POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING


OF 230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS
AT KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

VOLUME 3 OF 3

BID FORM, PRICES AND SCHEDULES

DECEMBER 2014
POWER GRID COMPANY OF BANGLADESH
LIMITED
BIDDING DOCUMENT
FOR
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF
230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

INDEX TO VOLUMES

Volume 1 of 3

Section 1 - Instruction to Bidders


Section 2 - Bid Data Sheet
Section 3 - Evaluation and Qualification Criteria
Section 4 - Bid Forms
Section 5 - Eligible Countries
Section 6 - Employer’s Requirements
Section 7 - General Conditions of Contract
Section 8 - Special Conditions of Contract
Section 9 - Contract Forms

Volume 2 of 3

Scope of Work
Technical Specifications
Drawings forming Part of Specifications

Volume 3 of 3

Bid Forms
Schedule A Introduction & Preamble to the Price & Technical Schedules
Schedule B Bid Prices
Schedule C Bar Chart Programme of Key Activities
Schedule D Manufacturers, Places of Manufacture and Testing
Schedule E Technical Particulars and Guarantees
Schedule F Departure from Specifications
Schedule G Proposed Alternative Standards to which Equipment shall Provided
Schedule H Proposed Contract and Site Organization
Schedule I Drawings and Documents to be Submitted with Bid
Schedule J Proposed Subcontractors

Schedule A: Requirements SA-2


POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE A

INTRODUCTION & PREAMBLE TO THE PRICE


& TECHNICAL SCHEDULES

Schedule A: Requirements SA-3


SCHEDULE A: INTRODUCTION & PREAMBLE TO THE
PRICE & TECHNICAL SCHEDULES
BRIEF DESCRIPTION OF THE WORKS

1) SECTION OF WORK NO. 1: 230KV EXTENSION IN EXISTING 230/132KV KHULNA SOUTH


SUBSTATION

230 kV Outdoor Double busbar with Circuit breaker bypass arrangement Switchyard

The existing 230kV outdoor switchyard has two spare bays for the connection of two overhead line
circuits to upcoming Mongla 230kV substation. This contract includes the design, supply, installation
& testing & commissioning of new overhead lines terminal equipment in the switchyard, associated
line control, protection & metering equipment, extension of fiber optic multiplexer equipment for
protection & communication and extension of existing digital fault recorder (SIMENS, Germany
make) & integration with the existing NLDC system and associated equipments with all related civil
works. The contract also includes supply of line protection panels for two overhead lines and
fiber optic multiplexer equipment for the remote station at Mongla.

DESCRIPTION OF THE WORKS

The descriptions presented below outline the basic requirements for each Section of the Works.
This schedule is not intended to detail each and every item necessary to complete the works, but to
outline the facilities to be provided under the contract. The Contractor shall be responsible for
ensuring that all items necessary for the safe, efficient and complete functioning of the work in
compliance with the Specification are provided, be they described or not.

The following method of reference shall be used to identify the various items required.

ITEM PLANT DESCRIPTION


A 230 kV Switchgear
B Control, Protection, Metering.
C Multicore Cables
D Earthing and Lightning Protection
E Batteries, Chargers and DC Distribution
F LVAC Distribution
G Civil Works and Foundations
H Building Lighting, Small Power and Air Conditioning
I Fiber Optic Multiplexer Equipment for Communication and Protection and necessary
RTUs required for and integration with the existing NLDC system.
J Digital Fault and Disturbance Recorder (DFDR)

The Contractor is to carry out the works taking full account of the limitations imposed by existing
sites and the requirement to maintain all existing supplies during the construction works. Any
temporary works, structures, connections, etc, necessary to achieve this requirement are to be included
in the bid price.

Schedule A: Requirements SA-4


SCHEDULE A

REQUIREMENTS

I) SECTION OF WORK NO.1: EXTENSION OF EXISTING KHULNA SOUTH 230KV


SUBSTATION FOR TWO NOS. LINE BAYS TO MONGLA

The equipment to be supplied, installed and commissioned is shown on Drawing No.


PGCB/DESIGN/2014/SS/KS-02 & 03, with single line diagram of main connections, control and
protection requirements shown in drawing no. PGCB/DESIGN/2014/SS/KS-01:-

The Contractor shall be deemed to have visited site, inspected, gathered data and verified details of the
as-built system in order to design supply and interface his new equipment. All necessary materials,
adjustment, dismantling, remedial, and tidying up work in order to complete the work specified shall
be included in the contract price. This includes all ancillary equipment such as cabling, earthing,
LVAC and DC supplies, steel support structures, lightning protection, switchyard lighting and
associated civil works, foundations, drainage, cable trenching and site finishes.

Item Description

1A 245 kV Switchgear, equipment connection and steel structures

The 245 kV switchgear shall comply with the particular requirements as detailed in
the Schedule of Technical Requirements included as Appendix A1 to this section and
shall comprise the following:-

Design, supply, delivery, installation, testing & commissioning of two spare 230 kV
Overhead Line circuit bays in the existing 230kV double busbar switchyard
arrangement to connect two 230kV overhead line circuits from upcoming Maitree
Super Thermal Power Project (STPP) 230kV substation complete with all necessary
ancillary equipment and associated works.

1A1 Design, supply, delivery, installation, testing & commissioning of new two (2) sets of
245 kV, 3150A, 40kA, 50Hz, 1050kVp BIL, live tank type, single-pole operation,
SF6 gas circuit breakers with spring-stored energy operating mechanism.

1A2 Design, supply, delivery, installation, testing & commissioning of new two (2) sets of
245kV, 1600A, 40kA, 50Hz, 1050kVp BIL, single throw horizontal center air break
, post type, motor operated disconnectors with motor and manual operated earthing
switches.

1A3 Design, supply, delivery, installation, testing & commissioning of new eight (8) sets
of 245kV, 1600A, 40kA, 50Hz, 1050kVp BIL, single throw horizontal center air
break, center rotating post type, motor operated disconnectors.

1A4 Design, supply, delivery, installation, testing & commissioning of new six (6) nos. of
single-phase, 4-core, multi ratio, 245kV, 1600A, 40kA, 50Hz, 1050kVp BIL, post
type current transformer.

Schedule A: Requirements SA-5


1A5 Design, supply, delivery, installation, testing & commissioning of new six (6) nos. of
single-phase, 245kV, 40kA, 50Hz, 1050kVp BIL, capacitor type voltage
transformers.

1A6 Design, supply, delivery, installation, testing & commissioning of six (6) nos. of
186kV continuous operating voltage, 10kA nominal discharge current, 50Hz, Heavy
duty station class, gapless metal oxide type, single phase surge arresters.

1A7 One (1) lot of conductors for jack bus , jumper & equipment connections as required
to complete 245kV switchgear as specified in the technical specifications and bid
drawings.

1A8 Design, supply, delivery, installation, testing & commissioning of four (4) nos. of
245kV post type support insulators required for completing 245kV switchgear
connections.

1A9 One (1) lot of insulators and fittings including all necessary clamps and connectors
required for completing 245kV switchyard specified in the technical specifications
and bid drawings.

1A10 One (1) lot of steel structures for gantry and equipment supports structures including
nuts & bolts and cable tray including all necessary fitting & fixing accessories
required for completing 245kV switchgear specified in the technical specifications
and bid drawings.

1B Control, Protection and Metering

All control, protection, alarm and metering panels are to be installed in the existing
control building.

The equipment to be supplied, installed and commissioned is shown on Drawings


nos. PGCB/DESIGN/2014/SS/KS-01:-

1B1 Complete Control & protection panels for two (2) sets of overhead line circuits to
Mongla (Mongla -1 & 2).

1B2 Extension, connection and modifications to existing busbar protection to


accommodate two new lines and synchronization with existing system.

1B3 Supply, delivery and installation of Tariff meter in the existing panels. The tariff
meters shall be programmable & recordable digital 3-phase, 4-wire import and
export MWh and MVArh meters (accuracy class 0.2) including necessary
software for two Overhead Line feeder circuit. For each feeder minimum two
meters (one main & one check) shall be provided. Tariff Metering is to be supplied
from Europe, USA or Japan origin. Printed catalogue, operation and service manual
are to be provided.

Schedule A: Requirements SA-6


1B4 Complete line protection panels for two (2) sets of overhead line circuits from Khulna
South (Khulna South-1 & 2) at Mongla. The panels shall be supplied only and
handover for future installation by other contractor at Mongla.

1C Multicore Cables

1C1 Complete set of multicore low voltage XLPE auxiliary power and control cables
required for connection of all items and equipment supplied under the Contract shall
be supplied, installed, glanded, terminated and have individual cores identified.

1D Earthing and Lightning Protection

1D.1 Complete set of design, supply and installation for extending of earthing system and
lightning protection screen including connections, connectors and clamps, for the
additional switchgear and ancillary equipment being installed.

1E DC Distribution Connection

1E1 One (1) lot of modification of existing DCDB system by necessary additional
switchgear (MCB/MCCB), cables, connectors etc. required for the additional plant
being installed, shall be provided.

1F LVAC Distribution Connection

1F1 One (1) lot of modification of existing LVAC existing systems for substation services
including supply of all necessary additional switchgear (MCB/MCCB), bus material,
connection cables, lugs etc. to provide the 415/240V supplies to all equipment being
supplied under this turnkey bid.

1G Civil Works and Foundations

1G1 Complete design, supply and construction of all civil items required for the
outdoor works suitable for switchyard gantry & equipment foundations, cable
trenches, surfacing, gravel laying and drainage system etc.

1H Lighting & Small Power.

1H1 Complete design and calculations, supply, installation and commissioning of


equipment to provide lighting (sodium light) for security, roadway and switchyard
and emergency DC lighting at strategic locations for equipment operations and
inspections to suit the substation overall arrangement for the additional switchgear
and ancillary equipment to be installed under this turnkey bid.

1I Fibre Optic Multiplexer Equipment for Teleprotection and Communication

1I1 The equipment to be supplied, installed and commissioned shall be as shown on


Drawing Nos. PGCB/DESIGN/2014/SS/KS-04. The scope of supply is summarised
as follows:-

1 set - Extension of existing teleprotection equipment (AREVA, France make DIP


5000 type) and fibre optic multiplexer equipment (AREVA, France make
MSE 5010 type/ABB, Switzerland make FOX515 type) at Khulna (South)
Substation for two new line circuits (Mongla 1 & 2) for protection and
communication (voice and data)
Schedule A: Requirements SA-7
1I2 One (1) lot of underground optical fibre (48 cores) cables from terminal box at
230kV gantry structures (For Mongla-1 & 2 line feeders) to MDF (Main distribution
Frame) in control room. The Contract includes supply and installation of underground
optical fibre and pigtail cables with adequate length.

1I3 Extension of existing Remote Terminal Units (RTU, AREVA, France make C262
type) system for new two line bays and connection & integration with the existing
NLDC (National Load Despatch Center) system.

