BIDDING DOCUMENT
FOR
VOLUME 3 OF 3
DECEMBER 2014
POWER GRID COMPANY OF BANGLADESH
LIMITED
BIDDING DOCUMENT
FOR
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF
230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS
INDEX TO VOLUMES
Volume 1 of 3
Volume 2 of 3
Scope of Work
Technical Specifications
Drawings forming Part of Specifications
Volume 3 of 3
Bid Forms
Schedule A Introduction & Preamble to the Price & Technical Schedules
Schedule B Bid Prices
Schedule C Bar Chart Programme of Key Activities
Schedule D Manufacturers, Places of Manufacture and Testing
Schedule E Technical Particulars and Guarantees
Schedule F Departure from Specifications
Schedule G Proposed Alternative Standards to which Equipment shall Provided
Schedule H Proposed Contract and Site Organization
Schedule I Drawings and Documents to be Submitted with Bid
Schedule J Proposed Subcontractors
BIDDING DOCUMENT
FOR
SCHEDULE A
230 kV Outdoor Double busbar with Circuit breaker bypass arrangement Switchyard
The existing 230kV outdoor switchyard has two spare bays for the connection of two overhead line
circuits to upcoming Mongla 230kV substation. This contract includes the design, supply, installation
& testing & commissioning of new overhead lines terminal equipment in the switchyard, associated
line control, protection & metering equipment, extension of fiber optic multiplexer equipment for
protection & communication and extension of existing digital fault recorder (SIMENS, Germany
make) & integration with the existing NLDC system and associated equipments with all related civil
works. The contract also includes supply of line protection panels for two overhead lines and
fiber optic multiplexer equipment for the remote station at Mongla.
The descriptions presented below outline the basic requirements for each Section of the Works.
This schedule is not intended to detail each and every item necessary to complete the works, but to
outline the facilities to be provided under the contract. The Contractor shall be responsible for
ensuring that all items necessary for the safe, efficient and complete functioning of the work in
compliance with the Specification are provided, be they described or not.
The following method of reference shall be used to identify the various items required.
The Contractor is to carry out the works taking full account of the limitations imposed by existing
sites and the requirement to maintain all existing supplies during the construction works. Any
temporary works, structures, connections, etc, necessary to achieve this requirement are to be included
in the bid price.
REQUIREMENTS
The Contractor shall be deemed to have visited site, inspected, gathered data and verified details of the
as-built system in order to design supply and interface his new equipment. All necessary materials,
adjustment, dismantling, remedial, and tidying up work in order to complete the work specified shall
be included in the contract price. This includes all ancillary equipment such as cabling, earthing,
LVAC and DC supplies, steel support structures, lightning protection, switchyard lighting and
associated civil works, foundations, drainage, cable trenching and site finishes.
Item Description
The 245 kV switchgear shall comply with the particular requirements as detailed in
the Schedule of Technical Requirements included as Appendix A1 to this section and
shall comprise the following:-
Design, supply, delivery, installation, testing & commissioning of two spare 230 kV
Overhead Line circuit bays in the existing 230kV double busbar switchyard
arrangement to connect two 230kV overhead line circuits from upcoming Maitree
Super Thermal Power Project (STPP) 230kV substation complete with all necessary
ancillary equipment and associated works.
1A1 Design, supply, delivery, installation, testing & commissioning of new two (2) sets of
245 kV, 3150A, 40kA, 50Hz, 1050kVp BIL, live tank type, single-pole operation,
SF6 gas circuit breakers with spring-stored energy operating mechanism.
1A2 Design, supply, delivery, installation, testing & commissioning of new two (2) sets of
245kV, 1600A, 40kA, 50Hz, 1050kVp BIL, single throw horizontal center air break
, post type, motor operated disconnectors with motor and manual operated earthing
switches.
1A3 Design, supply, delivery, installation, testing & commissioning of new eight (8) sets
of 245kV, 1600A, 40kA, 50Hz, 1050kVp BIL, single throw horizontal center air
break, center rotating post type, motor operated disconnectors.
1A4 Design, supply, delivery, installation, testing & commissioning of new six (6) nos. of
single-phase, 4-core, multi ratio, 245kV, 1600A, 40kA, 50Hz, 1050kVp BIL, post
type current transformer.
