with main motor,
electrical actuator, and sensor elements of pressure temperature, etc. Therefore, the wiring on
site for the user is very simple. Only the chilled water flow switch line and chilled water pump
linked control line (control contact is active) need to be connected. For the detailed connection
way, please refer to the circuit wiring diagram in the operation manual for the unit. (The
attached circuit diagram represents the case of air-cooled heat pump unit for user’s reference,
as for the details, the operation manual supplied with the unit shall be final.)
11) Target-type flow switch is set on the chilled water pipeline which shall be installed at the outlet of
the chilled water. The NO contact of the target-type flow switch shall be connected to the
control circuit as per the wiring diagram.
Note: Disordered water flow may lead to wrong action of the flow switch; therefore, the control
cabinet will command the unit to stop after receiving continuous disconnection signals during
10 s.
12) The tube where the temperature sensing probe is installed shall be filled with lubricating oil or
other grease that will not freeze at the temperature of the leaving chilled water for the
convenience of heat transfer. Thermostatic insulation and enclosing measures shall be taken
for the temperature sensing device.
Inspect whether there is temperature deviation for the entering and leaving water temperature
57
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
sensor caused by insufficient heat transfer oil in the thermostatic pipe.
Armored dip-type
temperature sensor
For later armored dip-type temperature sensor, no lubricating oil is required for heat transfer.
In shutdown status,
the high and low
voltages shall be the
same and equal to the
saturation pressure
corresponding to the
current temperature.
In the pressure gauge scale, taking the right figure for example: the outside values are pressure
values (unit: bar), and the inside values indicate saturation temperatures of refrigerant R134a
respectively under the relative pressure. The types of refrigerants indicated in different pressure
gauges might differ. [Table 1]
Compressor oil
heater, working
when the unit is
electrified.
(3) Inspect whether there is alarm for trouble of the display screen. if there is, the trouble must be
corrected.
(4) Inspect the electronic expansion valve control module for alarm trouble.
(5) Inspect whether various temperature points displayed on the display screen are within the
normal range.
Before the operation of the unit, the showed temperatures of discharge、fin and the ambient
temperature are close to the current actual ambient temperature, and whether the entering and
leaving water temperatures are close to the water temperature at the user side. If there is any
obvious deviation of the above temperatures, inspect whether the temperature sensor is in
normal condition and whether the connection is firm and reliable.
Values of various
temperature and
pressure points
showed in the main
page of the unit.
(6) Inspect whether the flow in the water pump meets the requirements of the unit.
(7) Inspect whether the power supply of the unit is stable.
2) Parameters Inspections during Start-up and Operation
59
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
(1) The maximum range of parameters for normal operation of R134a refrigerant unit
See table 2 for the maximum range of performance parameters of R134a refrigerant:
[Table 2]
Refrigeration
Working Condition
Discharge temp. ℃ <110
Suction temp. ℃ --
Condensation temp. ℃ <65
Evaporation temp. ℃ <15
Economizer super-cooling degree ℃ --
Suction super-heating degree ℃ ~
Discharge pressure MPa <1.8
Suction pressure MPa <0.38
(2) Keep good record of unit data during commissioning.
60
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2. Maintenance
2.1 Common Troubleshooting
1) High Voltage Protection
High
voltage
protection
Yes
Yes
No
No
Yes
Expansion valve Replace the
can not be opened. expansion valve.
No
Yes
Press controller is
in trouble. Replace the press
controller.
No
Yes
Fin heat exchanger for cooling is too Replace the heat
dirty or aged; or, too heavy exchanger.
encrustation in tube shell for
heating.
No
Yes
One way valve is Replace the one way
blocked. valve.
No
Yes
Air exists in system
(generally likely after Empty the air, re-extract
service of the unit) vacuum if necessary.
No
Yes
False alarm of Inspect whether it is
controller frequent, if is, replace
PCB.
No
Yes
Yes
No
Yes
Compressor suction Open the suction
stop valve is not open. stop valve.
No
Yes
Blower stops rotating or rotates
in reversed direction when Inspect the blower or open
cooling; water pump is not open
or the flow insufficient when the water pump.
heating
No
Yes
No
Yes
No
Yes
Fin heat exchanger for cooling is
too dirty or aged; or, too heavy Clean heat exchanger.
encrustation in tube shell for
heating.
No
Yes
One way valve is Replace the
blocked. one way valve.
No
Yes
Water pipeline is not properly Adjust the water
designed. When it is closed at
the end, the water flow is pipeline system.
smaller.
No
Yes
No
62
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Yes
No
Overheat discharge
temperature
Yes
Yes
No
Yes
Yes
No
Yes
Wrong discharge temperature sensor
package is used (generally likely after Install correct temperature sensor
service of the unit). package
No
Yes
No
63
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
4) Compressor Overload Protection
Compressor
overload
Yes
Yes
No
Differential pressure
alarm
Yes
Yes
Reduce water flow for air conditioning
Ambient temperature in by around 60% and restart up the
winter is too low for starting machine, and then adjust it to the
heating. normal flow.
No
Yes
Pressure sensor is in Replace pressure sensor.
trouble.
No
Yes
No
64
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6) Flow Switch Failure
Flow switch
failure
No
Yes
No
Yes
Water flow switch is not Install or Inspect the
installed or properly installation of water flow
installed. switch.
No
Yes
Water flow switch is in Service the water flow
trouble. switch.
No
Yes
False alarm of Inspect whether it is frequent, if
controller is, replace PCB.
No
7) Power Failure
Power failure
Yes
Yes
Wrong power phase Adjust wiring.
sequence
No
Yes
No
Yes
65
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2.2 Common Items and Tools for Unit Commissioning and Service
In order to realize immediate and effective commissioning, maintenance and service, the following tools
and items shall be available depending on units.
I. Common tools and applications:
1) External hex wrench, incl. adjustable and non-adjustable wrenches.
2) Internal hex wrench, comp. better
3) Pressure gauge, incl. gas/liquid gauge and connective gauge pipe, mainly for measuring
pressures of various locations in the system, monitoring the pressure during adding of
refrigerant, and functioning as a switch.
4) Refrigerant recycling machine, recycling refrigerant in the system.
5) Welding torch and relative equipment, welding torch, electrode (both common electrode and
high silver electrode), and scaling powder. For copper pipe with diameter above 9.52mm, larger
welding torch is required to facilitate even heating of the copper pipe.
6) As for vacuum pump and connection gauge pipe, if the vacuum pump connection is not
common for the general gauge pipe, the connection transition pipe must be prepared.
7) As for the refrigerant tank and connection, the refrigerant tank connection must be sound and
not damaged. In addition, it is important that the connection is common for related connection
gauge pipe.
8) Scissors, generally used for connecting gasket of relative connective parts of cutting unit.
9) Brush, used for cleaning dry filter and oil filter, etc.
10) Cutter, used for cutting copper pipe. Cutters with appropriate sizes shall be prepared for cutting
copper pipes of different sizes.
11) Pliers, auxiliary tool.
12) Mouth expander, consisting of bell mouth and mouth expansion.
13) Screwdriver, incl. slotted screwdriver and Phillips screwdriver, with complete sizes.
14) Leak detector (Leak detection powder is alternative if leak detector is not convenient for
carrying.)
15) Universal meter, for measuring current and voltage of the unit (incl. compressor, fan and other
parts), as well as coil resistances of compressor, fan and electronic expansion valve, line
connection and disconnection, etc.
16) Temperature detector, for measuring temperatures of various points in the system of the unit.
66
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
17) Pipe bender, for bending the copper pipe to certain degree, and frequently used for tubing of
pipeline in the unit.
18) Measuring tape, for measuring distance and length, etc.
II. Common items and application:
1) Copper nut, incl. metric and British systems, for making connective pipe with copper pipe.
2) Gasket cardboard, for making gasket seal as sealing is frequently required during maintenance
and service.
3) PTFE tape, for tightening nut, connection, etc.
4) Insulating tape
5) Tighten strip, for tightening wire or sensor, etc.
The above are only common tools and materials. Exceptional cases require particular
considerations.
67
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Low-pressure alarm Low-pressure Low-pressure To be detected during both stop and running.
alarm switch Switch off the low-pressure switch when
discharge pressure of the system is lower than
1Bar, report low-pressure protection, stop the
module immediately in the failure stop
procedure, and save the content of failure.
Compressor Compressor Motor To be detected during both stop and running.
internal protection internal protector Switch off the protection switch in compressor in
protection the case of high temperature of compressor
winding, or high compressor discharge
temperature, or phase sequence error of
compressor power, or phase lack. Stop the units
immediately in the failure stop procedure and
save the content of failure. Do not switch on the
units in accordance with the conditions of
temperature and time until this failure is
confirmed manually on touch screen as required
after failure is eliminated.
Oil level protection Oil level Oil level To be continuously monitored prior to start,
protection switch report oil level protection in case of continuous
switch-off of oil level switch for 3S, and start of
compressor is not allowed; to be detected in
running, switch off the oil level switch in case of
continuous switch-off of oil level switch of
compressor for 60S during running of
compressor. Then report oil level switch
protection. Immediately stop the units in the
failure stop procedure, and save the content of
failure.
Oil differential Oil differential Oil differential To be detected in running, switch off the oil
pressure protection pressure pressure differential pressure switch when the difference
protection switch between oil pressure and discharge pressure of
compressor is higher than the setting value
during running of compressor. The indicator of
oil differential pressure switch in input interface
will be out. Do not switch on the units in
accordance with the conditions of temperature
and time until this failure is confirmed manually
on touch screen as required after switch
resetting.
Contactor failure Contactor Contactor To be detected after start of master, report the
failure contactor failure in case of incorrect pull-in of
contactor. Do not switch on the units in
accordance with the conditions of temperature
and time until this failure is confirmed manually
on touch screen as required after switch
resetting.
Compressor Compressor Compressor Report compressor overload protection when
overload overload overload relay the current value of unit compressor is greater
than the setting value and energy accumulated
to result in thermorelay trip. Stop the module
immediately in the failure stop procedure, and
save the content of failure. Do not switch on the
units in accordance with the conditions of
temperature and time until this failure is
confirmed manually on touch screen as required
after failure is eliminated.
68
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Fans overload Fans overload Fans overload Report fans motor overload protection when the
relay current value of unit fans is greater than the
setting value and energy accumulated to result
in thermorelay trip. Stop the compressors and
fans (simultaneously) immediately for this
module, and save the content of failure. Do not
switch on the units in accordance with the
conditions of temperature and time until this
failure is confirmed manually on touch screen as
required after switch resetting.
Power Failure Power Failure Phase To be detected at any time, report power failure
sequence in cases of high / low voltage of power or phase
protector unbalance and phase lack. Failure will be
eliminated after power gets right. Notes: phase
lack / phase stagger of power will be detected
during both initial stage of power-on and unit
running.
High Fin temp. High Fin Fin temp. To be detected in running, the fin temperature of
temp. sensor the system is higher than 65℃, and the failure
record indicates that the fin temperature is too
high.
Leaving water Leaving water Leaving water Switch off compressors in case of failure of the
temp. sensor failure temp. sensor temp. sensor sensor itself. Switch-off of pump and fans will be
failure delayed. The failure indicator of display board
Entering water Entering Entering will be on, and a corresponding alarm mark will
temp. sensor failure water temp. water temp. be displayed in “Failure Query”. The
sensor failure sensor compressors will not be restarted until the failure
Fin temp. sensor Fin temp. Fin temp. of sensor is eliminated, and the failure signal
failure sensor failure sensor must be cleared manually, otherwise it cannot be
Ambient temp. Ambient Ambient cleared.
sensor failure temp. sensor temp. sensor
failure
Discharge temp. Discharge Discharge
sensor failure temp. sensor temp. sensor
failure
Suction temp. Suction temp. Suction temp.
sensor failure sensor failure sensor
Low-pressure alarm Low-pressure Low-pressure Do not restart the units until confirming manually
alarm switch on touch screen as required when the suction
pressure detected by the system is lower than
the setting value for continuously 1s.
High-pressure High-pressure High-pressure Do not restart the units until confirming manually
alarm alarm switch on touch screen as required when the discharge
pressure detected by the system is lower than
the setting value for continuously 1s.
Beyond the Beyond the Ambient The system will be automatically stopped when
operation range operation temp. sensor, the ambient temperature detected by the system
range entering water exceeds that set by the system for continuously
temp. sensor 5 minutes.
Mode water temp. Mode water Entering / Detect water temperature in the refrigeration
protection temp. Leaving water mode after start for 5 minutes, and report mode
protection temp. sensor water temp. protection when leaving water
temperature is not lower than entering water
temperature for continuously 5s.
