Protected System Summary - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 1 of 1

Plant: Denver Test


Protected System Unit: Ursu Anamaria

Summary WS Version: 1.1.6.51


Reported: 2019-07-19

System Status: Protected System:


Checked Fresh Flexsorb Supply Drum 4

Protecting Relief Device Equipment


ASME Restricted-Lift
Equipment ID # Type Serial # Pset Orifice Area Orifice Area Adequate Spare Status

SV-512A Relief Valve 175 psig 0.371 in² - Yes No Checked


SV-512B Relief Valve 183.7 psig 1.43 in² - Yes No Checked

Protected Equipment
Equipment ID # Type Serial # MAWP Protected Status

D-509 ~ Vessel 175 psig Yes Checked

OVP Sources Ancillary Equipment


Equipment ID # Type Status Equipment ID # Type Status

There are no OVP Sources. There is no Ancillary Equipment.

Compound Streams
There are no Compound Streams.

Contingency Scenarios
Area Controlling Scenario: Inlet Controlling Scenario: Outlet Controlling Scenario: Worksheet Version:
Blocked Outlet Blocked Outlet Blocked Outlet 1.1.6.51 [ Current ]

Contingency Type Req'd ASME Area Inlet Drop Back Press. AIV Status Apply Status

1 Blocked Outlet | Given Flow Rate - Vapor 1.6051 in² 2.413 % 14.286 % Passed Yes Checked
2 Fire | Fire Vapor Generation - Vapor 0.24682 in² 2.363 % 14.286 % Passed Yes Checked

Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria
Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Active 1.0 New

System Notes
2019-07-18 08:44:25 - Anamaria Ursu
Cloned from system "[Plant] Denver Test > [Unit] Ursu Anamaria > [System] Fresh Flexsorb Supply Drum", with updated
worksheet versions.

Protected System Protected System: iPRSM / AECOM 1.1.6.72 2.0


Summary Report Fresh Flexsorb Supply Drum 4 2019-07-19 01:23:59

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
System Pressure Relief Valve Data Sheets - Fresh Flexsorb Supply Drum 4 - iPRSM / ... Page 1 of 3

Plant: Denver Test


Unit: Ursu Anamaria
System PRV Data Sheets WS Version: 1.1.6.51
Reported: 2019-07-19

System Status: Protected System:


Checked Fresh Flexsorb Supply Drum 4

Sizing Basis (Controlling Scenario)


Cause of OVP: Blocked Outlet
Atmospheric Pressure: 14.4 psia Relief Pressure.: 217.4 psia Equation Type: Vapor
Code: ASME Sec. 8 % OVP.: 16 % Fluid: Amine
MAWP (min): 175 psig Relief Temperature: 110 °F Required Capacity: 50000 lbm/hr
Operating Pressure: 40 psig API Kd (Gas): 0.953 Molecular Weight: 115.4
Set Pressure (min): 175 psig Specific Heats Ratio: 1.15
Operating to Set %: 22.857 % Specific Gravity: -
Gas Flow Constant: 332
Compressibility: 0.8
Back Pressures from Pipeloss Calculations
Equipment Name Spare Relief Flow BP Sup Const BP Sup Var BP Built-Up BP Total

SV-512A No 10300 lbm/hr 2 psig 3 psig 20 psig 25 psig


SV-512B No 39700 lbm/hr 2 psig 3 psig 20 psig 25 psig

Resolved ASME Area: 1.6051 in² Resolved API Area: 1.4446 in²

Pressure Relief Valve: SV-512A


P & ID #: Serial Number: Blocked Valve - Inlet: Yes
PFD #: Service: Blocked Valve - Outlet: No
Line #: Equip Ref #: Available During Run: -
Spare: No Discharge To: Flare Header Assoc. Rupture Disk #(s):
Service Interval:

Model Selection
Manufacturer: Farris Set Pressure: 175 psig Inlet Outlet
Model Number: 26FB10 BP Superimposed Constant: 2 psig Size: 1.5 in 2 in
Valve Type: Balanced Bellows BP Superimposed Variable: 3 psig Rating: 150 # 150 #
Cap Construction: - BP Built-Up: 20 psig Facing: - Raised Face
ASME Orifice Area: 0.371 in² Cold Diff. Test Pressure: 175 psig
API Designation: F - 0.307" Maximum % OVP: 16 % Test Media: -
Max. Rel. Cap: 11557 lbm/hr Operating Temperature: 100 °F NPC (Air): 1209 SCFM
Noise Level (Atm): - NACE: No NPC (Steam): 3396 lbm/hr
Reactive Force: - Rupture Disk Coefficient: 1

Model Materials
Body: Carbon Steel (SA-216 Gr. WCB) Disk: 316 SS Bellows: Inconel Composite Option 1:
Bonnet: Carbon Steel (SA-216 Gr. WCB) Guide: 316 SS O-Ring: None Option 2:
Nozzle: 316 SS Spring: Chrome Alloy Spring #: Option 3:
Spring Range: - Other/SP:

Pressure Relief Valve: SV-512B


P & ID #: Serial Number: Blocked Valve - Inlet: Yes
PFD #: Service: Blocked Valve - Outlet: No
Line #: Equip Ref #: Available During Run: -
Spare: No Discharge To: Flare Header Assoc. Rupture Disk #(s):
Service Interval:

Model Selection
Manufacturer: Farris Set Pressure: 183.7 psig Inlet Outlet
Model Number: 26JB10 BP Superimposed Constant: 2 psig Size: 2 in 3 in
Valve Type: Balanced Bellows BP Superimposed Variable: 3 psig Rating: 150 # 150 #

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
System Pressure Relief Valve Data Sheets - Fresh Flexsorb Supply Drum 4 - iPRSM / ... Page 2 of 3

Cap Construction: - BP Built-Up: 20 psig Facing: - Raised Face


ASME Orifice Area: 1.43 in² Cold Diff. Test Pressure: 183.7 psig
API Designation: J - 1.287" Maximum % OVP: 10.506 % Test Media: -
Max. Rel. Cap: 44547 lbm/hr Operating Temperature: 100 °F NPC (Air): 4875 SCFM
Noise Level (Atm): - NACE: No NPC (Steam): 13697 lbm/hr
Reactive Force: - Rupture Disk Coefficient: 1

Model Materials
Body: Carbon Steel (SA-216 Gr. WCB) Disk: 316 SS Bellows: Inconel Composite Option 1:
Bonnet: Carbon Steel (SA-216 Gr. WCB) Guide: 316 SS O-Ring: None Option 2:
Nozzle: 316 SS Spring: Chrome Alloy Spring #: Option 3:
Spring Range: - Other/SP:

PRV Notes
2019-07-18 08:49:33 - Anamaria Ursu
Cloned from equipment "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A".

