Process Dynamics and Control Experiment 5 Heat Exchanger Process Control Lab Report
Process Dynamics and Control Experiment 5 Heat Exchanger Process Control Lab Report
1.0 INTRODUCTION
Shell and tube heat exchanger is widely used in the industries. The reason that this
type of heat exchanger is applicable in chemical industries is because of the thermal stressed
that can be applied in it. Other than that, the boiling or condensation can be applied either in
shell or in the tube. In addition, the pressure drop can be varied in wide range plus the design
of heat exchanger can be done either in vertical or horizontal; suitable with plant layout
(Subramanian, n.d).
From the table 1 above, it shows that major variables for operational design (other
than flow rate) are varying with temperatures, viscosities and thermal conductivities. By
application on process control, thermal and temperatures that present in shell and tube heat
exchanger can be influenced the process itself.
In this heat exchanger process control experiment, the controller that had been used is
PID controller (proportional-integral-derivatives controller) which by using this, the offset
can be eliminated and it can reduce the error to zero. It also gives a better performance of the
process control
Figure 1 shows the response of typical PID in closed loop system. From the figure, it
can deduce that by applied this type of controller in process control system, the offset can be
eliminate and also the error can be reduce to zero.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P age |3
2.0 PROCEDURE
A. STARTUP PROCEDURES
1. The following steps had been carried out before starting the experiment:
i. The tank T62 and the product tank T61 were filled with water up their
overflow drain pipe.
ii. The manual valve was checked at the product downstream pipeline TSV62
was opened to the external drain system.
iii. The main power supply at the front cubicle was turned on.
2. The various manual valve was checked as follow:
i. All suction and discharge valve pumps (P61, P62 and P611) were opened.
ii. Manual pass valve for each pumps and control valve TCV61, TSV61, TSV62
and LSV61 was shut.
iii. The manual valve at the inlet of LSV61 was opened.
iv. Bottom drain valves of tank T61 and T62 were always shut.
3. The PID controller TIC61 was learned to use
i. The TIC61 was displayed in mode Manual (M) mode. The MV was set MV=
100% to open the control. The control valve was checked was open at the
plant.
ii. The SV was set to 40 °C.
iii. The PID turning page PID1 was accessed and the PID values was change to
first (I) trial values.
a. PB1= 15 %
b. T11= 35 sec
c. TD1= 8 sec
iv. The on/off control (TIC61 and TIC611) at the ‘P/T register page at PO1 and
PO2 were accessed.
v. The recorder TR61 was started by pressing On the RCD pushbutton.
4. The control valve was stroke with MV= 25 % , 50 % and 100 % with TIC61 in the
Manual (M) mode where the opening TCV61 at the plant was checked.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P age |4
The heating medium for the heat exchanger was produced by heating water in the tank T62. It
maintained constant by the on/off controller TIC62. It controlled with 0.5°C less or more
from the set point values.
ii. The product flow rate was stepped change by opening fully MV61. The flow
rate FI61 was noted and the value at chart paper was written.
iii. The relevant portions of the chart paper were watched and the result was
attached in the report.
7. The relevant portions of the chart paper were retrieved and the results were attached
to the report.
8. SHUTDOWN PROCEDURE
i. The controller TIC61 was switched to Manual (M) mode and MV= 100 % were
switched.
ii. Heater was switched off
iii. All pumps P61, P62 and P611 were stopped
iv. The main power supply was switched off.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P age |8
Next action in this stage is to access on/off controller (TIC62, TIC611) at “P/T
Register page at PO1 and PO5 and the recorder TR61 is been started by pressing it on the
RCD pushbutton. By TIC61 in manual mode, control valve is being stroke with
MV=25%,50% and 100%. This is done in stage to learn the PID controller system and
observe the graph produce.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 12
Figure 2 shows the result in start-up procedure about learning the PID controller. It
been initially put in conditions manual mode with MV=100%, SV=40%, with PID values of
PB1=15%, T11=35sec and TD1=8sec. after that, the control valve had been stroke to change
the MV to 25%, 50% and 100%. The figure 2 shows the result of this PID controller
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 13
The On/Off control results were tabulated in the table below for different process. Table 3,
shows the values of set point for high temperature limit and dead band for controller and
annunciator when the heater was OFF.
Table 3: On/Off temperature control of the electric heaters, when Heater OFF
P T Register I/O Data
High Temp
Dead Band Status
Limit
Meanwhile Table 4 shows the values of set point and dead band for controller and
annunciator when the heater is ON.