1A6 Design, supply, delivery, installation, testing & commissioning of six (6) nos. of
186kV continuous operating voltage, 10kA nominal discharge current, 50Hz, Heavy
duty station class, gapless metal oxide type, single phase surge arresters.
1A7 One (1) lot of conductors for jack bus , jumper & equipment connections as required
to complete 245kV switchgear as specified in the technical specifications and bid
drawings.
1A8 Design, supply, delivery, installation, testing & commissioning of four (4) nos. of
245kV post type support insulators required for completing 245kV switchgear
connections.
1A9 One (1) lot of insulators and fittings including all necessary clamps and connectors
required for completing 245kV switchyard specified in the technical specifications
and bid drawings.
1A10 One (1) lot of steel structures for gantry and equipment supports structures including
nuts & bolts and cable tray including all necessary fitting & fixing accessories
required for completing 245kV switchgear specified in the technical specifications
and bid drawings.
All control, protection, alarm and metering panels are to be installed in the existing
control building.
1B1 Complete Control & protection panels for two (2) sets of overhead line circuits to
Mongla (Mongla -1 & 2).
1B3 Supply, delivery and installation of Tariff meter in the existing panels. The tariff
meters shall be programmable & recordable digital 3-phase, 4-wire import and
export MWh and MVArh meters (accuracy class 0.2) including necessary
software for two Overhead Line feeder circuit. For each feeder minimum two
meters (one main & one check) shall be provided. Tariff Metering is to be supplied
from Europe, USA or Japan origin. Printed catalogue, operation and service manual
are to be provided.
1C Multicore Cables
1C1 Complete set of multicore low voltage XLPE auxiliary power and control cables
required for connection of all items and equipment supplied under the Contract shall
be supplied, installed, glanded, terminated and have individual cores identified.
1D.1 Complete set of design, supply and installation for extending of earthing system and
lightning protection screen including connections, connectors and clamps, for the
additional switchgear and ancillary equipment being installed.
1E DC Distribution Connection
1E1 One (1) lot of modification of existing DCDB system by necessary additional
switchgear (MCB/MCCB), cables, connectors etc. required for the additional plant
being installed, shall be provided.
1F1 One (1) lot of modification of existing LVAC existing systems for substation services
including supply of all necessary additional switchgear (MCB/MCCB), bus material,
connection cables, lugs etc. to provide the 415/240V supplies to all equipment being
supplied under this turnkey bid.
1G1 Complete design, supply and construction of all civil items required for the
outdoor works suitable for switchyard gantry & equipment foundations, cable
trenches, surfacing, gravel laying and drainage system etc.
1I3 Extension of existing Remote Terminal Units (RTU, AREVA, France make C262
type) system for new two line bays and connection & integration with the existing
NLDC (National Load Despatch Center) system.
1I4 One (1) lot complete set of design, supply, installation and commissioning of fibre
optic multiplexer equipment covering five (5) related substation optical interfaces
with necessary works to interface with existing system is to be provided for:
1J1 Extension and modification of existing Digital Fault Disturbance Recorder (DFDR)
system (SIEMENS, Germany make SIMEAS model DFR) to monitor the proposed
Mongla 1 & 2 line feeders using available analog and digital inputs in existing DFDR
system.