EXV module failure EXV module EXV Control Start detection upon power-on of units, and
failure Module report immediately failure of EXV module when
the alarm output point of EXV control module is
switched off.
70
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2.4 Installation/Removal and Service of Key Parts
1) Refrigerant Recycling and Adding
If transfer and recycling of refrigerant are
required during the maintenance and service, the
following items shall be carefully considered: The deformation and
failure of the oil
(1) If oil differential pressure alarm occurs in the
filtering net, need to
unit, the lubricating oil deteriorates and is be replaced
emulsified, or the unit is used for too long,
the compressor oil filter and tank shall be
cleaned, and the unit lubricating oil shall be
replaced. If the unit oil filter is deformed or damaged, it needs to be replaced.
71
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
vacuum, and then add 2~3kg refrigerant.
If only to clean the dry filter, but not to replace it, before removal of the filter, ensure that the
refrigerant in the dry filter is completely
discharged and the dry filter has remained not in
use for a time (to ensure the temperature of the
dry filter core is close to the ambient temperature)
so that the removed dry filter core with low
temperature would not cause the moisture in the
air to immediately reach to the dew point to
condense and absorb water. Protective measures
shall be taken to the removed filter to prevent it
from directly contacting with the air.
If the dry filter core is dirt or has absorbed too much moisture, it must be replaced with a dry
one.
During the operation, inspect whether the dry filter is blocked and whether the temperatures at
the dry filter inlet and outlet are close in normal conditions. If there is obvious temperature
difference (above 5℃) between the front and end of the filter, or even that frost exists at the end
of the filter, it is likely to block the dry filter.
If frost exists at
Seriously blocked dry the end, the dry
filter must be cleaned filter is seriously
or replaced. blocked.
If the temperature
difference between dry
filter front and end
exceeds 5℃, the dry
filter is likely blocked.
(4) If refrigerant is desired to be extracted for the complete machine, the refrigerant in the system
shall be transferred to particular refrigerant container via fluorine recycling machine.
72
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
2) Replacement of Compressor
(take careful consideration before continuing with the
following steps)
(1) Inspect the refrigerant system and various lines to
figure out the cause of burnout of the compressor
as far as possible.
(2) Recycle the refrigerant, and before that, prepare
relative equipment and tools, and especially keep
good ventilation condition in the working
environment.
(3) Remove the compressor from the system, and replace the dry filter.
(4) Inspect and clean the thermostatic expansion valve.
(5) Clean repeatedly the entire system with high pressure nitrogen.
(6) Extract vacuum in the system three times, and reduce the pressure of the system to an
appropriate value.
(7) Fill refrigerant in the system. Pay attention not to start up the unit until the filling amount is at
least 60% of the rated amount of the unit. This can be realized by lifting the refrigerant steel
cylinder and fill it in backward direction.
(8) Continue filling refrigerant after the start-up till it reaches the rated filling amount. It can be filled
in liquid if necessary. Ensure that the liquid filling point is before the vapor-liquid separator,
better at the inlet of the evaporator.
(9) Leave the system running for 48 h, extract a small amount of compressor oil, inspect the taste
and measure the acidity with PH paper. Replace the compressor oil if necessary.
(10) After step 9 is completed, leave the system running for another 48 h. If everything is normal,
change the dry filter to the original model for the unit.
(11) After the above steps, inspect the system again in two weeks to ensure the working conditions
and operation of the unit meet the requirements of the design.
3) Replacement of Shell and Tube Evaporator
(1) Inspect the water system and various lines for whether the evaporator is damaged.
(2) If it is damaged and needs replacement, disconnect the power supply of the unit and recycle
the refrigerant.
(3) Loosen the water inlet and outlet joints, separate the pipeline connected to the evaporator
through welding (different units have different heat exchange types; therefore, when welding
the connective pipeline, all connection locations shall be recorded. Wrong connected pipelines
will cause gas-cross in the system).
(4) Clean the system depending on particular situations.
(5) Loosen screws of fixing base of the evaporator, remove the shell and tube evaporator and
replace the heat exchanger with one of the same model, and connect the pipeline through
welding.
73
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
(6) Pay attention to nitrogen filled protection during welding.
(7) Keep the pressure of the system, extract vacuum, and refill refrigerant.
4) Replacement of Condenser
(1) Disconnect the power supply of the unit and recycle refrigerant.
(2) Remove the metal plate connected to the condenser and remove the guard of the condenser.
(3) Remove the parts of collector tube and gas-distributing
subassemblies connected to the condenser through welding.
Pay attention to the direction of the flame to prevent contact
with condenser fin and metal plate of the unit.
(4) Clean the system depending on particular situations.
(5) Loosen the fixing bolts connecting the condenser and metal
plate of the unit, remove and replace the condenser, and
connecting corresponding pipelines through welding.
(6) Pay attention to nitrogen filled protection during welding.
(7) Keep the pressure of the system, extract vacuum, and refill refrigerant.
5) Replacement of Thermostatic Expansion Valve and Strainer
(1) Inspect the refrigerant system and various lines to figure out the cause of damage of the
expansion valve or strainer.
(2) If the expansion valve or strainer is to be replaced, disconnect the power supply of the unit and
recycle the refrigerant.
(3) Wrap the expansion valve body or strainer with wet cloth, remove the inlet and outlet tubes of
the expansion valve through welding, and then remove the expansion valve or strainer.
(4) Replace the thermostatic expansion valve or strainer with the one of the same model, wrap the
thermostatic expansion valve body or strainer with wet cloth again, and connect the inlet and
outlet tubes of the expansion valve through welding.
(5) Pay attention to nitrogen filled protection during welding. Besides, pay attention that no water
flows into the pipeline.
(6) Keep the pressure of the system, extract vacuum, and refill refrigerant.
74
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
angle valve connector 1 and two main pipelines 2 and 3 are interconnected.
Ball Valve
When the ball valve core is turned
outward, the two main pipelines are
interconnected;
When the core is turned inward, the
two pipelines are not
interconnected
2) Each time when acing or cleaning the strainer, oil filter, stop valve, etc., inspect relative sealing
faces for leakage after filling of refrigerant.
3) Recycling of refrigerant is not part of the normal running, therefore, the protection settings of
the unit must be ensured valid, especially when the unit needs to operate. If the protection
switch is short connected due to protection failure, start-up is in principle not recommended.
4) The system of air cooling screws unit is generally complicated, and the flow line is long, if
replacement, cleaning and welding of parts at some area are required, close the valve as close
to the engaged area as possible, and minimize the volume of vacuum extraction.
5) If vacuum extraction is required for the complete machine, because of the complicated system,
it is better to divide the system into several parts for vacuum extraction, or extract vacuum at
several points in the system, generally 3 points at least, in addition, it is better to choose the
vacuum pump of larger model. If the vacuum pump is relatively small, sufficient time for vacuum
extraction shall be guaranteed.
6) During filling of refrigerant, valid metering device is required for accuracy of filling amount.
Empty the connective pipeline before filling refrigerant each time. Refrigerant pipe with reliable
quality shall be chosen to prevent accident during transfer or filling of refrigerant.
7) It is better to use filling machine to fill the refrigerant. If no filling machine is available, refrigerant
tank can be used to fill refrigerant directly. However, the pressure in the refrigerant tank is too
limited to fill the refrigerant required completely to the system. It is suggested to heat the
refrigerant tank in 40~50℃ water (heating temperature shall not be too high). When there is
60% of the rated amount of refrigerant in the system, start up the machine for filling. Fill
refrigerant at the gas side of the system, and control the flow of the refrigerant. Gas of
refrigerant is better. If it is liquid, it is better to be filled before the evaporator. If after the
evaporator, it shall be filled slowly and in small flow.
75
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Explain to the users that operation of the unit shall be carried out strictly as per the steps and
methods specified in the operation manual. If anyone has any problems about descriptions in
the manual, he shall enquire after-sale personnel or professionals in the factory and carry out
the operation only when he understands it. Any deviation in the installation of the unit from the
requirements in the manual shall be pointed out to the part responsible for installation, and the
after-sale personnel or professionals in the factory will determine whether change is necessary.
3) Short-connection is forbidden when all protection functions of the unit are normal. Ensure all
protection functions are available and reliable.
Various protection switches in the unit are for safety of the unit or user, and are not permitted to
be short connected in principle. If short-connection is required for commissioning, the operation
shall be done by the after-sale personnel or professionals in the factory on site. After the
commissioning, connect the protection switches to the system before starting up the unit for
long-time running.
4) Open the water pump and wait until the water flow is stable before starting up the master
compressor. For shutdown, the water pump must be closed in a delayed time. It is not allowed
to forcibly close the water pump when the master compressor is still running. If the water pump
fails, and the flow switch does not jump, the unit must be emergently shut down.
5) The unit must be disconnected from the power supply during inspection or replacement of the
lines of the unit.
If it is required to tighten the line bank screw or replacing the wire and element in the electrical
cabinet during commissioning and maintenance, it shall be down when the power supply is
disconnected. Similar operations by the user in later maintenance and service shall also be
done when the power supply is disconnected.
6) The non-user parameters in the touch screen of the unit and electronic expansion valve control
module are forbidden to be changed.
The non-user parameters in the touch screen of the unit and electronic expansion valve control
module are directly related to the performance and reliability of the unit, and are not allowed to
be changed in principle. Even if it is required to adjust some parameters due to special local
climate, it shall be done by or under the instructions of after-sale personnel or professionals in
the factory.
7) If any exceptional case occurs to the unit, it is forbidden to forcibly start up the unit unless under
the instructions of professionals.
Exceptional temperature, pressure, sound, or vibration, etc. of the unit during the running shall
be clearly recorded in details, and reported to after-sale personnel or professionals in the
factory. It is forbidden to forcibly start up the unit unless permitted.
76
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
V. Control Logic
Step A: Power-on
Complete
initialization
Switch on pump
Detect water temperature every
other temperature control cycle
Step C:
Idle status Detect water
energy temperature, see
adjustment NO whether load is
YES
YES
YES
Energy adjustment
execution
Description:
1. Double-head Start Mode:
According to the running time of compressors, the unit of shorter running time will be started
prior to the other in the case that both compressors meet the starting condition, and No 1 head
78
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
If water temperature has been within loading area after the head started prior to the other, the
other will be started in two minutes. If water temperature has been (or had been) immerged in
loading area in two minutes, the other head will not be started until the head started prior to the
other has been started and loaded to 100% in case that further loading is required for the unit
according to the energy adjustment process.
2. Multi-Connected Start Mode:
Water pump starts to run upon point start of units, and the duration of switching on the water
pump is from 3 to 5 minutes. The units will be converted into idle mode upon switching on the
water pump, and then attempt will be made to switching on the compressor.
The running times of all jointly-controlled units will be sequenced in case of multi-connection
provided that the condition for switching on the compressor is satisfied. The unit of shorter
running time will be started prior to the other when both units meet the Start condition, and the
unit of smaller station number will be switched on prior to the other in the case of identical
running time.
Double-Compressor running time: the running time of one head of shorter running time than
that of the other will be taken as the reference during loading, and the running time of the other
head will be directly taken as the reference if one head does not meet the starting condition; the
running time of one head of longer running time than that of the other will be taken as the
reference during unloading, and the running time of the other head will be directly taken as the
reference if one head does not meet the unloading condition.
When no unit running has been started, the jointly-controlled units will be started at the interval
of 2 minutes for each in the Start order with water temperature is in the loading area, (to be
executed as per the above double-head single-unit mode, with double-head treated as one
unit), and energy adjustment will be executed individually by the unit that has been started;
when water temperature is not in the loading area, a single unit will no longer execute energy
adjustment individually, nor the unit that has not been switched on will be switched on at the
interval of two minutes, and the complete machine will start to run in accordance with the
normal process of energy adjustment.
Shut-down signal
YES 79
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Power-on 25%
solenoid valve, system
A compressor
Power-off main
contactor, system A
compressor
Step F:
Power-on 25%
solenoid valve,
system A compressor
80
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
When all modules are in the energy adjustment idle status, 3 minutes will be delayed to switch off
water pump after Stop signal is received.
Other modular
Remain in current NO Whether water units not stop
status temp. is in executed this
unloaded area step every other
temperature
YES
NO
Whether there is
any modular unit
satisfying the
shortest
compressor running
YES
Power-on 25%
solenoid valve, system
A compressor
Power-off main
contactor, system A
compressor
Power-off 25%
solenoid valve, system
A compressor
81
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
3) Downtime
Power-off 25%
solenoid valve of this
failure module
Water pump will stop running after Stop of the last failure module for 3 minutes when any non-resettable
failure not resulting from flow switch occur in all modular units.
