Protected System: Protecting Relief Device Equipment
Protected System: Protecting Relief Device Equipment
Protected System: Protecting Relief Device Equipment
Protected Equipment
Equipment ID # Type Serial # MAWP Protected Status
Compound Streams
There are no Compound Streams.
Contingency Scenarios
Area Controlling Scenario: Inlet Controlling Scenario: Outlet Controlling Scenario: Worksheet Version:
Blocked Outlet Blocked Outlet Blocked Outlet 1.1.6.51 [ Current ]
Contingency Type Req'd ASME Area Inlet Drop Back Press. AIV Status Apply Status
1 Blocked Outlet | Given Flow Rate - Vapor 1.6051 in² 2.413 % 14.286 % Passed Yes Checked
2 Fire | Fire Vapor Generation - Vapor 0.24682 in² 2.363 % 14.286 % Passed Yes Checked
Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria
Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
System Notes
2019-07-18 08:44:25 - Anamaria Ursu
Cloned from system "[Plant] Denver Test > [Unit] Ursu Anamaria > [System] Fresh Flexsorb Supply Drum", with updated
worksheet versions.
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
System Pressure Relief Valve Data Sheets - Fresh Flexsorb Supply Drum 4 - iPRSM / ... Page 1 of 3
Resolved ASME Area: 1.6051 in² Resolved API Area: 1.4446 in²
Model Selection
Manufacturer: Farris Set Pressure: 175 psig Inlet Outlet
Model Number: 26FB10 BP Superimposed Constant: 2 psig Size: 1.5 in 2 in
Valve Type: Balanced Bellows BP Superimposed Variable: 3 psig Rating: 150 # 150 #
Cap Construction: - BP Built-Up: 20 psig Facing: - Raised Face
ASME Orifice Area: 0.371 in² Cold Diff. Test Pressure: 175 psig
API Designation: F - 0.307" Maximum % OVP: 16 % Test Media: -
Max. Rel. Cap: 11557 lbm/hr Operating Temperature: 100 °F NPC (Air): 1209 SCFM
Noise Level (Atm): - NACE: No NPC (Steam): 3396 lbm/hr
Reactive Force: - Rupture Disk Coefficient: 1
Model Materials
Body: Carbon Steel (SA-216 Gr. WCB) Disk: 316 SS Bellows: Inconel Composite Option 1:
Bonnet: Carbon Steel (SA-216 Gr. WCB) Guide: 316 SS O-Ring: None Option 2:
Nozzle: 316 SS Spring: Chrome Alloy Spring #: Option 3:
Spring Range: - Other/SP:
Model Selection
Manufacturer: Farris Set Pressure: 183.7 psig Inlet Outlet
Model Number: 26JB10 BP Superimposed Constant: 2 psig Size: 2 in 3 in
Valve Type: Balanced Bellows BP Superimposed Variable: 3 psig Rating: 150 # 150 #
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
System Pressure Relief Valve Data Sheets - Fresh Flexsorb Supply Drum 4 - iPRSM / ... Page 2 of 3
Model Materials
Body: Carbon Steel (SA-216 Gr. WCB) Disk: 316 SS Bellows: Inconel Composite Option 1:
Bonnet: Carbon Steel (SA-216 Gr. WCB) Guide: 316 SS O-Ring: None Option 2:
Nozzle: 316 SS Spring: Chrome Alloy Spring #: Option 3:
Spring Range: - Other/SP:
PRV Notes
2019-07-18 08:49:33 - Anamaria Ursu
Cloned from equipment "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A".