1. Site Condition
Max. Altitude above sea level M not more than 1000
Max. Ambient temperature outdoor +45
Min. Ambient temperature outdoor +4
Max. Ambient relative humidity % 100
Max. Seismic acceleration at floor level
- horizontal G 0.2
- vertical G 0.2
2. Electrical Data
Rated Voltage KV 245
Rated Frequency Hz 50
Insulation Level
- lightning impulse withstand kVp 1050
- switching impulse withstand kVp —
- 50 Hz withstand 1 minute KV 460
Rated continuous current at 40
ambient temperature
- main busbar A 2000
- line bay A 1600
Rated short time withstand
- current KA 40
- duration Sec 1
Rated peak withstand current KA 100
3. Secondary Circuit
Auxiliary voltage
- for control and signal V dc 110
- for remote control V dc 110
- for heating V ac 415/240
- tolerances % -15/+10
1 Type Outdoor,
single throw horizontal center air
break, center rotating post type,
2 Standard IEC 62271-102
3 Rated voltage 245 kV
4 Rated short-duration power frequency withstand voltage
(1 min.) 460 kV rms
- To earth 530 kV rms
- Across isolating distance
5 Rated lightning impulse withstand voltage
- To earth 1050 kV peak
- Across isolating distance 1200 kV peak
6 Rated normal current
6. Instrument Transformers
16 One minute power frequency 4(10 if the low voltage terminal is exposed)
withstand voltage between LV terminal
and earth(kV rms)
17 Withstand voltage for secondary winding 2
(kV rms)
7 Surge Arresters
1 Max. highest system voltage 245kV
2 Type Outdoor type, ZnO, Gapless
3 Standard IEC 60099-4
4 Rated voltage 186kV
5 Max. continuous operating voltage 160kVrms
6 Nominal discharge current 10kA
7 Discharge class Heavy
duty 3
8 Surge counter Yes
9 Leakage current detector Yes
1.0 GENERAL:
1.1 Type of multiplexer SDH: ADM
1.2 Complying to ITU-T rec. Yes
1.3 Transmission Capacity Mbit/s STM-4: 620
1.4 Access capacity on 64 kbit/s channels Minimum 200
1.5 Access capacity on 2 Mbit/s channels Minimum 40
1.6 Redundant central processor Shall be available
1.7 Digital cross connect function Fully non-blocking
2.0 Available AGGREGATES:
2.1 Optical aggregates (ITU-T G.957) L-1.1, L-1.2
3.0 Available TRUNK INTERFACES:
3.1 HDB3, 2 Mbit/s interfaces per module Nos. Minimum 8
3.2 Complying to ITU-T rec. G.703, transparent
G.704, selectable
3.3 HDSL, 2Mbit/s interface: no of copper wires Nos. 4 or 2
ch
Capacity on 2Mbit/s or on 1Mbit/s ch / pair of wire 30 or 15
Capacity selectable 30 / 2 pairs
30 / 1 pair
15 / 1 pair
4.0 Available USER INTERFACES
4.1 Voice interfaces for trunk lines:
4.1.1 1 + 1 com path protection, available for all Yes
4.1.2 Analogue, 4wire with E&M: Input level dBr +7.5 .. –16
Output level +7.0 .. –16.5
4.1.3 Analogue, 2wire with E&M: Input level dBr +6.5 .. –12.5
Output level –1.0 .. -20
4.1.4 Digital, 2Mbit/s CAS or PRI Yes
4.2 Voice interfaces for remote subscriber:
4.2.1 2wire, subscriber side dBr -5 .. +4 / -7.5 .. -1
4.2.2 2wire, PABX side dBr -5 .. +4 / -7.5 .. -3
4.3 Integrated teleprotection
4.3.1 Interface for Commands:
4.3.1.1 Number of independent commands Nos. 4
4.3.1.2 Transmission time max. ms 6
4.3.1.3 Signal voltage Vpeak 250
4.3.1.4 1 + 1 com path protection Yes
4.3.2 Interface(s) for Differential Protection:
4.3.2.1 Electrical interface: G.703 kbit/s 64
4.3.2.2 Optical Interface kbit/s Minimum 64
4.4 Data: channels per module
APPENDIX A4
(D) MEMORY
1 Size MB 64 MB or Higher
2 Type Solid State
3 Pre-fault time (fast scanning rate) sec 0.1-2 user programmable
4 Post-fault (fast scanning rate sec 0.1-2 user programmable
5 Pre and Post-fault time (slow sec min. 180 user programmable
scanning rate)
6 In-Built hard disk (auto-maintained GB min. 4 GB
Schedule B1-1
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH
SUBSTATION ON TURNKEY BASIS
Schedule B1: Plants Supplied from Outside the Employer's Country
Foreign Currency(F/C) Price ………. Local Currency(L/C) Price (in Taka)
Unit Qty Country Unit Price Total Price Insurance Freight Total Price Local Local Total L/C
of origin FOB FOB CIF transport & Insurance Cost
Item Description
handling cost to destination
to destination
1 2 3=1x2 4 5 6=3+4+5 7 8 9=7+8
1B Control, Protection and Metering
Complete control & protection panel for two sets
1B.1 of overhead line circuits to Mongla (Mongla -1 & set 2
2)
1B.3 Tariff meters(Imp & exp) for two new lines lot 1
Complete protection panels for two (2) sets of