Protected Equipment
Equipment Number Description P & ID Number MAWP Operating P Design T

D-509 ~ Vessel 175 psig 40 psig 150 °F

Contingency Scenarios
# Name Cause of OVP Equation Type Relief Load Set P Relief T Req'd Area

1 Blocked Outlet Vapor 50000 lbm/hr 175 psig 110 °F 1.6051 in²
2 Fire Vapor 5455.9 lbm/hr 175 psig 653 °F 0.24682 in²

Scenario: Blocked Outlet -- Vapor -- Amine

for bellows, or conventional and pilot with critical flow

Acalc 1.6051 in² Calculated ASME orifice area before C 332 Gas-Vapor flow constant
consistency checks
K gas 0.8577 Calculated ASME certified gas
Wvapor 50000 lbm/hr Required vapor capacity coefficient of discharge
Trelief 110 °F Vapor relieving temperature at device inlet KCCF 1 Aggregate rupture disk coefficient
[ Basis = 569.67 °R ] gas
Kbp 1 Backpressure vapor-gas correction
Z 0.8 Compressibility factor factor
Prelief 217.4 psia Relieving pressure Mvapor 115.4 Mol Wt Avg mol weight of vapor

Scenario: Fire -- Vapor -- Amine

for bellows, or conventional and pilot with critical flow

Acalc 0.24682 in² Calculated ASME orifice area before KCCF 1 Aggregate rupture disk
consistency checks coefficient
Wvapor 5455.9 lbm/hr Required vapor capacity gas 1 Backpressure vapor-gas
Kbp
correction factor
Trelief 653 °F Vapor relieving temperature at valve inlet
[ Basis = 1112.7 °R ] Mvapor 115.4 Mol Wt Avg mol weight of vapor
Z 0.828 Compressibility factor Q 829302 Btu/hr Total heat input
Prelief 226.15 psia Relieving pressure Lheat 152 Btu/lbm Latent heat
C 322 Gas-Vapor flow constant R 21000 Btu/hr-ft² Heat absorption rate from fire

K gas 0.8577 Calculated ASME certified gas coefficient of Fenv 1 Environmental Factor
discharge given 88.5 ft² Given wetted surface area
Awet

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
System Pressure Relief Valve Data Sheets - Fresh Flexsorb Supply Drum 4 - iPRSM / ... Page 3 of 3

Notes
2019-07-18 08:44:25 - Anamaria Ursu
Cloned from system "[Plant] Denver Test > [Unit] Ursu Anamaria > [System] Fresh Flexsorb Supply Drum", with updated
worksheet versions.

Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria

Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Active 1.0 New

System PRV System ID: iPRSM / AECOM 1.1.6.72 2.2


Data Sheets Fresh Flexsorb Supply Drum 4 2019-07-19 01:24:00

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Protected System Contingency Analysis - "Fresh Flexsorb Supply Drum 4" - iPRSM / ... Page 1 of 1

Unit: Ursu Anamaria


Protected System Plant: Denver Test
WS Version: 1.1.6.51
Contingency Analysis Reported: 2019-07-19

Protecting Equipment Spare System Status: Protected System:


SV-512A Checked Fresh Flexsorb Supply Drum 4
SV-512B

Contingencies
Required ASME Inlet Back AIV
# Contingency Type Apply Status
Area or Flow Drop Pressure Status

1 Blocked Outlet | Given Flow Rate - Vapor 1.6051 in² 2.413 % 14.286 % Passed Yes Checked
2 Fire | Fire Vapor Generation - Vapor 0.24682 in² 2.363 % 14.286 % Passed Yes Checked

Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria

Protected System Protected System: iPRSM / AECOM 1.1.6.72 1.8


Contingency Analysis Fresh Flexsorb Supply Drum 4 2019-07-19 01:24:01

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Protected System Piping Losses - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 1 of 1

Plant: Denver Test


Protected System Unit: Ursu Anamaria
WS Version: 1.1.6.51
Piping Losses Reported: 2019-07-19

System Status: Protected System:


Checked Fresh Flexsorb Supply Drum 4

Connected Equipment
Protected Equipment: OVP Sources: Ancillary Equipment:
D-509 ~

Protecting Equipment: SV-512A


Type: Status: Spare: Last DB Δ By: Last DB Δ: Last Signoff By:
Relief Valve Checked No Ursu, Anamaria 2019-07-18 Ursu, Anamaria

Flow Back AIV


Contingency Scenario / Worksheet Hazard Type Inlet Drop Max.Rel.Cap. C/S Piping Flow
Type Pressure Status

11557 lbm/hr
1. Blocked Outlet Given Flow 2.0688 psig 25 psig
Vapor Passed std 11557 lbm/hr
1.1.6.51 [ Ok ] Rate 1.1822 % 14.286 % 633.37
ft³/min
8201 lbm/hr
2. Fire Fire Vapor 2.0279 psig 25 psig
Vapor Passed std 8201 lbm/hr
1.1.6.51 [ Ok ] Generation 1.1588 % 14.286 % 449.44
ft³/min

Protecting Equipment: SV-512B


Type: Status: Spare: Last DB Δ By: Last DB Δ: Last Signoff By:
Relief Valve Checked No Ursu, Anamaria 2019-07-18 Ursu, Anamaria

