Objective Type Questions For Power System Operation and Control Final Year
Objective Type Questions For Power System Operation and Control Final Year
MEWAR UNIVERSITY
DEPARTMENT OF ELECTRICAL ENGINEERING
UNIT – 1
Questions 1 to 4 refer to the figures given below:
The input-output curves for two units with supply in parallel a common load are shown in the
figure
Q 4. If both generators have 2 MW load each then which of the following statements is
correct?
(A) Generator A runs at higher speed as compared to generator B
(B) Generator B runs more efficiently as compared to generator A
(C) Input to generator A is less than 75% of the input to generator B
(D) Input to generator B is less than the input to generator A by about 23%
A bulk supply was taken by a large industrial consumer at the rate of Rs 80 per KW plus 2
5 paisa per KWh
Q 5. The average charge per KWh when the load factor is 20% will be
(A) 3 cents
(B) 5 cents
(C) 7 cents
(D) cannot be determined on the basis of the information provided
Q 6. The average charges per KWh will be least when the plant load factor is
(A) 100%
(B) 75%
(C) 50%
(D) 20%
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) The area under the curve gives the average demand
(B) The ratio of the area under the curves to the total area of rectangle in which it is
contained gives the load factor for the day
(C) The peak of the curve gives the 'installed capacity of the plant
(D) The area of the curves divided by the number of hours gives load factor
Q 8. An Equipment purchased for Rs10, 000 two years ago has a market value of Rs
12500 at present. It can be concluded that
(A) Condenser
(B) Boiler
(C) Turbine
Four loads as shown in figure given below are connected to a power station Abscise is time from
0 to 24 hrs in all cases, Ordinate represents the load in KW
Load A
Load B
Load C
Load D
(A) A and B
(B) B and C
(C) C and D
(D) A, B and D
(A) 3000 KW
(B) 3500 KW
(C) 4000 KW
(D) 4250 KW
Q 13. The load factor of the plant supplying power to these loads will be nearly
(A) 11%
(B) 15%
(C) 18%
(D) 21%
Q 14. The diversity factor of the plant supplying these loads will be
(A) 0.5
(B) 1.0
(C) 1.5
(D) 0.2
Q 15.
n
∑ PGi−P D −P Loss=0
i=1
Pmin max
Q 16. Gi ≤ P Gi ≤ P Gi , i=1,2, … … . , N
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
N
Q 18. F ( PGi )=∑ ai +bi PGi + c i P2Gi W h ere i=1, … … … … , N
i=0
Q 20. Which of the following generating station has minimum ruining cost?
(A) Nuclear
(B) Hydro
(C) Thermal
(D) Diesel
d Ci
(A) IC=
d PGi
d PGi
(B) IC=
d Ci
N
(C) IC=∑ a i+ bi PGi +c i PGi
2
i=0
(D) None of these
Q 38. “Its loading from now on is held fixed at this value and the balance load is then
shared between the remaining generators on equal incremental cost basis.” This theory
knows
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 39. Incremental fuel costs in rupees per MWh for a plant consisting of two units are:
IC 1=0.20 PG 1+ 40
IC 2=0.25 PG 2 +30
Where PG 1 and PG 2 (in MW) are power generated by both the units for a total demand of
250 MW, The total shared by the two units are
350 400
(A) PG 1= ∧PG2=
3 3
Q 40. “Its loading from now on is held fixed at this value and the balance load is then
shared between the remaining generators on equal incremental cost basis.” This theory
knows
Q 42. The input when the plant was running on no load was
(D) zero
Q 44. When the load on the generator was 25 MW the heat rate in kcal / MW hr was
nearly
(A) 16 x 106
(B) 20 x 106
(C) 30 x 106
Q 46. At what KW rating the initial cost of the two machines will be identical?
(A) 5500 KW
(B) 6000 KW
(C) 7600 KW
(D) 8500 KW
Q 47. At what rating in KWh the two sets will be equally economical to operate?
(A) KWh / KW
(D) KW / KWh
Q 49. For the same cylinder dimensions and speed, which engine will produce least
power?
(C) Batteries
(A) No blades
(A) I and II
(A) I
(B) III
(C) IV
(D) V
Q 57. A certain plant has fixed cost of Rs 40,000 and a salvage value of Rs 4000 at the
end of a useful life of 20 years The depreciated value of the plant at the end of 10 years
will be least (interest rate being 6% compounded annually) when calculated by
Q 58. In the above problem the value will be highest when calculated by
Q 60. Which type of plant has the least running cost per KWh of energy generated?
