Operator Client

An operator client stopped working after a ghost copy was performed to backup and restore the system. The operator client gave a message to verify domain settings and user accounts. The document recommends using the system software user settings in the configuration wizard to reset the lock status and start the services on the client.

Uploaded by

Sivaprasad Kc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
133 views

Operator Client

An operator client stopped working after a ghost copy was performed to backup and restore the system. The operator client gave a message to verify domain settings and user accounts. The document recommends using the system software user settings in the configuration wizard to reset the lock status and start the services on the client.

Uploaded by

Sivaprasad Kc
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

6/11/2019 operator client stopped(/)(800xA Operations Display Operations System Administration & configuration Administration Backup, restore 800…

Search
 Question details

operator client stopped Related Topics


800xA >
after ghost copy to operator client 6 of 800xa v5.0.2 system on this operator stopped and gave this message: Operations >
Display (https://forum-
afw trayicon controlsystems.abb.com/Topic/800xA/Ope
verify domain settingsand user accounts
FO L LOW ( /ACCO U N T/ S U B S C R I B E ? C AT E G O
use system software user settings in the afw config wizard to reset the lock status

800xA >
Operations (https://forum-
Comments (0) (javacript:void(0)) New comment (javacript:void(0))
controlsystems.abb.com/Topic/800xA/Ope

eng_shahada (https://forum-controlsystems.abb.com/Profile/eng_shahada/) Rank: 3016 FO L LOW ( /ACCO U N T/ S U B S C R I B E ? C AT E G O


(https://forum-controlsystems.abb.com/Report/Submit/56000)
Asked 5 years ago

A N S W E R T H I S Q U E ST I O N ( H T T P S : / / FO R U M - CO N T R O L SYST E M S . A B B .CO M /Q U E ST I O N /A N S W E R ? Q U E ST I O N I D = 5 6 0 0 0 ) 800xA >


System >
FO L LOW ( H T T P S : / / FO R U M - CO N T R O L SYST E M S . A B B .CO M /Q U E ST I O N / FO L LOW/ 5 6 0 0 0 ) Administration & configuration >
Administration (https://forum-
controlsystems.abb.com/Topic/800xA/Syst
Answers configuration/Administration/Documents/
FO L LOW ( /ACCO U N T/ S U B S C R I B E ? C AT E G O

0 on the configuration wizard in the client --> on the system software user settings.
800xA >
System >
Backup, restore (https://forum-
check your system admin group name, system user group name are set properly and controlsystems.abb.com/Topic/800xA/Syst
(/Question/AnswerVote? restore/Documents/6046)

answerId=56040&value=1) FO L LOW ( /ACCO U N T/ S U B S C R I B E ? C AT E G O

type the service account user name , password and apply the settings to start the
800xA (https://forum-
controlsystems.abb.com/Topic/800xA/Doc
services on the client. FO L LOW ( /ACCO U N T/ S U B S C R I B E ? C AT E G O

AKS experts
Comments (1) (javacript:void(0)) New comment (javacript:void(0))

kmk691 (https://forum-controlsystems.abb.com/Profile/kmk691/) Rank: 17 (https://forum-controlsystems.abb.com/Report/Submit/56040)


Answered 5 years ago
Stefan Stromqvist (https://forum-
controlsystems.abb.com/Profile/Stefan
Stromqvist/)
Rank: 1
2 You say you made a "ghost copy". You can't just copy one node to another with ghost to make a new client.
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S

If you retored a disk ... Ghost Backups are designed to restore the SAME node after a disk failure. This means that things
(/Question/AnswerVote?
like the Windows System ID (SID) etc remain unchanged. A restored computer should rejoin to the same domain with
relatively little trouble. You may need to run the AfwConfigWizard to set the Service Account names and passwords ( ie
answerId=56081&value=1)
the system settings) after a node is restored. That is what your AfwTrayIcon is telling you to do.
Flavio Mussolin (https://forum-
controlsystems.abb.com/Profile/Flavio
Mussolin/)
Rank: 4

If you actually "Copied" one computer to another using a Ghost image file, then there is a lot more work to do. A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S

- The computer name and IP address must be changed.