Flow Back AIV


Contingency Scenario / Worksheet Hazard Type Inlet Drop Max.Rel.Cap. C/S Piping Flow
Type Pressure Status

44547 lbm/hr
1. Blocked Outlet Given Flow 4.4327 psig 25 psig
Vapor Passed std 44547 lbm/hr
1.1.6.51 [ Ok ] Rate 2.413 % 13.609 % 2441.3
ft³/min
31610 lbm/hr
2. Fire Fire Vapor 4.3407 psig 25 psig
Vapor Passed std 31610 lbm/hr
1.1.6.51 [ Ok ] Generation 2.363 % 13.609 % 1732.3
ft³/min

Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria

Protected System Protected System: iPRSM / AECOM 1.1.6.72 1.6


Piping Losses Fresh Flexsorb Supply Drum 4 2019-07-19 01:24:02

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 1 of 4

Plant: Denver Test


Protected System Unit: Ursu Anamaria
WS Version: 1.1.6.51
Piping Loss Details Reported: 2019-07-19

System Status: Protected System:


Checked Fresh Flexsorb Supply Drum 4

Protecting Equipment: SV-512A


Type: Status: Spare: Last DB Δ By: Last DB Δ: Last Signoff By:
Relief Valve Checked No Ursu, Anamaria 2019-07-18 Ursu, Anamaria

Blocked Outlet - Given Flow Rate - Vapor

Inlet Pressure Drop   (1.1822 %   2.0688 psig)


Flow Weighted f NonRecoverable %
# Fitting Rate Xnode Flow d K (Crane) e Length PDrop of PSet

11557 56099 6.065 0.0018 0.036268


I-1 Entrance 4.854 0.5 0.014903 - 0.063469 psig
lbm/hr lbm/hr in in %
11557 56099 6.065 0.0018 9.7083 0.021082
I-2 Pipe 4.854 0.29064 0.015131 0.036893 psig
lbm/hr lbm/hr in in ft %
11557 56099 6.065 0.0018 11.625 0.025244
I-3 Pipe 4.854 0.34802 0.015131 0.044177 psig
lbm/hr lbm/hr in in ft %
11557 56099 6.065 0.0018 0.02162
I-4 Elbow - 90 4.854 0.29806 0.014903 - 0.037835 psig
lbm/hr lbm/hr in in %
11557 56099 6.065 0.0018 0.02162
I-5 Elbow - 90 4.854 0.29806 0.014903 - 0.037835 psig
lbm/hr lbm/hr in in %
11557 56099 6.065 0.0018 0.02162
I-6 Elbow - 90 4.854 0.29806 0.014903 - 0.037835 psig
lbm/hr lbm/hr in in %
Tee - Side 11557 11557 6.065 0.0018 0.002753
I-7 1 0.89417 0.014903 - 0.004817 psig
Flow lbm/hr lbm/hr in in %
11557 11557 1.939 0.0018 0.080997
I-8 Reducer 1 0.27486 0.014903 - 0.14174 psig
lbm/hr lbm/hr in in %
11557 11557 1.939 0.0018 4.4167 0.15654
I-9 Pipe 1 0.5312 0.019434 0.27394 psig
lbm/hr lbm/hr in in ft %
11557 11557 1.939 0.0018 11.865 0.42052
I-10 Pipe 1 1.427 0.019434 0.73592 psig
lbm/hr lbm/hr in in ft %
11557 11557 1.939 0.0018 0.11366
I-11 Elbow - 90 1 0.38569 0.019285 - 0.1989 psig
lbm/hr lbm/hr in in %
11557 11557 1.939 0.0018 0.11366
I-12 Elbow - 90 1 0.38569 0.019285 - 0.1989 psig
lbm/hr lbm/hr in in %
Gate Valve 11557 11557 1.939 0.0018 0.045464
I-13 1 0.15428 0.019285 - 0.079562 psig
- Full Port lbm/hr lbm/hr in in %
11557 11557 0.0018 0.10115
I-14 Reducer 1 1.5 in 0.12293 0.019285 - 0.17702 psig
lbm/hr lbm/hr in %

Outlet Back Pressure   (14.286 %   25 psig)

No Piping Loss Pressure Drops found.

Fire - Fire Vapor Generation - Vapor


Inlet Pressure Drop   (1.1588 %   2.0279 psig)
Flow Weighted f NonRecoverable %
# Fitting Rate Xnode Flow d K (Crane) e Length PDrop of PSet

8201 39808 6.065 0.0018 0.035489


I-1 Entrance 4.854 0.5 0.014903 - 0.062106 psig
lbm/hr lbm/hr in in %
I-2 Pipe 4.854 0.29235 0.01522 0.036313 psig

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 2 of 4

8201 39808 6.065 0.0018 9.7083 0.020751


lbm/hr lbm/hr in in ft %
8201 39808 6.065 0.0018 11.625 0.024847
I-3 Pipe 4.854 0.35007 0.01522 0.043483 psig
lbm/hr lbm/hr in in ft %
8201 39808 6.065 0.0018 0.021156
I-4 Elbow - 90 4.854 0.29806 0.014903 - 0.037022 psig
lbm/hr lbm/hr in in %
8201 39808 6.065 0.0018 0.021156
I-5 Elbow - 90 4.854 0.29806 0.014903 - 0.037022 psig
lbm/hr lbm/hr in in %
8201 39808 6.065 0.0018 0.021156
I-6 Elbow - 90 4.854 0.29806 0.014903 - 0.037022 psig
lbm/hr lbm/hr in in %
Tee - Side 8201 8201 6.065 0.0018 0.002694
I-7 1 0.89417 0.014903 - 0.004714 psig
Flow lbm/hr lbm/hr in in %
8201 8201 1.939 0.0018 0.079257
I-8 Reducer 1 0.27486 0.014903 - 0.1387 psig
lbm/hr lbm/hr in in %
8201 8201 1.939 0.0018 4.4167 0.15365
I-9 Pipe 1 0.53283 0.019493 0.26888 psig
lbm/hr lbm/hr in in ft %
8201 8201 1.939 0.0018 11.865 0.41276
I-10 Pipe 1 1.4314 0.019493 0.72233 psig
lbm/hr lbm/hr in in ft %
8201 8201 1.939 0.0018 0.11122
I-11 Elbow - 90 1 0.38569 0.019285 - 0.19463 psig
lbm/hr lbm/hr in in %
8201 8201 1.939 0.0018 0.11122
I-12 Elbow - 90 1 0.38569 0.019285 - 0.19463 psig
lbm/hr lbm/hr in in %
Gate Valve 8201 8201 1.939 0.0018 0.044488
I-13 1 0.15428 0.019285 - 0.077853 psig
- Full Port lbm/hr lbm/hr in in %
8201 8201 0.0018 0.098981
I-14 Reducer 1 1.5 in 0.12293 0.019285 - 0.17322 psig
lbm/hr lbm/hr in %