1I4 One (1) lot complete set of design, supply, installation and commissioning of fibre
optic multiplexer equipment covering five (5) related substation optical interfaces
with necessary works to interface with existing system is to be provided for:

- 21 relay for each transmission line protection (through fibre cores)


- 21 relay carrier signal (main and back-up)
- SCADA data from switchgear and control system
- Hot-line telephone system
- Substation LAN system
This equipment including panels shall be for supply only and handed over for future
installation by other contractor at Mongla.

1J Digital Fault Disturbance Recorder

1J1 Extension and modification of existing Digital Fault Disturbance Recorder (DFDR)
system (SIEMENS, Germany make SIMEAS model DFR) to monitor the proposed
Mongla 1 & 2 line feeders using available analog and digital inputs in existing DFDR
system.

Schedule A: Requirements SA-8


APPENDIX A1

SCHEDULE OF TECHNICAL REQUIREMENTS OF


245kV AIR INSULATED SWITCHGEAR (AIS)

Sl. No. Description Unit 230kV

1. Site Condition
Max. Altitude above sea level M not more than 1000
Max. Ambient temperature outdoor +45
Min. Ambient temperature outdoor +4
Max. Ambient relative humidity % 100
Max. Seismic acceleration at floor level
- horizontal G 0.2
- vertical G 0.2

2. Electrical Data
Rated Voltage KV 245
Rated Frequency Hz 50
Insulation Level
- lightning impulse withstand kVp 1050
- switching impulse withstand kVp —
- 50 Hz withstand 1 minute KV 460
Rated continuous current at 40
ambient temperature
- main busbar A 2000
- line bay A 1600
Rated short time withstand
- current KA 40
- duration Sec 1
Rated peak withstand current KA 100

3. Secondary Circuit
Auxiliary voltage
- for control and signal V dc 110
- for remote control V dc 110
- for heating V ac 415/240
- tolerances % -15/+10

Schedule A: Requirements SA-9


4.1 245kV Class Circuit Breakers
1 Type Outdoor, SF6 insulated,
live tank type
2 Standard IEC 62271-100
3 Rated voltage 245 kV
4 Rated short-duration power frequency withstand voltage (1 min.)
- Between line terminal and ground 460 kV rms
- Between terminals with CB open 460 kV rms
- Between terminals with isolator open 530 kV rms
5 Rated lightning impulse withstand voltage
- Between line terminal and ground 1050 kV peak
- Between terminals with CB open 1050 kV peak
- Between terminals with isolator open 1200 kV peak
6 First pole to clear factor 1.5
7 Rated current 3150 A
8 Rated short circuit breaking current 40 kA rms
9 Rated short circuit making current 100 kA peak
10 Short time withstand current for 1 sec. 40 kA rms
11 Max. radio interference voltage for frequency between 0.5MHz 1000 micro V
and 2MHz in all positions (at 156 kV rms)
12 Total closing time Not more than 150 ms
13 Total breaking time 65 ms
14 Operating mechanism Spring or Spring-
hydraulic combination
15 Rated duty cycle O-0.3S-CO-3min-CO
16 Reclosing Single phase & Three
phase auto-reclosing
17 Creepage distance 25 mm/kV
18 Number of closing coils 1
19 Number of tripping coils 2
20 Number of auxiliary contacts for:
- Making Min. 12
- Breaking Min. 12
- Middle position 0
21 Protection class IP55

Schedule A: Requirements SA-10


5. 245kV Disconnector Switches/Isolators and Earthing Switch

1 Type Outdoor,
single throw horizontal center air
break, center rotating post type,
2 Standard IEC 62271-102
3 Rated voltage 245 kV
4 Rated short-duration power frequency withstand voltage
(1 min.) 460 kV rms
- To earth 530 kV rms
- Across isolating distance
5 Rated lightning impulse withstand voltage
- To earth 1050 kV peak
- Across isolating distance 1200 kV peak
6 Rated normal current

- Line bay 1600 A


7 Rated short circuit current (Ith), 1s 40 kA rms
8 Rated short circuit current (Idyn) 100 kA peak
9 Creepage distance of insulator 25 mm/kV
10 Operating mechanism of isolator / earthing switch AC motor operated
11 Number of auxiliary contacts for main switch
- Making Min. 6
- Breaking Min. 6
- Middle position Min. 1
12 Number of auxiliary contacts for earthing switch
- Making Min. 6
- Breaking Min. 6
- Middle position Min. 1
13 Radio interference level for 0.5 MHz to 2 MHz 1000 micro V
(at 156 kV rms)

6. Instrument Transformers

6.1 Instrument Transformers


245 kV
1 Rated lightning impulse withstand 1050 kVp
voltage
2 Rated switching impulse withstand
- -
voltage
Power frequency withstand voltage (1 460 kVrms
3
min.)

Schedule A: Requirements SA-11


4 Corona extinction voltage 156 kVrms
-

5 Radio interference level for 0.5 MHz to 1000 micro V


2 MHz (at 156 kVrms)
6 Partial discharge level 10 pC
7 Type of insulation Class A

6.2 245kV Class Current Transformers


1 Core Nos. 4
2 Ratio 1600-800/1
3 Class of accuracy - Protection : 5P20
- Metering : Class 0.2
4 Burden (VA) 30VA
5 Min. knee point voltage at lowest ratio (Volts) >1kV@ max ratio for protection
core
<150V@ max ratio for metering
core
6 Max. magnetizing current guaranteed at M.R.
knee point voltage & the lowest ratio(mA)
7 Max. resistance of secondary winding at M.R.
75 0C and at lowest ratio(ohms)

6.3 245kV Class Voltage Transformer


1 Rated voltage levels 245 kV
2 High frequency capacitance for entire Within 80% to 150% of rated capacitance
carrier frequency range

3 Rated Voltage Factor 1.2 continuous; 1.5 for 30 seconds


4 Rated total capacitance(pF) 4400, +10% and -5%
5 Phase angle error (minutes) 20
6 Acceptable limit of variation of total + 50% and -20% of the rated capacitance
capacitance over the entire carrier
frequency range
7 Equivalent series resistance over the entire Less than 40
carrier frequency range or temperature
range (ohms)
8 Stray capacitance and stray conductance As per IEC-358
of low voltage terminal over the entire
capacitance.
9 Standard reference range of frequencies 97% to 103% for protection
for which the accuracies are valid 99% to 101% for metering

Schedule A: Requirements SA-12


10 Core details Core-I : Core-II :

11 Purpose Protection Metering

12 Secondary Voltage 110/√3 110/√3

13 Burden (VA) 150 150

14 Class of accuracy 3P 0.5

15 Rated total thermal burden(VA) 150 150

16 One minute power frequency 4(10 if the low voltage terminal is exposed)
withstand voltage between LV terminal
and earth(kV rms)
17 Withstand voltage for secondary winding 2
(kV rms)

7 Surge Arresters
1 Max. highest system voltage 245kV
2 Type Outdoor type, ZnO, Gapless
3 Standard IEC 60099-4
4 Rated voltage 186kV
5 Max. continuous operating voltage 160kVrms
6 Nominal discharge current 10kA
7 Discharge class Heavy
duty 3
8 Surge counter Yes
9 Leakage current detector Yes

Schedule A: Requirements SA-13


APPENDIX A2

SCHEDULE OF TECHNICAL REQUIREMENTS OF


FIBRE OPTIC MULTIPLEXER EQUIPMENT

SL.Nos. DESCRIPTION UNIT REQUIRED

1.0 GENERAL:
1.1 Type of multiplexer SDH: ADM
1.2 Complying to ITU-T rec. Yes
1.3 Transmission Capacity Mbit/s STM-4: 620
1.4 Access capacity on 64 kbit/s channels Minimum 200
1.5 Access capacity on 2 Mbit/s channels Minimum 40
1.6 Redundant central processor Shall be available
1.7 Digital cross connect function Fully non-blocking
2.0 Available AGGREGATES:
2.1 Optical aggregates (ITU-T G.957) L-1.1, L-1.2
3.0 Available TRUNK INTERFACES:
3.1 HDB3, 2 Mbit/s interfaces per module Nos. Minimum 8
3.2 Complying to ITU-T rec. G.703, transparent
G.704, selectable
3.3 HDSL, 2Mbit/s interface: no of copper wires Nos. 4 or 2
ch
Capacity on 2Mbit/s or on 1Mbit/s ch / pair of wire 30 or 15
Capacity selectable 30 / 2 pairs
30 / 1 pair
15 / 1 pair
4.0 Available USER INTERFACES
4.1 Voice interfaces for trunk lines:
4.1.1 1 + 1 com path protection, available for all Yes
4.1.2 Analogue, 4wire with E&M: Input level dBr +7.5 .. –16
Output level +7.0 .. –16.5
4.1.3 Analogue, 2wire with E&M: Input level dBr +6.5 .. –12.5
Output level –1.0 .. -20
4.1.4 Digital, 2Mbit/s CAS or PRI Yes
4.2 Voice interfaces for remote subscriber:
4.2.1 2wire, subscriber side dBr -5 .. +4 / -7.5 .. -1
4.2.2 2wire, PABX side dBr -5 .. +4 / -7.5 .. -3
4.3 Integrated teleprotection
4.3.1 Interface for Commands:
4.3.1.1 Number of independent commands Nos. 4
4.3.1.2 Transmission time max. ms 6
4.3.1.3 Signal voltage Vpeak 250
4.3.1.4 1 + 1 com path protection Yes
4.3.2 Interface(s) for Differential Protection:
4.3.2.1 Electrical interface: G.703 kbit/s 64
4.3.2.2 Optical Interface kbit/s Minimum 64
4.4 Data: channels per module

Schedule A: Requirements SA-14


4.4.1 1 + 1 com path protection, available for all Yes
4.4.2 V.24/V.28 (RS-232): up to 38.4kbit/s Nos. 4
4.4.3 V.11/X.24 (RS-422): 64kbit/s Nos. 4
4.4.4 V.35: 64kbit/s Nos. 4
4.4.5 V.36 (RS-449): 64kbit/s Nos. 2
4.4.6 G.703: 64kbit/s Nos. 8
4.4.7 Ethernet: 10/100 BaseT Nos. 1
Mbit/s
WAN capacity Min: 2x 2Mbit/s
Protocols Min.: IP
4.5 Integrated alarm gathering module:
4.5.1 Number of external alarms per module Nos. Min. 20
4.5.2 Auxiliary power supply for ext. contacts Yes
4.6 Network Management System
4.6.1 Type/Name of configuration tool
4.6.2 For fault / configuration management Yes / yes
4.6.3 For local / remote operation Yes / yes
4.6.4 Data communication network (DCN) Ethernet / IP or
Ethernit / OSI
4.7 Ambient Conditions:
4.7.1 Storage: ETS 300 019-1-1, class 1.2 °C / % hum -25 .. + 55 / class 1.2
4.7.2 Transport: ETS 300 019-1-2, class 2.2 °C / % hum -25 .. + 70 / class 2.2
4.7.3 Operation: ETS 300 019-1-3, class 3.1E °C / % hum -5 .. +45 / class 3.1E
4.8 Power Supply
4.8.1 Operation VDC 48 / 60 (-15/+20%)
4.8.2 Fully redundant power supply Yes