(A) High capital cost, high operating cost and high load factor
(B) High capital cost, low operating cost and high load factor
(C) Low capital cost, low operating cost and low load factor
(D) Low capital cost, high operation cost and high load factor
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 64. In a thermal power station of moderate size, the electrical power is generated at a
voltage of
(A) 115 V
(B) 230 V
(C) 440 V
(D) 11 kV
Q 65. The resistance of the dry skin of human body, between the tip of the left hand
finger and right hand finger, is of the order of
Q 66. If the resistance of dry skin of human body is 100,000 ohms, the resistance of the
wet body will be
(A) Voltage
(B) Current
Q 69. Death is almost certain when the current through human body is
(D) 100milliamperes
(A) Bandage
(B) Massage
Q 72. When a power plant is not able to meet the demand of consumers it will resort to
(A) Penalizing high load consumers by increasing the charges for electricity
Q 74. Which of the following power plants can generate power at unpredictable or
uncontrollable times?
(C) Batteries
(A) Oxygen
(B) Ammonia
(C) Hydrogen
(A) Debentures
(B) Bonds
(C) Share
Q 78. Ideally depreciated value of the plant plus the accumulation in the depreciation
fund should be equal to
Q 81. Maximum demand tariff is generally not applied to domestic consumers because
Q 82. How much must be deposited at the end of each year in a sinking fund for 15
years to accumulate Rs 1000 if interest is at 5 percent?
(A) Rs 46.34
(B) Rs 54.55
(C) Rs 59.50
(D) Rs 60.00.
Q 83. If Rs. 50 were deposited at the end of each year for 12 years in a sinking fund
earning 6%,the total accumulation would be
(A) Rs 1000
(B) Rs 925.50
(C) Rs 843.50
(D) Rs 799.75.
Q 85. All of the following are repayable after some time EXCEPT
(A) Bonds
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(B) Shares
(A) Diversity factor is less than one and demand factor is more than one
(B) Diversity factor more than one and demand factor is less than is one
Q 87. The amount repaid to a person at the end of 15 years, who invests Rs 12,000 at 4
percent interest compounded annually, will be
(A) Rs 12,400
(B) Rs 16,120
(C) Rs 21,612
(D) Rs 26,121.
Q 88. What is the present worth of receiving Rs 1000 twenty years from now if money
can earn 5% interest compounded annually?
(A) Rs 376.93
(B) Rs 445.50
(C) Rs 500.00
(D) Rs 617.27.
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 89. The amount accumulated, when the interest is compounded annually will be
(A) Rs 27,020
(B) Rs 30,270
(C) Rs 32,070
(D) Rs 35,600.
Q 90. The amount accumulated when the interest is compounded semi-annually will be
(A) Rs 32,070
(B) Rs 32,474
(D) Rs 32,888.
Q 91. The amount accumulated when the interest is compounded monthly will be
(A) Rs 32,070
(B) Rs 32,620
(C) Rs 32,898
(D) Rs 33,100.
Q 92. As the load factor approaches unity, the shape of load duration curve will be
nearly
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) L shaped
(C) Triangular
(D) Rectangular.
Q 93. When maximum and average loads are equal, the load factor will be
(A) Zero
(B) 0.01
(C) 0.5
(D) 1.0
I. Diesel
II. Thermal
III. Hydro
IV. Nuclear.
Q 99. Plants in ascending order of their operating cost per MWH generated are
1 D 21 A 41 A 61 B 81 D
2 B 22 D 42 C 62 A 82 A
3 A 23 A 43 C 63 C 83 C
4 C 24 A 44 A 64 D 84 D
5 C 25 C 45 B 65 D 85 B
6 A 26 A 46 C 66 D 86 B
7 D 27 D 47 C 67 D 87 C
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
8 D 28 A 48 B 68 A 88 A
9 B 29 C 49 A 69 D 89 C
10 C 30 A 50 C 70 D 90 C
11 D 31 D 51 A 71 D 91 D
12 D 32 C 52 A 72 D 92 D
13 A 33 D 53 A 73 D 93 D
14 B 34 A 54 D 74 D 94 D
15 A 35 C 55 A 75 A 95 A
16 B 36 A 56 B 76 A 96 C
17 C 37 B 57 C 77 C 97 A
18 C 38 B 58 B 78 D 98 C
19 D 39 A 59 A 79 D 99 B
20 B 40 B 60 A 80 D 100 A
Unit - 2
Q 101. Load curve helps in deciding
Q 104. Which of the following plants is almost inevitably used as base load plant?
Q 105. A thermal power station was designed to bum coal containing 12% ash
When the plant actually started operating coal having 22% ash was made available
Which unit of the plant will need major modifications ?
Q 107. Which of the following plants will take least time in starting from cold conditions
to full load operation?
Q 109. For the same plant size, initial cost of which plant is the highest?