Outlet Back Pressure   (14.286 %   25 psig)

No Piping Loss Pressure Drops found.

Protecting Equipment: SV-512B


Type: Status: Spare: Last DB Δ By: Last DB Δ: Last Signoff By:
Relief Valve Checked No Ursu, Anamaria 2019-07-18 Ursu, Anamaria

Blocked Outlet - Given Flow Rate - Vapor

Inlet Pressure Drop   (2.413 %   4.4327 psig)


Flow Weighted f NonRecoverable %
# Fitting Rate Xnode Flow d K (Crane) e Length PDrop of PSet

44547 56084 6.065 0.0018 0.034532


I-1 Entrance 1.259 0.5 - - 0.063436 psig
lbm/hr lbm/hr in in %
44547 56084 6.065 0.0018 9.7083 0.020073
I-2 Pipe 1.259 0.29064 0.015131 0.036874 psig
lbm/hr lbm/hr in in ft %
44547 56084 6.065 0.0018 11.625 0.024036
I-3 Pipe 1.259 0.34802 0.015131 0.044154 psig
lbm/hr lbm/hr in in ft %
44547 56084 6.065 0.0018 0.020585
I-4 Elbow - 90 1.259 0.29806 0.014903 - 0.037815 psig
lbm/hr lbm/hr in in %
44547 56084 6.065 0.0018 0.020585
I-5 Elbow - 90 1.259 0.29806 0.014903 - 0.037815 psig
lbm/hr lbm/hr in in %
44547 56084 6.065 0.0018 0.020585
I-6 Elbow - 90 1.259 0.29806 0.014903 - 0.037815 psig
lbm/hr lbm/hr in in %
Tee -
44547 56084 6.065 0.0018 0.020585
I-7 Through 1.259 0.29806 0.014903 - 0.037815 psig
lbm/hr lbm/hr in in %
Flow
44547 56084 6.065 0.0018 0.004135
I-8 Pipe 1.259 0.059875 0.015131 2 ft 0.007596 psig
lbm/hr lbm/hr in in %
I-9 1 0.89417 0.014903 - 0.071571 psig

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 3 of 4

Tee - Side 44547 44547 6.065 0.0018 0.038961


Flow lbm/hr lbm/hr in in %
44547 44547 3.068 0.0018 0.15159
I-10 Reducer 1 0.22781 - - 0.27847 psig
lbm/hr lbm/hr in in %
44547 44547 3.068 0.0018 4.4167 0.20005
I-11 Pipe 1 0.30063 0.017402 0.36749 psig
lbm/hr lbm/hr in in ft %
44547 44547 3.068 0.0018 11.865 0.53741
I-12 Pipe 1 0.80761 0.017402 0.98722 psig
lbm/hr lbm/hr in in ft %
44547 44547 3.068 0.0018 0.23044
I-13 Elbow - 90 1 0.3463 0.017315 - 0.42332 psig
lbm/hr lbm/hr in in %
44547 44547 3.068 0.0018 0.23044
I-14 Elbow - 90 1 0.3463 0.017315 - 0.42332 psig
lbm/hr lbm/hr in in %
Gate Valve 44547 44547 3.068 0.0018 0.092176
I-15 1 0.13852 0.017315 - 0.16933 psig
- Full Port lbm/hr lbm/hr in in %
44547 44547 1.939 0.0018 0.76684
I-16 Reducer 1 0.18386 - - 1.4087 psig
lbm/hr lbm/hr in in %

Outlet Back Pressure   (13.609 %   25 psig)

No Piping Loss Pressure Drops found.

Fire - Fire Vapor Generation - Vapor


Inlet Pressure Drop   (2.363 %   4.3407 psig)
Flow Weighted f NonRecoverable %
# Fitting Rate Xnode Flow d K (Crane) e Length PDrop of PSet