- The computer must be removed from then joined to the domain again.

- The 800xA cache must be deleted. kstoilov (https://forum-


controlsystems.abb.com/Profile/kstoilov/)
- The 800xA system identity must be deleted from the registry.
Rank: 5
- The Node must be added back into the 800xA system as a new computer.
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S

( Sorry, I dont want to post on an open forum about how to mess with registry settings as this is potentially quite
dangerous. )
Ingo (https://forum-
controlsystems.abb.com/Profile/Ingo/)

Comments (1) (javacript:void(0)) New comment (javacript:void(0)) Rank: 39

A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S
Rob Lyon (https://forum-controlsystems.abb.com/Profile/Rob Lyon/) Rank: 2 (https://forum-controlsystems.abb.com/Report/Submit/56081)
https://forum-controlsystems.abb.com/56000/operator-client-stopped
Answered 5 years ago 1/2
6/11/2019 operator client stopped (800xA Operations Display Operations System Administration & configuration Administration Backup, restore 800…

raudales (https://forum-
controlsystems.abb.com/Profile/raudales/

1 The domain controller is not reachable (possibly due to improper cloning) and/or System Software User Settings are
Rank: 20
stale need to be re-applied.
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S

(/Question/AnswerVote?
As already mentioned by others, there are a few mandatory measures required after cloning of one running computer
into another running computer:
answerId=56424&value=1)
- Change hostname Geof Ledin (https://forum-
controlsystems.abb.com/Profile/Geof
- Change IP-address Ledin/)
Rank: 42
- A duplicated SID is not critical to System 800xA, AFAIK.
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S
- Rejoin domain

- Removal of IndustrialITData + Temp folders*

- Removal of 800xA System Registry key* Dash (https://forum-


controlsystems.abb.com/Profile/Dash/)
- Apply correct service account in System Software User Settings
Rank: 21
- Insertion as new client/server using proper methods (Add C/S or "Connect Node")
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S

*) The two latter ones is preferably done prior cloning. E.g. by "Disconnect" or "Remove" Client.

Titus (https://forum-
Cloning is not officially documented in any System 800xA User's Guide. controlsystems.abb.com/Profile/Titus/)

Rank: 6

/Stefan A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S

Comments (3) (javacript:void(0)) New comment (javacript:void(0))

Stefan Stromqvist (https://forum-controlsystems.abb.com/Profile/Stefan Stromqvist/) Rank: 1 (https://forum-controlsystems.abb.com/Report/Submit/564


Answered 5 years ago

Other questions needing answers


OPC write values from 3th party to 800M best practice (https://forum-controlsystems.abb.com/20210166/OPC-write-values-from-3th-party-to-
800M-best-practice)
Secure Network Protocol on AC800M Controller (https://forum-controlsystems.abb.com/20210150/Secure-Network-Protocol-on-AC800M-
Controller)
Fatal 103 (ICI) error during "load to controller" to MFP12 (https://forum-controlsystems.abb.com/20210147/Fatal-103-ICI-error-during-load-to-
controller-to-MFP12)
Modbus RTU communication Error (https://forum-controlsystems.abb.com/20210119/Modbus-RTU-communication-Error)
ABB M2M NETWORK ANALYZER TO PC (https://forum-controlsystems.abb.com/20210112/ABB-M2M-NETWORK-ANALYZER-TO-PC)
PU STATE FEEDBACK ERROR IN ACS 880 (https://forum-controlsystems.abb.com/20210096/PU-STATE-FEEDBACK-ERROR-IN-ACS-880)

https://forum-controlsystems.abb.com/56000/operator-client-stopped 2/2

You might also like