From the figure 3 above, the graph indicates the increase in line and then constant
steady line (green pen). The increase in line indicates the temperature is keep rising until the
temperature constant at 55oC with dead band of 0.5oC. For the constant steady line, during
this time, the input variables; X2, is not exceed the high limit temperatures and also in the
range of dead band. The process is run smoothly without any disturbance applied on it.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 15
From the figure 4 above, the graph indicates the change in line (green pen) which now
it oscillates with half cycle. During this time, the input variables; X2 is now below the dead
band range; which by that, the heater at DO1 need to be switch on while the annunciator at
DO2 is to be switch off. Here is the disturbance; that is heater, is being switch on to make the
process back to the steady state as shown in the graph. By switch the heater to on, it increases
the temperature in shell and tube heat exchanger and maintain the dead band around 0.5oC.
Part 2: PID control of temperature
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 16
From figure 5 above, it shows the changes from manual mode process to auto mode
process. At manual mode; by referring to red pen, the line kept at steady line. This indicates
the process is run smoothly without any disturbance occurred. By switching the process to
auto mode, by referring to red pen, the line become decline drastically due to disturbance
occurred. By comparing the manipulated values; MV from both manual at auto mode, the
values are 100% and 47.5% respectively. From the MV values of both modes, there is 52.5%
big difference of them. By such a great difference, that is the reason why the red line decline
drastically when converting the process mode from auto to manual.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 17
From the figure 6 above, for the set point change from 40oC to 42oC, the line for
green pen oscillates continually. But for red pen, the line after changing the set point
oscillates at the beginning and then after a few minutes, it keeps in steady state line. The
reason that the line keep oscillates for green lines is due to changing of set point in the
process. The disturbance was introduced in the process. Supposedly, the set point is to be set
at 40 oC but after changing it to 42 oC, the process needs to reduce it to initial set point so that
a steady state line can be achieved. The PID controller keeps changing because it needs to
reduce the set point so that the zero error can be reduced and the offset can be eliminated.
That is the reason why the green pen line keeps oscillate throughout the process.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 18
From the figure 7 above, after changing the load by opening fully MV61, the line shows
continually oscillations which indicates this process not steady and the disturbance is kept
been applying in this process. The PID controller need to minimize the zero error during the
disturbance takes place in the system.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 19
4.0 ANALYSIS
In this experiment, two types of sensor is used which are red pen and green pen. Red pen
indicates the wall of the heater temperature which it represent RTD by ON/OFF controller.
Green pen indicates the temperature of the flow rate and it represented RTD by PID
controller.
This experiment is to operate ON/OFF temperature control and RTD is used because of
its sensitivity. Table 3 and 4 show the P T register and I/O Data input for ON/OFF
temperature control of the heater. The setting of the value will keep the temperature stable
around 55°C. The ON/OFF controller will always switch the output only when the
temperature has crossed the set point. The heater will automatically turn off when the
temperature of the water reached above the set temperature which is 55°C. The heater will
automatically turn on in order to keep the temperature at the desired temperature when the
temperature drop below the set temperature.
Green pen represented PID controller. Based on the response observed in the chart
paper, it can be seen that there is an increase in the amplitude of an oscillation compared to
the red pen. To be concluded, from the response observed, the ON/OFF controller has higher
damping compared with PID controller where damping is the decrease in amplitude of an
oscillation.
The experiment continued with test disturbance with setpoint change and load change
respectively. It is shown on the chart paper that both of the pen show the fluctuate reading of
the oscillations as the set point changed. PID controller is more fluctuated that ON/OFF
controller. The flow rate was changed by opened fully the valve under steady state system.
The oscillation ON/OFF controller is more stable compared to PID controller. The oscillation
of PID controller response is quite slow compared to before disturbance. If there is a
disturbance, the reading of the response are easily fluctuate.
The temperature increased slowly and in time it fluctuate and went down a little bit
before going up again when the mode is change from Manual [M] mode to Auto [A] mode.
Annunciator is initiated when the temperature exceed the desired value as the heater is not
turn off because of the heater will automatically turn on when the temperature is lowered than
wanted temperature.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 20
5.0 DISCUSSION
The Heat Exchanger Process Control objectives were to study the On/Off temperature
control of electric heaters and to study the temperature control in heat exchanger using PID
controller. Based on the results obtained as shown in Figure 3 and Figure 4, the chart shows
that the High Temperature Limit of the process being controlled by the heat exchanger
perfectly. The curves in Figure 3 shows that the temperature increasing gradually until reach
the temperature limit, and it stopped increasing afterward. It also shows that the process was
able to run smoothly when there is no disturbance applied to the process.
The disturbance might interfere with the process thus resulting a decreasing or increasing in
temperature if applied to the process. By referring to Figure 4, the process curves show that it
oscillates in half cycle. In this step, the disturbance has cause the process output variable, X2
reading below the dead band range. To control this condition, the heater is on and able to
regulate the temperature in shell and heat exchanger and maintain the dead band around 0.5
°C.