31610 39797 6.065 0.0018 0.033791


I-1 Entrance 1.259 0.5 - - 0.062074 psig
lbm/hr lbm/hr in in %
31610 39797 6.065 0.0018 9.7083 0.019758
I-2 Pipe 1.259 0.29235 0.01522 0.036295 psig
lbm/hr lbm/hr in in ft %
31610 39797 6.065 0.0018 11.625 0.023658
I-3 Pipe 1.259 0.35007 0.01522 0.043461 psig
lbm/hr lbm/hr in in ft %
31610 39797 6.065 0.0018 0.020143
I-4 Elbow - 90 1.259 0.29806 0.014903 - 0.037003 psig
lbm/hr lbm/hr in in %
31610 39797 6.065 0.0018 0.020143
I-5 Elbow - 90 1.259 0.29806 0.014903 - 0.037003 psig
lbm/hr lbm/hr in in %
31610 39797 6.065 0.0018 0.020143
I-6 Elbow - 90 1.259 0.29806 0.014903 - 0.037003 psig
lbm/hr lbm/hr in in %
Tee -
31610 39797 6.065 0.0018 0.020143
I-7 Through 1.259 0.29806 0.014903 - 0.037003 psig
lbm/hr lbm/hr in in %
Flow
31610 39797 6.065 0.0018 0.00407
I-8 Pipe 1.259 0.060228 0.01522 2 ft 0.007477 psig
lbm/hr lbm/hr in in %
Tee - Side 31610 31610 6.065 0.0018 0.038124
I-9 1 0.89417 0.014903 - 0.070034 psig
Flow lbm/hr lbm/hr in in %
31610 31610 3.068 0.0018 0.14834
I-10 Reducer 1 0.22781 - - 0.27249 psig
lbm/hr lbm/hr in in %
31610 31610 3.068 0.0018 4.4167 0.19615
I-11 Pipe 1 0.30124 0.017438 0.36033 psig
lbm/hr lbm/hr in in ft %
31610 31610 3.068 0.0018 11.865 0.52693
I-12 Pipe 1 0.80924 0.017438 0.96798 psig
lbm/hr lbm/hr in in ft %
31610 31610 3.068 0.0018 0.22549
I-13 Elbow - 90 1 0.3463 0.017315 - 0.41423 psig
lbm/hr lbm/hr in in %
31610 31610 3.068 0.0018 0.22549
I-14 Elbow - 90 1 0.3463 0.017315 - 0.41423 psig
lbm/hr lbm/hr in in %
Gate Valve 31610 31610 3.068 0.0018 0.090197
I-15 1 0.13852 0.017315 - 0.16569 psig
- Full Port lbm/hr lbm/hr in in %
31610 31610 1.939 0.0018 0.75038
I-16 Reducer 1 0.18386 - - 1.3784 psig
lbm/hr lbm/hr in in %

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Piping Loss Details - "Fresh Flexsorb Supply Drum 4" - iPRSM / AECOM Page 4 of 4

Outlet Back Pressure   (13.609 %   25 psig)

No Piping Loss Pressure Drops found.

Revision History
Rev. Stage: As At: Signoff By: Prepared By: Approved By: Accepted By:
New 2019-07-18 Ursu, Anamaria

Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Active 1.0 New

Notes
2019-07-18 08:44:25 - Anamaria Ursu
Cloned from system "[Plant] Denver Test > [Unit] Ursu Anamaria > [System] Fresh Flexsorb Supply Drum", with updated worksheet versions.

Protected System System ID: iPRSM / AECOM 1.1.6.72 1.6


Piping Loss Details Fresh Flexsorb Supply Drum 4 2019-07-19 01:24:03

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//system/005570809/... 7/19/2019
Equipment Data Sheet - ID # SV-512A - iPRSM / AECOM Page 1 of 2

Plant: Denver Test


Relief Valve Unit:
Equip ID #:
Ursu Anamaria
SV-512A
Data Sheet WS Version: 1.1.6.51
Reported: 2019-07-19

Identification Description Service History


Equipment ID #: SV-512A Equipment Type: Relief Valve Date Installed:
P & ID #: PFD #: Date Serviced:
Description: Serial #: Date Inspected:
Service: Manufacturer: Farris Date Last Test:
Equip. Ref. #: Model: 26FB10 Date Next Test:
Location: Test Interval:
Line #:: Adequate Yes Data Source:

Protected Systems
System Name Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Fresh Flexsorb Supply Drum 4 Active 1.0 New

Parameters
General
Mfgr. Farris Equipment manufacturer

Series Farris 2600 D-U Series for selecting device dependent curves

Model 26FB10 Equipment model number

Constr Balanced Bellows Valve construction

Trim Vapor Fluid trim

Code ASME Sec. 8 Engineering code stamp

Restricted Lift No Restricted lift

Test Media Undefined Test media


name 3396.7 lbm/hr Name plate capacity (steam)
Wplate steam
name
Wplate air 1209 SCFM Name plate capacity (air) [ Basis = 1209 std ft³/min ]

name 101.81 US gal/min Name plate capacity (water)


Wplate water

NACEcompliant No Valve is NACE compliant?

Orifice Area
API Orf. F - 0.307" API orifice designation

AASME 0.371 in² Actual ASME orifice area

Aorifice 0.371 in² Orifice area used in calculations


gas 0.953 Manufacturers API gas coefficient of discharge (ASME K/0.9)
Kd
steam 0.953 Manufacturers API steam coefficient of discharge (ASME K/0.9)
Kd
liquid 0.62 Manufacturers API liquid coefficient of discharge (ASME K/0.9)
Kd

K gas 0.8577 Calculated ASME certified gas coefficient of discharge

K steam 0.8577 Calculated ASME certified steam coefficient of discharge

K liquid 0.558 Calculated ASME certified liquid coefficient of discharge

KCCF 1 Rupture disk coefficient, within range [0.9-1.0]

Valve Configuration
dnom_in 1.5 in Nominal inlet size

Fin Undefined Inlet facing

dnom_out 2 in Nominal outlet size

Fout Raised Face Outlet facing

Rout 150 # Outlet rating

Dual outlet

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/d... 7/19/2019
Equipment Data Sheet - ID # SV-512A - iPRSM / AECOM Page 2 of 2

Dual Outlet No
Process Conditions
Pset 175 psig Set pressure
maxallow% 3% Max allowable inlet pressure drop as % of PSet
Pdrop-in
maxmech
Pback 230 psig Mechanical backpressure limit from manufacturer (for flanges, bellows, etc.)

const 2 psig Max expected constant portion of superimposed backpressure


Pback
var 3 psig Max expected variable portion of superimposed backpressure
Pback
built
Pback 20 psig Max expected built up backpressure

PCDTP 175 psig Cold differential test pressure

Toperating 100 °F Operating temperature [ Basis = 559.67 °R ]

Tdesign 150 °F Design temperature [ Basis = 609.67 °R ]