Description:
1. Double-Compressor Stop Mode:
When the units meet the Stop condition after point Stop of units,
When both compressors are running with regard to the double-head mode, the unit of longer
running time will be stopped prior to the other, and the other stopped in 30S provided both units
meet the Stop condition.
The compressors will be unloaded and stopped in accordance with the step by step unloading
mode. For example, with regard to the compressor running at 75%, when the condition for
compressor Stop is satisfied after point Stop, the units will firstly be unloaded to 50% then
unloaded to 25% to run for a period of time followed by Stop of compressors.
25% solenoid valve will continue to be powered on for a period of time to facilitate resetting of
the solenoid valve when both compressors are switched off.
The whole process of Stop will be completed upon running of water pump for 3 to 5 minutes
after the compressors are switched off.
Remarks:
① The units Stop command must be executed whenever there is a Stop signal in any case
(except the defrosting process, the user must be prompted whenever there is a Stop signal in
the process of unit defrosting, Stop will not be allowed until the defrosting process is completed
followed by the Stop sequence of the last module) after the compressors meet the requirement
of limitation of the shortest running time. Any controller which has not been output, independent
of the Stop process, shall not be output once again.
② The Stop signal exists when some modules among interconnected modules do not meet the
Stop condition. Unit modules which meet the Stop condition will be stopped as per the normal
Stop procedure, and those which fail to meet the Stop condition will not be stopped in sequence
after entering the normal Stop procedure until they meet the Stop condition. 3 minutes will be
delayed to switch off water pump after Stop of compressors of all unit interconnected modules.
③ The Stop signal exists when all modules among interconnected modules fail to meet the Stop
condition, with output displayed in the table of unit running status as required, and Stop will not
be allowed until the Stop condition is satisfied.
④ The compressors will not be stopped with the variation of water temperature within the shortest
running time once the modular unit is started, except for failure protection.
⑤ The compressors will not be started up with any Start command at the shortest Stop interval or
between two Starts once the modular unit is stopped, and they will not be started up for
operation until the shortest Stop interval and the interval between two Starts of compressors.
Start Reset Temperature Tin≥ T△(T△≥ (Ts+1) The temperature control cycle for
85
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
The module will remain in the status after unloaded to 50% load, and the other module of longer
running time will be unloaded if unloading is still required. All modules running in an interconnected
mode will be unloaded to 50% load, and modules of longer running time will be firstly stopped if
entering water temperature needs to be unloaded.
Compressors and fans will not be started once again to run when entering water temperature meet
the reset Start condition while meeting the shortest Stop time of compressors.
87
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Note:
Control Type of protection
state running 1 Display first kinds of variables
Low superheat 2 Display second kinds of variables
ON Run LowSH
protection 3 Relay output status
Low evaporation
OFF Standby LOP temperature 4 Alarm
protection 5 Start of the protection
High evaporation
6 Control state
POS Locate MOP temperature
protection
High condensing
WAIT Wait HiTcond temperature
protection
CLOSE Close
Keypad:
Button Function
Open the display screen, enter the password to enter the programming
Prg
mode
• In the alarm state, the display alerts the queue;
• When the "producer" level under the rolling parameters, the display
shows the interface
• To exit the programming (maintenance / producer) and display mode;
Esc
• set a parameter, the exit without saving changes
• Display screen navigation;
UP/DOWN • Increase / decrease the value
• from the parameter setting mode, the display switches to
Enter • Confirm the list of parameters and return the value
Terminal Explanation
G\G0 Power supply
VABT Emergency Power Supply
Functional ground
1,2,3,4 Stepper motor power supply
COM1,NO1 Alarm Relay
GND Signal Ground
VREF Sensor power supply
Sensor 1 (pressure) or an external
S1
signal 4 to 20mA
Sensor 2 (temperature) or 0 to 10V
S2
external signal
S3 Sensor 3 (pressure)
S4 Sensor 4 (temperature)
88
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Terminal Explanation Terminal Explanation
Connection tLAN, pLAN, RS485, Modbus ®
DI1 Digital input 1
terminal
DI2 Digital input 2 Connection pLAN, RS485, Modbus ® terminal
Connection tLAN, pLAN, Service port, after removal of the cover need to
aa
RS485, Modbus ® terminal be connected LED
1 Green
2 yellow
3 Brown
4 white
5 sets of personal computers
6 USB / tLAN converter
7 Adapter
ratio of pressure sensor -
8
evaporation pressure
9 NTC suction temperature
10 start-controlled digital input 1
11 free contacts (up to 230Vac)
12 solenoid valve
13 warning signs
89
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Note: this table of pressure values for absolute pressure value, the pressure value ( unit touch screen
display value ) for the vast pressure value and the local atmospheric pressure difference.
Appendix 2: the flow chart of the system
90
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Appendix 2: system working principle map:
LSBLGW380/C,LSBLGW500/C
91
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
LSBLGW600/C,LSBLGW720/C
92
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
LSBLGW880/C,LSBLGW1000/C
93
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
LSBLGW1200/C,LSBLGW1420/C
94
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Appendix 3: capacity table
Ambient temperature
15 20 25 30 35 40 43
Outlet
Model Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
Temp.
Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input
/kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw
5 418.0 93.0 397.3 101.4 380.6 108.1 362.3 115.7 349.8 120.8 324.3 130.8 310.1 137.1
6 436.0 94.5 414.3 103.0 396.6 109.7 376.9 117.3 362.5 122.4 337.5 132.6 322.0 138.8
7 453.9 96.0 431.3 104.5 412.6 111.3 392.0 119.0 376.0 124.0 350.6 134.3 334.5 140.6
8 471.9 97.5 448.3 106.1 428.6 112.9 407.0 120.6 390.7 125.8 363.8 136.1 347.1 142.4
9 489.8 99.0 465.3 107.6 444.7 114.5 422.1 122.3 404.8 127.5 376.9 137.8 359.7 144.2
380 10 507.8 100.4 482.3 109.2 460.7 116.1 437.2 123.9 417.2 129.0 390.1 139.6 370.7 145.7
11 525.8 101.9 499.3 110.7 476.7 117.7 452.2 125.6 433.1 131.0 403.2 141.4 384.9 147.7
12 543.7 103.4 516.3 112.2 492.8 119.3 467.3 127.2 447.2 132.7 416.3 143.1 397.5 149.5
13 561.7 104.9 533.3 113.8 508.8 120.9 482.3 128.9 461.3 134.4 429.5 144.9 410.0 151.3
14 579.6 106.4 550.3 115.3 524.8 122.5 497.4 130.6 475.4 136.1 442.6 146.7 422.6 153.1
15 597.6 107.9 567.3 116.9 540.8 124.1 512.5 132.2 490.5 138.0 455.8 148.4 436.0 155.0
5 527.4 120.7 504.5 131.3 489.1 139.4 470.0 148.9 461.8 154.7 431.7 167.6 413.1 175.3
6 552.2 122.1 527.8 132.8 510.5 141.2 489.6 150.7 478.4 156.8 447.9 169.8 428.7 177.8
7 576.9 123.4 551.1 134.3 532.3 143.0 509.9 152.7 496.0 159.0 465.3 172.3 445.4 180.3
8 601.6 124.7 574.5 135.8 554.0 144.7 530.3 154.7 515.6 161.5 482.7 174.7 462.2 182.8
9 626.3 126.0 597.8 137.3 575.8 146.5 550.6 156.7 534.3 163.8 500.1 177.2 478.9 185.3
500 10 651.0 127.3 621.2 138.8 597.6 148.3 570.9 158.7 550.5 165.8 517.5 179.6 493.2 187.5
11 675.7 128.7 644.5 140.3 619.4 150.0 591.2 160.7 571.5 168.5 535.0 182.1 512.4 190.4
12 700.4 130.0 667.8 141.8 641.2 151.8 611.6 162.7 590.2 170.8 552.4 184.5 529.2 192.9
13 725.0 131.3 691.2 143.3 663.0 153.6 631.9 164.7 608.8 173.2 569.8 187.0 545.9 195.4
14 749.7 132.6 714.5 144.8 684.7 155.3 652.2 166.7 627.4 175.5 587.2 189.4 562.6 197.9
15 774.3 133.9 737.9 146.4 706.9 157.1 673.3 168.8 647.5 178.0 605.9 192.1 580.6 200.6
95
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Ambient temperature
15 20 25 30 35 40 43
Outlet
Model Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
Temp.
Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input
/kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw
5 634.0 133.6 609.2 147.7 591.0 159.7 569.4 172.7 557.4 182.6 526.4 198.7 507.2 208.6
6 653.3 135.9 627.9 150.1 609.5 162.0 587.5 175.1 575.2 184.8 543.7 201.2 524.0 211.1
7 674.0 138.5 647.9 152.8 629.3 164.6 606.9 177.6 594.0 187.0 562.2 203.7 541.8 213.8
8 694.6 141.2 667.9 155.5 649.1 167.2 626.3 180.2 614.5 189.5 580.7 206.3 559.7 216.5
9 715.3 143.8 687.9 158.2 668.9 169.8 645.7 182.8 634.1 191.9 599.3 208.8 577.5 219.2
600 10 735.9 146.4 705.4 160.2 688.7 172.4 665.1 185.4 651.3 194.0 617.8 211.4 593.2 221.6
11 756.6 149.1 727.9 163.5 708.5 175.0 684.4 188.0 673.4 196.6 636.3 213.9 613.2 224.5
12 777.2 151.7 747.9 166.2 728.3 177.6 703.8 190.6 693.1 199.0 654.9 216.5 631.1 227.2
13 797.9 154.3 767.9 168.9 748.1 180.2 723.2 193.1 712.8 201.3 673.4 219.0 648.9 229.9
14 818.5 157.0 787.9 171.6 767.9 182.8 742.6 195.7 732.4 203.7 691.9 221.6 666.8 232.6
15 840.6 159.9 809.2 174.6 789.0 185.4 763.2 198.5 753.5 206.2 711.7 224.3 685.7 235.4
5 767.1 177.6 744.1 189.9 717.3 204.2 690.5 218.7 676.9 227.9 636.8 247.1 611.2 259.2
6 790.8 180.9 767.3 193.6 739.5 207.8 711.8 222.1 697.9 230.8 657.0 250.3 630.8 262.6
7 815.4 184.8 791.4 197.4 763.2 211.5 735.1 225.6 720.0 234.0 678.5 253.9 650.9 266.3
8 840.0 188.6 815.5 201.1 787.0 215.1 758.4 229.1 744.1 237.6 699.9 257.5 671.1 269.9
9 864.6 192.4 839.6 204.9 810.7 218.7 781.8 232.6 767.3 241.0 721.3 261.2 691.2 273.5
720 10 887.3 195.2 863.7 208.6 834.4 222.3 805.1 236.1 787.8 243.7 742.8 264.8 709.9 276.7
11 913.7 200.1 887.8 212.4 858.1 226.0 828.5 239.6 813.5 247.8 764.2 268.4 731.4 280.8
12 938.3 203.9 911.9 216.1 881.8 229.6 851.8 243.1 836.6 251.3 785.7 272.1 751.5 284.5
13 962.9 207.7 936.0 219.9 905.6 233.2 875.1 246.6 859.7 254.7 807.1 275.7 772.5 288.4
14 987.5 211.6 960.1 223.6 929.3 236.8 898.5 250.1 882.8 258.1 828.5 279.4 751.7 268.9
15 1013.0 215.9 985.2 227.3 954.5 240.5 923.8 253.7 907.4 261.9 851.2 283.4 773.6 272.9
96
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Ambient temperature
15 20 25 30 35 40 43
Outlet
Model Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
Temp.
Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input
/kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw
5 953.4 216.6 910.2 235.5 878.1 249.9 840.4 267.1 818.7 277.7 765.1 300.7 732.2 314.9
6 995.4 218.4 949.8 236.9 914.9 252.9 874.6 270.2 848.6 281.2 794.1 304.7 758.6 318.8
7 1037.3 220.8 989.4 239.5 951.9 256.0 909.2 273.6 880.0 285.0 823.8 308.8 787.0 323.0
8 1079.1 223.2 1028.9 242.2 988.8 259.1 943.7 277.0 912.1 289.1 853.4 313.0 815.4 327.2
9 1121.0 225.5 1068.4 244.8 1025.8 262.2 978.2 280.5 943.9 293.1 883.0 317.1 843.7 331.4
880 10 1162.9 227.9 1107.9 247.5 1062.8 265.2 1012.7 283.9 975.7 297.1 912.7 321.2 872.1 335.6
11 1204.7 230.3 1147.5 250.2 1099.7 268.3 1047.3 287.3 1007.4 301.0 942.3 325.3 900.5 339.8
12 1246.6 232.7 1187.0 252.8 1136.7 271.4 1081.8 290.7 1039.2 305.0 971.9 329.4 928.8 344.0
13 1288.4 235.0 1226.5 255.5 1173.7 274.4 1116.3 294.1 1071.0 308.9 1001.5 333.6 957.2 348.2
14 1330.3 237.4 1266.1 258.1 1210.7 277.5 1150.8 297.6 1102.7 312.9 1031.2 337.7 985.6 352.4
15 1372.0 240.3 1305.5 262.1 1247.8 280.6 1185.7 301.3 1136.3 317.2 1061.4 341.9 1015.9 357.0
5 1047.0 244.0 1002.7 264.9 975.8 280.5 940.2 298.8 929.6 309.6 869.0 335.4 831.3 351.3
6 1107.1 246.2 1058.0 267.4 1024.5 283.6 983.2 302.4 961.8 313.7 900.6 339.9 861.2 355.8
7 1156.0 248.3 1104.1 269.9 1067.2 286.8 1022.8 306.1 996.0 318.0 934.0 344.6 893.4 360.7
8 1204.9 250.3 1150.3 272.4 1110.0 290.0 1062.5 309.8 1033.4 322.8 967.5 349.4 925.5 365.5
9 1253.8 252.4 1196.4 274.9 1152.7 293.1 1102.1 313.5 1069.2 327.3 1001.0 354.2 957.7 370.4
1000 10 1302.8 254.5 1260.9 277.5 1195.5 296.3 1141.8 317.2 1105.0 331.9 1034.4 358.9 985.3 374.5
11 1351.7 256.6 1288.6 280.0 1238.2 299.5 1181.4 320.9 1140.9 336.4 1067.9 363.7 1022.0 380.2
12 1400.6 258.7 1334.8 282.5 1280.9 302.6 1221.1 324.6 1176.7 341.0 1101.4 368.4 1054.1 385.0
13 1449.6 260.8 1380.9 285.0 1323.7 305.8 1260.7 328.3 1212.5 345.5 1134.8 373.2 1086.3 389.9
14 1498.5 262.9 1427.0 287.5 1366.4 308.9 1300.4 331.9 1248.3 350.1 1168.3 378.0 1118.4 394.8
15 1536.3 264.9 1464.0 290.1 1403.2 312.1 1336.7 335.8 1286.7 355.0 1203.6 383.0 1152.8 400.1
97
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
Ambient temperature
15 20 25 30 35 40 43
Outlet
Model Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
Temp.
Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input
/kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw /kw
5 1316.6 271.8 1260.9 299.9 1216.0 323.3 1165.7 350.3 1131.1 370.7 1065.1 402.6 1024.8 422.0
6 1367.3 274.4 1308.5 303.0 1259.8 327.2 1206.0 354.6 1166.1 375.7 1098.5 408.1 1056.8 427.7
7 1417.8 276.9 1356.1 306.1 1304.3 331.0 1247.5 359.1 1203.0 381.0 1134.0 413.9 1090.7 433.7
8 1468.3 279.4 1403.7 309.2 1348.8 334.9 1289.0 363.6 1242.7 386.8 1169.5 419.7 1124.5 439.7
9 1518.8 282.0 1451.3 312.3 1393.3 338.7 1330.5 368.1 1281.0 392.3 1205.0 425.6 1158.4 445.8
1200 10 1569.3 284.5 1498.9 315.4 1437.8 342.6 1372.0 372.7 1315.1 397.1 1240.5 431.4 1188.5 451.1
11 1619.8 287.0 1546.5 318.4 1482.3 346.5 1413.5 377.2 1357.6 403.3 1276.0 437.3 1226.2 457.8
12 1670.3 289.6 1594.1 321.5 1526.8 350.3 1455.0 381.7 1395.8 408.9 1311.5 443.1 1260.0 463.8
13 1720.8 292.1 1641.7 324.6 1571.3 354.2 1496.5 386.2 1434.1 414.4 1347.0 449.0 1293.9 469.9
14 1771.3 294.7 1689.3 327.7 1615.8 358.0 1538.0 390.8 1472.4 419.9 1382.5 454.8 1327.8 475.9
15 1821.6 297.1 1736.9 330.8 1661.0 361.9 1580.7 395.5 1513.1 425.8 1420.0 461.0 1363.6 482.3
5 1516.8 353.6 1469.6 378.0 1416.0 406.7 1362.3 435.6 1331.3 453.7 1255.0 492.3 1206.7 516.6
6 1562.6 360.0 1515.5 385.4 1460.4 413.8 1405.3 442.3 1375.8 459.7 1296.5 498.7 1245.4 523.4
7 1610.9 367.5 1563.1 392.7 1507.4 421.0 1451.6 449.2 1419.0 466.0 1339.2 505.9 1285.2 530.6
8 1659.2 375.0 1610.7 400.1 1554.3 428.1 1497.9 456.1 1468.8 473.3 1381.8 513.1 1325.0 537.8
9 1707.6 382.5 1658.3 407.5 1601.3 435.3 1544.2 463.0 1515.3 480.2 1424.4 520.3 1364.7 545.0
1420 10 1755.9 390.0 1705.9 414.9 1648.2 442.4 1590.5 469.9 1561.8 487.0 1467.1 527.5 1404.5 552.1
11 1804.2 397.5 1753.5 422.2 1695.2 449.6 1636.7 476.9 1608.3 493.8 1509.7 534.7 1444.2 559.3
12 1852.6 405.0 1801.1 429.6 1742.1 456.7 1683.0 483.8 1654.8 500.7 1552.3 541.9 1484.0 566.5
13 1900.9 412.5 1848.7 437.0 1789.1 463.8 1729.3 490.7 1701.3 507.5 1595.0 549.1 1525.4 574.3
14 1949.2 420.0 1896.3 444.3 1836.0 471.0 1775.6 497.6 1747.8 514.3 1637.6 556.3 1491.7 535.5
15 2000.1 428.5 1945.7 451.7 1885.5 478.1 1825.3 504.8 1794.5 521.6 1681.4 564.3 1538.1 543.9
98
3P+N+PE 50Hz 380-400V
N
N X1 X2 X2 2/1B
L1 1L1 X1 L1 2/1B
L2 1L2
L3 1L3
PE 1QF 261A
3QF 16A
3*1.5mm+1*1.5mm, 11.6A
2QF 1A
0.75mm,0.1A
KR1 L1 L2 L3 125
127
KM1 KM2 KM3 KM4 KM5 KM6
16 15 18 TA1 TA2
FR U11V11W11 U21V21W21 U31V31W31 U41V41W41 U51V51W51 U61V61W61
2 32 FR1 FR2 FR3 FR4 FR5 FR6
U1 V1 W1 PE U2 V2 W2 PE U3 V3 W3 PE U4 V4 W4 PE U5 V5 W5 PE U6 V6 W6 PE
123
4/9B 4/9C
KM11 KM12
3P 50Hz 380-400V 2.2kW 5.8A
3*70mm+1*35mm,132A 3*70mm
W
V
U
Air-cooled screw chiller technical manual (PLC series)
PE
L1 L2 L3
Appendix 4: circuit principle reference map
3P 50Hz M
JTX-A 380-400V 228A 3~
L N S1 S2 M1 M2
Z
X
Y
2
20
LSBLGW380/C WIRING DIAGRAM
L12 1X:22
Nb 1X:21
1X:43
1X:44
KM13
4/7B
4/7C
3/12C
3/12C
1ST1 1ST2
MCAC-CTSM-2013-01
99
T1 0.75mm,3A
L1 QF1 L1' L11 QF2 L21 FU1 QF4 L41 FU2 L51
1/12B 3/1B
1P 50Hz 1P 50Hz 6A 4A
1/12B N 230V 6A Na 230V 4A
N L
3/1B
~220V
L31 A10
24V
+V -V
57 N2
4/10B
FU3 59 84 86 88 90 4/10B
2A
A8 EVD
53 51 55
1X:25 1X:28
M EH1 EH2 76 78 80 82
1X:75 1X:76
NTC KA1
Air-cooled screw chiller technical manual (PLC series)
1X:26 1X:27
6/9F
6/10F
MCAC-CTSM-2013-01
100
SB
2/12B L51 L12 4/2F
1X:23
2/12B Na Nb SP4 4/2F
1X:24
61 1/3G
FR 1/3G
63
KA1
65
101
2
3/6E 6/1E
3/6E 4 6/1F
1X:36 X:2 X:3 X:6 1X:371X:401X:411X:44 1X:481X:49 X:7 1X:521X:53
SQ1 SQ2 SP1 SP2 SQ3 KM12 SL1 SP3 FR FR1-6 KR1 SA1 SF1 SA
100
1X:35 X:1 X:4 X:5 1X:381X:391X:421X:43 KM11 1X:471X:50 X:8 1X:511X:54
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
3/6E
A1 TM218LDAE40DRPHN 5/2E
92 94 96 98 1 3 5 7 9 11 13 15 17 19 21 23
X:9 X:10 X:11 X:12 X:13 1X:1 1X:4 1X:5 1X:8
KA3 KA1 YV1 YV2 YV3 YV4 KM1 KM2 KM3 KM4 KM5 KM6
Air-cooled screw chiller technical manual (PLC series)
X:14 1X:2 1X:3 1X:6 1X:7 FR1 FR2 FR3 FR4 FR5 FR6
Nb Nb
3/12B 5/2C
L12 1X:29 1X:30 L13
3/12B 5/2C
SA
MCAC-CTSM-2013-01
102
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6/5A
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 COM1COM1
A3 TM2DRA16RT
KA6 KA7
X:22 X:21
43
X:19 X:20
41
YV5 YV6 YV7 YV8 YV9 KA4 KA2 KA5
X:18 X:17
39
X:15 X:16
37
1X:19 1X:20
35
1X:18 1X:17
33
1X:15 1X:16
31
1X:14 1X:13
29
1X:11 1X:12
27
1X:10 1X:9
25
A2
TM2DOCKN
L13
Nb
4/12D
4/12F
4/12F
103
5/12E
1X:55 1X:67
40 A A 64
1X:56 1X:68 RT5
RT1 B' B'
IN0
IN4
42 66
1X:57 1X:69
44 B B 68 P P
1X:58 TP1 TP2
46 A A + I_ + I_
1X:59
RT2 B' B'
IN1
IN5
48
1X:73
1X:72
1X:71
1X:70
1X:60
50 B A6 B 70 74
NC NC
1X:61
52 A A
1X:62
B' B'
IN2
IN6
54
TM2ARI8LT
1X:63
56 B B A7TM2AMM6HT
1X:64
58 A A
1X:65
RT4 B' B'
IN3
IN7
60
1X:66
62 B B
78 76
Air-cooled screw chiller technical manual (PLC series)
4/12B 2
+
4/12B 4