Schedule A: Requirements SA-15


APPENDIX A3

SCHEDULE OF TECHNICAL REQUIREMENTS OF


INSULATOR
1 Rated Voltage 245kV
2 Lightning impulse withstand positive and 1050
negative (kVp) (Dry and wet)
3 Switching impulse withstand voltage (kVp) - -
4 One min. power freq. withstand voltage (kVrms) 460
(Wet and Dry)
5 Total creepage distance (mm) pedestal 6125
6 Total min. cantilever strength (kg) 800
7 Corona extinction voltage (kVrms) 156
8 Total min. height of insulator (mm) 2500

APPENDIX A4

SCHEDULE OF TECHNICAL REQUIREMENTS OF


INSULATOR STRING
1 Rated voltage 245kV
2 Type Anti FOG
3 Size of insulators units (mm) 255 x 145
4 Creepage distance of individual insulator unit 430
(Minimum or as required to obtain total
creepage distance, mm)
5 Electromechanical strength (kN) 120
6 Power frequency withstand voltage of the 460
complete string (kVrms)
7 Lightning impulse withstand voltage of the 1050
complete string with C.C. ring (Dry and wet, kVp)
8 Switching surge withstand voltage of the complete -
string with C.C. rings(Dry & wet, kVp)
9 Power frequency puncture withstand voltage for a 1.3 times the
string insulator unit actual wet
flashover
voltage of
the unit.
10 Minimum corona extinction voltage level of the 156
complete string with C.C. ring (Dry, kVrms)
11 R.I.V. Level of the complete string with C.C. ring. 1000
(micro V)
12 Total creepage distance of complete insulator 6125
string (mm)

Schedule A: Requirements SA-16


APPENDIX A5
SCHEDULE OF TECHNICAL REQUIREMENTS
DIGITAL FAULT AND DISTURBANCE RECORDER [DFDR]
FOR KHULNA SOUTH SUBSTATION
. Sl. ITEM UNITS
(A) GENERAL
1 Manufacturer’s name & address
2 Type
3 Power Supply VDC 110
-Power supply for printer VAC 230

(B) ANALOGUE INPUTS

1 Number of Channel 4-for current & 4 for voltage


Total 8 for 230kV

2 Nominal Current Amp 1A/5A


3 Nominal voltage Vac/Vdc
- Current mA/Amp
4 Frequency response
5 Cut-off frequency
(a) Bandwidth dB
(b) Attenuation at dB
(c) Auto adjusted anti-aliasing filters Yes/No Yes
for chosen sampling rate
d Simultaneously programmable Min 2 for FAST and SLOW
sampling rate for all feeders/inputs Recording
-Locally Changeable Yes/No
-Remotely Changeable Yes/No Yes
Yes
e Possible sampling rates 3 different samplig rates:
Samples/sec Slow. 1Hz-500Hz
Samples/sec fast: 0.5 kHz – 6kHz
Samples/sec continuous (variable rate)
6 DC coupled inputs Yes/No Yes
7 Resolution bits 12 or better
8 Accuracy % Min 0.5
9 Burden
1. Current Circuit at IN VA
2. Voltage Circuit VA
10 Over load
1. Current % In 100% In continuously, Min 600
2. Voltage circuit % Vn % in for 1 Second
2Vn and max. 350 Vn
(C) DIGITAL INPUTS

Schedule A: Requirements SA-17


1 Number of Channel 16 for 230kV
min. 360
-Expandability (Without and time
skew)
2 Selectable input level Vdc N/O or N/C, 110 VDC
3 Type Potential or potential free
contact
4 Resolution ms

(D) MEMORY

1 Size MB 64 MB or Higher
2 Type Solid State
3 Pre-fault time (fast scanning rate) sec 0.1-2 user programmable
4 Post-fault (fast scanning rate sec 0.1-2 user programmable
5 Pre and Post-fault time (slow sec min. 180 user programmable
scanning rate)
6 In-Built hard disk (auto-maintained GB min. 4 GB

Sl. ITEM UNITS


(E) SENSORS/ TRIGERRING CRITERIA
All sensors/trigerrs are preferable Yes/No Yes
Programmable and Virtually recordable
1. Logical combination sensor Yes/No Yes
2. Three phase over or under Voltage / Yes/No Yes
Current
3. Mono phase over or under Voltage / Yes/No Yes
Current
4. *du/dt, dp/dt, dq/dt, [Single/3 Phases], df/dt. Yes/No Yes
etc.
5. RMS [Voltage / Current] Yes/No Yes
6. Zero Sequence Yes/No Yes
7. Negative, Positive Sequence Yes/No Yes
8. Frequency Yes/No Yes
9. DC Step Yes/No Yes
10. Pendling / Swing Yes/No Yes
11. Digital level and edge Yes/No Yes
12. Sensor trigger Yes/No Yes
13. Event Trigger Yes/No Yes
14. Manual Trigger Yes/No Yes
15. Remote Trigger Yes/No Yes

(F) CLOCK SYSTEM

1. Internal Clock Yes/No Yes


2. Accuracy
3. External Synchronization Yes/No Yes
4. Time resolution between 2 synchronized
pulses
Schedule A: Requirements SA-18
(G) OUTPUT ALARM RELAY
CONTACT

1. Max. operation Voltage DC/AC Vac / 250 Vac or above, 60 Vdc or


Vdc above
2. Make and carry for 0.5 sec A Min 8A
3. Carry Continuously A Min 5A
4. Break ( DC ) – resistive W

(H) INTERFACE FOR DATA


COMMUNICATION

1. Full definition compression Yes/No Yes


2. Maximum transmission rate bits / Sec
3. Standard serial port ( EIA-232-D) Yes / No Yes
4. Printer Port Yes/No Yes
5. Dedicated serial port for modem Yes/No Yes

(I) PRINTER DATA

1. Printer amplitude (scaling peak to peak)


2. Time Scal (mm / s )
3. Printer resolution mm
4. Auto printing Yes/No Yes

(J) Fault Priority transmission Yes/No Yes

(K) Fault location (distance calculation) Yes/No Yes

(L) Test certificates from internationally Yes/No Yes


recognized Laboratories

(M) COMMUNICATION AND REMOTE


ANALYZING UNIT

1. Processor Pentium (MHz) Yes, at least 450 MHz


Yes/No Pentium
2. Co-Processor Pentium Yes/No Yes
3. Main memory capacity (Mb) Yes, at least 64 MB
Yes/No
4. Color graphics board S-VGA Yes/No Yes
5. Screen S-VGA Yes/No Yes
6. Hard disk unit Yes/No Yes, at least 40 GB
7. Printer Yes/No Yes
8. Modem Yes/No Yes.
*Note: du/dt=Change of voltage, dp/dt=Change of active power, dq/dt=change of reactive power, df/dt=Change of frequency.

Schedule A: Requirements SA-19


Schedule A: Requirements SA-20
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH
SUBSTATION ON TURNKEY BASIS
Schedule B1: Plants Supplied from Outside the Employer's Country
Foreign Currency(F/C) Price ………. Local Currency(L/C) Price (in Taka)
Unit Qty Country Unit Price Total Price Insurance Freight Total Price Local Local Total L/C
of origin FOB FOB CIF transport & Insurance Cost
Item Description
handling cost to destination
to destination
1 2 3=1x2 4 5 6=3+4+5 7 8 9=7+8
1A 245 kV Air Insulated Switchgear
SF6 Circuit breaker, live tank, single pole
1A.1 sets 2
operating

Single throw horizontal center air break , post


1A.2 sets 2
type disconnector switch with E/S , 1600A

Single throw horizontal center air break, center


1A.3 rotating post type disconnector switch without E/S sets 8
, 1600A

1A.4 Single phase current transformer nos. 6

1A.5 Single phase capacitive voltage transformer CVT nos. 6

1A.6 Single phase surge arrester nos. 6


Flexiable Conductor for jackbus , jumper &
1A.7 lot 1
equipment connection
1A8 Post insulators nos. 4
Strain Insulators and fittings including all
1A.9 lot 1
necessary clamps and connectors
i) Insulator lot 1
ii) Fittings lot 1
iii) Clamps & Connectors lot 1
1A.10 Steel Structures & cable tray
i) Gantry Column including nuts bolts lot
ii) Gantry Beam including nuts bolts

iii) Equipment support structures including nut&bolts lot 1

iv) Cable tray including fitting, fixing accessories lot 1

Schedule B1-1
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH
SUBSTATION ON TURNKEY BASIS
Schedule B1: Plants Supplied from Outside the Employer's Country
Foreign Currency(F/C) Price ………. Local Currency(L/C) Price (in Taka)
Unit Qty Country Unit Price Total Price Insurance Freight Total Price Local Local Total L/C
of origin FOB FOB CIF transport & Insurance Cost
Item Description
handling cost to destination
to destination
1 2 3=1x2 4 5 6=3+4+5 7 8 9=7+8
1B Control, Protection and Metering
Complete control & protection panel for two sets
1B.1 of overhead line circuits to Mongla (Mongla -1 & set 2
2)

Extension, connection and modification to


1B.2 existing busbar protection and sunchronizing with lot 1
existing system

1B.3 Tariff meters(Imp & exp) for two new lines lot 1
Complete protection panels for two (2) sets of
1B.4 overhead line circuits from Khulna South (Khulna set 2
South-1 & 2) at Mongla
1C. Multicore Cables
Multicore Low Voltage power and control cable
1C.1 lot 1
i) LV power Cable lot 1
ii) LV Control Cable lot 1
1D.1 Earthing and Lightning Protection System
i) Earthing System lot 1
ii) Lightning Protection System lot 1
1E DC Distribution Connection
1E.1 Extension of existing DC distribution system with Lot 1
necessary MCB/MCCB etc. for connecting the
new line feeder equipment with 110V & 48V DC
system
1F
LVAC Distribution
1F.1 Extension of existing LVAC system for connecting Lot 1
the new line feeder equipment

1H Lighting and small power


1H1 Lighting & Small power lot 1

Schedule B1-2
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH
SUBSTATION ON TURNKEY BASIS
Schedule B1: Plants Supplied from Outside the Employer's Country
Foreign Currency(F/C) Price ………. Local Currency(L/C) Price (in Taka)
Unit Qty Country Unit Price Total Price Insurance Freight Total Price Local Local Total L/C
of origin FOB FOB CIF transport & Insurance Cost
Item Description
handling cost to destination
to destination
1 2 3=1x2 4 5 6=3+4+5 7 8 9=7+8
1I Fiber Optic Multiplexer Equipment for
Teleprotection and Communication

1I.1 Extension of Indoor type Fibre Optic Multipexer Lot 1


Equipment for communication and protection for
Mongla 1 & 2

1I.2 Fibre Optic cable(48 cores) and termination box Lot 1

1I.3 Necessary works for integration of New bays with Lot 1


existing Areva, France make NLDC system.