Q 110. A consumer takes a steady load of 200 kW at a power factor of 0.85 lagging for 8
hours per day and 315 days per annum. The annual payment under the tariff of Rs80 per
annum per kA plus 10 cents per kWh will be
(A) Rs 5040
(B) Rs 50,400
(C) Rs 69,200
(D) Rs 88,400
The estimated total annual operating cost and capital charges for two proposed power stations
are given by the following expressions
Annual cost of station A = Rs (600,000 + 3.0 kW + 0.015 kW hr) Annual cost of station B = Rs
(750,000 + 5.0 kW + 0.014 kW hr)
Where kW represents the capacity of the station and kWh represents the total annual output
Load duration curve of the plant is shown in the figure given below
(A) Station A
(B) Station B
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(B) 1000hrs
Q 113. The capacity of the base load plant should not be less than
(A) 3860 kW
(B) 4180 kW
(C) 5000 kW
(D) 5500 kW
(B) 15 x 106
(C) 18 x 106
Q 116. For a load flow solution the quantities normally specified at a voltage controlled
bus are:
(A) P and Q
(B) P and I V I
(C) Q and I VI
(D) P and ᵟ
Q 117. For a 15-bus power system with 3 voltage controlled bus, the size of Jacobian
matrix is (a) 11 x 11 (b)12 x 12 (c) 24 x 24 (d) 28 x 28.
In the solution of load-flow equation, Newton-Raphon (NR) method is superior to the Gauss-
Seidal (GS) method, because the
(A) time taken to perform one iteration in the NR method is less when compared to
the time taken in the GS method
(B) number of iteration required in the NR method is more when compared to that in
the GS method
(C) number of iterations required is not independent of the size of the system in the
NR method
(D) convergence characteristic of the NR method are not affected by the selection of
slack bus.
Q 118. Which one of the following matrices reveals the topology of the power system
network ?
(C) constant real and reactive powers drawn from the bus
(E)
Q 120. In Gauss-Seidel method of power flow problem, the number of iterations may be
re-duced if the correction in voltage at each bus is multiplied by
Q 121. Consider the following statements : 1. It is easier to construct the YBus matrix as
compared to ZBus. 2. ZBus is a full matrix while Ybus is sparse. 3. Y-bus can be easily
modified whenever the network changes as compared to the ZBus. Which of these
statements are correct ?
(A) 1 and 2
(B) 2 and 3
(C) 1 and 3
(D) 1, 2 and 3.
Q 122. In load flow studies of a power system, a voltage control bus is specified by
Q 123. At slack bus, which one of the following combinations of variables is specified ?
(A) I V I,ᵟ
(B) P, Q
(C) P, I V I
(D) Q, I V I.
Q 124. Consider the following quantities : 1. Real power 3. Power factor 5. Bus voltage
magnitude
For the purpose of the load flow studies of a power system, each bus or node is associated with
which one of the combinations of the above four quantities ?
(A) 1, 3, 4 and 5
(B) 1, 2, 3 and 4
(C) 2, 3, 5 and 6
(D) 1, 2, 5 and 6.
Q 126. Gausss - Seidel iterative method can be used for solving a set of
Q 127. A power system consists of 300 buses out of which 20 buses are generator buses,
25 buses are the ones with reactive power support and 15 buses are the ones with fixed
shunt capacitors. All the other buses are load buses. It is proposed to perform a load flow
analysis for the system using Newton - Raphson method. The size of the Newton -
Raphson Jacobian matrix is
(c) Constant real and reactive powers drawn from the bus
(a) 1/2 hr
(b) 24 hr
(c) 1 sec
(d) 1 week
(a) k-cal/kwhr Vs KW
(b) K-cal/hr Vs KW
(c) k-cal/KW Vs Kw
(d) K-cal Vs KW
Q 133. In power system each bus is associated with how many quantities.
(a) 4
(b) 3
(c) 5
(d) none
Q 134. If real and reactive power components are specified then it is which type of bus.
(a) PQ bus
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(b) PV bus
(d) none
Q 135. For which bus in the power system the voltage magnitude corresponding to the
generation voltage and real power corresponding to its ratings are specified.
(a) PQ bus
(b) PV bus
(d) none
Q 136. Which bus is in the power system is made to take additional real and reactive
power to supply transmission losses.
(a) PQ bus
(b) PV bus
(d) none
Q 137. For which bus we have to find out the voltage magnitude and phase angle of the
bus through the load flow solution.
(a) PQ bus
(b) PV bus
(d) none
Q 138. For which bus we have to find out the reactive power generation and phase angle
of the bus through the load flow solution
(a) PQ bus
(b) PV bus
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(d) none
(a) True
(b) false
Q 140. I BUS= YBUS VBUS ,is the equation for n bus system, in this the matix size of YBUS is
nXn.
(A) True
(B) False
Q 141. I BUS= YBUS VBUS ,is the equation for n bus system, in this the matix size of YBUS is
nX1.