1B.4 overhead line circuits from Khulna South (Khulna set 2
South-1 & 2) at Mongla
1C. Multicore Cables
Multicore Low Voltage power and control cable
1C.1 lot 1
i) LV power Cable lot 1
ii) LV Control Cable lot 1
1D.1 Earthing and Lightning Protection System
i) Earthing System lot 1
ii) Lightning Protection System lot 1
1E DC Distribution Connection
1E.1 Extension of existing DC distribution system with Lot 1
necessary MCB/MCCB etc. for connecting the
new line feeder equipment with 110V & 48V DC
system
1F
LVAC Distribution
1F.1 Extension of existing LVAC system for connecting Lot 1
the new line feeder equipment
Schedule B1-2
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH
SUBSTATION ON TURNKEY BASIS
Schedule B1: Plants Supplied from Outside the Employer's Country
Foreign Currency(F/C) Price ………. Local Currency(L/C) Price (in Taka)
Unit Qty Country Unit Price Total Price Insurance Freight Total Price Local Local Total L/C
of origin FOB FOB CIF transport & Insurance Cost
Item Description
handling cost to destination
to destination
1 2 3=1x2 4 5 6=3+4+5 7 8 9=7+8
1I Fiber Optic Multiplexer Equipment for
Teleprotection and Communication
Total price
Schedule B1-3
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH
SUBSTATION ON TURNKEY BASIS
Schedule B1: Plants Supplied from Outside the Employer's Country
Foreign Currency(F/C) Price ………. Local Currency(L/C) Price (in Taka)
Unit Qty Country Unit Price Total Price Insurance Freight Total Price Local Local Total L/C
of origin FOB FOB CIF transport & Insurance Cost
Item Description
handling cost to destination
to destination
1 2 3=1x2 4 5 6=3+4+5 7 8 9=7+8
Schedule B1-4
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country
Schedule B2-9
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country
Schedule B2-10
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country
Schedule B2-11
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country
Schedule B2-12
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230KV EXTENSION IN
EXTENSION 230/132KV SUBSTATIONS AT KHULNA SOUTH ON TURNKEY BASIS
CONTRACT NO : PGCB/230KV/SS/KS
Design
Item Desctiption Unit Qty Foreign Currency Local Currency in Taka
Schedule B3-1
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN
EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS
Schedule_B4 -Installation & Other Services
1A.1 SF6 Circuit breaker, live tank, single pole operating sets 2
1F LVAC Distribution
1F.1 Extension of existing LVAC system for connecting the Lot 1
new line feeder equipment
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN
EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS
Schedule_B4 -Installation & Other Services
Total:
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN
EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS
Schedule_B4 -Installation & Other Services
1 2 3 4 5 6=2+3+4+5 7 8
Outside Employer's Country (Schedule B1) N/A N/A N/A N/A N/A
Extension of
Khulna South Within Employer's Country (Schedule B2) N/A N/A N/A
Substaton
Installation & other Service (Schedule B4) N/A N/A N/A N/A N/A
Schedule B5-1
Total L/C Cost
excluding VAT on
EXW
9=6+7+8
Schedule B5-2
POWER GRID COMPANY OF BANGLADESH
LIMITED
BIDDING DOCUMENT
FOR
SCHEDULE C
SC-1
POWER GRID COMPANY OF BANGLADESH LIMITED
BIDDING DOCUMENT
SCHEDULE C
TIMES FOR DELIVERY AND COMPLETION
The times given under Column D are the commissioning target dates at present planned to be
achieved and may be the subject of mutual adjustment.
Column A details the earliest dates by which access to site can be given for storage purposes.
The times entered under column B are to be the dates guaranteed for arrival at Site of the first
shipment of parts for the circuits in question being also the dates when the contract requires
access to the Site for plant erection, to the extent necessary to enable him to proceed with
work to meet the dates under column C guaranteed for complete delivery, erection and
commissioning of the shipment.
The times include all necessary control, relay, metering, auxiliary power ancillary equipment
to enable the respective circuit or item of plant to be completely commissioned and put into
commercial operation, together with such other associated equipment, e.g. busbars, etc as
will ensure that subsequent shutdown are unnecessary or at least only of a temporary or short
time nature.