1I.4 i) Fibre Optic Multipexer Equipment for Lot 1


communication & protection at Mongla

ii) Hot line Telephone system Lot 1


1J Digital Fault Disturbance Recorder
1J1 Extension and modification of existing digital Lot 1
fault disturbance recorder

Total price

Schedule B1-3
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH
SUBSTATION ON TURNKEY BASIS
Schedule B1: Plants Supplied from Outside the Employer's Country
Foreign Currency(F/C) Price ………. Local Currency(L/C) Price (in Taka)
Unit Qty Country Unit Price Total Price Insurance Freight Total Price Local Local Total L/C
of origin FOB FOB CIF transport & Insurance Cost
Item Description
handling cost to destination
to destination
1 2 3=1x2 4 5 6=3+4+5 7 8 9=7+8

Schedule B1-4
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country

Foreign Currency in …….. Local Currency in Taka


Unit Qty Country Unit Price Total Price Unit Price Total Price Transport Insurance Total L/C
Item Description of origin EXW EXW EXW EXW & Handling Cost
Excluding VAT Excluding VAT Excluding VAT Excluding VAT to distination Excluding VAT
on EXW
1 2 3=1x2 4 5=1x4 6 7 8=5+6+7
1A 245 kV Air Insulated Switchgear
SF6 Circuit breaker, live tank, single pole
1A.1 sets 2
operating

Single throw horizontal center air break , post


1A.2 sets 2
type disconnector switch with E/S , 1600A

Single throw horizontal center air break, center


1A.3 rotating post type disconnector switch without sets 8
E/S , 1600A

1A.4 Single phase current transformer nos. 6


Single phase capacitive voltage transformer
1A.5 nos. 6
CVT
1A.6 Single phase surge arrester nos. 6
Flexiable Conductor for jackbus , jumper &
1A.7 lot 1
equipment connection
1A8 Post insulators nos. 4
Strain Insulators and fittings including all
1A.9 lot 1
necessary clamps and connectors
i) insulator lot 1
ii) Fittings lot 1
iii) Clamps & Connectors lot 1
1A.10 Steel Structures & cable tray
i) Gantry Column including nuts bolts lot
ii) Gantry Beam including nuts bolts
Equipment support structures including
iii) lot 1
nut&bolts
Cable tray including fitting, fixing accessories
iv) lot 1

Schedule B2-9
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country

Foreign Currency in …….. Local Currency in Taka


Unit Qty Country Unit Price Total Price Unit Price Total Price Transport Insurance Total L/C
Item Description of origin EXW EXW EXW EXW & Handling Cost
Excluding VAT Excluding VAT Excluding VAT Excluding VAT to distination Excluding VAT
on EXW
1 2 3=1x2 4 5=1x4 6 7 8=5+6+7
1B Control, Protection and Metering
Complete control & protection panel for two
1B.1 sets of overhead line circuits to Mongla set 2
(Mongla -1 & 2)
Extension, connection and modification to
1B.2 lot 1
existing busbar protection and sunchronizing
1B.3 Tariff meters(imp & exp) for two new lines lot 1
Complete protection panels for two (2) sets of
1B.4 overhead line circuits from Khulna South set 2
(Khulna South-1 & 2) at Mongla
1C. Multicore Cables
Multicore Low Voltage power and control
1C.1 lot 1
cable
i) LV power Cable lot 1
ii) LV Control Cable lot 1
1D.1 Earthing and Lightning Protection System lot 1
i) Earthing System lot 1
ii) Lightning Protection System lot 1
1E DC Distribution Connection
1E.1 Extension of existing DC distribution system Lot 1
with necessary MCB/MCCB etc. for
connecting the new line feeder equipment with
110V & 48V DC system
1F LVAC Distribution
1F.1 Extension of existing LVAC system for Lot 1
connecting the new line feeder equipment
1H Lighting and small power
1H1 Lighting & Small Power lot 1

Schedule B2-10
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country

Foreign Currency in …….. Local Currency in Taka


Unit Qty Country Unit Price Total Price Unit Price Total Price Transport Insurance Total L/C
Item Description of origin EXW EXW EXW EXW & Handling Cost
Excluding VAT Excluding VAT Excluding VAT Excluding VAT to distination Excluding VAT
on EXW
1 2 3=1x2 4 5=1x4 6 7 8=5+6+7
1I Fiber Optic Multiplexer Equipment for
Teleprotection and Communication
1I.1 Extension of Indoor type Fibre Optic Lot 1
Multipexer Equipment for communication and
protection for Mongla 1 & 2
1I.2 Fibre Optic cable(48 cores) and termination Lot 1
box
1I.3 Necessary works for integration of New bays Lot 1
with existing Areva, France make NLDC
system.
1I.4 i) Fibre Optic Multipexer Equipment for Lot 1
communication & protection at Mongla
ii) Hot line Telephone system Lot 1
1J Digital Fault Disturbance Recorder
1J1 Extension and modification of existing digital Lot 1
fault disturbance recorder
Total Price

Sub Total Price in words............................................................................................................................................................................

Schedule B: Bid Price

Schedule B2-11
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA
SOUTH SUBSTATION ON TURNKEY BASIS
Schedule B2: Plants Supplied from within the Employer's country

Foreign Currency in …….. Local Currency in Taka


Unit Qty Country Unit Price Total Price Unit Price Total Price Transport Insurance Total L/C
Item Description of origin EXW EXW EXW EXW & Handling Cost
Excluding VAT Excluding VAT Excluding VAT Excluding VAT to distination Excluding VAT
on EXW
1 2 3=1x2 4 5=1x4 6 7 8=5+6+7

Schedule B2-12
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230KV EXTENSION IN
EXTENSION 230/132KV SUBSTATIONS AT KHULNA SOUTH ON TURNKEY BASIS

CONTRACT NO : PGCB/230KV/SS/KS

Schedule No. B3 : Design Services

Design
Item Desctiption Unit Qty Foreign Currency Local Currency in Taka

All Design Cost for this Contract


- is deemed to be included in - - Not applicable Not applicable
Schedule Nos. B1, B2, and B4.

Total Price carried to Summary of Price Schedule - -

Schedule B3-1
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN
EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS
Schedule_B4 -Installation & Other Services

Local Currency Prices in Bangladesh Taka


Item Description Unit Qty Unit Price
(1) (2)
1A 245 kV Air Insulated Switchgear

1A.1 SF6 Circuit breaker, live tank, single pole operating sets 2

Single throw horizontal center air break , post type


1A.2 sets 2
disconnector switch with E/S , 1600A
Single throw horizontal center air break, center
1A.3 rotating post type disconnector switch without E/S , sets 8
1600A
1A.4 Single phase current transformer nos. 6
1A.5 Single phase capacitive voltage transformer CVT nos. 6
1A.6 Single phase surge arrester nos. 6
Flexiable Conductor for jackbus , jumper & equipment
1A.7 lot 1
connection
1A8 Post insulators nos. 4
Strain Insulators and fittings including all necessary
1A.9
clamps and connectors
i) Insulator lot 1
ii) Fittings lot 1
iii) Clamps & Connectors lot 1
1A.10 Steel Structures & cable tray
i) Gantry Column including nuts bolts lot
ii) Gantry Beam including nuts bolts
Equipment support structures including nut&bolts
iii) lot 1

iv) Cable tray including fitting, fixing & accessories lot 1


DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN
EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS
Schedule_B4 -Installation & Other Services

Local Currency Prices in Bangladesh Taka


Item Description Unit Qty Unit Price
(1) (2)
1B Control, Protection and Metering

Complete control & protection panel for two sets of


1B.1 set 2
overhead line circuits to Mongla (Mongla -1 & 2)

Extension, connection and modification to existing


1B.2 busbar protection and synchronization with existing lot 1
system
1B.3 Tariff meters (imp & exp) for two new lines lot 1

1C. Multicore Cables

1C.1 Multicore Low Voltage power and control cable lot 1


i) LV power Cable lot 1
ii) LV Control Cable lot 1
1D.1 Earthing and Lightning Protection System lot 1
i) Earthing System lot 1
ii) Lightning Protection System lot 1
1E DC Distribution Connection
1E.1 Extension of existing DC distribution system with Lot 1
necessary MCB/MCCB etc. for connecting the new
line feeder equipment with 110V & 48V DC system

1F LVAC Distribution
1F.1 Extension of existing LVAC system for connecting the Lot 1
new line feeder equipment
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN
EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS
Schedule_B4 -Installation & Other Services

Local Currency Prices in Bangladesh Taka


Item Description Unit Qty Unit Price
(1) (2)
1G1 Civil Works and Foundation
i) Outdoor gantry foundation Lot 1
ii) Outdoor equipment Foundation Lot 1

iii) Cable trench extension Lot 1


iv) Surface drain extension Lot 1
v) Internal Road extension Lot 1
vi) Switchyard surface finishing Lot 1
vii) Gravel laying Lot 1
1H Lighting and small power
1H1 Lighting & Small Power lot 1
1I Fiber Optic Multiplexer Equipment for Teleprotection and
Communication
1I.1 Extension of Indoor type Fibre Optic Multipexer Lot 1
Equipment for communication and protection for
Mongla 1 & 2

1I.2 Fibre Optic cable(48 cores) and termination box Lot 1


1I.3 Necessary works for integration of New bays with Lot 1
existing Areva, France make NLDC system.

1J Digital Fault Disturbance Recorder


1J1 Extension and modification of existing digital fault Lot 1
disturbance recorder system

Total:
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN
EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS
Schedule_B4 -Installation & Other Services

Local Currency Prices in Bangladesh Taka


Item Description Unit Qty Unit Price
(1) (2)
kV EXTENSION IN
KEY BASIS

rency Prices in Bangladesh Taka


Total Price
(3)
kV EXTENSION IN
KEY BASIS

rency Prices in Bangladesh Taka


Total Price
(3)
kV EXTENSION IN
KEY BASIS

rency Prices in Bangladesh Taka


Total Price
(3)
kV EXTENSION IN
KEY BASIS

rency Prices in Bangladesh Taka


Total Price
(3)
DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING 230/132kV KHULNA SOUTH SUBSTATION ON TURNKEY BASIS

SCHEDULE B5: SUMMARY OF PRICE SCHEDULE

Foreign Currency Price:


Foreign Currency Prices
Within the Total F/C Cost
Outside Employer's Country Employer's
Description of Works
Country Excluding VAT on
Total EXW Price
Total Price FOB Insurance Freight Total CIF Price
Excluding VAT EXW
1 2 3 4 5=(2+3+4) 6 7=5+6
Outside Employer's Country (Schedule B1) N/A `
Extension of
Khulna South Within Employer's Country (Schedule B2) N/A N/A N/A N/A
Substaton
Design Service (Schedule B3) N/A N/A N/A N/A N/A N/A

TOTAL FOREIGN CURRENCY AMOUNT

Local Currency Price:


Local Currency Prices in Bangladesh Taka
Within the Emplyoer's Country Outside the Employer's Country

Description of Works Total Price Transportation & Local Transportaton


Insurance to Installaton and Local Insurance to
EXW incuding Handling to Total Amount & Handling Cost to
Destination other services Destinaton
VAT destination Destinaton

1 2 3 4 5 6=2+3+4+5 7 8
Outside Employer's Country (Schedule B1) N/A N/A N/A N/A N/A
Extension of
Khulna South Within Employer's Country (Schedule B2) N/A N/A N/A
Substaton
Installation & other Service (Schedule B4) N/A N/A N/A N/A N/A

TOTAL AMOUNT (Bangladesh Taka)

TOTAL CONTRACT PRICE in words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . plus Bangladesh Taka . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


The above price shall appear on the FORM OF PRICE BID
N/A: Not applicable.
Schedule B: Bid Price

Schedule B5-1
Total L/C Cost
excluding VAT on
EXW

9=6+7+8

Schedule B5-2
POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE C

BAR CHART PROGRAMME OF KEY ACTIVITIES

SC-1
POWER GRID COMPANY OF BANGLADESH LIMITED
BIDDING DOCUMENT

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING


230/132KV KHULNA SOUTH SUBSTATION ON TRUNKEY BASIS.