EquipOK Yes Device worksheet evaluated, equipment parameters computed and ok

Materials - Main Valve


Body Carbon Steel (SA-216 Gr. WCB) Body material

Bonnet Carbon Steel (SA-216 Gr. WCB) Bonnet material

Nozzle 316 SS Nozzle material

Disk 316 SS Disk material

Guide 316 SS Guide material

Bellows Inconel Composite Bellows material

Bellows Gasket Non-Asbestos Bellows gasket material

Spring Chrome Alloy Spring material

O-Ring/Seals None O-Ring/Seals material

Options
Cap Undefined Cap construction

Test Gag Undefined With test gag

Option 1 Other material or special option 1

Option 2 Other material or special option 2

Option 3 Other material or special option 3

Availability Undefined Available during run

Spring # Spring number

From: Unknown psig Spring range

To: Unknown psig


Cold Diff. Test Pressure

for balanced bellows

KCDTP 0% Cold test temperature compensation

PDiffTest 175 psig Differential test pressure

Relief Valve Equipment ID: iPRSM / AECOM 1.1.6.72 1.4


Data Sheet SV-512A 2019-07-19 01:24:04

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/d... 7/19/2019
Relief Device Piping & Fittings - "SV-512A" - iPRSM / AECOM Page 1 of 1

Plant: Denver Test


Unit: Ursu Anamaria
Relief Device Equip ID #: SV-512A
Device Type: Relief Valve
Piping & Fittings WS Version: 1.1.6.51
Reported: 2019-07-19

Inlet Piping & Fittings - From Entrance to Device


Fitting Type / Schedule
#
Equiv. Equip't
Count
In & Out d iin & diout Xnode ε Hdelta f K L/D L

0.0018
1 Entrance 1 6.00" S.40 6.065 in 4.854 0 ft 0.014903 0.5 33.551
in
0.0018 9.7083
2 Pipe 1 6.00" S.40 6.065 in 0 ft 0.015 - -
in ft
0.0018 11.625 11.625
3 Pipe 1 6.00" S.40 6.065 in 0.015 - -
in ft ft
0.0018
4 Elbow - 90 1 6.00" S.40 6.065 in 0 ft 0.014903 0.29806 20
in
0.0018
5 Elbow - 90 1 6.00" S.40 6.065 in 0 ft 0.014903 0.29806 20
in
0.0018
6 Elbow - 90 1 6.00" S.40 6.065 in 0 ft 0.014903 0.29806 20
in
0.0018
7 Tee - Side Flow 1 6.00" S.40 6.065 in 1 0 ft 0.014903 0.89417 60
in
6.00" S.40 6.065 in 0.0018
8 Reducer 1 0 ft 0.014903 0.27486 18.443
2.00" S.80 1.939 in in
0.0018 4.4167
9 Pipe 1 2.00" S.80 1.939 in 0 ft 0.019 - -
in ft
0.0018 11.865
10 Pipe 1 2.00" S.80 1.939 in 0 ft 0.019 - -
in ft
0.0018
11 Elbow - 90 1 2.00" S.80 1.939 in 0 ft 0.019285 0.38569 20
in
0.0018
12 Elbow - 90 1 2.00" S.80 1.939 in 0 ft 0.019285 0.38569 20
in
0.0018
13 Gate Valve - Full Port 1 2.00" S.80 1.939 in 0 ft 0.019285 0.15428 8
in
2.00" S.80 1.939 in 0.0018
14 Reducer 1 0 ft 0.019285 0.12293 6.3747
1.50" S.80 1.5 in in

Outlet Piping & Fittings - From Device to Exit


Fitting Type / Schedule
#
Equiv. Equip't
Count
In & Out diin & diout Xnode ε Hdelta f K L/D L

There is no Outlet Piping connected to this equipment.

diin, diout Inflow / Outflow inside diameters ε Roughness f Friction factor Hdelta Fitting height
L/D Equivalent length of resistance K Resistance coefficient L Length Xnode Manifold factor

Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria

Relief Device PRD ID: iPRSM / AECOM 1.1.6.72 1.3


Piping & Fittings SV-512A 2019-07-19 01:24:05

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/pi... 7/19/2019
ISA Data Sheet - PRV - ID # SV-512A - iPRSM / AECOM Page 1 of 1

Plant: Denver Test


ISA Data Sheet Unit:
Equip ID #:
Ursu Anamaria
SV-512A
Pressure Relief Valve WS Version: 1.1.6.51
Reported: 2019-07-19

General
Tag #: SV-512A Protected Equipment: NACE Compliant: No
D-509 ~
P & ID #: Valve Type: Balanced Bellows
Service: Trim: Vapor
Line No.:

Valve Data
ASME
Manufacturer: Model Number: API Designation:
Serial Number: Orifice Area:
Farris 26FB10 F - 0.307"
0.371 in²

Valve Configuration
Inlet Outlet Body: Carbon Steel (SA-216 Gr. WCB) O-Ring: None Opt 1:
Size: 1.5 in 2 in Bonnet: Carbon Steel (SA-216 Gr. WCB) Spring: Chrome Alloy Opt 2:
Rating: 150 # 150 # Nozzle: 316 SS Bellows: Inconel Composite Opt 3:
Facing: - Raised Face Disk: 316 SS Cap: -

Sizing Basis
Code: ASME Sec. 8 Controlling Contingency: Blocked Outlet -- Given Flow Rate - Vapor

Fluid: Amine Barometric Pressure.: 14.4 psia Operating Temperature: 100 °F


Equation Type: Vapor Operating Pressure: 40 psig Relief Temperature: 110 °F
Required Capacity: 10300 lbm/hr Set Pressure: 175 psig Latent Heat: -
Required ASME Area: 1.6051 in² Cold Diff. Test Pressure: 175 psig Specific Heats Ratio: 1.15
Maximum Relief Capacity: 11557 lbm/hr BP Superimposed Constant: 2 psig Compressibility: 0.8
Molecular Weight: 115.4 BP Superimposed Variable: 3 psig Specific Gravity @ Relief Temp.: -
API Kd (Gas): 0.953 BP Built-Up: 20 psig Viscosity @ Relief Temp.: -
BP Total: 25 psig
OVP %: 16 %

Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria

Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Active 1.0 New

ISA Data Sheet Equipment ID: iPRSM / AECOM 1.1.6.72 2.1


Pressure Relief Valve SV-512A 2019-07-19 01:24:05

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570813/d... 7/19/2019
Equipment Data Sheet - ID # SV-512B - iPRSM / AECOM Page 1 of 2

Plant: Denver Test


Relief Valve Unit:
Equip ID #:
Ursu Anamaria
SV-512B
Data Sheet WS Version: 1.1.6.51
Reported: 2019-07-19

Identification Description Service History


Equipment ID #: SV-512B Equipment Type: Relief Valve Date Installed:
P & ID #: PFD #: Date Serviced:
Description: Serial #: Date Inspected:
Service: Manufacturer: Farris Date Last Test:
Equip. Ref. #: Model: 26JB10 Date Next Test:
Location: Test Interval:
Line #:: Adequate Yes Data Source:

Protected Systems
System Name Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Fresh Flexsorb Supply Drum 4 Active 1.0 New

Parameters
General
Mfgr. Farris Equipment manufacturer

Series Farris 2600 D-U Series for selecting device dependent curves

Model 26JB10 Equipment model number

Constr Balanced Bellows Valve construction

Trim Vapor Fluid trim

Code ASME Sec. 8 Engineering code stamp

Restricted Lift No Restricted lift

Test Media Undefined Test media


name 13697 lbm/hr Name plate capacity (steam)
Wplate steam
name
Wplate air 4875.4 SCFM Name plate capacity (air) [ Basis = 4875.4 std ft³/min ]

name 403.47 US gal/min Name plate capacity (water)


Wplate water

NACEcompliant No Valve is NACE compliant?

Orifice Area
API Orf. J - 1.287" API orifice designation

AASME 1.43 in² Actual ASME orifice area

Aorifice 1.43 in² Orifice area used in calculations


gas 0.953 Manufacturers API gas coefficient of discharge (ASME K/0.9)
Kd
steam 0.953 Manufacturers API steam coefficient of discharge (ASME K/0.9)
Kd
liquid 0.62 Manufacturers API liquid coefficient of discharge (ASME K/0.9)
Kd

K gas 0.8577 Calculated ASME certified gas coefficient of discharge

K steam 0.8577 Calculated ASME certified steam coefficient of discharge

K liquid 0.558 Calculated ASME certified liquid coefficient of discharge

KCCF 1 Rupture disk coefficient, within range [0.9-1.0]

Valve Configuration
dnom_in 2 in Nominal inlet size

Fin Undefined Inlet facing

dnom_out 3 in Nominal outlet size

Fout Raised Face Outlet facing

Rout 150 # Outlet rating

Dual outlet

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/d... 7/19/2019
Equipment Data Sheet - ID # SV-512B - iPRSM / AECOM Page 2 of 2

Dual Outlet No
Process Conditions
Pset 183.7 psig Set pressure
maxallow% 3% Max allowable inlet pressure drop as % of PSet
Pdrop-in
maxmech
Pback 230 psig Mechanical backpressure limit from manufacturer (for flanges, bellows, etc.)

const 2 psig Max expected constant portion of superimposed backpressure


Pback
var 3 psig Max expected variable portion of superimposed backpressure
Pback
built
Pback 20 psig Max expected built up backpressure

PCDTP 183.7 psig Cold differential test pressure

Toperating 100 °F Operating temperature [ Basis = 559.67 °R ]

Tdesign 150 °F Design temperature [ Basis = 609.67 °R ]

EquipOK Yes Device worksheet evaluated, equipment parameters computed and ok

Materials - Main Valve


Body Carbon Steel (SA-216 Gr. WCB) Body material

Bonnet Carbon Steel (SA-216 Gr. WCB) Bonnet material

Nozzle 316 SS Nozzle material

Disk 316 SS Disk material

Guide 316 SS Guide material

Bellows Inconel Composite Bellows material

Bellows Gasket Non-Asbestos Bellows gasket material

Spring Chrome Alloy Spring material

O-Ring/Seals None O-Ring/Seals material

Options
Cap Undefined Cap construction

Test Gag Undefined With test gag

Option 1 Other material or special option 1

Option 2 Other material or special option 2

Option 3 Other material or special option 3

Availability Undefined Available during run

Spring # Spring number

From: Unknown psig Spring range

To: Unknown psig


Cold Diff. Test Pressure

for balanced bellows

KCDTP 0% Cold test temperature compensation

PDiffTest 183.7 psig Differential test pressure

Notes
2019-07-18 08:49:33 - Anamaria Ursu
Cloned from equipment "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A".

Relief Valve Equipment ID: iPRSM / AECOM 1.1.6.72 1.4


Data Sheet SV-512B 2019-07-19 01:24:06

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/d... 7/19/2019
Relief Device Piping & Fittings - "SV-512B" - iPRSM / AECOM Page 1 of 2

Plant: Denver Test


Unit: Ursu Anamaria
Relief Device Equip ID #: SV-512B
Device Type: Relief Valve
Piping & Fittings WS Version: 1.1.6.51
Reported: 2019-07-19

Inlet Piping & Fittings - From Entrance to Device


Fitting Type / Schedule
#
Equiv. Equip't
Count
In & Out diin & diout Xnode ε Hdelta f K L/D L