Site A* B* C* D*
Latest Access Guaranteed Arrival Guaranteed Target
Permitted of first shipment Completion Completion
Khulna 7 days from the 365 days
South date of signing of
the Contract
* Time in days, from contract effective date.
Preliminary SLD, overall layout and control building drawings of the Technical
Specifications shall be provided within 2.0 months of the contract commencing date.
SC-2
Design, Supply, Erection, Testing & Commissioning of 230kV Extension of Existing 230/132kV Khulna South Substation
SCHEDULE C
BAR CHART PROGRAM M E OF K EY ACTI VI TI ES
Foundation
Calculation/Drawings of gantry structures and equipment supports
Calculaiton /Drawings of control building
Calculaiton /Drawings of earthing System
Construction and Installation Works
Site Survey
Geo-technical survey
Switchyard
- Piling
- Foundation works incl. earthing
- Cable trenches
- Gantry and equpment support installation
switchgear equipment installation
- Busbars, Jumper condcutors and OH earthwire installation
Construction of Control Building/GIS Bulding
Cable laying & Termination
Installation of LVAC & DC system
Installation of Indoor equipment (Control, protection, metering & FOX and
DFDR etc.)
Testing & Commissioning
Note: Time to complete the plant and services from the effective date is 12 months
SC-3
POWER GRID COMPANY OF BANGLADESH
LIMITED
BIDDING DOCUMENT
FOR
SCHEDULE D
MANUFACTURERS, PLACES OF MANUFACTURE AND TESTING
BIDDING DOCUMENT
FOR
SCHEDULE D
The following Subcontractors and/or manufacturers are proposed for carrying out the item of
the facilities indicated.
Bidders are free to propose more than one for each item.
Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection
Steel Structure
Circuit Breaker
Disconnector
Current Transformer
Voltage Transformer
Surge Arrester
Flexible Conductor
Earth Wire
Clamps
Connectors
Insulator
-Post
-Disc
PROTECTION
METERING AND
2
CONTROL
Panels
Instruments
Protective relays
Meters
Transducers
Energy Meter
DFDR
3
DC EQUIPMENT
4
Distribution Boards
MULTICORE CABLES
6
XLPE Insulated Cables
Cable trays
EARTHING
Copper flatbar/ Copper
7 conductor
Insulated copper
Earthing Rod
Exothermic Joint
8 FIBRE OPTIC
MULTIPLEXER
EQUIPMENT
Design to be performed
by:-
Constructed by:-
BIDDING DOCUMENT
FOR
SCHEDULE E
General
230kV AIR INSULATED SWITCHGEAR (AIS)
Bidders Data
Sl.
No. Description Unit 245kV
1 Manufacturer
3 Number of Poles
4 Rated Voltage
5 Rated frequency
31 Mechanism Type:
34 Closing supply
Volts max/min V
Amps A
42 Minimum creepage
(a) to earth mm
(b) across interrupter terminals mm
50 Length of stroke mm
Bidders Data
Sl.
No. Description Unit 245kV
1 Manufacturer
2 Type Number
3 Operating type
(b) Pantograph
9 Method of operation
11 Operating power
13 Consumption electric A
19 Insulator Creepage mm
23 Mechanical endurance:
1 Manufacturer/type
4 Rated frequency Hz
1 Manufacturer -
2 Type No. -
3 Transformer type -
8 Type of Insulation
11 Primary insulation
16 Capacitor
1 Manufacturer
2 Model Number
3 Type:
11 Duty Class
12 Discharge class
19 Clearances:
phase to earth (from centre line) mm
phase to phase (centre line to centre line) mm
A. FLEXIBLE CONDUCTORS
1 Manufacturer
2 Conductor material
3 Material specification
aluminium alloy
4 Minimum use of grease
5 Number of sub conductor per phase /
6 Nominal diameter of conductor
7 Rated current (site rating)
8 Temperature rise at rated current
9 Short time withstand current for 1 sec C
10 Peak withstand current
11 Conductor spacer type description reference:
Technical particulars & Guarantees SE-12
12 Creep period of conductor years
B. SHIELD WIRES
1 Manufacturer
2 Conductor material
3 Material specification
aluminium alloy
C. CLAMPS AND FITTINGS
Manufacturer
Types
D STEEL STRUCTURES
1 Manufacturer
2 Proposed standards for steel
Item 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Number of core
Core section mm2
Core diameter mm
Conductor insulation mm
Type of filler
Type of tape
Sheath thickness mm
Sheath outer diameter mm
Armour wires no.