SCHEDULE C
TIMES FOR DELIVERY AND COMPLETION

The individual dates are all contractually binding.

The times given under Column D are the commissioning target dates at present planned to be
achieved and may be the subject of mutual adjustment.

Column A details the earliest dates by which access to site can be given for storage purposes.
The times entered under column B are to be the dates guaranteed for arrival at Site of the first
shipment of parts for the circuits in question being also the dates when the contract requires
access to the Site for plant erection, to the extent necessary to enable him to proceed with
work to meet the dates under column C guaranteed for complete delivery, erection and
commissioning of the shipment.
The times include all necessary control, relay, metering, auxiliary power ancillary equipment
to enable the respective circuit or item of plant to be completely commissioned and put into
commercial operation, together with such other associated equipment, e.g. busbars, etc as
will ensure that subsequent shutdown are unnecessary or at least only of a temporary or short
time nature.

The dates assume an order is placed by . . . . . . . . . . . . . . . . . . . . .


(to be advised or stated by Bidder)

Site A* B* C* D*
Latest Access Guaranteed Arrival Guaranteed Target
Permitted of first shipment Completion Completion
Khulna 7 days from the 365 days
South date of signing of
the Contract
* Time in days, from contract effective date.
Preliminary SLD, overall layout and control building drawings of the Technical
Specifications shall be provided within 2.0 months of the contract commencing date.

SC-2
Design, Supply, Erection, Testing & Commissioning of 230kV Extension of Existing 230/132kV Khulna South Substation

SCHEDULE C
BAR CHART PROGRAM M E OF K EY ACTI VI TI ES

Time Period in month


1 2 3 4 5 6 7 8 9 10 11 12
Equipment
Drawings of single line diagram
Drawings of 132kV and 33kV Switchgear Layout
Drawings of 132kV Switchgear Equipment
Manufacture of 132kV &33kV Switchgear Equipment
Manufacture of Control, Protection, and Metering System

Factory Routine Test


Delivery of equpment to site

Foundation
Calculation/Drawings of gantry structures and equipment supports
Calculaiton /Drawings of control building
Calculaiton /Drawings of earthing System
Construction and Installation Works
Site Survey
Geo-technical survey
Switchyard
- Piling
- Foundation works incl. earthing
- Cable trenches
- Gantry and equpment support installation
switchgear equipment installation
- Busbars, Jumper condcutors and OH earthwire installation
Construction of Control Building/GIS Bulding
Cable laying & Termination
Installation of LVAC & DC system
Installation of Indoor equipment (Control, protection, metering & FOX and
DFDR etc.)
Testing & Commissioning

Note: Time to complete the plant and services from the effective date is 12 months

SC-3
POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE D
MANUFACTURERS, PLACES OF MANUFACTURE AND TESTING

Schedule D: Manufactures, place of manufacture and testing SD-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

DESIGN, SUPPLY,ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING


230/132KV KHULNA SOUTH SUBSTATION ON TRUNKEY BASIS.

SCHEDULE D

MANUFACTURERS, PLACES OF MANUFACTURE AND TESTING

The following Subcontractors and/or manufacturers are proposed for carrying out the item of
the facilities indicated.

Bidders are free to propose more than one for each item.

Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection

1 245 kV AIS SWITCHGEAR

Steel Structure

Circuit Breaker

Disconnector

Current Transformer

Voltage Transformer

Surge Arrester

Flexible Conductor

Earth Wire
Clamps
Connectors
Insulator
-Post
-Disc

Schedule D: Manufactures, place of manufacture and testing SD-2


Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection
Fittings
Steel Structures

PROTECTION
METERING AND
2
CONTROL

Panels

Instruments

Protective relays

Meters

Transducers

Energy Meter

DFDR
3

DC EQUIPMENT
4
Distribution Boards

415 kV SWITCH FUSE


BOARD
5

MULTICORE CABLES
6
XLPE Insulated Cables

Cable trays

EARTHING
Copper flatbar/ Copper
7 conductor

Insulated copper

Schedule D: Manufactures, place of manufacture and testing SD-3


Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection
Conductor

Earthing Rod

Exothermic Joint

8 FIBRE OPTIC
MULTIPLEXER
EQUIPMENT

9 SITE ERECTION AND


COMMISSIONING BY
CIVIL WORKS

Design to be performed
by:-
Constructed by:-

Schedule D: Manufactures, place of manufacture and testing SD-4


Proposed Place of
Place of
Item Description Subcontractors/ Testing and
Manufacture
Manufacturers Inspection

Schedule D: Manufactures, place of manufacture and testing SD-5


POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE E

TECHNICAL PARTICULARS AND GUARANTEES

Technical particulars & Guarantees SE-1


SCHEDULE E

TECHNICAL PARTICULARS AND GUARANTEES

General
230kV AIR INSULATED SWITCHGEAR (AIS)

Sl. No. Description Unit 230kV


1. Site Condition
Max. Altitude above sea level m
Max. Ambient temperature outdoor ℃
Min. Ambient temperature outdoo ℃
r
Max. Ambient relative humidity %
Max. Seismic acceleration at floor level
- horizontal g
- vertical g
2. Electrical Data
Rated Voltage kV
Rated Frequency Hz
Insulation Level
- lightning impulse withstand kVp
- switching impulse withstand kVp
- 50 Hz withstand 1 minute kV
Rated continuous current at 40℃
ambient temperature
- main busbar and bus coupler A
- transformer bay A
- line bay A
Rated short time withstand
- current kA
- duration Sec
Rated peak withstand current kA
3. Secondary Circuit
Auxiliary voltage
- for control and signal V dc
- for remote control V dc
- for heating V ac
- tolerances %

Technical particulars & Guarantees SE-2


PART 1 - SWITCHGEAR

1.1 HV OUTDOOR CIRCUIT BREAKERS

Bidders Data
Sl.
No. Description Unit 245kV

1 Manufacturer

2 Type Reference (Manufacturer’s designation)

3 Number of Poles

4 Rated Voltage

5 Rated frequency

6 Rated normal current-feeder/transformer/bus A


coupler

7 Rated breaking currents: kA rms


Line charging
Cable charging
Small inductive

8 Rated short-circuit breaking current kA,rms

9 First pole to clear factor

10 Rated transient recovery voltage for terminal faults kV


if other than standard

11 Rated characteristics for short-line faults

12 Rated short-circuit making current kA

13 Rated operating sequence

14 Rated duration of short-circuit s

15 Rated out of phase breaking current kA

16 Rated opening time ms

17 Rated break time ms

18 Rated closing time ms


Maximum arcing time of any duty cycle to IEC 56
19 ms

20 Is circuit-breaker re-strike free Yes/No


21 Test Authority

22 Test Certificate ref.

23 Rated short time withstand current kA

24 Rated duration of short-circuit s

25 Rated peak withstand current kA

26 Rated insulation levels:-

26.1 Lightning impulse withstand to earth kV pk

(wave shape 1.2/50µs)


Technical particulars & Guarantees SE-3
Bidders Data
Sl.
No. Description Unit 245kV

26.2 Lightning impulse withstand across open kV pk

contacts (wave shape 1.2/50µs)

26.3 Power frequency voltage withstand to earth kV rms

26.4 Power frequency voltage withstand across open kV rms


contacts

27 Rated supply pressure of gas for interruption MPa (g)

28 Limits for correct operation


max MPa (g)
min MPa (g)

29 Frequency of operation yr-1

30 Operating mechanism Manufacturer

31 Mechanism Type:

32 Trip free/or fixed trip

33 Is lockout facility fitted?

34 Closing supply
Volts max/min V
Amps A

35 Rated supply voltage of shunt opening release V

36 Current required at rated supply voltage to open A


circuit-breaker
37 Spring charging motor
- Current A
- Voltage AC/DC V

38 Number of auxiliary switch contacts


- normally open
- normally closed
- adjustable

39 Other auxiliary loads:


Voltage:
Current:

40 Degree of Protection for


(a) auxiliary circuits
(b) moving parts

41 Minimum clearances in air:


(a) between phases mm
(b) phases to earth mm
(c) across interrupters mm
(d) live parts to ground level mm

42 Minimum creepage
(a) to earth mm
(b) across interrupter terminals mm

43 Radio interference voltage μV

Technical particulars & Guarantees SE-4


Bidders Data
Sl.
No. Description Unit 245kV

44 Guaranteed maximum gas leakage % per


annum

45 Number of interrupters per pole

46 Material of interrupter chamber

47 Wall thickness of interrupter chamber mm

48 Material of contact surfaces primary arcing

49 Length of each break mm

50 Length of stroke mm

51 Operating rod for moving contact(s) material


dimensions, etc.