(a) True
(b) False
Q 142. I BUS= YBUS VBUS ,is the equation for n bus system, in this the matix size of YBUS is
(a) nXn
(b) 1Xn
(c) nX1
(d) 1X1
Q 143. I BUS= YBUS VBUS ,is the equation for n bus system, in this the matix size of IBUS is
(A) nXn
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(B) 1Xn
(C) nX1
(D) 1X1
Q 144. I BUS= YBUS VBUS ,is the equation for n bus system, in this the matix size of
VBUS is
(a) nXn
(b) 1Xn
(c) nX1
(d) 1X1
(a) true
(b) false
(a) true
(b) false
(c) both
(d) none
(c) both
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(d) none
(a) true
(b) false
(d) none.
(a) true
(b) false
(a) true
(b) false
(a) true
(b) false
(a) true
(b) false
(a) true
(b) false
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(a) true
(b) false
(c) both
(d) none
Q 158. Load flow solution for power network can be worked out operation under
(c) both
(d) none
(d) none
Q 160. If real and reactive power components are specified then it is which type of bus.
(d) none
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 161. For which bus in the power system the voltage magnitude corresponding to the
generation voltage and real power corresponding to its rating s are specified
(d) none
Q 162. Which bus is in the power system is made to take additional real and reactive
power to supply transmission losses.
(d) none
Q 163. For which bus we have to find out the voltage magnitude and phase angle of the
bus through the load flow solution.
(d) none
Q 164. For which bus we have to find out the reactive power generation and phase angle
of the bus through the load flow solution
(d) none
Q 165. slack bus is in the power system is made to take additional real and reactive
power to supply transmission losses.
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(a) true
(b) false
Q 166. For generator bus we have to find out the voltage magnitude and phase angle of
the bus through the load flow solution
(a) True
(b) False
Q 167. For generator bus we have to find out the reactive power generation and phase
angle of the bus through the load flow solution.
a) true
b) false
Q 168. The voltage controlled bus is treated as a load bus in subsequent iteration when its
Voltage limit is violated.
(a) True
(b) False
Q 169. The voltage controlled bus is treated as a load bus in subsequent iteration when
its:active power limit is violated.
(a) true
(b) false
Q 170. The load flow solution is always assured in case of Newton-Raphson method.
(a) True
(b) False
Q 171. The bus admittance matrix (Ybus) of a power system is Symmetric matrix.
(a) true
(b) false
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 172. The bus admittance matrix (Ybus) of a power system is Sparse matrix.
a) true
b) false
Q 173. The bus admittance matrix (Ybus) of a power system is equal to Zbus matrix.
(a) True
(b) False
Q 174. The voltage controlled bus is treated as a load bus in subsequent iteration when
its:
none of these
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(d)none of these
Q 178. At slack bus, which one of the following combination of variables is specified?
(a) |V|, δ
(b) P, θ
(c) P, |V|
(d) θ,|V|
(a) |V|, δ
(b) P, |V|
(c) P, θ
(d) θ, |V|
Q 180. At Load bus, which one of the following combination of variables is specified?
(a) P, θ
(b) θ, |V|
(c) |V|, δ
(d) P, Q
Q 181. Which of the following quantity is associated with each bus or node for the
purpose of load flow studies of a power system
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(d) frequency
(a) Symmetric
Q 183. If a voltage controlled bus is treated as load bus, then which of the following
limits would be violated?
(a) Volatge
Q 184. For a 15-bus power system with 3 voltage controlled bus, the size of Jacobian
matrix is
(a) 11 X 11
(b) 12 X 12
(c) 24 X 24
(d) 28 X 28
Q 185. The diagonal elements of a nodal admittance matrix are strengthen by adding
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(c) loads
(d) Generators
a. Newton-Raphson method
b. Gauss method
c. Gauss-Seidel method
Q 187. In which of the following methods of load flow analysis the convergence of
solution does not depend upon choice of slack bus
a. Newton-Raphson method
b. Gauss method
c. Gauss-Seidel
d. none of these
d. None of these
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 189. Which fundamental law is applied at each node in a multi bus system to obtain
Ybus matrix
a. KVL
b. KCL
c. both
Q 190. In a large system of 100 nodes, the non-zero elements may be as small as
a. 20%
b. 22%
c. 2%
d. 9%
a. Singular matrix
b. Symmetric matrix
c. Sparse matrix
Q 192. In load flow studies of a power system, a voltage control bus is specified by
Q 193. In Gauss-Seidel method of power flow problem, the number of iterations may be
reduced if the correction in voltage at each bus is multiplied by
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
a. Gauss constant
b. Acceleration constant
c. Deceleration constant
d. Blocking factor
a. Fault calculations
b. stability studies
c. System planning
a) quadratic b) linear
C) geometric d) cubic
1. Load bus
2. PV bus(b)
3. Slack bus
Q 198.
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 199. The principal information obtained from load flow studies in a power system are
(A) 1 and 2
(B) 3 and 4
(C) 1, 2 and 3
(D) 2 and 4
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 200. Direction : The following two items consist of two statements, one labelled as
Assertion ‘A’ and the other labelled as Reason ‘R’. You are to examine these two
statements carefully and decide if the Assertion A and the Reason R are individually true
and if so, whether the Reason is a correct explanation of the Assertion. Select your
answers to these items using the codes given below.