Armour wires diameter mm
Outer covering type
Outer covering thickness
Completed cable:
diameter mm
weight per metre kg
maximum drum length m
Minimum installed bending
radius mm
Maximum conductor temperature C
SE-14
PART 3- FOR DCDB & LVAC EQUIPMENT
3.1
Miniature Circuit Breakers
For DCDB
1 Manufacturer
3 Rating Amps
5 Voltage Volts
1 Manufacturer
2 Type
3 Rating Amps
PART 4 - PROTECTION
SE-15
8.2 Minimum necessary voltage for fault at zone 1 reach
point (if applicable)
Earth faults Volts
Phase faults Volts
8.3 Minimum zone 1 ohmic impedance to which relay can
be set Ohms
8.4 Maximum zone 1 ohmic impedance to which relay can
be set and maintain accuracy Ohms
8.5 Minimum zone 2 ohmic impedance to which relay can
be set Ohms
8.6 Maximum zone 2 ohmic impedance to which relay can
be set and maintain accuracy Ohms
SE-16
16 Has distance protection previously been used in the
type of blocking scheme offered for this contract?
If yes: Yes/No
SE-17
MAIN 1 DISTANCE PROTECTION (Continued)
18 Zone 1 operating times when relay fed from capacitive voltage transformer. This
section must be completed in addition to supplying diagrams showing the effect of
source to line ratio and fault position on operating times.
1 0 (relay point)
50
90
10 0
50
90
30 0
50
90
1 0 (relay point)
50
90
10 0
50
90
30 0
50
90
SE-18
18.3 Three Phase Faults:
1 0 (relay point)
50
90
10 0
50
90
30 0
50
90
SE-19
4.2 LINE PROTECTION FOR 230 kV OVERHEAD
LINE BETWEEN KHULNA –M0NGLA
MAIN 2 DISTANCE PROTECTION Bidders Data
1 Manufacturer
2 Manufacturer’s type designation
3 Phase switched Yes/No
4 Zone switched Yes/No
5 Number of zones
6 Shape of impedance characteristic
Zone 1
Zone 2
Zone 3
7 Reverse looking element (blocking signal initiation)
8 Sensitivity:
8.1 Minimum operating current
Earth faults amps
Phase faults amps
8.2 Minimum necessary voltage for fault at zone 1 reach
point (if applicable)
Earth faults Volts
Phase faults Volts
8.3 Minimum zone 1 ohmic impedance to which relay can
be set ohms
8.4 Maximum zone 1 ohmic impedance to which relay can
be set and maintain accuracy ohms
8.5 Minimum zone 2 ohmic impedance to which relay can
be set ohms
8.6 Maximum zone 2 ohmic impedance to which relay can
be set and maintain accuracy ohms
SE-20
4.2 MAIN 2 DISTANCE PROTECTION
(Continued)
8.7 Maximum zone 3 ohmic reach
Forward reach ohms
Reverse reach ohms
9 Arc forward and reverse reach setting independent
of each other? Yes/No
10 Can resistance and reactance reaches be set
independent of each other Yes
11 Directional sensitivity volts
12 Current transformer requirements
13 Voltage transformer requirements
14 Back up zone time ranges
Zone 2 secs
Zone 3 secs
15 Method used to clear close-in faults
(a) which occur when line is already energised in
service
(b) which exist upon line energisation
16 Has distance protection previously been used in the
type of blocking scheme offered for this contract?
If yes: Yes/No
SE-21
4.2 MAIN-2 Distance Protection (continued)
18 Zone 1 operating times when relay fed from capacitive voltage transformer. This
section must be completed in addition to supplying diagrams showing the effect of
source to line ratio and fault position on operating times.