52 Weight of circuit-breaker unit complete kg

53 Maximum shock load imposed on floor or


foundations when opening under fault conditions
(state whether tension or compression)
kg

54 Quantity of gas in complete three-phase circuit


breaker

55 Maximum pressure rise in circuit breakers due to


the making or breaking of rated current

56 Routine pressure test on circuit-breaker tanks or


containers

57 Pressure type test on circuit-breaker tanks or


containers

58 Interrupting gas pressure at 20C Normal

59 Limits of gas pressure at 20C Maximum


Minimum

60 Period of time equipment has been in commercial


operation

61 Number of the same type of circuit breakers


supplied to date

1.2 DISCONNECTORS AND EARTHING SWITCHES

Bidders Data
Sl.
No. Description Unit 245kV

1 Manufacturer

2 Type Number

3 Operating type

(a) horizontal/vertical break

Technical particulars & Guarantees SE-5


Bidders Data
Sl.
No. Description Unit 245kV

(b) Pantograph

(c) Number of support insulation for pole

(d) Number of breaks per pole

(e) Material of contact surfaces

(f) Type of Contacts

4 Rated normal current A

5 Rated short time withstand current kA, rms

6 Rated duration of short time current s

7 Rated peak withstand current kA pk

8 Rated insulation levels:

8.1 Lightning impulse withstand to earth


(waveshape: 1.2/50µs) kV pk

8.2 Lightning impulse withstand across open contacts kV pk


(waveshape: 1.2/50µs)

8.3 Power frequency voltage withstand to earth kV rms

8.4 Power frequency voltage withstand across open kV rms


contacts

9 Method of operation

10 Type of operating mechanism


manual/power

11 Operating power

12 Voltage/pressure rated V/MPa(g)


max V/MPa(g)
min V/MPa(g)

13 Consumption electric A

14 Operating time: open max ms


min ms

15 Operating time: close max ms


min ms

16 Manual operating torque kNm

17 Load switching capability A

18 Mechanical Terminal Load N

19 Insulator Creepage mm

20 Radio interference voltage mV

21 Number of auxiliary switches


- normally open
- normally closed
- adjustable

Technical particulars & Guarantees SE-6


Bidders Data
Sl.
No. Description Unit 245kV

22 Other auxiliary loads


- voltage
- current

23 Mechanical endurance:

Number of operations carried out for mechanical


operation test

24 Degree of protection for


1) auxiliary circuits
2) moving parts

25 Total weight of three pole disconnector complete kg

26 Type test certificate date/reference

27 Period of time equipment has been in commercial


operation

28 Number of the same type of disconnectors supplied


to date

1.3 CURRENT TRANSFORMERS (line bay)

Sl. Bidders Data


No. Description Unit 245kV

1 Manufacturer/type

2 Rated primary current A rms

3 Rated secondary current A rms

4 Rated frequency Hz

5 Highest voltage for equipment kV

6 Rated insulation level - primary winding kV

7 Lightning impulse withstand kV pk

8 (a) Power frequency withstand (dry) kV rms


(b) Power frequency withstand (wet) kV rms

9 Insulator creepage (phase to earth) mm

10 Electrical dissipation factor at power frequency test


voltage

11 Radio influence voltage measured at U/3 1 MHz µV

12 Rated short term thermal current for 1s A rms


13 Rated short term thermal current for 3s A rms

14 Rated dynamic current kA pk


15 Insulation class

16 Number of secondary windings


Location of core

Technical particulars & Guarantees SE-7


Core 1 Rated output
Accuracy class *
Accuracy limit factor
Core 2 Rated output
Accuracy class *
Accuracy limit factor
Core 3 Rated output
Accuracy class *
Accuracy limit factor
Core 4 Rated output
Accuracy class *
Accuracy limit factor
Class x winding:
- Rated knee point emf V
- Exciting current
*including instrument security factor where A
applicable
17 Is earth screen fitted between primary and
secondary windings
18 Type test certificate ref/date

1.4 VOLTAGE TRANSFORMERS


Description Bidder’s Data
Sl. Unit
No. 245kV

1 Manufacturer -

2 Type No. -

3 Transformer type -

4 Rated primary voltage kV rms

Rated secondary voltage for each secondary


5 kV rms
winding

Accuracy class for each winding


6 Rated output for each winding VA
Rated volt-ampere rating for each winding VA

7 Rated voltage factor

8 Type of Insulation

9 Maximum temperature rise C

10 Short-circuit withstand capability kA rms

11 Primary insulation

11.1 Lightning impulse withstand dry kV pk

11.2 (a) Power frequency withstand wet kV rms


(b) Power frequency withstand dry kV rms

12 Partial discharge magnitude pC

13 Total external creepage distance mm

Technical particulars & Guarantees SE-8


Description Bidder’s Data
Sl. Unit
No. 245kV

Radio influence voltage measured at


14 µV
11 Um/3 at 1 MHz

15 Total installed weight kg

16 Capacitor

16.1 High voltage capacitor (C1) pF

16.2 Intermediate - voltage capacitor (C2) pF

16.3 Total Capacitor (Cn) pF

17 Open circuit intermediate voltage kV


18 Rated open-circuit intermediate voltage kV
19 Reference range of frequency +/- Hz
o
20 Reference range of temperature C

21 Protective device to limit overvoltage

1.5 SURGE ARRESTERS


Bidder’s Data
Sl. Description Unit
No. 245kV

1 Manufacturer

2 Model Number

3 Type:

4 Continuous operating voltage kV rms

5 Rated voltage kV rms

6 Standard nominal discharge current kA

7 Reference current at ambient temperature mA

8 Reference voltage for above kV rms

9 Steep current impulse residual voltage kV pk

10 Lightning impulse residual voltage at


5kA kV pk
10kA kV pk
20kA kV pk

11 Duty Class

12 Discharge class

13 Pressure relief class

14 Nominal diameter of resistor blocks mm

15 Number of resistor blocks connected electrically


in parallel

Technical particulars & Guarantees SE-9


16 Number of separately housed units per phase

17 Overall height of arrester (without supporting m


structure)

18 Overall height of arrester including grading ring mm


if applicable

19 Clearances:
phase to earth (from centre line) mm
phase to phase (centre line to centre line) mm

20 Overall Weight of arrester (without supporting kg


structure)

21 Maximum cantilever strength Nm

22 Maximum force due to wind (at maximum Nm


specified gust speed)

23 Minimum creepage distance over insulator mm


housing

24 Insulator shed profile - Reference Document

25 Terminal palm details - Drawing No.

26 Earthing terminal - Drawing No.

27 Type & Description of surge monitoring device

28 Type test certificate ref/date

29 Number of the same type of surge arresters


supplied to date
1.6 POST TYPE INSULATORS

Sl. Nominal System Voltage 245 kV


No.
1 Manufacturer
2 Insulator material
3 IEC.273 reference
4 Insulator type and manufacturer’s reference
5 Maximum working vertical load: tension kN
compression kN
6 Minimum failing load (tension) kN
7 Maximum bending working load kN
8 Minimum failing load (torsion) Nm
Technical particulars & Guarantees SE-10
9 Minimum failing load (bending) kN
10 Shed profile (to be enclosed with Tender)
Drawing No.
11 Greatest diameter mm
12 Number of units in one insulator
13 Overall length per complete post mm
14 Weight of complete post kg
15 Electrostatic capacity pF
16 Power frequency withstand voltage (dry) kV
17 Power frequency withstand voltage (wet) kV
18 Dry lightning impulse withstand voltage
1.2/50 micro sec. Wave kV
19 Minimum creepage distance:
(a) Specified, subject to acceptable
shed profile mm
(b) Guaranteed mm
20 Protected creepage distance mm
21 Radio influence voltage measured at Um/3 at µV
1 MHz

1.7 INSULATOR STRINGS

Sl. Nominal System Voltage 245 kV


No.
1 Manufacturer
2 Insulator type (normal) and
manufacturer’s reference
3 Insulation material
4 Number of units per string
5 Outside diameter mm
6 Distance between centres mm
7 Length of string overall mm
8 Maximum working load kN
9 Minimum failing load per unit kN

Technical particulars & Guarantees SE-11


10 Mechanical routine load test kN
11 Electro-mechanical failing load kN
12 Mechanical failing load kN
13 Electrostatic capacity pF
14 Weight of complete string kg
15 50 Hz 1 minute withstand voltage of unit kV
(dry)
16 50 Hz 1 minute withstand voltage of unit kV
(wet)
17 Minimum 50 Hz puncture voltage kV
18 Dry lightning impulse withstand voltage
of string1.2/50 micro sec. Wave kV
19 Minimum creepage distance per unit:
(a) Specified, subject to acceptable
shed profile mm
(b) Guaranteed mm
20 Protected creepage distance per unit mm
21 Radio influence voltage measured at µV
Um/3 at 1 MHz

1.8 CONDUCTORS AND CONNECTIONS

Sl. No. Nominal System Voltage 245 kV

A. FLEXIBLE CONDUCTORS
1 Manufacturer
2 Conductor material
3 Material specification
aluminium alloy
4 Minimum use of grease
5 Number of sub conductor per phase /
6 Nominal diameter of conductor
7 Rated current (site rating)
8 Temperature rise at rated current
9 Short time withstand current for 1 sec C
10 Peak withstand current
11 Conductor spacer type description reference:
Technical particulars & Guarantees SE-12
12 Creep period of conductor years
B. SHIELD WIRES
1 Manufacturer
2 Conductor material
3 Material specification
aluminium alloy
C. CLAMPS AND FITTINGS
Manufacturer

Types

Maximum working stresses

D STEEL STRUCTURES
1 Manufacturer
2 Proposed standards for steel

Technical particulars & Guarantees SE-13


2. AUXILIARY POWER AND MULTICORE CONTROL CABLES

Item 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Number of core
Core section mm2
Core diameter mm
Conductor insulation mm
Type of filler
Type of tape
Sheath thickness mm
Sheath outer diameter mm
Armour wires no.
Armour wires diameter mm
Outer covering type
Outer covering thickness
Completed cable:
diameter mm
weight per metre kg
maximum drum length m
Minimum installed bending
radius mm
Maximum conductor temperature C

SE-14
PART 3- FOR DCDB & LVAC EQUIPMENT

Sl.No. Description Bidder's Data

3.1
Miniature Circuit Breakers
For DCDB

1 Manufacturer

2 Manufacturer’s type designation

3 Rating Amps

4 Fault Rating for 1 sec KA

5 Voltage Volts

3.2 Miniature Circuit Breakers for LVAC

1 Manufacturer

2 Type

3 Rating Amps

4 Fault Rating for 1 sec kA

PART 4 - PROTECTION

4.1 LINE PROTECTION FOR 230 kV OVERHEAD


LINE BETWEEN KHULNA –MONGLA
Bidders Data
MAIN 1 DISTANCE PROTECTION
1 Manufacturer
2 Manufacturer’s type designation
3 Phase switched Yes/No
4 Zone switched Yes/No
5 Number of zones
6 Shape of impedance characteristic
Zone 1
Zone 2
Zone 3
7 Reverse looking element (blocking signal initiation)
8 Sensitivity:
8.1 Minimum operating current
Earth faults amps
Phase faults amps

SE-15
8.2 Minimum necessary voltage for fault at zone 1 reach
point (if applicable)
Earth faults Volts
Phase faults Volts
8.3 Minimum zone 1 ohmic impedance to which relay can
be set Ohms
8.4 Maximum zone 1 ohmic impedance to which relay can
be set and maintain accuracy Ohms
8.5 Minimum zone 2 ohmic impedance to which relay can
be set Ohms
8.6 Maximum zone 2 ohmic impedance to which relay can
be set and maintain accuracy Ohms

MAIN 1 DISTANCE PROTECTION


(Continued)
8.7 Maximum zone 3 ohmic reach
Forward reach ohms
Reverse reach ohms
9 Arc forward and reverse reach setting independent
of each other? Yes/No
10 Can resistance and reactance reaches be set
independent of each other Yes
11 Directional sensitivity volts
12 Current transformer requirements
13 Voltage transformer requirements
14 Back up zone time ranges
Zone 2 secs
Zone 3 secs
15 Method used to clear close-in faults
(a) which occur when line is already energised
in service
(b) which exist upon line energisation

SE-16
16 Has distance protection previously been used in the
type of blocking scheme offered for this contract?
If yes: Yes/No

(a) number of schemes in service


(b) year first in service
17 Approximate number of years distance relay in
service. (A complete reference list should be
submitted stating client, system voltage and year of
going into service).