Protected Equipment
Equipment Number Description P & ID Number MAWP Operating P Design T
Contingency Scenarios
# Name Cause of OVP Equation Type Relief Load Set P Relief T Req'd Area
1 Blocked Outlet Vapor 50000 lbm/hr 175 psig 110 °F 1.6051 in²
2 Fire Vapor 5455.9 lbm/hr 175 psig 653 °F 0.24682 in²
Acalc 1.6051 in² Calculated ASME orifice area before C 332 Gas-Vapor flow constant
consistency checks
K gas 0.8577 Calculated ASME certified gas
Wvapor 50000 lbm/hr Required vapor capacity coefficient of discharge
Trelief 110 °F Vapor relieving temperature at device inlet KCCF 1 Aggregate rupture disk coefficient
[ Basis = 569.67 °R ] gas
Kbp 1 Backpressure vapor-gas correction
Z 0.8 Compressibility factor factor
Prelief 217.4 psia Relieving pressure Mvapor 115.4 Mol Wt Avg mol weight of vapor
Acalc 0.24682 in² Calculated ASME orifice area before KCCF 1 Aggregate rupture disk
consistency checks coefficient
Wvapor 5455.9 lbm/hr Required vapor capacity gas 1 Backpressure vapor-gas
Kbp
correction factor
Trelief 653 °F Vapor relieving temperature at valve inlet
[ Basis = 1112.7 °R ] Mvapor 115.4 Mol Wt Avg mol weight of vapor
Z 0.828 Compressibility factor Q 829302 Btu/hr Total heat input
Prelief 226.15 psia Relieving pressure Lheat 152 Btu/lbm Latent heat
C 322 Gas-Vapor flow constant R 21000 Btu/hr-ft² Heat absorption rate from fire
K gas 0.8577 Calculated ASME certified gas coefficient of Fenv 1 Environmental Factor
discharge given 88.5 ft² Given wetted surface area
Awet
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
System Pressure Relief Valve Data Sheets - Fresh Flexsorb Supply Drum 4 - iPRSM / ... Page 3 of 3
Notes
2019-07-18 08:44:25 - Anamaria Ursu
Cloned from system "[Plant] Denver Test > [Unit] Ursu Anamaria > [System] Fresh Flexsorb Supply Drum", with updated
worksheet versions.
Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria
Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Protected System Contingency Analysis - "Fresh Flexsorb Supply Drum 4" - iPRSM / ... Page 1 of 1
Contingencies
Required ASME Inlet Back AIV
# Contingency Type Apply Status
Area or Flow Drop Pressure Status
1 Blocked Outlet | Given Flow Rate - Vapor 1.6051 in² 2.413 % 14.286 % Passed Yes Checked
2 Fire | Fire Vapor Generation - Vapor 0.24682 in² 2.363 % 14.286 % Passed Yes Checked
Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Protected System Piping Losses - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 1 of 1
Connected Equipment
Protected Equipment: OVP Sources: Ancillary Equipment:
D-509 ~
11557 lbm/hr
1. Blocked Outlet Given Flow 2.0688 psig 25 psig
Vapor Passed std 11557 lbm/hr
1.1.6.51 [ Ok ] Rate 1.1822 % 14.286 % 633.37
ft³/min
8201 lbm/hr
2. Fire Fire Vapor 2.0279 psig 25 psig
Vapor Passed std 8201 lbm/hr
1.1.6.51 [ Ok ] Generation 1.1588 % 14.286 % 449.44
ft³/min
44547 lbm/hr
1. Blocked Outlet Given Flow 4.4327 psig 25 psig
Vapor Passed std 44547 lbm/hr
1.1.6.51 [ Ok ] Rate 2.413 % 13.609 % 2441.3
ft³/min
31610 lbm/hr
2. Fire Fire Vapor 4.3407 psig 25 psig
Vapor Passed std 31610 lbm/hr
1.1.6.51 [ Ok ] Generation 2.363 % 13.609 % 1732.3
ft³/min
Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 1 of 4
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 2 of 4
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 3 of 4
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 4 of 4
Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria
Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
Notes
2019-07-18 08:44:25 - Anamaria Ursu
Cloned from system "[Plant] Denver Test > [Unit] Ursu Anamaria > [System] Fresh Flexsorb Supply Drum", with updated worksheet versions.
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Equipment Data Sheet - ID # SV-512A - iPRSM / AECOM Page 1 of 2
Protected Systems
System Name Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
Parameters
General
Mfgr. Farris Equipment manufacturer
Series Farris 2600 D-U Series for selecting device dependent curves
Orifice Area
API Orf. F - 0.307" API orifice designation
Valve Configuration
dnom_in 1.5 in Nominal inlet size
Dual outlet
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/d... 7/19/2019
Equipment Data Sheet - ID # SV-512A - iPRSM / AECOM Page 2 of 2
Dual Outlet No
Process Conditions
Pset 175 psig Set pressure
maxallow% 3% Max allowable inlet pressure drop as % of PSet
Pdrop-in
maxmech
Pback 230 psig Mechanical backpressure limit from manufacturer (for flanges, bellows, etc.)