Codes :
(B) Both A and R are true but R is NOT the correct explanation of A
Reason (R) : In load flow studies, one of the buses is take as a slack bus.
Consider the following statements in respect of load flow studies in power systems :
2. Gauss-Seidel method is preferred over Newton-Raphson method for load flow studies
(A) 1, 2 and 3
(B) 1 and 2
(C) 1 and 3
(D) 2 and 3
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Unit- 3
Q 201.
Q 202. The YBUS matrix of a 100-bus interconnected system is 90% sparse. Hence the
number of transmission lines in the system must be
(A) 450
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(B) 500
(C) 900
(D) 1000
Q 203.
Q 204.
Q 204. At a particular unbalanced node, the real powers specified
are: Leaving the node 20 MW, 25 MW
Entering the node 60 MW, 30 MW The
balancing power will be:
(d) 22.5 MW entering the node and 22.5 MW leaving the node.
Q 205. The loss coefficients for a two-bus system are given as follows:]
Q 206. For economic operation, the generator with highest positive incremental
transmission • loss will operate at:
(A) ±5 Hz
(B) ±0.5 Hz
(C) ±0.6 Hz
(D) ± 0.05 Hz
Q 211. The change in load demand, this will meet out by alternator
Q 213. Maintain network frequency constant so that the powers so that the power station
are satisfactorily parallel on the system run at the desired speed correct time is obtained
from
(A) Synchronoscope
(C) A and B
(A) frequency
(B) Voltage
(D) Speed
(A) frequency
(B) Voltage
(D) Speed
(A) ∆ Pc ( s)
(B) ∆ P D (s)
(C) ∆ PG ( s)
(D) ∆ F (s )
(A) ∆ Pc ( s)
(B) ∆ P D (s)
(C) ∆ PG ( s)
(D) ∆ F ( s )
(A) ∆ Pc ( s)
(B) ∆ Y E ( s)
(C) ∆ PG ( s)
(D) ∆ F (s )
(A) ∆ Pc ( s)
(B) ∆ P D (s)
(C) ∆ PG ( s)
(D) ∆ F ( s )
(A) ∆ Pc ( s)
(B) ∆ P D (s)
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(C) ∆ PG ( s)
(D) ∆ F (s )
(A) ∆ Pc ( s)
(B) ∆ P D (s)
(C) ∆ PG ( s)
(D) ∆ F ( s )
(A) ∆ Pc ( s)
(B) ∆ P D (s)
(C) ∆ PG ( s)
(D) ∆ F (s )
(A) K1KC/K2
(C) 1/K5 K4
(A) K1KC/K2
(C) 1/K5 K4
(A) K1KC/K2
(C) 1/K5 K4
−1
(A) 1
B+
R ( )
(B) B+ ( 1R )
(C) ( R1 )
(D) None of them
Q 235. For 250 MW machine with an operating load of 125 MW. let the change in load
∂P
be 1% for 1% change in frequency (scheduled frequency = 50 Hz). Then
∂f
Q 236. For 250 MW machine with an operating load of 125 MW. let the change in load
∂P
be 1% for 1% change in frequency (scheduled frequency = 50 Hz). Then
∂f
(D) 1 pu MW/Hz
Q 237. A 100 MVA synchronous generator operates on full load at frequency of 50 Hz.
The load is suddenly reduced to 50 MW. Due to time lag in governor system, the steam
valve begins to close after 0.4 seconds. Given H = 5 kW-sec/KVA of generator capacity.
Determine the change in frequency that occurs in this time.
(A) 51 Hz
(B) 50 Hz
(C) 48 Hz
(D) 49 Hz
Q 238. A 100 MVA synchronous generator operates on full load at frequency of 50 Hz.
The load is suddenly reduced to 50 MW. Due to time lag in governor system, the steam
valve begins to close after 0.4 seconds. Given H = 5 kW-sec/KVA of generator capacity.
Determine Excess power input to generator
(A) 50 MW
(B) 52 MW
(C) 53 MW
(D) 40 MW
Q 239. A 100 MVA synchronous generator operates on full load at frequency of 50 Hz.
The load is suddenly reduced to 50 MW. Due to time lag in governor system, the steam
valve begins to close after 0.4 seconds. Given H = 5 kW-sec/KVA of generator capacity.
Determine Kinetic energy stored in rotating parts of generator and turbine
(A) 0.5 MW
(B) 5.0 MW
(C) 3.0 MW
(D) 1.6 MW
Q 240. A 100 MVA synchronous generator operates on full load at frequency of 50 Hz.
The load is suddenly reduced to 50 MW. Due to time lag in governor system, the steam
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
valve begins to close after 0.4 seconds. Given H = 5 kW-sec/KVA of generator capacity.