SE-17
MAIN 1 DISTANCE PROTECTION (Continued)

18 Zone 1 operating times when relay fed from capacitive voltage transformer. This
section must be completed in addition to supplying diagrams showing the effect of
source to line ratio and fault position on operating times.

18.1 Earth faults:

Operating time m.sec


Source to Line Fault Position
Ratio % of Relay Setting Minimum Maximum

1 0 (relay point)
50
90
10 0
50
90
30 0
50
90

18.2 Phase to Phase Faults

Operating time m.sec


Source to Line Fault Position
Ratio % of Relay Setting Minimum Maximum

1 0 (relay point)
50
90
10 0
50
90
30 0
50
90

SE-18
18.3 Three Phase Faults:

Operating time m.sec


Source to Line Fault Position
Ratio % of Relay Setting Minimum Maximum

1 0 (relay point)
50
90
10 0
50
90
30 0
50
90

19 Directional Earth Fault Protection


Associated with Main 1 Distance Protection
19.1 Manufacturer
19.2 Manufacturer’s type designations
19.3 Current setting range:
(a) Forward element A
(b) Reverse element A
19.4 Minimum polarising quantity required for correct
directional decision
Voltage
(a) Forward element V
(b) Reverse element V
Current
(a) Forward element V
(b) Reverse element V
19.5 Characteristic angle degrees
19.6 Time ranges:
(a) Blocking scheme sec
(b) Back-up sec
19.7 Has protection previously been used in the
blocking scheme offered for this contract? Yes
19.8 CT requirements

SE-19
4.2 LINE PROTECTION FOR 230 kV OVERHEAD
LINE BETWEEN KHULNA –M0NGLA
MAIN 2 DISTANCE PROTECTION Bidders Data
1 Manufacturer
2 Manufacturer’s type designation
3 Phase switched Yes/No
4 Zone switched Yes/No
5 Number of zones
6 Shape of impedance characteristic
Zone 1
Zone 2
Zone 3
7 Reverse looking element (blocking signal initiation)
8 Sensitivity:
8.1 Minimum operating current
Earth faults amps
Phase faults amps
8.2 Minimum necessary voltage for fault at zone 1 reach
point (if applicable)
Earth faults Volts
Phase faults Volts
8.3 Minimum zone 1 ohmic impedance to which relay can
be set ohms
8.4 Maximum zone 1 ohmic impedance to which relay can
be set and maintain accuracy ohms
8.5 Minimum zone 2 ohmic impedance to which relay can
be set ohms
8.6 Maximum zone 2 ohmic impedance to which relay can
be set and maintain accuracy ohms

SE-20
4.2 MAIN 2 DISTANCE PROTECTION
(Continued)
8.7 Maximum zone 3 ohmic reach
Forward reach ohms
Reverse reach ohms
9 Arc forward and reverse reach setting independent
of each other? Yes/No
10 Can resistance and reactance reaches be set
independent of each other Yes
11 Directional sensitivity volts
12 Current transformer requirements
13 Voltage transformer requirements
14 Back up zone time ranges
Zone 2 secs
Zone 3 secs
15 Method used to clear close-in faults
(a) which occur when line is already energised in
service
(b) which exist upon line energisation
16 Has distance protection previously been used in the
type of blocking scheme offered for this contract?
If yes: Yes/No

(a) number of schemes in service


(b) year first in service
17 Approximate number of years distance relay in
service. (A complete reference list should be
submitted stating client, system voltage and year of
going into service).

SE-21
4.2 MAIN-2 Distance Protection (continued)
18 Zone 1 operating times when relay fed from capacitive voltage transformer. This
section must be completed in addition to supplying diagrams showing the effect of
source to line ratio and fault position on operating times.
18.1 Earth faults:

Source to Line Fault Position Operating time m.sec


Ratio % of Relay Setting Minimum Maximum
1 0 (relay point)
50
90
10 0
50
90
30 0
50
90
18.2 Phase to Phase Faults

Source to Line Fault Position Operating time m.sec


Ratio % of Relay Setting Minimum Maximum
1 0 (relay point)
50
90
10 0
50
90
30 0
50
90

18.3 Three Phase Faults:

Source to Line Operating time m.sec


Fault Position
Ratio Minimum Maximum
% of Relay Setting
0 (relay point)
1
50
90
0
10
50
90
0
30
50
90

SE-22
19 Directional Earth Fault Protection
Associated with Main 1 Distance Protection
19.1 Manufacturer
19.2 Manufacturer’s type designations
19.3 Current setting range:
(a) Forward element A
(b) Reverse element A
19.4 Minimum polarising quantity required for correct
directional decision
Voltage
(a) Forward element V
(b) Reverse element V
Current
(a) Forward element V
(b) Reverse element V
19.5 Characteristic angle degrees
19.6 Time ranges:
(a) Blocking scheme sec
(b) Back-up sec
19.7 Has protection previously been used in the
blocking scheme offered for this contract? Yes
19.8 CT requirements

4.3 230 kV AUTO RECLOSE EQUIPMENT


4.3.1 Auto Reclose Relay
1 Manufacturer
2 Manufacturer’s type designations
3 Dead time ranges:
(a) High speed single phase reclosure secs
(b) Delayed three phase reclosure secs
4 Reclaim time range secs
5 Does the circuit breaker duty cycle permit any
combination of dead time and reclaim time within
the above ranges? Yes/No

4.3.2 Dead Line Check Relays


1 Manufacturer
SE-23
2 Manufacturer’s type designations
3 Voltage setting ranges
(a) Busbar voltage volts
(b) Line voltage volts
4 Any time delays (specify function and value)
4.3.3 Synchronising Check Relays
1 Manufacturer
2 Manufacturer’s type designations
3 Setting ranges
(a) Phase angles degrees
(b) Voltage difference volts
(c) Frequency Hz
4 Any time delays (specify function and value)

4.4 BUSBAR PROTECTION


1 Manufacturer
2 Manufacturer’s type designations
3 Operating principle, e.g. high impedance
4 Minimum relay setting A
5 Sensitivity of scheme, (allowing for CT
magnetising current, etc)
6 Maximum through fault current at which
protection is stable A
7 CT requirements
8 Estimated magnetising current at relay setting A
9 Operating time at twice relay minimum setting msec
10 Operating time at ten times relay minimum msec
setting
4.5 CIRCULATING CURRENT PROTECTION
4.5.1 T-Point Protection
1 Manufacturer
2 Manufacturer’s type designations
3 Operating principle, e.g. high impedance
4 Minimum relay setting A

SE-24
5 Sensitivity of scheme, (allowing for CT
magnetising current, etc)
6 Maximum through fault current at which
protection is stable A
7 CT requirements
8 Estimated magnetising current at relay setting A
9 Operating time at twice relay minimum setting msec
4.5.2 FEEDER END Protection
1 Manufacturer
2 Manufacturer’s type designations
3 Operating principle, e.g. high impedance
4 Minimum relay setting A
5 Sensitivity of scheme, (allowing for CT
magnetising current, etc)
6 Maximum through fault current at which
protection is stable A
7 CT requirements
8 Estimated magnetising current at relay setting A
9 Operating time at twice relay minimum setting msec

SE-25
4.6 INVERSE TIME OVERCURRENT AND
EARTH FAULT PROTECTION
1 Manufacturer
2 Manufacturer’s type designations
3 Inverse time element
3.1 Range of current settings: amperes
- overcurrent amperes
- earth fault
3.2 Range of operating times at highest timing setting seconds
at ten times current setting
3.3 Range of operating times at highest timing setting seconds
at twice current setting
4 High set instantaneous element
Range of settings:
- overcurrent amperes
- earth fault amperes
5 Transient overreach at X = 10
R
6 Operating time with Maximum offset current at 5 msecs
times current setting
7 Burden of relay on minimum inverse time element
current setting at a current ten times setting
- overcurrent VA
- earth fault VA

SE-26
4.7 BREAKER FAILURE PROTECTION
1 Manufacturer
2 Manufacturer’s type designations
3 Setting of current elements:
- phase faults amperes
- earth faults amperes
4 Timer setting range seconds
5 Burden of relay at minimum current setting at 10
times CT secondary rated current during:
- phase fault VA
- earth faults VA
6 Operating time m secs
reset time m secs

4.8 TRIPPING RELAYS


1 Manufacturer

2 Manufacturer type designation

3 Nominal operating voltage V

4 Minimum operating voltage V

5 Operation indicator
6 Operating time at nominal voltage m sec

7 Contact rating:
Make and carry continuously VA
Make and carry for 3 secs VA
Break: resistive watts
Inductive VA

4.9 OVERALL FAULT CLEARANCE TIMES AT


KHULNA
1 Busbar Faults
Main protection relay operating time ms
Auxiliary and tripping relay time (where used) ms
Circuit breaker time ms
Total ms
2 KHULNA –MONGLA 230kV Line Faults
SE-27
2.1 Fault Clearance at Khulna (Main 1)
Distance protection maximum operating time ms
Permissive scheme time delay ms
Auxiliary relay time (where used) ms
Circuit breaker time ms
Total clearance time at Khulna ms
2.2 Fault Clearance at Khulna (Main 2)
Distance protection maximum operating time ms
Permissive scheme time delay ms
Auxiliary relay time (where used) ms
Circuit breaker time ms
Total clearance time at Khulna ms

4.10 OVERALL FAULT CLEARANCE TIMES AT


Mongla

1 Busbar Faults 230 kV


Main protection relay operating time ms
Auxiliary and tripping relay time (where used) ms

Circuit breaker time ms

Total ms

2 KHULNA-MONGLA 230kV Line Faults


2.1 Fault Clearance at Mongla (Main 1)

Distance protection maximum operating time ms

Permissive scheme time delay ms

Auxiliary relay time (where used) ms

Circuit breaker time ms

Total clearance time at Mongla ms

2.2 Fault Clearance at Mongla (Main 2)

Distance protection maximum operating time ms

SE-28
Permissive scheme time delay ms

Auxiliary relay time (where used) ms

Circuit breaker time ms

Total clearance time at Mongla ms

SE-29
PART 5 Digital Fault and Disturbance Recorder [DFDR]

5.1 Digital Fault and Disturbance UNITS BIDDER’S DATA


Recorder [DFDR]
(A) GENERAL
1 Manufacturer’s name & address
2 Type
3 Power Supply VDC
-power Supply for printer VAC

(B) ANALOGUE INPUTS


1 Number of Channel
-Expandability
2 Nominal Current Amp
3 Nominal voltage Vac/Vdc
- Current mA/Amp
4 Frequency response
5 Cut-off frequency
(a) Bandwidth dB
(b) Attenuation at dB
(c) Auto adjusted anti-aliasing filters for Yes/No
chosen sampling rate
d Simultaneously programmable sampling
rate for all feeders/inputs
-Locally Changeable Yes/No
-Remotely Changeable Yes/No
e Possible sampling rates
Samples/sec
Samples/sec
Samples/sec
6 DC coupled inputs Yes/No
7 Resolution bits
8 Accuracy %
9 Burden
1. Current Circuit at IN VA
2. Voltage Circuit VA
10 Over load
1. Current % In
2. Voltage circuit % Vn
(C) DIGITAL INPUTS
1 Number of Channel
-Expandability (Without and time skew)
2 Selectable input level Vdc
3 Type
4 Resolution ms