The experiment was continued to the second part, to study the Manual Mode (M), and
Auto Mode (A) control of process. According to the chart paper retrieved, when the process
was in Manual mode, the process able to run smoothly because there is no disturbance when
the process is being control in Manual mode. Differ from the Auto mode, when the process
was conducted automatically, the process shows that there is disturbance in the process,
where can be seen in Figure 5, the curve line decrease and decline drastically. Big difference
can be seen for the manipulated value, MV for Manual and Auto mode where for Manual
mode, the MV is at 100% while in Auto mode, the MV is at 47.5%.
Auto mode in PID control, the output is calculated by the controller using the error signal -
the difference between set point and the process variable. Meanwhile, manual mode is
when the output is set manually (Common terms in the process control terminology, n.d)
Auto mode of PID control have a better response compared to Manual mode because Auto
mode able to regulate the condition of the process to the set point compared to Manual mode
where the process need to be controlled manually by human to regulate the operating
condition to original set point. So, Auto mode is much better compare to Manual mode.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 21
However, based on the results obtained, its shown that Manual mode results is much better
than Auto mode controller.
For the next part, the process was continued with test disturbance-set point change. The set
point value is 42 °C, PB1 is 10%, TI1 is 30 secs and TD1 is 7 secs. The curve as shown in
Figure 6, where the disturbance applied to this process shows an oscillation where the
process control was reducing the disturbance to produce a stable process to achieve a steady
state line. The controller tries to eliminate the disturbance to achieve zero error of a process.
Lastly, the process was tested with test disturbance to observe the ability of the process
controller in reducing the disturbance being apply to the process. based on Figure 7, the
curves in the chart portion retrieved shows that it keeps oscillating, indicates that the
controller try to reduce the disturbance applied throughout the whole process.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 22
Differences/ characteristics
No.
Thermocouple RTD
Thermocouples are temperature sensors RTDs are temperature sensors that use the
that use two different metals in the changes in the electrical resistance of
1.
sensor to produce a voltage that can be metals to measure the changes in the local
read to determine the local temperature. temperature.
Thermocouple has better cost, cheaper, RTD has high cost, low measurement
2. measurement speeds and range of speeds and narrow range of temperature.
temperature than RTD
Thermocouples are designed to be more RTDs are superior to thermocouples in
durable and react faster to changes in that their readings are more accurate and
3. temperature because of that same more repeatable which over multiple trials,
design. the readings of temperature produce same
results.
Thermocouple is produced to be RTD react slower than thermocouple to
4. sturdier and react quickly to changes in changes in temperature in same design.
temperature in same design.
Thermocouple accept less strong RTD continue bearing constant readings
signals and it is complicated to alter and longer than Thermocouple. RTD accept
5. read the readings. more strong signals and it is easier to
mechanically alter or read the readings due
to the design produced
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 23
7.0 CONCLUSION
There are two main objectives in the Heat Exchanger Process Control experiment.
They are to study on/off temperature control of electric heaters and to study temperature
control in heat exchanger using PID controller. By controlling the on/off of the heater, the
temperature in shell and tube heat exchanger was managed to increase or and the dead band
was maintained around 0.5˚C. The heater was switched on so that the process can go back to
its steady state as shown in the graph. Except on figure 6, the green line was oscillating
perfectly but for the red line it oscillates at the beginning and kept a steady line after a few
minutes. This happened because the set point was changed or a disturbance was introduced.
The PID controller keeps changing because it needs to reduce the set point so that the zero
error can be reduced and the offset can be eliminated. By seeing all the important findings
throughout the experiment, the objectives of the experiment was achieved and it was a
success.
To make sure the experiment was running smoothly, all members must follow the
instructions in the lab manual very carefully. The result that we obtained could have been
better if we remember to close the by-pass valve B62 during on/off temperature procedure.
This is an important step to obtain more accurate and desirable result and data of this
experiment in the future. It is necessary to make sure manual valves is in correct whether
open or shut and the manual valve. Besides that, make sure the result or chart is recorded
subsequently the data is set up in monitor so that the output response in the chart will stable.
Other than that, make sure to know the differences between oscillatory and steady. This is
important to test whether the set point was set up correctly or not. If not, the objective to
study temperature control using the PID controller cannot be achieved.
CPB30004- Process Dynamics and Control
Experiment 5: Heat Exchanger Process Control P a g e | 25
9.0 REFERENCES
2. National instrument. (2011, March 29). PID Theory Explained. Retrieved November
17, 2016, from National Instrument: http://www.ni.com/white-paper/3782/en/#toc2
4. Process Control and Common Terms. (n.d.). Retrieved November 17, 2016, from
http://www.engineeringtoolbox.com/process-control-terms-d_666.htm