Determine Excess energy input to rotating parts in 0.4 sec
Q 241. Two generators rated 200 MW and 400 MW are operating in parallel. The droop
characteristics of their governors are 4% and 5%, respectively from no load to full load.
Assuming that the generators are operating at 50 Hz at no load, Assume free governor
operation, how would a load of 600 MW be shared between them?
Q 242. Two generators rated 200 MW and 400 MW are operating in parallel. The droop
characteristics of their governors are 4% and 5%, respectively from no load to full load.
Assuming that the generators are operating at 50 Hz at no load, What will be the system
frequency at this load? Assume free governor operation.
(A) 51.59 Hz
(B) 47.69 Hz
(C) 48.99 Hz
(D) 49.00 Hz
(A) CEDC
(B) CEC
(C) EDC
(A)
|V 1||V 2|
PX
|V 1||V 2|
(B) sin ( δ 01−δ 01 )
P r 1 X 12
(C)
|V 1||V 2|
sin ( δ 1−δ 2)
P
Q 246. Maintain network frequency constant so that the powers so that the power station
are satisfactorily parallel on the system run at the desired speed correct time is obtained
from
(A) Synchronoscope
(C) A and B
K sg
Q 250. This equation shows
1+T sg s
Kt
Q 251. This equation shows
1+T t s
K ps
Q 252. This equation shows
1+T ps s
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
213 A 233 C
214 A 234 A
215 A 235 A
216 C 236 B
217 A 237 A
218 D 238 A
219 D 239 A
220 A 240 B
Unit=4
Q 253. Zero power factor method of an alternator is used to find its
(C) efficiency
(A) excitation
(B) speed
(C) load
Q 256. For alternation having fractional pitch of 5/6 the coil span is
(A) 90°
(B) 120°
(C) 150°
(D) 180°
(A) 7/6
(B) 6/7
(C) 6/5
(D) 3/5
Of these statements
Q 259. A 3-phase synchronous generator, with its armature resistance and the leakage
reactance being neglected, is synchronized to an infinite bus and its field excitation is
kept constant thereafter Now the machine is loaded by Supplying mechanical input
to the shaft so that the load-angle δ reaches a value of 60° Under this condition, the
operating power-factor would be
(C) 0 .5 leading
Q 260. A round rotor synchronous generator has a leakage reactance of 10%, armature
reaction reactance of 90% and negligible armature resistance with the machine initially
running at rated speed and terminal voltage of 1.0 pu, a 3-phase short-circuit is applied
The sustained armature current will be
(A) 1.25 pu
(B) 1.11 pu
(C) 1.0 pu
(D) 0.9 pu
(A) establish the armature flux through the direct-axis magnetic circuit of the
machine
(B) allow only partial linkage of the armature flux with the main field winding
(C) confine the armature flux to completely link the damper winding
(D) repel the armature flux and confine it to the leakage flux path in the air-gap
(A) magnetizing
(B) demagnetizing
(C) cross-magnetizing
Q 263. Which of the following limit the reactive power output of a synchronous
generator ?
1 Armature current
2 Field current
3 Load angle
Codes
(A) 1 and 2
(B) 2 and 3
(C) 3 and 4
(D) 1 and 4
State whether the following statements related to Synchronous Generator are true (T) or
false (F):
Q 265. Synchronous reactance can be determined from open circuit and short circuit tests
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) TRUE
(B) FALSE
(A) TRUE
(B) FALSE
Q 267. Percentage resistance is the resistance drop at rated current and frequency
expressed as the percentage of the rated voltage
(A) TRUE
(B) FALSE
Q 268. MMF method for regulation does not use data available from open circuit and
short circuit tests
(A) TRUE
(B) FALSE
Q 269. In short-pitch windings fractional number of slots per pole can be used
(A) TRUE
(B) FALSE
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) TRUE
(B) FALSE
(A) TRUE
(B) FALSE
(A) TRUE
(B) FALSE
(A) TRUE
(B) FALSE
Q 274. Synchronous generator must operate at the correct speed as it determines the
frequency since the number of poles is fixed for any given machine
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) TRUE
(B) FALSE
Q 275. The voltage regulation of an ac generator is defined as the rise in voltage when
the load is reduced from full-rated load value to zero, speed and field current remaining
constant
(A) TRUE
(B) FALSE
(A) TRUE
(B) FALSE
(A) TRUE
(B) FALSE
(A) The greatest of all "short time interval averaged" demand during a period
(D) Forty
Q 280. Squirrel cage bars placed in the rotor pole faces of an alternator help reduce
hunting
Q 282. With a unity load p f, the effect of armature reaction on the main field flux
of an alternator is
(A) Distortional
(B) Magnetizing
(C) Demagnetizing
(D) Nominal
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) Cross-magnetising
(B) Demagnetizing
(C) Non-effective
(D) Magnetizing
Q 284. The frequency of voltage generated by an alternator having 4 poles and rotating at
1800 rpm is
(A) 60 Hz
(B) 7200 Hz
(C) 120 Hz
(D) 450 Hz
Q 285. The main disadvantages of using short pitch winding in alternators is that it
(A) Efficiency