(D) MEMORY
1 Size MB
2 Type
3 Pre-fault time (fast scanning rate) sec
4 Post-fault (fast scanning rate sec
5 Pre and Post-fault time (slow scanning rate) sec
6 In-Built hard disk (auto-maintained GB

SE-30
Sl. ITEM UNITS BIDDER’S DATA
(E) SENSORS/ TRIGERRING CRITERIA
All sensors/trigerrs are preferable Yes/No
Programmable and Virtually recordable
1. Logical combination sensor Yes/No
2. Three phase over or under Voltage / Current Yes/No
3. Mono phase over or under Voltage / Current Yes/No
4. *du/dt, dp/dt, dq/dt, [Single/3 Phases], df/dt. etc. Yes/No
5. RMS [Voltage / Current] Yes/No
6. Zero Sequence Yes/No
7. Negative, Positive Sequence Yes/No
8. Frequency Yes/No
9. DC Step Yes/No
10. Pendling / Swing Yes/No
11. Digital level and edge Yes/No
12. Sensor trigger Yes/No
13. Event Trigger Yes/No
14. Manual Trigger Yes/No
15. Remote Trigger Yes/No
(F) CLOCK SYSTEM
1. Internal Clock Yes/No
2. Accuracy
3. External Synchronization Yes/No
4. Time resolution between 2 synchronized pulses

(G) OUTPUT ALARM RELAY CONTACT


1. Max. operation Voltage DC/AC Vac / Vdc
2. Make and carry for 0.5 sec A
3. Carry Continuously A
4. Break ( DC ) – resistive W

(H) INTERFACE FOR DATA COMMUNICATION


1. Full definition compression Yes/No
2. Maximum transmission rate bits / Sec
3. Standard serial port ( EIA-232-D) Yes / No
4. Printer Port Yes/No
5. Dedicated serial port for modem Yes/No

(I) PRINTER DATA


1. Printer amplitude (scaling peak to peak)
2. Time Scal (mm / s )
3. Printer resolution mm
4. Auto printing Yes/No

(J) Fault Priority transmission Yes/No

(K) Fault location (distance calculation) Yes/No

(L) Test certificates from internationally recognized Yes/No


Laboratories

(M) COMMUNICATION AND REMOTE ANALYZING UNIT


1. Processor Pentium (MHz) Yes/No
2. Co-Processor Pentium Yes/No
3. Main memory capacity (Mb) Yes/No
4. Color graphics board S-VGA Yes/No
5. Screen S-VGA Yes/No
6. Hard disk unit Yes/No
7. Printer Yes/No
8. Modem Yes/No
*Note: du/dt=Change of voltage, dp/dt=Change of active power, dq/dt=change of reactive power, df/dt=Change of frequency.

SE-31
SE-32
PART-6: Extension of Existing AREVA, France make Fibre Optic
Multiplexer Equipment For Communication and Protection

Unit Bidders Data


6.1 FIBRE OPTIC MULTIPLEXER
EQUIPMENT
6.1.1 GENERAL:
6.1.1.1 Name of the Manufacturer
6.1.1.2 Model No.
6.1.1.3 Type:

Bidder shall provide all necessary information which deem to be necessary to complete the project in
all respects.

SE-33
PART-7: Extension of Existing AREVA, France make Remote Terminal
Unit (RTU) Equipment For SCADA

Unit Bidders Data


7.1 REMOTE TERMINAL UNIT (RTU)
EQUIPMENT
7.1.1 GENERAL:
7.1.1.1 Name of the Manufacturer
7.1.1.2 Model No.
7.1.1.3 Type:

Bidder shall provide all necessary information which deem to be necessary to complete the project in
all respects.

SE-34
PART 8 - FIBRE OPTIC MULTIPLEXER EQUIPMENT

SL.
Description Unit Bidder’s Data
No.
1 GENERAL:
Manufacturer
Model No.
Type
Type of multiplexer
Complying to ITU-T rec.
Transmission Capacity Mbit/s
Access capacity on 64 kbit/s channels
Access capacity on 2 Mbit/s channels
Redundant central processor
Digital cross connect function
2 Available AGGREGATES:
Optical aggregates (ITU-T G.957)
3 Available TRUNK INTERFACES:
HDB3, 2 Mbit/s interfaces per module No.
Complying to ITU-T rec.
HDSL, 2Mbit/s interface: no of copper wires No.
- Capacity on 2Mbit/s or on 1Mbit/s ch
- Capacity selectable ch / pair of wir
e
4 Available USER INTERFACES
5 Voice interfaces for trunk lines:
1 + 1 com path protection, available for all
Analogue, 4wire with E&M: Input level dBr
Output level dBr
Analogue, 2wire with E&M: Input level dBr
Output level dBr
Digital, 2Mbit/s CAS or PRI
6 Voice interfaces for remote Subscriber:
2wire, subscriber side dBr
2wire, PABX side dBr
7 Integrated teleprotection

8 Interface for Commands:


Number of independent commands No.
Transmission time max. ms
Signal voltage Vpeak
1 + 1 com path protection
9 Interface(s) for Differential Protection:
Electrical interface: G.703 kbit/s
Optical Interface kbit/s
10 Data: channels per module
1 + 1 com path protection, available for all
V.24/V.28 (RS-232): up to 38.4kbit/s No.
V.11/X.24 (RS-422): 64kbit/s No.
V.35: 64kbit/s No.
V.36 (RS-449): 64kbit/s No.
G.703: 64kbit/s No.
Ethernet: 10/100 BaseT No.
WAN capacity Mbit/s
Protocols Mbit/s
11 Integrated alarm gathering module:
Number of external alarms per module No.
Auxiliary power supply for ext. contacts
SE-35
SL.
Description Unit Bidder’s Data
No.
12 Network Management System
Type/Name of configuration tool
For fault / configuration management
For local / remote operation
Data communication network (DCN)
13 Ambient Conditions:
Storage: ETS 300 019-1-1, class 1.2 °C / % hum
Transport: ETS 300 019-1-2, class 2.2 °C / % hum
Operation: ETS 300 019-1-3, class 3.1E °C / % hum
14 Power Supply
Operation VDC
Fully redundant power supply

Bidder shall provide all necessary information which deem to be necessary to complete the
project in all respects.

SE-36
POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE F

DEPARTURES FROM THE SPECIFICATION

Schedule F: Departure from Specification SF-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

DESIGN, SUPPLY,ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING


230/132KV KHULNA SOUTH SUBSTATION ON TRUNKEY BASIS.

SCHEDULE F

DEPARTURES FROM THE SPECIFICATION

Bidders are to list all departures from the requirements of the specification in this schedule.

All departures whether they be commercial, financial, technical or of a contractual nature are
to be included and shall be submitted with the Technical proposal

Any item that does not have a departure listed in this schedule will be deemed to be in full
accordance with the requirements of the specification.

No other document or detail accompanying the tender will be considered in evaluating


departures.
Bidders are not permitted to offer any alternative to this schedule.

Item Volume Clause Detail of Departure from Specification

Schedule F: Departure from Specification SF-2


POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE G

PROPOSED ALTERNATIVE STANDARDS


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING


230/132KV KHULNA SOUTH SUBSTATION ON TRUNKEY BASIS.

SCHEDULE G

PROPOSED ALTERNATIVE STANDARDS TO WHICH


EQUIPMENT SHALL BE PROVIDED

The bidder shall list below all the alternative engineering and design Standards, which he
proposes to use in his design, manufacture and testing of equipment to be supplied. Should
these standards differ from the specified standard in any respect, the bidder shall detail the
differences between the proposed and specified standard.

Compliance with any standard equal or superior to those specified will be considered
acceptable.

In the absence of any listed alternative standard, it is deemed that the standards specified in
the Tender documents are fully complied with.

Specified Standard Alternative Standard


Number Title

Schedule G: Proposed Alternative standards SG-2


POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE H

PROPOSED CONTRACT AND SITE ORGANISATION

Schedule H: Proposed contract & site organization and site resources SH-1
POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING


230/132KV KHULNA SOUTH SUBSTATION ON TRUNKEY BASIS.

SCHEDULE H

PROPOSED CONTRACT & SITE ORGANISATION

Personnel

Bidders should provide the names of suitably qualified personnel to meet the requirements specified
in Section 3 (Evaluation and Qualification Criteria) of Volume 1 of 3 of the Bidding Document. The
data on their experience should be supplied using the Form below for each candidate.

Form PER – 1: Proposed Personnel

1. Title of position*

Name

2. Title of position*

Name

3. Title of position*

Name

4. Title of position*

Name

*As listed in Section 3 (Evaluation and Qualification Criteria).

Schedule H: Proposed contract & site organization and site resources SH-2
Form PER – 2: Resume of Proposed Personnel

Position

Personnel Name Date of birth


information

Professional qualifications

Present Name of employer


employment

Address of employer

Telephone Contact (manager / personnel officer)

Fax E-mail

Job title Years with present employer

Summarize professional experience in reverse chronological order. Indicate particular technical and
managerial experience relevant to the project.

From To Company / Project / Position / Relevant technical and management experience

Schedule H: Proposed contract & site organization and site resources SH-3
POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE I

DRAWING AND DOCUMENTS TO BE SUBMITTED WITH BID

Schedule I: Drawings and Documents SI-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING


230/132KV KHULNA SOUTH SUBSTATION ON TRUNKEY BASIS.

SCHEDULE I

DRAWINGS AND DOCUMENTS TO BE SUBMITTED WITH TENDER

Please refer to Volume 1 of 3 in Section 6 (Employers Requirements) of the


Bidding Document.

Schedule I: Drawings and Documents SI-2


POWER GRID COMPANY OF BANGLADESH
LIMITED

BIDDING DOCUMENT

FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF


230KV EXTENSION IN EXISTING 230/132KV SUBSTATIONS AT
KHULNA SOUTH ON TURNKEY BASIS

[CONTRACT NO. PGCB/230kV/SS/KS]

SCHEDULE J

PROPOSED SUBCONTRACTORS

Schedule J: Proposed Subcontractor SJ-1


POWER GRID COMPANY OF BANGLADESH LIMITED

BIDDING DOCUMENT
FOR

DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230kV EXTENSION IN EXISTING


230/132KV KHULNA SOUTH SUBSTATION ON TRUNKEY BASIS.

SCHEDULE J

PROPOSED SUBCONTRACTORS

The bidder shall propose a list of the Sub-contractors in the following table as per sub-clause
2.6, Item 7, Section-3, Evaluation and Qualification Criteria, Volume 1 of 3 of the Bidding
Document.

Sl. No. Name and Address of the Subcontractor

Signature ----------------------------------
Date ----------------------------------

Schedule J: Proposed Subcontractor SJ-2