OV
2/8E
2/7E
MCAC-CTSM-2013-01
104
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR6 26 A1
8 M M A2
M 3~ 27
9 KT1 28 A3
10 KM1~KM6 29 A6
11 SB 30 A7
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 HMI
13 EH1 EH2 32 A8
14 SQ1 33 A9
15 SQ2 34 A10
16 KA1 35
17 SA
18 SA1
19 SL1
MCAC-CTSM-2013-01
105
3P+N+PE 50Hz 380-400V
N 2/1B
N X1 X2 X2 X3 X3
L1 L1 L1 2/1B
L2 L2
L3 L3
PE 1QF 375A
3QF 16A
3*1.5mm+1*1.5mm
2QF 1A 11.6A
0.75mm,0.1A
KR1 L1 L2 L3 125
127
KM1 KM2 KM3 KM4 KM5 KM6 KM7 KM8
16 15 18 TA1 TA2
FR U11V11W11 U21V21W21 U31V31W31 U41V41W41 U51V51W51 U61V61W61 U71V71W71 U81V81W81
2 32 FR1 FR2 FR3 FR4 FR5 FR6 FR7 FR8
U1 V1 W1 PE U2 V2 W2 PE U3 V3 W3 PE U4 V4 W4 PE U5 V5 W5 PE U6 V6 W6 PE U7 V7 W7 PE U8 V8 W8 PE
123
4/9B 4/9C
KM11 KM12
3P 50Hz 380-400V 2.2kW 5.8A
3*95mm+1*50mm,191A
3*95mm
Air-cooled screw chiller technical manual (PLC series)
W
V
U
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 331A 3~
L N S1 S2 M1 M2
Z
X
Y
2
20
LSBLGW500/C WIRING DIAGRAM
1X:43
1X:44
L12 1X:22
Nb 1X:21
KM13
4/7B
4/7C
3/12C
3/12C
1ST1 1ST2
MCAC-CTSM-2013-01
106
0.75mm,3A
QF1 L1' T1 L11 QF2 L21 FU1 QF4 L41 FU2 L51
1/12B L1 3/1B
1P 50Hz 1P 50Hz 6A 4A
1/12B N 230V 6A Na 230V 4A
N L
3/1B
~220V
A10
L31 24V
+V -V
57 N2
4/10B
FU3 59 84 86 88 90 4/10B
2A
A8 EVD
53 51 55
1X:25 1X:28
M EH1 EH2 76 78 80 82
1X:75 1X:76
Air-cooled screw chiller technical manual (PLC series)
NTC KA1
1X:26 1X:27
6/9F
6/10F
MCAC-CTSM-2013-01
107
SB
2/12B L51 L12 4/2F
1X:23
2/12B Na Nb
SP4 4/2F
1X:24
61 1/3G
FR 1/3G
63
KA1
65
108
2
3/6E 6/1E
3/6E 4 6/1F
1X:36 X:2 X:3 X:6 1X:371X:401X:411X:44 1X:481X:49 X:7 1X:521X:53
SQ1 SQ2 SP1 SP2 SQ3 KM12 SL1 SP3 FR FR1-8 KR1 SA1 SF1 SA
100
1X:35 X:1 X:4 X:5 1X:381X:391X:421X:43 KM111X:471X:50 X:8 1X:511X:54
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
3/6E
A1 TM218LDAE40DRPHN 5/2E
X:14 1X:2 1X:3 1X:6 1X:7 FR1 FR2 FR3 FR4 FR5 FR6 FR7 FR8
Nb Nb
3/12B 5/2C
L12 1X:29 1X:30 L13
3/12B 5/2C
SA
MCAC-CTSM-2013-01
109
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6/5A
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15COM1COM1
KA6 KA7
X:22 X:21
43
X:19 X:20
41
YV5 YV6 YV7 YV8 YV9 KA4 KA2 KA5
X:18 X:17
39
A3 TM2DRA16RT
X:15 X:16
37
1X:19 1X:20
35
1X:18 1X:17
33
1X:15 1X:16
31
1X:14 1X:13
29
1X:11 1X:12
27
1X:10 1X:9
25
A2
TM2DOCKN
L13
Nb
4/12D
4/12F
4/12F
110
5/12E
1X:55 1X:67
40 A A 64
1X:56 RT5
RT1 B'
IN0
IN4
42 B' 66 1X:68
1X:57
B
A6 1X:69
44 B 68 P P
1X:58 TP1 TP2
46 A A + I_ + I_
1X:59
RT2 B' B'
IN1
IN5
48
1X:73
1X:72
1X:71
1X:70
1X:60
50 B B 70 74
TM2ARI8LT
NC NC
1X:61
52 A A
1X:62
B' B'
IN2
IN6
54
1X:63
56 B B A7TM2AMM6HT
1X:64
58 A A
1X:65
RT4 B' B'
IN3
IN7
60
1X:66
62 B B
2 78 76
Air-cooled screw chiller technical manual (PLC series)
4/12B +
4/12B 4
OV
2/8E
2/7E
MCAC-CTSM-2013-01
111
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR8 26 A1
8 M M A2
M 3~
27
9 KT1 28 A3
10 KM1~KM8 29 A6
11 SB 30 A7
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 HMI
13 EH1 EH2 32 A8
14 SQ1 33 A9
15 SQ2 34 A10
16 KA1 35
17 SA
18 SA1
19 SL1
MCAC-CTSM-2013-01
112
3P+N+PE 50Hz 380-400V
N B
N X1 X1 X2 X2 X3 X3 L1 2/1
L1 L1 2/1B
L2 L2
L3 L3
PE 1QF 385A
3QF 16A
3*1.5mm+1*1.5mm
2QF 1A 11.6A
0.75mm,0.1A
U01V01W01
KR1 L1 L2 L3 125
127
KM1 KM2 KM3 KM4 KM5 KM6 KM7 KM8 KM9 KM10
12 11 14 TA1 TA2
FR U11V11W11 U21V21W21 U31V31W31 U41V41W41 U51V51W51 U61V61W61 U71V71W71 U81V81W81 U91V91W91 U101V101W101
2 32 FR1 FR2 FR3 FR4 FR5 FR6 FR7 FR8 FR9 FR10
U1 V1 W1 PE U2 V2 W2 PE U3 V3 W3 PE U4 V4 W4 PE U5 V5 W5 PE U6 V6 W6 PE U7 V7 W7 PE U8 V8 W8 PE U9 V9 W9 PE U10V10W10 PE
123
4/9B 4/9C
KM11 KM12
3P 50Hz 380-400V 2.2kW 5.8A
3*95mm+1*50mm,191A
3*95mm
W
V
U
PE
Air-cooled screw chiller technical manual (PLC series)
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 330A 3~
L N S1 S2 M1 M2
Z
X
Y
2
20
LSBLGW600/C WIRING DIAGRAM
1X:43
1X:44
L12 1X:22
Nb 1X:21
KM13
4/7B
4/7C
3/12C
3/12C
1ST1 1ST2
MCAC-CTSM-2013-01
113
0.75mm,3A
QF1 L1' T1 L11 QF2 L21 FU1 QF4 L41 FU2 L51
1/12B L1 3/1B
1P 50Hz 1P 50Hz 6A 4A
1/12B N 230V 6A Na 230V 4A
N L
3/1B
~220V
A10
L31 24V
+V -V
57 N2
4/10B
FU3 59 84 86 88 90 4/10B
2A
A8 EVD
53 51 55
1X:25 1X:28
M EH1 EH2 76 78 80 82
1X:75 1X:76
Air-cooled screw chiller technical manual (PLC series)
NTC KA1
1X:26 1X:27
6/9F
6/10F
MCAC-CTSM-2013-01
114
SB
2/12B L51 L12 4/2F
1X:23
2/12B Na Nb SP4 4/2F
1X:24
61 1/3G
FR 1/3G
63
KA1
65
115
2
3/6E 6/1E
3/6E 4 6/1F
1X:36 X:2 X:3 X:6 1X:371X:401X:411X:44 1X:481X:49 X:7 1X:521X:53
SQ1 SQ2 SP1 SP2 SQ3 KM12 SL1 SP3 FR FR1-10 KR1 SA1 SF1 SA
100
1X:35 X:1 X:4 X:5 1X:381X:391X:421X:43 KM11 1X:471X:50 X:8 1X:511X:54
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
3/6E
A1 TM218LDAE40DRPHN 5/2E
X:14 1X:2 1X:3 1X:6 1X:7 FR1 FR2 FR3 FR4 FR5 FR6 FR7 FR8 FR9 FR10
Nb Nb
3/12B 5/2C
L12 1X:29 1X:30 L13
3/12B 5/2C
SA
MCAC-CTSM-2013-01
116
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6/5A
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15COM1COM1
KA6 KA7
X:22 X:21
43
X:19 X:20
41
YV5 YV6 YV7 YV8 YV9 KA4 KA2 KA5
X:18 X:17
39
A3 TM2DRA16RT
X:15 X:16
37
1X:19 1X:20
35
1X:18 1X:17
33
1X:15 1X:16
31
1X:14 1X:13
29
1X:11 1X:12
27
1X:10 1X:9
25
A2
TM2DOCKN
L13
Nb
4/12D
4/12F
4/12F
117
5/12E
1X:55 1X:67
40 A A 64
1X:56 RT5
RT1 B'
IN0
IN4
42 B' 66 1X:68
1X:57
B
A6 1X:69
44 B 68 P P
1X:58 TP1 TP2
46 A A + I_ + I_
1X:59
RT2 B' B'
IN1
IN5
48
1X:73
1X:72
1X:71
1X:70
1X:60
50 B B 70 74
TM2ARI8LT
NC NC
1X:61
52 A A
1X:62
B' B'
IN2
IN6
54
1X:63
56 B B A7TM2AMM6HT
1X:64
58 A A
1X:65
RT4 B' B'
IN3
IN7
60
1X:66
62 B B
2 78 76
Air-cooled screw chiller technical manual (PLC series)
4/12B +
4/12B 4
OV
2/8E
2/7E
MCAC-CTSM-2013-01
118
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR10 26 A1
8 M M M 27 A2
3~
9 KT1 28 A3
10 KM1~KM10 29 A6
11 SB 30 A7
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 HMI
13 EH1 EH2 32 A8
14 SQ1 33 A9
15 SQ2 34 A10
16 KA1 35
17 SA
18 SA1
19 SL1
MCAC-CTSM-2013-01
119
3P+N+PE 50Hz 380-400V
N 2/1B
N X1 X1 X2 X2 X3 X3
L1 L1 L1 2/1B
L2 L2
L3 L3
PE 1QF 545A
3QF 16A
3*1.5mm+1*1.5mm
2QF 1A 11.6A
0.75mm,0.1A
KR1 L1 L2 L3 125
127
KM1 KM2 KM3 KM4 KM5 KM6 KM7 KM8 KM9 KM10
12 11 14 TA1 TA2
FR U11V11W11 U21V21W21 U31V31W31 U41V41W41 U51V51W51 U61V61W61 U71V71W71 U81V81W81 U91V91W91 U101V101W101
2 32 FR1 FR2 FR3 FR4 FR5 FR6 FR7 FR8 FR9 FR10
U1 V1 W1 PE U2 V2 W2 PE U3 V3 W3 PE U4 V4 W4 PE U5 V5 W5 PE U6 V6 W6 PE U7 V7 W7 PE U8 V8 W8 PE U9 V9 W9 PE U10V10W10 PE
123
4/9B 4/9C
KM11 KM12
3P 50Hz 380-400V 2.2kW 5.8A
3*150mm+1*95mm,283A
3*150mm
W
Air-cooled screw chiller technical manual (PLC series)
V
U
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 490A 3~
L N S1 S2 M1 M2
Z
X
Y
2
20
LSBLGW720/C WIRING DIAGRAM
1X:43
1X:44
L12 1X:22
Nb 1X:21
KM13
4/7B
4/7C
3/12C
3/12C
1ST1 1ST2
MCAC-CTSM-2013-01
120
0.75mm,3A
QF1 L1' T1 L11 QF2 L21 FU1 QF4 L41 FU2 L51
1/12B L1 3/1B
1P 50Hz 1P 50Hz 6A 4A
1/12B N 230V 6A Na 230V 4A
N L
3/1B
~220V
A10
L31 24V
+V -V
57 N2
4/10B
FU3 59 84 86 88 90 4/10B
2A
A8 EVD
53 51 55
1X:25 1X:28
M EH1 EH2 76 78 80 82
1X:75 1X:76
Air-cooled screw chiller technical manual (PLC series)
NTC KA1
1X:26 1X:27
6/9F
6/10F
MCAC-CTSM-2013-01
121
SB
