Exp 1: OC and SC Test Along With Direct Load Test On A Single Phase Transformer
Exp 1: OC and SC Test Along With Direct Load Test On A Single Phase Transformer
Experiment – 1
1. A. Objectives:
To conduct the OC & SC test on a given single phase transformer and
1. To determine the equivalent circuit parameters of Transformer.
2. To estimate the efficiency of transformer for different loads at different power factors.
3. To estimate the regulation of transformer at full load for different power factors.
To conduct the direct load test on a given single phase transformer and
1. To determine the efficiency and regulation of the transformer at various loading conditions.
2. To compare the results obtained from both OC & SC test and direct load test.
1. B. Theory:
a. Open Circuit Test
The equivalent circuit diagram is given in Fig. 1(a). The purpose of this test is to determine the shunt
branch parameters (i.e., R0 and X0) of the equivalent circuit of the transformer as shown in the figure. The
primary winding is to be connected to supply at rated voltage, while the secondary one remains open circuited.
The input power (Pnl), no-load current (Inl) and applied voltage (Vnl) are measured. With the help of these
three parameters, R0 and X0 are to be calculated as follows:
Pnl Vnl I nl cos( nl ) where, ϕnl is the no-load power factor angle.
V Vnl
I or I nl cos nl ; I om I nl sin nl ; R0 nl ; X0 ;
I or and I om
Xe1 Re1
Inl
Ior Iom
V1 Ro Xo V¢2
Fig. 1(a) Equivalent circuit diagram of a single phase transformer referred to primary side.
Wattmeter
MCB Fuse Ammeter Transformer
A under test
P1 S1
Single Phase V
Power Supply
Voltmeter
P2 S2
N1 : N2
b) For SC Test
1. All the connections have to be made as per the circuit diagram as shown in Fig. 1(b). In addition to
this, the secondary terminals have to be made shorted.
2. Supply switch is closed and the single phase auto transformer is adjusted to rated current of the
transformer.
3. The readings of voltmeter, ammeter and wattmeter are to be noted.
4. The single phase auto transformer voltage has to be reduced to zero gradually and again bring it to
a particular voltage for which rated current will flow through secondary. The same procedure has
to be done for third reading also.
5. Finally, the auto transformer voltage has to be reduced to zero and the supply has to be made
switched off.
6. Calculate the series branch or short circuit parameters (Re1 and Xe1) of the transformer using
necessary formulae.
5. Load the transformer by turning on the switches in the load box at desired loading condition and
note down the readings of the voltmeter, ammeter & wattmeter in primary as well as secondary
side.
6. Repeat the above step for various loading conditions.
7. The single phase auto transformer voltage has to be reduced to zero gradually and the supply has
to be made switched off.
Ammeter
Ammeter Wattmeter Wattmeter
MCB Fuse Transformer
under test
A A
P1 S1
Single Phase V V
Power Supply
Voltmeter Voltmeter
P2 S2
N1 : N2 Load
230/230 V, 2 kVA,
Auto-Transformer 1 – ϕ, 50 Hz
Fig. 1(c) Circuit diagram for testing of the transformer by direct loading method
1. D. Formulae:
To determine the efficiency at different power factors for different loads:
𝑆𝑋 cos ∅ × 103
% 𝐸𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 =
𝑆𝑋 cos ∅ × 103 + (𝑊0 ) + 𝑋 2 (𝑊𝑆𝐶 )
S = Rated KVA of the Transformer X = load Factor*
W0 = No-load losses or Core losses Wsc = Full- load Copper losses
*for Example X = ¼ for 1/4th of full load, and X= ¾ for 3/4th of full load
1. E. Result Tables:
Table 1:
% Efficiency
Sl No. PF Load (x) Theoretical Practical
(OC & SC Test) (DL Test)
1 1/4 Full load
2 1/2 Full load
UPF
3 1/3 Full load
4 Full load
5 1/4 Full load
6 1/2 Full load
0.6 PF
7 1/3 Full load
8 Full load
Table 2:
% Regulation
Power Factor Theoretical Practical
(OC & SC Test) (DL Test)
0.2
0.4
Leading 0.6
0.8
1.0
0.2
0.4
Lagging 0.6
0.8
1.0
1. F. Graphs:
a. Output vs Efficiency b. Power factor vs Regulation
1. G. Conclusion:
a. Graphs, result tables and equivalent Circuits (neat sketches with proper labeling/marking).
b. Your observation during experiment and your comments on obtained results and graphs.
1. H. Questions:
Q.1. What is the significance of O.C. & S.C. test?
Q.2. Why h.v. winding is kept open during O.C. test in case of large transformers?
Q.3. Why l.v. winding is shorted during S.C. test in case of large transformers?
Q.4. In O.C. test, a voltmeter is connected across secondary winding and still it is called as O.C. test.
Why?
Q.5. What will happen if DC supply instead of AC supply is applied to a transformer?
Q.6. Which is the alternate method for finding efficiency and regulation of a transformer other than
O.C. & S.C. tests? What are their advantages over each other?
Q.7. What is the importance of equivalent circuit?
Q.8. Why regulation of transformer is negative for leading p.f. load?
Q.9. “The wattmeter reading during O.C. test is considered as core loss while wattmeter reading
during S.C. test is considered as copper loss” Justify.
Q.10. Why LPF wattmeter is used in OC test?
1. I. Reference:
1. P. S Bimbhra “Electrical Machinery” 7th Edition, Khanna Publishers, 2008.
2. J. Nagarath, D. P. Kothari, “Electric Machines” Tata McGraw Hill, 4th Edition, 2010
3. S.G. Tarnekar, P.K. Kharbanda, S. B. Bodkhe, S.D. Naik and D.J. Dahigaonkar, “Laboratory
Courses In Electrical Engineering”, S. Chand, 6th Edition, 2013