Q 288. The effect of increasing air gap length in the induction motor will increase the
(B) Speed
Q 289. The principle of operation of a 3 phase induction motor is most similar to that of a
Q 290. Squirrel cage bars placed in the rotor pole faces of an alternator help reduce
hunting
Q 291. The stationary alternator should not be connected to live bus-bars because it
Q 292. With a unity load pf, the effect of armature reaction on the main field flux of an
alternator is
(A) Distortional
(B) Magnetizing
(C) Demagnetizing
(D) Nominal
(A) Cross-magnetising
(B) Demagnetizing
(C) Non-effective
(D) Magnetizing
Q 294. The frequency of voltage generated by an alternator having 4 poles and rotating at
1800 rpm is
(A) 60 Hz
(B) 7200 Hz
(C) 120 Hz
(D) 450 Hz
Q 295. The main disadvantages of using short pitch winding in alternators is that it
(A) Efficiency
Q 298. The effect of increasing air gap length in the induction motor will increase the
(B) Speed
Q 299. The principle of operation of a 3 phase induction motor is most similar to that of a
(A) Voltages
(B) Frequencies
(D) A synchroscope
Q 303. Alternators shouldn't be paralleled unless the synchronizing lamps are lighting &
dimming ___
(A) In rotation
(C) In unison
(D) Alternately
Q 304. Three lights flashing rapidly in unison while paralleling alternators means that
____
(A) A synchroscope
Q 306. When the pointer of a synchroscope is stationary & points upward during the
paralleling operation, the ____
(C) The alternator will continue to run as a synchronous motor rotating in the same
direction
(D) The alternator will continue to run as a synchronous motor rotating in the
opposite direction
Q 311. The figure shows the characteristics of an alternator. Which curve represents
synchronous impedance?
(A) curve A
(B) curve B
(C) curve C
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(D) curve D
Q 312. In the above figure (Figure of Question 49) which curve represents short circuit ?
(A) curve A
(B) curve B
(C) curve C
(D) curve D
Q 313. In the above figure which curve represents open circuit voltage ?
(A) curve A
(B) curve B
(C) curve C
(D) curve D
Q 314. For a peripheral speed of 314 m/s, a 2 pole cylindrical machine will have
maximum diameter of
(A) 255 cm
(B) 235 cm
(C) 200 cm
(D) 170 cm
Q 315. The rotor of the salient pole alternator has 24 poles. The number of cycles of emf
in one revolution would be
(A) 24
(B) 12
(C) 6
(D) 4
Q 316. Two alternators A and B are sharing an inductive load equally If the
excitation of alternator A is increased
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) alternator B will deliver more current and alternator A will deliver less current
(B) alternator B will deliver less current and alternator A will deliver more current
(A) 25 Hz
(B) 50 Hz
(C) 100 Hz
(D) 400 Hz
Q 320. A 20 pole ac generator rotates at 600 rpm The periodic time of current in
seconds per cycle is
(A) 0.009
(B) 0. 004
(C) 0 .008
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(D) 0. 01
Q 322. The synchronizing power developed in one of the alternators, when two
alternators are running in parallel, will load the same alternator in which it is developed
and reduce its speed
(A) True
(B) False
Q 323. If the input to the prime mover of an alternator is kept constant but the excitation
is changed then the
Q 324. If two machines are running in synchronism and the voltage of one machine is
suddenly increased
Q 325. In an alternator, at 0.8 lagging power factor, the generated voltage per phase is
240 V to give a rated terminated voltage ' V ' . If the power factor of load increases to
unity, the generated voltage per phase must be
(A) 260 V
(B) 250 V
(C) 240 V
(D) 225 V
Q 327. Magnetization curves for no load and full load unity power factor are shown in
figure below Which is the magnetization curve for full load 0 8 power
factor?
(A) curve A
(B) curve B
(C) curve C
(D) curve D
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(A) the speed of the alternator will increase but kW delivered will remain unchanged
(B) the speed of the alternator will increase and kW delivered will also increase
(C) the speed of the alternator will remain unchanged but it can meet more kW
demand
(D) the speed of the alternator will remain unchanged but it will deliver more kVA
Q 329. Two alternators A and B are sharing a resistive load (P f = 1 ) equally. Now if
the excitation of alternator A is increased
(A) alternator A will become lagging and alternator B will become leading
(B) alternator A will become leading and alternator B will become lagging
(B) provide a low resistance path for the currents due to unbalancing of voltage
Q 331. When two alternators are running in exactly synchronism, the synchronising
power wil be
(A) zero
(C) unity
(D) 0.707
Q 333. Load characteristic curves for an alternator are shown. The curves are drawn for
0. 8 pf lagging, 0.8 pf leading, 0.7 p f leading and 0. 9 pf lagging. Which curve
represents the characteristics for 0 .8 p f leading ?