2/12B L51 L12 4/2F
1X:23
2/12B Na Nb SP4 4/2F
1X:24
61 1/3G
FR 1/3G
63
KA1
65
122
2
3/6E 6/1E
3/6E 4 6/1F
1X:36 X:2 X:3 X:6 1X:371X:401X:411X:44 1X:481X:49 X:7 1X:521X:53
SQ1 SQ2 SP1 SP2 SQ3 KM12 SL1 SP3 FR FR1-10 KR1 SA1 SF1 SA
100
1X:35 X:1 X:4 X:5 1X:381X:391X:421X:43 KM11 1X:471X:50 X:8 1X:511X:54
6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38
3/6E
A1 TM218LDAE40DRPHN 5/2E
X:14 1X:2 1X:3 1X:6 1X:7 FR1 FR2 FR3 FR4 FR5 FR6 FR7 FR8 FR9 FR10
Nb Nb
3/12B 5/2C
L12 1X:29 1X:30 L13
3/12B 5/2C
SA
MCAC-CTSM-2013-01
123
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2013-01
6/5A
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15COM1COM1
KA6 KA7
X:22 X:21
43
X:19 X:20
41
YV5 YV6 YV7 YV8 YV9 KA4 KA2 KA5
X:18 X:17
39
A3 TM2DRA16RT
X:15 X:16
37
1X:19 1X:20
35
1X:18 1X:17
33
1X:15 1X:16
31
1X:14 1X:13
29
1X:11 1X:12
27
1X:10 1X:9
25
A2
TM2DOCKN
L13
Nb
4/12D
4/12F
4/12F
124
5/12E
1X:55 1X:67
40 A A 64
1X:56 RT5
RT1 B'
IN0
IN4
42 B' 66 1X:68
1X:57
B
A6 1X:69
44 B 68 P P
1X:58 TP1 TP2
46 A A + I_ + I_
1X:59
RT2 B' B'
IN1
IN5
48
1X:73
1X:72
1X:71
1X:70
1X:60
50 B B 70 74
TM2ARI8LT
NC NC
1X:61
52 A A
1X:62
B' B'
IN2
IN6
54
1X:63
56 B B A7TM2AMM6HT
1X:64
58 A A
1X:65
RT4 B' B'
IN3
IN7
60
1X:66
62 B B
2 78 76
Air-cooled screw chiller technical manual (PLC series)
4/12B +
4/12B 4
OV
2/8E
2/7E
MCAC-CTSM-2013-01
125
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR10 26 A1
8 M M 27 A2
M 3~
9 KT1 28 A3
10 KM1~KM10 29 A6
11 SB 30 A7
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 HMI
13 EH1 EH2 32 A8
14 SQ1 33 A9
15 SQ2 34 A10
16 KA1 35
17 SA
18 SA1
19 SL1
MCAC-CTSM-2013-01
126
3P+N+PE 50Hz 380-400V
N X1 1X1 1X1 1X2
L1 1L1
L2 1L2
L3 1L3
PE 1.1QF 261A
1.3QF 16A
3*1.5mm+1*1.5mm
2QF 1A 11.6A
0.75mm,0.1A
L1 L2 L3 KR1 1.125
2/1B 1.127 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6
2/1B
2/1B 16 15 18 1TA1 1TA2
1.U11
1.U21
1.U31
1.U41
1.U51
1.U61
1.W11
1.W21
1.W31
1.W41
1.W51
1.W61
1.V11
1.V21
1.V31
1.V41
1.V51
1.V61
W1
V1
U1
PE
Air-cooled screw chiller technical manual (PLC series)
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 228A 3~
L N S1 S2 M1 M2
2
Z1
X1
Y1
LSBLGW880/C WIRING DIAGRAM
Nb 1X:21
L12 1X:22
1.20 1X:43
1X:44
1KM13
5/7C
5/7B
4/12C
4/12C
1ST1 1ST2
MCAC-CTSM-2013-01
127
3P+N+PE 50Hz 380-400V
1/3D N 2X1 2X1 2X2 2X2
1/3D L1 2L1
L2 2L2
1/3D L3
1/3D PE 2L3
1/3D 2.1QF 375A
3*1.5mm+1*1.5mm
11.6A
2.125
2.127 2KM1 2KM2 2KM3 2KM4 2KM5 2KM6 2KM7 2KM8
2TA1 2TA2
2.U71
2.U81
2.U11
2.U21
2.U31
2.U41
2.U51
2.U61
2.W11
2.W21
2.W31
2.W41
2.W51
2.W61
2.V71
2.W71
2.V81
2.W81
2.FR
2.V11
2.V21
2.V31
2.V41
2.V51
2.V61
W2
V2
U2
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 331A 3~
L N S1 S2 M1 M2
2
Z2
X2
Y2
Nb 2X:21
L12 2X:22
2X:44
2.20 2X:43
2KM13
4/12D
4/12C
5/11C
5/11B
2ST1 2ST2
MCAC-CTSM-2013-01
128
T1 L11 QF2 L21 FU1 0.75mm,3A QF4 L41 FU2 L51 4/1B
L1 QF1 L1'
1/3D 1P 50Hz 1P 50Hz 6A 4A
N 230V 6A Na 230V 4A 4/1B
1/3D L31 N L
~ 220V
M M
3/9C
3/9C
A10
24V
+V -V 1X:77 1X:781X:791X:80 2X:77 2X:782X:792X:80
57 N2
FU3 59
3/5B
3/5B
7/8B
7/8B
5/10B
5/10B
2A 1.84 1.86 1.88 1.90
EH1 M 1EH2 2EH2 1.76 1.78 1.80 1.82 2.76 2.78 2.80 2.82
1X:75
1X:76
2X:75
2X:76
Air-cooled screw chiller technical manual (PLC series)
7/8G
7/7G
MCAC-CTSM-2013-01
129
SB1
L51 L12 L12
3/12B 5/2F
1X:23 2X:23
3/12B Na Nb Nb
1SP4 2SP4 5/2F
1X:24 2X:24 L12
1/2G
1.61 2.61
Nb
1FR 2FR 1/3G
L12
1.63 2.63 2/2G
Nb
2/3G
1KA1 2KA1 1X:31 2
1.65 2.65 5/8B
L
N
1.SL1
1KM13 1KM11 1KM13 1KM12 2KM13 2KM11 2KM13 2KM12
HMI
1.67 1.71 2.67 2.71 1X:32
N L 1.24 5/8C
24V 0V FG
~220V 1KT1 1KM12 1KT1 2KT1 2KM12 2KT1
A9 RS485
24V 5/1D 2X:31 2
+V -V 1.73 2.73
4 1.75 1.69 2.75 2.69 7/7B
5/3B L
2 5/3B 1KM11 1KM12 1KM13 1KT1 2KM11 2KM12 2KM13 2KT1 2.SL1
N
Air-cooled screw chiller technical manual (PLC series)
130
2
4/4E 7/1H
4/4E 4 7/1H
1X:36 X:2 X:3 X:6 1X:37 1X:40 1X:41 1X:44 1X:48 1X:49 X:7 1X:52 1X:53 2X:40 2X:41 2X:44
SQ1 SQ2 1.SP1 1.SP21.SQ3 1KM12 1.SL1 1.SP3 1.FR 1.FR1-6 KR1 SA1 1.K5 SA 2.SP1 2.SP2 2.SQ3
1.100
1X:35 X:1 X:4 X:5 1X:38 1X:39 1X:42 1X:43 1KM111X:47 1X:50 X:8 1X:51 1X:54 2X:39 2X:42 2X:43
1.6 1.8 1.10 1.12 1.14 1.16 1.18 1.20 1.22 1.24 1.26 1.28 1.30 1.32 1.34 1.36 1.38 2.16 2.18 2.20
A1 TM218LDAE40DRPHN 6/3D
4/4E
92 94 96 98 1.1 1.3 1.5 1.7 1.9 1.11 1.13 1.15 1.17 1.191.21 1.23
X:9 X:10 X:11 X:12 X:13 1X:1 1X:4 1X:5 1X:8
KA3 1KA1 1YV1 1YV2 1YV3 1YV4 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6
4/12B Nb
6/1E
L12 L12 1X:29 1X:30 L13
4/12B 6/1F
SA
MCAC-CTSM-2013-01
131
2X:10
2X:14
2X:15
2X:18
X:23
2X:11
2FR2 2FR3 2FR4 2FR5 2FR6 2FR7 2FR8
2YV5 2YV6 2YV7 2YV8 2YV9 2KA2
A2 2KM2 2KM3 2KM42KM5 2KM62KM7 2KM8
2X:9
2X:13
2X:12
2X:16
2X:17
X:24
2.15 2.172.192.21 2.23 2.25 2.27 2.29 2.31 2.33 2.37
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15COM1COM1
A4 TM2DRA16RT
TM2DOCKN
5/12D
A3 TM2DRA16RT 7/5C
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 COM1COM1
1.25 1.27 1.29 1.31 1.33 1.35 1.37 1.39 1.41 1.43 2.3 2.5 2.7 2.9 2.11 2.13
1X:20
X:20
1X:13
1X:12
1X:16
1X:17
1X:9
X:16
X:17
2X:4
2X:5
2X:8
X:21
2X:1
2KM1
1YV5 1YV6 1YV7 1YV8 1YV9 KA4 1KA2 KA5 KA6 KA7 2KA1 2YV1 2YV2 2YV3 2YV4 2FR1
Air-cooled screw chiller technical manual (PLC series)
Nb
1X:10
2X:3
1X:14
1X:19
1X:15
1X:18
X:15
X:18
X:19
X:22
2X:2
2X:6
2X:7
1X:11
5/12F
5/12F L13
MCAC-CTSM-2013-01
132
1X:55 1X:67 2X:482X:49 2X:52 2X:53
1.40 A A 2.64
1X:56 2KM12 2.SL1 2.SP3 2.FR 2.K5
B'
IN0
IN4
1.42 B' 2.66 1X:68
1.RT1
1.RT5
2.100 2.FR1-8
1X:57 A6 1X:69
1.44 B B 2.68 2KM11 2X:472X:50 2X:51 2X:51
1X:58 2X:61 2.22 2.24 2.26 2.28 2.30 2.36 2.38
1.46 A A 2.52
1X:59 2X:62 I0 I1 I2 I3 I4 I5 I6 I7 COM COM I8 I9 I10 I11 I12 I13 I14 I15 COM COM
B' B' 6/11D
IN1
IN5
1.48 2.54
1.RT2
1X:60 2X:63 A5 TM2DDI16DT
1.50 B B 2.56
TM2ARI8LT
NC NC
1X:61 2X:67 1.TP1 1.TP2 2.TP1 2.TP2
1.52 A A 2.64 P P P P
1X:62 2X:68
B' + I_ + I_ + I_ + I_
IN2
IN6
1.54 B' 2.66
2.RT5
1X:63 2X:69
1.56 B
1X:73
2X:73
1X:72
2X:72
1X:71
B 2.68
1X:70
2X:71
2X:70
2 7/1H
1X:64 1.70 1.74 2.70 2.74 4
1.58 A A 7/1H
1X:65
B' B'
IN3
IN7
1.60
1.RT4
1X:66
Air-cooled screw chiller technical manual (PLC series)
1.62 B B
+ A7TM2AMM6HT
OV
4 2
5/12B 5/12B
MCAC-CTSM-2013-01
133
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR8 26 A1
8 M M 27 A2
M 3~
9 KT1 28 A3 A4
10 KM1~KM8 29 A5
11 SB 30 A6
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 A7
14 SQ1 33 A8
15 SQ2 34 A9
16 KA1 35 A10
17 SA 36
18 SA1
19 SL1
MCAC-CTSM-2013-01
134
3P+N+PE 50Hz 380-400V
N X1 1X1 1X1 1X2 1X2
L1 1L1
L2 1L2
L3 1L3
PE 1.1QF 375A
1.3QF 16A
3*1.5mm+1*1.5mm
2QF 1A 11.6A
0.75mm,0.1A
L1 L2 L3 KR1 1.125
2/1B 1.127 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6 1KM7 1KM8
2/1B
2/1B 16 15 18 1TA1 1TA2
1.U11
1.U21
1.U31
1.U41
1.U51
1.U61
1.U71
1.U81
1.W11
1.W21
1.W31
1.W41
1.W51
1.W61
1.W71
1.W81
1.V11
1.V21
1.V31
1.V41
1.V51
1.V61
1.V71
1.V81
W1
V1
U1
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 331A 3~
L N S1 S2 M1 M2
2
Z1
X1
Y1
LSBLGW1000/C WIRING DIAGRAM
Nb 1X:21
L12 1X:22
1.20 1X:43
1X:44
1KM13
5/7C
5/7B
4/12C
4/12C
1ST1 1ST2
MCAC-CTSM-2013-01
135
3P+N+PE 50Hz 380-400V
1/3D N 2X1 2X1 2X2 2X2
1/3D L1 2L1
2L2
1/3D L2 2L3
1/3D L3
1/3D PE 2.1QF 375A