18.1 Earth faults:
SE-22
19 Directional Earth Fault Protection
Associated with Main 1 Distance Protection
19.1 Manufacturer
19.2 Manufacturer’s type designations
19.3 Current setting range:
(a) Forward element A
(b) Reverse element A
19.4 Minimum polarising quantity required for correct
directional decision
Voltage
(a) Forward element V
(b) Reverse element V
Current
(a) Forward element V
(b) Reverse element V
19.5 Characteristic angle degrees
19.6 Time ranges:
(a) Blocking scheme sec
(b) Back-up sec
19.7 Has protection previously been used in the
blocking scheme offered for this contract? Yes
19.8 CT requirements
SE-24
5 Sensitivity of scheme, (allowing for CT
magnetising current, etc)
6 Maximum through fault current at which
protection is stable A
7 CT requirements
8 Estimated magnetising current at relay setting A
9 Operating time at twice relay minimum setting msec
4.5.2 FEEDER END Protection
1 Manufacturer
2 Manufacturer’s type designations
3 Operating principle, e.g. high impedance
4 Minimum relay setting A
5 Sensitivity of scheme, (allowing for CT
magnetising current, etc)
6 Maximum through fault current at which
protection is stable A
7 CT requirements
8 Estimated magnetising current at relay setting A
9 Operating time at twice relay minimum setting msec
SE-25
4.6 INVERSE TIME OVERCURRENT AND
EARTH FAULT PROTECTION
1 Manufacturer
2 Manufacturer’s type designations
3 Inverse time element
3.1 Range of current settings: amperes
- overcurrent amperes
- earth fault
3.2 Range of operating times at highest timing setting seconds
at ten times current setting
3.3 Range of operating times at highest timing setting seconds
at twice current setting
4 High set instantaneous element
Range of settings:
- overcurrent amperes
- earth fault amperes
5 Transient overreach at X = 10
R
6 Operating time with Maximum offset current at 5 msecs
times current setting
7 Burden of relay on minimum inverse time element
current setting at a current ten times setting
- overcurrent VA
- earth fault VA
SE-26
4.7 BREAKER FAILURE PROTECTION
1 Manufacturer
2 Manufacturer’s type designations
3 Setting of current elements:
- phase faults amperes
- earth faults amperes
4 Timer setting range seconds
5 Burden of relay at minimum current setting at 10
times CT secondary rated current during:
- phase fault VA
- earth faults VA
6 Operating time m secs
reset time m secs
5 Operation indicator
6 Operating time at nominal voltage m sec
7 Contact rating:
Make and carry continuously VA
Make and carry for 3 secs VA
Break: resistive watts
Inductive VA
Total ms
SE-28
Permissive scheme time delay ms
SE-29
PART 5 Digital Fault and Disturbance Recorder [DFDR]
(D) MEMORY
1 Size MB
2 Type
3 Pre-fault time (fast scanning rate) sec
4 Post-fault (fast scanning rate sec
5 Pre and Post-fault time (slow scanning rate) sec
6 In-Built hard disk (auto-maintained GB
SE-30
Sl. ITEM UNITS BIDDER’S DATA
(E) SENSORS/ TRIGERRING CRITERIA
All sensors/trigerrs are preferable Yes/No
Programmable and Virtually recordable
1. Logical combination sensor Yes/No
2. Three phase over or under Voltage / Current Yes/No
3. Mono phase over or under Voltage / Current Yes/No
4. *du/dt, dp/dt, dq/dt, [Single/3 Phases], df/dt. etc. Yes/No
5. RMS [Voltage / Current] Yes/No
6. Zero Sequence Yes/No
7. Negative, Positive Sequence Yes/No
8. Frequency Yes/No
9. DC Step Yes/No
10. Pendling / Swing Yes/No
11. Digital level and edge Yes/No
12. Sensor trigger Yes/No
13. Event Trigger Yes/No
14. Manual Trigger Yes/No
15. Remote Trigger Yes/No
(F) CLOCK SYSTEM
1. Internal Clock Yes/No
2. Accuracy
3. External Synchronization Yes/No
4. Time resolution between 2 synchronized pulses
SE-31
SE-32
PART-6: Extension of Existing AREVA, France make Fibre Optic
Multiplexer Equipment For Communication and Protection
Bidder shall provide all necessary information which deem to be necessary to complete the project in
all respects.