(A) curve A
(B) curve B
(C) curve C
(D) curve D
(A) curve A
(B) curve B
(C) curve C
(D) curve D
(A) curve A
(B) curve B
(C) curve C
(D) curve D
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
Q 336. The balanced short circuit current of a three phase alternator is 25 amperes at
1500 rpm For the same field current, the balanced short current at 1400 rpm will
be
(A) 18.00A
(B) 27 . 00 A
(C) 20.00 A
(D) 28.28A
Q 337. A three phase alternator has a phase sequence of RYB for its three output
voltages, for clockwise rotation Now if the alternator is rotated anticlockwise, the
phase sequence will be
(A) RYB
(B) RBY
(C) BYR
Q 338. In a synchronous machine, if the field flux axis is ahead of the armature field
axis, in the direction of rotation, the machine working as
Q 339. In synchronous alternator, which of the following coils will have emf closer to
sine waveform ?
Q 340. An alternator has rated field current of 4 A. The alternator develops 180 V while
drawing a field current of 2 A at 750 rpm. If the field current is made 4 A at 750 rpm
generated voltage could be
(A) 400 V
(B) 380 V
(C) 60V
(D) 330 V.
Q 341. The armature reaction of an alternator will be completely magnetizing in case the
load power factor is
(A) unity
(B) 0.707
Q 342. Which of the following is not an integral part of synchronous generator system ?
(A) 10 to 20 V
(B) 30 to 100 V
Q 344. In case of low speed hydrogenerators, the short circuit ratio is usually
Q 345. The permissible duration for which a generator of rated frequency 50 Hz can run
at 46 Hz is
(A) zero
(A) ± 2 %
(B) ± 5 %
(C) ± 10 %
(D) ± 25 %.
A phase, 50 Hz, 6600 V, alternator is rated at 6600 kW at 0.8 power factor and a full
load efficiency of 90%.
(A) 65.63 A
(B) 656.3 A
(C) 6563 A
(D) 65630 A.
(A) 666.6 kW
(B) 6666 kW
(C) 66660 kW
Q 352. If the input. to an alternator remains unaltered, but excitation is changed then
which of the following will not change ?
(B) kW output
Unit - 5
Q 353. SCO full name
Q 356. System security can be said to comprise of three major functions that are used in
an energy control centre:
(B) Maintenance
(A) Secure,
(C) Restoration
(A) 4
(B) 5
(C) 6
(D) 2
(A) Alert
(D) Restorative
(B) Alert
(B) Alert
(B) Alert
(B) Alert
(B) Secure
(C) Restorative
(D) EMS
Q 375. As the load factor approaches unity, the shape of load duration curve will be
nearly
(A) L shaped
(C) Triangular
(D) Rectangular.
(B) Maintenance
(A) Secure,
(C) Restoration
∆fl
(A) α li=
∆ PGi
∆ PGi
(B) α li=
∆fl
(C) For under voltage conditions, strategic load shedding should be resorted
(B) For under voltage conditions, strategic load shedding should be resorted
Q 387. When a power plant is not able to meet the demand of consumers it will resort to
(A) Penalizing high load consumers by increasing the charges for electricity
Q 389. Which of the following power plants can generate power at unpredictable or
uncontrollable times?
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(C) batteries
(B) Alert
(B) Alert
(B) Secure
(C) For under voltage conditions, strategic load shedding should be resorted
∆fl
(A) α li=
∆ PGi
∆ PGi
(B) α li=
∆fl
Q 399. A generating station has a maximum demand of 50 Mw, a load factor of 60%, a
plant capacity factor of 45% and if the plant while running as per schedule were fully
loaded. The daily energy produced will be
(A) 400 MW
(B) 720 MW
(C) 500 MW
(D) 600 MW
Q 400. A three-phase, 33kV oil circuit breaker is rated 1200A, 2000MVA, 3s. The
symmetrical breaking current is
(A) 1200A
(B) 3600A
(C) 35kA
(D) 104.8Ka
(C) For under voltage conditions, strategic load shedding should be resorted
MEWAR UNIVERSITY POWER SYSTEM
OPERATION AND CONTROL
DEPARTMENT OF ELECTRICAL ENGINEERING B. TECH. 4 Th YEAR 8Th
SEMESTER
(B) For under voltage conditions, strategic load shedding should be resorted
Q 406. When a power plant is not able to meet the demand of consumers it will resort to
(A) Penalizing high load consumers by increasing the charges for electricity
Q 408. Which of the following power plants can generate power at unpredictable or
uncontrollable times?
(C) batteries
(B) Alert
(B) Alert
(B) Secure
(C) For under voltage conditions, strategic load shedding should be resorted