3*1.5mm+1*1.5mm
11.6A
2.125
2.127 2KM1 2KM2 2KM3 2KM4 2KM5 2KM6 2KM7 2KM8
2TA1 2TA2
2.U11
2.U21
2.U31
2.U41
2.U51
2.U61
2.U71
2.U81
2.FR
2.W11
2.W21
2.W31
2.W41
2.W51
2.W61
2.W71
2.W81
2.V11
2.V21
2.V31
2.V41
2.V51
2.V61
2.V71
2.V81
W2
V2
U2
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 331A 3~
L N S1 S2 M1 M2
2
Z2
X2
Y2
Nb 2X:21
L12 2X:22
2X:44
2.20 2X:43
2KM13
4/12D
4/12C
5/11C
5/11B
2ST1 2ST2
MCAC-CTSM-2013-01
136
T1 L11 QF2 L21 FU1 0.75mm,3A QF4 L41 FU2 L51 4/1B
L1 QF1 L1'
1/3D 1P 50Hz 1P 50Hz 6A 4A
N 230V 6A Na 230V 4A 4/1B
1/3D L31 N L
~ 220V
M M
3/9C
3/9C
A10
24V
+V -V 1X:77 1X:781X:791X:80 2X:772X:782X:792X:80
57 N2
FU3 59
3/5B
3/5B
5/10B
5/10B
1.84 1.86 1.88 1.90 1.84 2.86 2.88 2.90
7/8B
7/8B
2A
EH1 M 1EH2 2EH2 1.76 1.78 1.80 1.82 2.76 2.78 2.80 2.82
1X:75
1X:76
2X:75
2X:76
7/8G
7/7G
7/9G
7/8G
MCAC-CTSM-2013-01
137
SB1
L51 L12 L12
3/12B 5/2F
1X:23 2X:23
3/12B Na Nb Nb
1SP4 2SP4 5/2F
1X:24 2X:24 L12
1/2G
1.61 2.61
Nb
1FR 2FR 1/3G
L12
1.63 2.63 2/2G
Nb
2/3G
1KA1 2KA1 1X:31 2
1.65 2.65 5/8B
L
N
1.SL1
1KM13 1KM11 1KM13 1KM12 2KM13 2KM11 2KM13 2KM12
HMI
1.67 1.71 2.67 2.71 1X:32
N L 1.24 5/8C
24V 0V FG
~220V 1KT1 1KM12 1KT1 2KT1 2KM12 2KT1
A9 RS485
24V 5/1D 2X:31 2
+V -V 1.73 2.73
4 1.75 1.69 2.75 2.69 7/7B
5/3B L
2 5/3B 1KM11 1KM12 1KM13 1KT1 2KM11 2KM12 2KM13 2KT1 2.SL1
N
Air-cooled screw chiller technical manual (PLC series)
138
2
4/4E 7/1H
4/4E 4 7/1H
1X:36 X:2 X:3 X:6 1X:37 1X:40 1X:41 1X:44 1X:48 1X:49 X:7 1X:52 1X:53 2X:40 2X:41 2X:44
SQ1 SQ2 1.SP1 1.SP2 1.SQ3 1KM12 1.SL1 1.SP3 1.FR 1.FR1-8 KR1 SA1 1.K5 SA 2.SP1 2.SP2 2.SQ3
1.100
1X:35 X:1 X:4 X:5 1X:38 1X:39 1X:42 1X:43 1KM111X:47 1X:50 X:8 1X:51 1X:54 2X:39 2X:42 2X:43
1.6 1.8 1.10 1.12 1.14 1.16 1.18 1.20 1.22 1.24 1.26 1.28 1.301.32 1.34 1.36 1.38 2.16 2.18 2.20
A1 TM218LDAE40DRPHN 6/3D
4/4E
92 94 96 98 1.1 1.3 1.5 1.7 1.9 1.11 1.13 1.15 1.17 1.191.21 1.23
X:9 X:10 X:11 X:12 X:13 1X:1 1X:4 1X:5 1X:8
KA3 1KA1 1YV1 1YV2 1YV3 1YV4 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6 1KM7 1KM8
4/12B Nb
6/1E
L12 L12 1X:29 1X:30 L13
4/12B 6/1F
SA
MCAC-CTSM-2013-01
139
2X:10
X:23
2X:14
2X:15
2X:18
2X:11
2FR2 2FR3 2FR4 2FR5 2FR62FR7 2FR8
2YV5 2YV6 2YV7 2YV8 2YV9 2KA2
A2 2KM2 2KM3 2KM42KM5 2KM62KM7 2KM8
2X:9
2X:13
2X:12
2X:16
2X:17
X:24
2.15 2.172.192.21 2.23 2.25 2.27 2.29 2.31 2.33 2.37
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15COM1COM1
A4 TM2DRA16RT
TM2DOCKN
5/12D
A3 TM2DRA16RT 7/5C
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 COM1COM1
1.25 1.27 1.29 1.31 1.33 1.35 1.37 1.39 1.41 1.43 2.3 2.5 2.7 2.9 2.11 2.13
1X:20
1X:13
X:20
1X:12
1X:16
1X:17
1X:9
X:16
X:17
2X:4
2X:5
2X:8
X:21
2X:1
2KM1
1YV5 1YV6 1YV7 1YV8 1YV9 KA4 1KA2 KA5 KA6 KA7 2KA1 2YV1 2YV2 2YV3 2YV4 2FR1
Air-cooled screw chiller technical manual (PLC series)
Nb
1X:10
2X:3
1X:14
1X:19
1X:15
1X:18
X:15
X:18
X:19
X:22
2X:2
2X:6
2X:7
1X:11
5/12F
5/12F L13
MCAC-CTSM-2013-01
140
1X:55 1X:67 2X:482X:49 2X:52 2X:53
1.40 A A 2.64
1X:56 1X:68 2KM12 2.SL1 2.SP3 2.FR 2.K5
B' B'
IN0
IN4
1.42 2.66
1.RT1
1.RT5
2.100 2.FR1-8
1X:57 A6 1X:69
1.44 B B 2.68 2KM11 2X:472X:50 2X:51 2X:51
1X:58 2X:61 2.22 2.24 2.26 2.28 2.30 2.36 2.38
1.46 A A 2.52
1X:59 2X:62 I0 I1 I2 I3 I4 I5 I6 I7 COM COM I8 I9 I10 I11 I12 I13 I14 I15 COM COM
B' B' 6/11D
IN1
IN5
1.48 2.54
1.RT2
1X:60 2X:63 A5 TM2DDI16DT
1.50 B B 2.56
TM2ARI8LT
NC NC
1X:61 2X:67 1.TP1 1.TP2 2.TP1 2.TP2
1.52 A A 2.64 P P P P
1X:62 2X:68
B' B' + I_ + I_ + I_ + I_
IN2
IN6
1.54 2.66
2.RT5
1X:63 2X:69
B B
1X:73
2X:73
1.56
1X:72
2X:72
1X:71
1X:70
2X:71
2.68
2X:70
2 7/1H
1X:64 1.70 1.74 2.70 2.74 4
1.58 A A 7/1H
1X:65
B' B'
IN3
IN7
1.60
1.RT4
1X:66
Air-cooled screw chiller technical manual (PLC series)
1.62 B B
+ A7TM2AMM6HT
OV
4 2
5/12B 5/12B
MCAC-CTSM-2013-01
141
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR8 26 A1
8 M M 27 A2
M 3~
9 KT1 28 A3 A4
10 KM1~KM8 29 A5
11 SB 30 A6
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 A7
14 SQ1 33 A8
15 SQ2 34 A9
16 KA1 35 A10
17 SA 36
18 SA1
19 SL1
MCAC-CTSM-2013-01
142
3P+N+PE 50Hz 380-400V
N X1 1X1 1X1 1X2 1X2
L1 1L1
L2 1L2
L3 1L3
PE 1.1QF 374A
1.3QF 16A
3*1.5mm+1*1.5mm
2QF 1A 11.6A
0.75mm,0.1A
L1 L2 L3 KR1 1.125
2/1B 1.127 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6 1KM7 1KM8
2/1B
2/1B 16 15 18 1TA1 1TA2
1.U11
1.U21
1.U31
1.U41
1.U51
1.U61
1.U71
1.U81
1.V11
1.W11
1.V21
1.W21
1.V31
1.W31
1.V41
1.W41
1.V51
1.W51
1.V61
1.W61
1.V71
1.W71
1.V81
1.W81
W1
Air-cooled screw chiller technical manual (PLC series)
V1
U1
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 330A 3~
L N S1 S2 M1 M2
2
Z1
X1
Y1
LSBLGW1200/C WIRING DIAGRAM
Nb 1X:21
L12 1X:22
1.20 1X:43
1X:44
1KM13
5/7C
5/7B
4/12C
4/12C
1ST1 1ST2
MCAC-CTSM-2013-01
143
3P+N+PE 50Hz 380-400V
1/3D N 2X1 2X1 2X2 2X2
1/3D L1 2L1
2L2
1/3D L2 2L3
1/3D L3
1/3D PE 2.1QF 374A
3*1.5mm+1*1.5mm
11.6A
2.125
2.127 2KM1 2KM2 2KM3 2KM4 2KM5 2KM6 2KM7 2KM8
2TA1 2TA2
2.U11
2.U21
2.U31
2.U41
2.U51
2.U61
2.U71
2.U81
2.W11
2.W21
2.W31
2.W41
2.W51
2.W61
2.W71
2.W81
2.V11
2.V21
2.V31
2.V41
2.V51
2.V61
2.V71
2.V81
2.FR
2FR1 2FR2 2FR3 2FR4 2FR5 2FR6 2FR7 2FR8
2U1 2V1 2W1 PE 2U2 2V2 2W2 PE 2U3 2V3 2W3 PE 2U4 2V4 2W4 PE 2U5 2V5 2W5 PE 2U6 2V6 2W6 PE 2U7 2V7 2W7 PE 2U8 2V8 2W8 PE
2.123
W2
V2
U2
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 330A 3~
L N S1 S2 M1 M2
2
Z2
X2
Y2
Nb 2X:21
L12 2X:22
2.20 2X:43
2X:44
2KM13
4/12D
4/12C
5/11C
5/11B
2ST1 2ST2
MCAC-CTSM-2013-01
144
T1 L11 QF2 L21 FU1 0.75mm,3A QF4 L41 FU2 L51 4/1B
L1 QF1 L1'
1/3D 1P 50Hz 1P 50Hz 6A 4A
N 230V 6A Na 230V 4A 4/1B
1/3D L31 N L
~ 220V
M M
3/9C
3/9C
A10
24V
+V -V 1X:77 1X:781X:791X:80 2X:772X:782X:792X:80
57 N2
FU3 59
3/5B
3/5B
5/10B
5/10B
1.84 1.86 1.88 1.90 1.84 2.86 2.88 2.90
7/8B
7/8B
2A
EH1 M 1EH2 2EH2 1.76 1.78 1.80 1.82 2.76 2.78 2.80 2.82
1X:75
1X:76
2X:75
2X:76
7/8G
7/7G
7/9G
7/8G
MCAC-CTSM-2013-01
145
SB1
L51 L12 L12
3/12B 5/2F
1X:23 2X:23
3/12B Na Nb Nb
1SP4 2SP4 5/2F
1X:24 2X:24 L12
1/2G
1.61 2.61
Nb
1FR 2FR 1/3G
L12
1.63 2.63 2/2G
Nb
2/3G
1KA1 2KA1 1X:31 2
1.65 2.65 5/8B
L
N
1.SL1
1KM13 1KM11 1KM13 1KM12 2KM13 2KM11 2KM13 2KM12
HMI
1.67 1.71 2.67 2.71 1X:32
N L 1.24 5/8C
24V 0V FG
~220V 1KT1 1KM12 1KT1 2KT1 2KM12 2KT1
A9 RS485
24V 5/1D 2X:31 2
+V -V 1.73 2.73
4 1.75 1.69 2.75 2.69 7/7B
5/3B L
2 5/3B 1KM11 1KM12 1KM13 1KT1 2KM11 2KM12 2KM13 2KT1 2.SL1
N
Air-cooled screw chiller technical manual (PLC series)
146
2
4/4E 7/1H
4/4E 4 7/1H
1X:36 X:2 X:3 X:6 1X:37 1X:40 1X:41 1X:44 1X:48 1X:49 X:7 1X:52 1X:53 2X:40 2X:41 2X:44
SQ1 SQ2 1.SP1 1.SP2 1.SQ3 1KM12 1.SL1 1.SP3 1.FR 1.FR1-8 KR1 SA1 1.K5 SA 2.SP1 2.SP2 2.SQ3
1.100
1X:35 X:1 X:4 X:5 1X:38 1X:39 1X:42 1X:43 1KM111X:47 1X:50 X:8 1X:51 1X:54 2X:39 2X:42 2X:43
1.6 1.8 1.10 1.12 1.14 1.16 1.18 1.20 1.22 1.24 1.26 1.28 1.301.32 1.34 1.36 1.38 2.16 2.18 2.20
A1 TM218LDAE40DRPHN 6/3D
4/4E
92 94 96 98 1.1 1.3 1.5 1.7 1.9 1.11 1.13 1.15 1.17 1.191.21 1.23
X:9 X:10 X:11 X:12 X:13 1X:1 1X:4 1X:5 1X:8
KA3 1KA1 1YV1 1YV2 1YV3 1YV4 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6 1KM7 1KM8
4/12B Nb
6/1E
L12 L12 1X:29 1X:30 L13
4/12B 6/1F
SA
MCAC-CTSM-2013-01
147
2X:10
X:23
2X:14
2X:15
2X:18
2X:11
2FR2 2FR3 2FR4 2FR5 2FR62FR7 2FR8