SE-33
PART-7: Extension of Existing AREVA, France make Remote Terminal
Unit (RTU) Equipment For SCADA
Bidder shall provide all necessary information which deem to be necessary to complete the project in
all respects.
SE-34
PART 8 - FIBRE OPTIC MULTIPLEXER EQUIPMENT
SL.
Description Unit Bidder’s Data
No.
1 GENERAL:
Manufacturer
Model No.
Type
Type of multiplexer
Complying to ITU-T rec.
Transmission Capacity Mbit/s
Access capacity on 64 kbit/s channels
Access capacity on 2 Mbit/s channels
Redundant central processor
Digital cross connect function
2 Available AGGREGATES:
Optical aggregates (ITU-T G.957)
3 Available TRUNK INTERFACES:
HDB3, 2 Mbit/s interfaces per module No.
Complying to ITU-T rec.
HDSL, 2Mbit/s interface: no of copper wires No.
- Capacity on 2Mbit/s or on 1Mbit/s ch
- Capacity selectable ch / pair of wir
e
4 Available USER INTERFACES
5 Voice interfaces for trunk lines:
1 + 1 com path protection, available for all
Analogue, 4wire with E&M: Input level dBr
Output level dBr
Analogue, 2wire with E&M: Input level dBr
Output level dBr
Digital, 2Mbit/s CAS or PRI
6 Voice interfaces for remote Subscriber:
2wire, subscriber side dBr
2wire, PABX side dBr
7 Integrated teleprotection
Bidder shall provide all necessary information which deem to be necessary to complete the
project in all respects.
SE-36
POWER GRID COMPANY OF BANGLADESH
LIMITED
BIDDING DOCUMENT
FOR
SCHEDULE F
BIDDING DOCUMENT
FOR
SCHEDULE F
Bidders are to list all departures from the requirements of the specification in this schedule.
All departures whether they be commercial, financial, technical or of a contractual nature are
to be included and shall be submitted with the Technical proposal
Any item that does not have a departure listed in this schedule will be deemed to be in full
accordance with the requirements of the specification.
BIDDING DOCUMENT
FOR
SCHEDULE G
BIDDING DOCUMENT
FOR
SCHEDULE G
The bidder shall list below all the alternative engineering and design Standards, which he
proposes to use in his design, manufacture and testing of equipment to be supplied. Should
these standards differ from the specified standard in any respect, the bidder shall detail the
differences between the proposed and specified standard.
Compliance with any standard equal or superior to those specified will be considered
acceptable.
In the absence of any listed alternative standard, it is deemed that the standards specified in
the Tender documents are fully complied with.
BIDDING DOCUMENT
FOR
SCHEDULE H
Schedule H: Proposed contract & site organization and site resources SH-1
POWER GRID COMPANY OF BANGLADESH LIMITED
BIDDING DOCUMENT
FOR
SCHEDULE H
Personnel
Bidders should provide the names of suitably qualified personnel to meet the requirements specified
in Section 3 (Evaluation and Qualification Criteria) of Volume 1 of 3 of the Bidding Document. The
data on their experience should be supplied using the Form below for each candidate.
1. Title of position*
Name
2. Title of position*
Name
3. Title of position*
Name
4. Title of position*
Name
Schedule H: Proposed contract & site organization and site resources SH-2
Form PER – 2: Resume of Proposed Personnel
Position
Professional qualifications
Address of employer
Fax E-mail
Summarize professional experience in reverse chronological order. Indicate particular technical and
managerial experience relevant to the project.
Schedule H: Proposed contract & site organization and site resources SH-3
POWER GRID COMPANY OF BANGLADESH
LIMITED
BIDDING DOCUMENT
FOR
SCHEDULE I
BIDDING DOCUMENT
FOR
SCHEDULE I
BIDDING DOCUMENT
FOR
SCHEDULE J
PROPOSED SUBCONTRACTORS
BIDDING DOCUMENT
FOR
SCHEDULE J
PROPOSED SUBCONTRACTORS
The bidder shall propose a list of the Sub-contractors in the following table as per sub-clause
2.6, Item 7, Section-3, Evaluation and Qualification Criteria, Volume 1 of 3 of the Bidding
Document.
Signature ----------------------------------
Date ----------------------------------