Options
Cap Undefined Cap construction
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/d... 7/19/2019
Relief Device Piping & Fittings - "SV-512A" - iPRSM / AECOM Page 1 of 1
0.0018
1 Entrance 1 6.00" S.40 6.065 in 4.854 0 ft 0.014903 0.5 33.551
in
0.0018 9.7083
2 Pipe 1 6.00" S.40 6.065 in 0 ft 0.015 - -
in ft
0.0018 11.625 11.625
3 Pipe 1 6.00" S.40 6.065 in 0.015 - -
in ft ft
0.0018
4 Elbow - 90 1 6.00" S.40 6.065 in 0 ft 0.014903 0.29806 20
in
0.0018
5 Elbow - 90 1 6.00" S.40 6.065 in 0 ft 0.014903 0.29806 20
in
0.0018
6 Elbow - 90 1 6.00" S.40 6.065 in 0 ft 0.014903 0.29806 20
in
0.0018
7 Tee - Side Flow 1 6.00" S.40 6.065 in 1 0 ft 0.014903 0.89417 60
in
6.00" S.40 6.065 in 0.0018
8 Reducer 1 0 ft 0.014903 0.27486 18.443
2.00" S.80 1.939 in in
0.0018 4.4167
9 Pipe 1 2.00" S.80 1.939 in 0 ft 0.019 - -
in ft
0.0018 11.865
10 Pipe 1 2.00" S.80 1.939 in 0 ft 0.019 - -
in ft
0.0018
11 Elbow - 90 1 2.00" S.80 1.939 in 0 ft 0.019285 0.38569 20
in
0.0018
12 Elbow - 90 1 2.00" S.80 1.939 in 0 ft 0.019285 0.38569 20
in
0.0018
13 Gate Valve - Full Port 1 2.00" S.80 1.939 in 0 ft 0.019285 0.15428 8
in
2.00" S.80 1.939 in 0.0018
14 Reducer 1 0 ft 0.019285 0.12293 6.3747
1.50" S.80 1.5 in in
diin, diout Inflow / Outflow inside diameters ε Roughness f Friction factor Hdelta Fitting height
L/D Equivalent length of resistance K Resistance coefficient L Length Xnode Manifold factor
Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/pi... 7/19/2019
ISA Data Sheet - PRV - ID # SV-512A - iPRSM / AECOM Page 1 of 1
General
Tag #: SV-512A Protected Equipment: NACE Compliant: No
D-509 ~
P & ID #: Valve Type: Balanced Bellows
Service: Trim: Vapor
Line No.:
Valve Data
ASME
Manufacturer: Model Number: API Designation:
Serial Number: Orifice Area:
Farris 26FB10 F - 0.307"
0.371 in²
Valve Configuration
Inlet Outlet Body: Carbon Steel (SA-216 Gr. WCB) O-Ring: None Opt 1:
Size: 1.5 in 2 in Bonnet: Carbon Steel (SA-216 Gr. WCB) Spring: Chrome Alloy Opt 2:
Rating: 150 # 150 # Nozzle: 316 SS Bellows: Inconel Composite Opt 3:
Facing: - Raised Face Disk: 316 SS Cap: -
Sizing Basis
Code: ASME Sec. 8 Controlling Contingency: Blocked Outlet -- Given Flow Rate - Vapor
Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria
Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/d... 7/19/2019
Equipment Data Sheet - ID # SV-512B - iPRSM / AECOM Page 1 of 2
Protected Systems
System Name Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
Parameters
General
Mfgr. Farris Equipment manufacturer
Series Farris 2600 D-U Series for selecting device dependent curves
Orifice Area
API Orf. J - 1.287" API orifice designation
Valve Configuration
dnom_in 2 in Nominal inlet size
Dual outlet
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/d... 7/19/2019
Equipment Data Sheet - ID # SV-512B - iPRSM / AECOM Page 2 of 2
Dual Outlet No
Process Conditions
Pset 183.7 psig Set pressure
maxallow% 3% Max allowable inlet pressure drop as % of PSet
Pdrop-in
maxmech
Pback 230 psig Mechanical backpressure limit from manufacturer (for flanges, bellows, etc.)
Options
Cap Undefined Cap construction
Notes
2019-07-18 08:49:33 - Anamaria Ursu
Cloned from equipment "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A".