2YV5 2YV6 2YV7 2YV8 2YV9 2KA2
A2 2KM2 2KM3 2KM42KM5 2KM62KM7 2KM8
2X:9
2X:13
2X:12
2X:16
2X:17
X:24
2.15 2.172.192.21 2.23 2.25 2.27 2.29 2.31 2.33 2.37
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15COM1COM1
A4 TM2DRA16RT
TM2DOCKN
5/12D
A3 TM2DRA16RT 7/5C
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 COM1COM1
1.25 1.27 1.29 1.31 1.33 1.35 1.37 1.39 1.41 1.43 2.3 2.5 2.7 2.9 2.11 2.13
1X:20
1X:13
X:20
1X:12
1X:16
1X:17
1X:9
X:16
X:17
2X:4
2X:5
2X:8
X:21
2X:1
2KM1
1YV5 1YV6 1YV7 1YV8 1YV9 KA4 1KA2 KA5 KA6 KA7 2KA1 2YV1 2YV2 2YV3 2YV4 2FR1
Air-cooled screw chiller technical manual (PLC series)
Nb
1X:10
2X:3
1X:14
1X:19
1X:15
1X:18
X:15
X:18
X:19
X:22
2X:2
2X:6
2X:7
1X:11
5/12F
5/12F L13
MCAC-CTSM-2013-01
148
1X:55 1X:67 2X:482X:49 2X:52 2X:53
1.40 A A 2.64
1X:56 1X:68 2KM12 2.SL1 2.SP3 2.FR 2.K5
B' B'
IN0
IN4
1.42 2.66
1.RT1
1.RT5
2.100 2.FR1-8
1X:57 A6 1X:69
1.44 B B 2.68 2KM11 2X:472X:50 2X:51 2X:51
1X:58 2X:61 2.22 2.24 2.26 2.28 2.30 2.36 2.38
1.46 A A 2.52
1X:59 2X:62 I0 I1 I2 I3 I4 I5 I6 I7 COM COM I8 I9 I10 I11 I12 I13 I14 I15 COM COM
B' B' 6/11D
IN1
IN5
1.48 2.54
1.RT2
1X:60 2X:63 A5 TM2DDI16DT
1.50 B B 2.56
TM2ARI8LT
NC NC
1X:61 2X:67 1.TP1 1.TP2 2.TP1 2.TP2
1.52 A A 2.64 P P P P
1X:62 2X:68
B' B' + I_ + I_ + I_ + I_
IN2
IN6
1.54 2.66
2.RT5
1X:63 2X:69
B B
1X:73
2X:73
1.56
1X:72
2X:72
1X:71
1X:70
2X:71
2.68
2X:70
2 7/1H
1X:64 1.70 1.74 2.70 2.74 4
1.58 A A 7/1H
1X:65
B' B'
IN3
IN7
1.60
1.RT4
1X:66
Air-cooled screw chiller technical manual (PLC series)
1.62 B B
+ A7TM2AMM6HT
OV
4 2
5/12B 5/12B
MCAC-CTSM-2013-01
149
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR8 26 A1
8 M M 27 A2
M 3~
9 KT1 28 A3 A4
10 KM1~KM8 29 A5
11 SB 30 A6
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 A7
14 SQ1 33 A8
15 SQ2 34 A9
16 KA1 35 A10
17 SA 36
18 SA1
19 SL1
MCAC-CTSM-2013-01
150
3P+N+PE 50Hz 380-400V
N X1 1X1 1X1 1X2 1X2 1X3
L1 1L1
L2 1L2
L3 1L3
PE 1.1QF 545A
1.3QF 16A
3*1.5mm
2QF 1A +1*1.5mm
11.6A
0.75mm,0.1A
L1 L2 L3 KR1 1.125
2/1B 1.127 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6 1KM7 1KM8 1KM9 1KM10
2/1B
2/1B 16 15 18 1TA1 1TA2
1.U11
1.U21
1.U31
1.U41
1.U51
1.U61
1.U71
1.U81
1.U91
1.U101
1.W11
1.W21
1.W31
1.W41
1.W51
1.W61
1.W71
1.W81
1.W91
1.V11
1.V21
1.V31
1.V41
1.V51
1.V61
1.V71
1.V81
1.V91
1.W101
1.V101
W1
Air-cooled screw chiller technical manual (PLC series)
V1
U1
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 490A 3~
L N S1 S2 M1 M2
2
Z1
X1
Y1
LSBLGW1420/C WIRING DIAGRAM
Nb 1X:21
L12 1X:22
1X:44
1.20 1X:43
1KM13
5/7C
5/7B
4/12C
4/12C
1ST1 1ST2
MCAC-CTSM-2013-01
151
3P+N+PE 50Hz 380-400V
1/3D N 2X1 2X1 2X2 2X2 2X3
1/3D L1 2L1
2L2
1/3D L2 2L3
1/3D L3
1/3D PE 2.1QF 545A
3*1.5mm+1*1.5mm
11.6A
2.125
2.127 2KM1 2KM2 2KM3 2KM4 2KM5 2KM6 2KM7 2KM8 2KM9 2KM10
2TA1 2TA2
2.U11
2.U21
2.U31
2.U41
2.U51
2.U61
2.U71
2.U81
2.U91
2.U101
2.W11
2.W21
2.W31
2.W41
2.W51
2.W61
2.W71
2.W81
2.W91
2.V11
2.V21
2.V31
2.V41
2.V51
2.V61
2.V71
2.V81
2.V91
2.W101
2.FR
2.V101
2FR1 2FR2 2FR3 2FR4 2FR5 2FR6 2FR7 2FR8 2FR9 2FR10
2U1 2V1 2W1 PE 2U2 2V2 2W2 PE 2U3 2V3 2W3 PE 2U4 2V4 2W4 PE 2U5 2V5 2W5 PE 2U6 2V6 2W6 PE 2U7 2V7 2W7 PE 2U8 2V8 2W8 PE 2U9 2V9 2W9 PE 2U10 2V10 2W10 PE
2.123
W2
V2
U2
PE
L1 L2 L3
3P 50Hz M
JTX-A 380-400V 490A 3~
L N S1 S2 M1 M2
2
Z2
X2
Y2
L12 2X:22
Nb 2X:21
2X:44
2.20 2X:43
2KM13
4/12D
4/12C
5/11C
5/11B
2ST1 2ST2
MCAC-CTSM-2013-01
152
T1 L11 QF2 L21 FU1 0.75mm,3A QF4 L41 FU2 L51 4/1B
L1 QF1 L1'
1/3D 1P 50Hz 1P 50Hz 6A 4A
N 230V 6A Na 230V 4A 4/1B
1/3D L31 N L
~ 220V
M M
3/9C
3/9C
A10
24V
+V -V 1X:77 1X:781X:791X:80 2X:772X:782X:792X:80
57 N2
FU3 59
3/5B
3/5B
5/10B
5/10B
1.84 1.86 1.88 1.90 1.84 2.86 2.88 2.90
7/8B
7/8B
2A
EH1 M 1EH2 2EH2 1.76 1.78 1.80 1.82 2.76 2.78 2.80 2.82
1X:75
1X:76
2X:75
2X:76
7/8G
7/7G
7/9G
7/8G
MCAC-CTSM-2013-01
153
SB1
L51 L12 L12
3/12B 5/2F
1X:23 2X:23
3/12B Na Nb Nb
1SP4 2SP4 5/2F
1X:24 2X:24 L12
1/2G
1.61 2.61
Nb
1FR 2FR 1/3G
L12
1.63 2.63 2/2G
Nb
2/3G
1KA1 2KA1 1X:31 2
1.65 2.65 5/8B
L
N
1.SL1
1KM13 1KM11 1KM13 1KM12 2KM13 2KM11 2KM13 2KM12
HMI
1.67 1.71 2.67 2.71 1X:32
N L 1.24 5/8C
24V 0V FG
~220V 1KT1 1KM12 1KT1 2KT1 2KM12 2KT1
A9 RS485
24V 5/1D 2X:31 2
+V -V 1.73 2.73
4 1.75 1.69 2.75 2.69 7/7B
5/3B L
2 5/3B 1KM11 1KM12 1KM13 1KT1 2KM11 2KM12 2KM13 2KT1 2.SL1
N
Air-cooled screw chiller technical manual (PLC series)
154
2
4/4E 7/1H
4/4E 4 7/1H
1X:36 X:2 X:3 X:6 1X:37 1X:40 1X:41 1X:44 1X:48 1X:49 X:7 1X:52 1X:53 2X:40 2X:41 2X:44
SQ1 SQ2 1.SP1 1.SP2 1.SQ3 1KM12 1.SL1 1.SP3 1.FR 1.FR1-10 KR1 SA1 1.K5 SA 2.SP1 2.SP2 2.SQ3
1.100
1X:35 X:1 X:4 X:5 1X:38 1X:39 1X:42 1X:43 1KM11 1X:47 1X:50 X:8 1X:51 1X:54 2X:39 2X:42 2X:43
1.6 1.8 1.10 1.12 1.14 1.16 1.18 1.20 1.22 1.24 1.26 1.28 1.30 1.32 1.34 1.36 1.38 2.16 2.18 2.20
A1 TM218LDAE40DRPHN 6/3D
4/4E
92 94 96 98 1.1 1.3 1.5 1.7 1.9 1.11 1.13 1.15 1.17 1.191.21 1.23
X:9 X:10 X:11 X:12 X:13 1X:1 1X:4 1X:5 1X:8
KA3 1KA1 1YV1 1YV2 1YV3 1YV4 1KM1 1KM2 1KM3 1KM4 1KM5 1KM6 1KM71KM81KM91KM10
155
2X:10
X:23
2X:14
2X:15
2X:18
2X:11
2FR2 2FR3 2FR4 2FR5 2FR62FR7 2FR82FR92FR10
2YV5 2YV6 2YV7 2YV8 2YV9 2KA2
A2 2KM2 2KM3 2KM42KM5 2KM62KM7 2KM82KM92KM10
2X:9
2X:13
X:24
2X:12
2X:16
2X:17
2.15 2.172.192.21 2.23 2.25 2.27 2.29 2.31 2.33 2.37
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7COM0COM0Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15COM1COM1
A4 TM2DRA16RT
TM2DOCKN
5/12D
A3 TM2DRA16RT 7/5C
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 COM0COM0 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 COM1 COM1
1.25 1.27 1.29 1.31 1.33 1.35 1.37 1.39 1.41 1.43 2.3 2.5 2.7 2.9 2.11 2.13
1X:20
X:20
1X:13
1X:9
1X:12
1X:16
1X:17
X:16
X:17
2X:4
2X:5
2X:8
X:21
2X:1
2KM1
1YV5 1YV6 1YV7 1YV8 1YV9 KA4 1KA2 KA5 KA6 KA7 2KA1 2YV1 2YV2 2YV3 2YV4 2FR1
Air-cooled screw chiller technical manual (PLC series)
Nb
1X:10
2X:3
1X:14
1X:15
1X:18
1X:19
X:15
X:18
X:19
X:22
2X:2
2X:6
2X:7
1X:11
5/12F
5/12F L13
MCAC-CTSM-2013-01
156
1X:55 1X:67 2X:482X:49 2X:52 2X:53
1.40 A A 2.64
1X:56 2KM12 2.SL1 2.SP3 2.FR 2.K5
B'
IN0
IN4
1.42 B' 2.66 1X:68
1.RT1
1.RT5
2.100 2.FR1-10
1X:57 A6 1X:69
1.44 B B 2.68 2KM11 2X:472X:50 2X:51 2X:51
1X:58 2X:61 2.22 2.24 2.26 2.28 2.30 2.36 2.38
1.46 A A 2.52
1X:59 2X:62 I0 I1 I2 I3 I4 I5 I6 I7 COM COM I8 I9 I10 I11 I12 I13 I14 I15 COM COM
B' B' 6/11D
IN1
IN5
1.48 2.54
1.RT2
1X:60 2X:63 A5 TM2DDI16DT
1.50 B B 2.56
TM2ARI8LT
NC NC
1X:61 2X:67 1.TP1 1.TP2 2.TP1 2.TP2
1.52 A A 2.64 P P P P
1X:62 2X:68
B' + I_ + I_ + I_ + I_
IN2
IN6
1.54 B' 2.66
2.RT5
1X:63 2X:69
B
1X:73
1.56
1X:72
2X:73
2X:72
1X:71
B 2.68
1X:70
2X:71
2X:70
2 7/1H
1X:64 1.70 1.74 2.70 2.74 4
1.58 A A 7/1H
1X:65
B' B'
IN3
IN7
1.60
1.RT4
1X:66
Air-cooled screw chiller technical manual (PLC series)
1.62 B B
+ A7TM2AMM6HT
OV
4 2
5/12B 5/12B
MCAC-CTSM-2013-01
157
ITEM SYMBOL ITEM DESCRIPTION ITEM SYMBOL ITEM DESCRIPTION
7 FR FR1~FR10 26 A1
8 M M 27 A2
M 3~
9 KT1 28 A3 A4
10 KM1~KM10 29 A5
11 SB 30 A6
Air-cooled screw chiller technical manual (PLC series)
12 T1 31 A7
14 SQ1 33 A8
15 SQ2 34 A9
16 KA1 35 A10
17 SA 36
18 SA1
19 SL1
MCAC-CTSM-2013-01
158
Air-cooled screw chiller technical manual (PLC series) MCAC-CTSM-2012-04
140