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/d... 7/19/2019
Relief Device Piping & Fittings - "SV-512B" - iPRSM / AECOM Page 1 of 2
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/pi... 7/19/2019
Relief Device Piping & Fittings - "SV-512B" - iPRSM / AECOM Page 2 of 2
2019-07-18 08:49:35 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.14 Reducer".
diin, diout Inflow / Outflow inside diameters ε Roughness f Friction factor Hdelta Fitting height
L/D Equivalent length of resistance K Resistance coefficient L Length Xnode Manifold factor
Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/pi... 7/19/2019
ISA Data Sheet - PRV - ID # SV-512B - iPRSM / AECOM Page 1 of 1
General
Tag #: SV-512B Protected Equipment: NACE Compliant: No
D-509 ~
P & ID #: Valve Type: Balanced Bellows
Service: Trim: Vapor
Line No.:
Valve Data
ASME
Manufacturer: Model Number: API Designation:
Serial Number: Orifice Area:
Farris 26JB10 J - 1.287"
1.43 in²
Valve Configuration
Inlet Outlet Body: Carbon Steel (SA-216 Gr. WCB) O-Ring: None Opt 1:
Size: 2 in 3 in Bonnet: Carbon Steel (SA-216 Gr. WCB) Spring: Chrome Alloy Opt 2:
Rating: 150 # 150 # Nozzle: 316 SS Bellows: Inconel Composite Opt 3:
Facing: - Raised Face Disk: 316 SS Cap: -
Sizing Basis
Code: ASME Sec. 8 Controlling Contingency: Blocked Outlet -- Given Flow Rate - Vapor
Notes
2019-07-18 08:49:33 - Anamaria Ursu
Cloned from equipment "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A".
Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria
Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/d... 7/19/2019
Equipment Data Sheet - ID # D-509 ~ - iPRSM / AECOM Page 1 of 4
Protected Systems
System Name Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By
Parameters
General
Mfgr. Equipment manufacturer
Design Criteria
Code ASME Sec. 8 Engineering code stamp
Tangent Select reference point for length/height (and for liquid levels and elevation for vertical vessels)
Ltan-tan 6 ft Vessel tangent-to-tangent length (or height), including length of any straight flange on head
D 4.5 ft Diameter
No Vessel is liquid-full?
Hgrade bottom 6 ft Height above grade of vessel bottom (bottom of lower head for vertical vessels)
Hgrade 6 ft Height above grade of vessel bottom (bottom of lower head for vertical vessels)
normal 30 in Normal liquid level from bottom of vessel (bottom of lower head for vertical vessels)
Hl bottom
[ Basis = 2.5 ft ]
Hl
normal 2.5 ft Normal liquid level from bottom of vessel (bottom of lower head for vertical vessels)
high 42 in High (alarm) liquid level from bottom of vessel (bottom of lower head for vertical vessels)
Hl bottom
[ Basis = 3.5 ft ]
high 3.5 ft High (alarm) liquid level from bottom of vessel (bottom of lower head for vertical vessels)
Hl
select High (Alarm) Liquid Level Liquid level for use in wetted surface area (fire exposure - liquid vaporization)
Hl
Process Parameters
PMAWP 175 psig Maximum working pressure
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570816/d... 7/19/2019
Equipment Data Sheet - ID # D-509 ~ - iPRSM / AECOM Page 2 of 4
Environment Factor
Fenv Calc No Insulation Environmental factor calculation method
Calculation Requirements
method API 521 Method of calculation for wetted area
Awet
No Select to override plant setting for increase of wetted area for piping (fire exposure - liquid
vaporization)
Awet
% incr 0% Percentage increase of wetted area for piping (fire exposure - liquid vaporization)
No Select to override plant setting for increase of exposed area for piping (fire exposure - gas
expansion)
% incr 0% Percentage increase of exposed area for piping (fire exposure - gas expansion)
Aexp
vessel 128.72 ft² Exposed area of vessel
Aexposed
piping
Aexposed 0 ft² Exposed area of piping
Volume Calculations
full 892.29 US gal Full vessel volume
Volvessel
high
Volvessel 751.66 US gal Volume of liquid at high (alarm) level
Unknown min Calculated fill time from high liquid level [ Basis = Unknown sec ]
Unknown min Calculated empty time from low liquid level [ Basis = Unknown sec ]
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570816/d... 7/19/2019
Equipment Data Sheet - ID # D-509 ~ - iPRSM / AECOM Page 3 of 4
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570816/d... 7/19/2019
Equipment Data Sheet - ID # D-509 ~ - iPRSM / AECOM Page 4 of 4
https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570816/d... 7/19/2019