1 Entrance 1 6.00" S.40 6.065 in 1.259 - 0 ft - 0.5 -


2019-07-18 08:49:33 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.1 Entrance".
9.7083
2 Pipe 1 6.00" S.40 6.065 in - 0 ft 0.015 - -
ft
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.2 Pipe".
11.625
3 Pipe 1 6.00" S.40 6.065 in - 11.625 ft 0.015 - -
ft
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.3 Pipe".
4 Elbow - 90 1 6.00" S.40 6.065 in - 0 ft - - 20
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.4 Elbow - 90".
5 Elbow - 90 1 6.00" S.40 6.065 in - 0 ft - - 20
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.5 Elbow - 90".
6 Elbow - 90 1 6.00" S.40 6.065 in - 0 ft - - 20
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.6 Elbow - 90".
7 Tee - Through Flow 1 6.00" S.40 6.065 in 1.259 - 0 ft - - 20
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.7 Tee - Side Flow".
8 Pipe 1 6.00" S.40 6.065 in - 0 ft 0.015 - - 2 ft
9 Tee - Side Flow 1 6.00" S.40 6.065 in 1 - 0 ft - - 60
6.00" S.40 6.065 in
10 Reducer 1 - 0 ft - 0.22781 -
3.00" S.40 3.068 in
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.8 Reducer".
4.4167
11 Pipe 1 3.00" S.40 3.068 in - 0 ft 0.018 - -
ft
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.9 Pipe".
11.865
12 Pipe 1 3.00" S.40 3.068 in - 0 ft 0.018 - -
ft
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.10 Pipe".
13 Elbow - 90 1 3.00" S.40 3.068 in - 0 ft - - 20
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.11 Elbow - 90".
14 Elbow - 90 1 3.00" S.40 3.068 in - 0 ft - - 20
2019-07-18 08:49:34 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.12 Elbow - 90".
15 Gate Valve - Full Port 1 3.00" S.40 3.068 in - 0 ft - - 8
2019-07-18 08:49:35 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.13 Gate Valve - Full Port".
3.00" S.40 3.068 in
16 Reducer 1 - 0 ft - 0.18386 -
2.00" S.80 1.939 in

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/pi... 7/19/2019
Relief Device Piping & Fittings - "SV-512B" - iPRSM / AECOM Page 2 of 2

2019-07-18 08:49:35 - Anamaria Ursu Cloned from "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A" fitting
"I.14 Reducer".

Outlet Piping & Fittings - From Device to Exit


Fitting Type / Schedule
#
Equiv. Equip't
Count
In & Out diin & diout Xnode ε Hdelta f K L/D L

There is no Outlet Piping connected to this equipment.

diin, diout Inflow / Outflow inside diameters ε Roughness f Friction factor Hdelta Fitting height
L/D Equivalent length of resistance K Resistance coefficient L Length Xnode Manifold factor

Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria

Relief Device PRD ID: iPRSM / AECOM 1.1.6.72 1.3


Piping & Fittings SV-512B 2019-07-19 01:24:08

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/pi... 7/19/2019
ISA Data Sheet - PRV - ID # SV-512B - iPRSM / AECOM Page 1 of 1

Plant: Denver Test


ISA Data Sheet Unit:
Equip ID #:
Ursu Anamaria
SV-512B
Pressure Relief Valve WS Version: 1.1.6.51
Reported: 2019-07-19

General
Tag #: SV-512B Protected Equipment: NACE Compliant: No
D-509 ~
P & ID #: Valve Type: Balanced Bellows
Service: Trim: Vapor
Line No.:

Valve Data
ASME
Manufacturer: Model Number: API Designation:
Serial Number: Orifice Area:
Farris 26JB10 J - 1.287"
1.43 in²

Valve Configuration
Inlet Outlet Body: Carbon Steel (SA-216 Gr. WCB) O-Ring: None Opt 1:
Size: 2 in 3 in Bonnet: Carbon Steel (SA-216 Gr. WCB) Spring: Chrome Alloy Opt 2:
Rating: 150 # 150 # Nozzle: 316 SS Bellows: Inconel Composite Opt 3:
Facing: - Raised Face Disk: 316 SS Cap: -

Sizing Basis
Code: ASME Sec. 8 Controlling Contingency: Blocked Outlet -- Given Flow Rate - Vapor

Fluid: Amine Barometric Pressure.: 14.4 psia Operating Temperature: 100 °F


Equation Type: Vapor Operating Pressure: 40 psig Relief Temperature: 110 °F
Required Capacity: 39700 lbm/hr Set Pressure: 183.7 psig Latent Heat: -
Required ASME Area: 1.6051 in² Cold Diff. Test Pressure: 183.7 psig Specific Heats Ratio: 1.15
Maximum Relief Capacity: 44547 lbm/hr BP Superimposed Constant: 2 psig Compressibility: 0.8
Molecular Weight: 115.4 BP Superimposed Variable: 3 psig Specific Gravity @ Relief Temp.: -
API Kd (Gas): 0.953 BP Built-Up: 20 psig Viscosity @ Relief Temp.: -
BP Total: 25 psig
OVP %: 10.506 %

Notes
2019-07-18 08:49:33 - Anamaria Ursu
Cloned from equipment "[Plant] Denver Test > [Unit] Ursu Anamaria > [Equip't] SV-512A".

Revision History
Status: As At: Last DB Δ By: Last Signoff By:
Checked 2019-07-18 Ursu, Anamaria Ursu, Anamaria
Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Active 1.0 New

ISA Data Sheet Equipment ID: iPRSM / AECOM 1.1.6.72 2.1


Pressure Relief Valve SV-512B 2019-07-19 01:24:07

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570858/d... 7/19/2019
Equipment Data Sheet - ID # D-509 ~ - iPRSM / AECOM Page 1 of 4

Plant: Denver Test


Vessel Unit:
Equip ID #:
Ursu Anamaria
D-509 ~
Data Sheet WS Version: 1.1.6.51
Reported: 2019-07-19

Identification Description Service History


Equipment ID #: D-509 ~ Equipment Type: Vessel Date Installed:
P & ID #: PFD #: Date Serviced:
Description: Serial #: Date Inspected:
Service: Manufacturer: Date Last Test:
Equip. Ref. #: Model: Date Next Test:
Location: Test Interval:
Line #:: Protected Yes Data Source:

Protected Systems
System Name Rev. Status Rev. # Rev. Stage Rev. Date Prepared By Approved By Accepted By

Fresh Flexsorb Supply Drum 4 Active 1.0 New

Parameters
General
Mfgr. Equipment manufacturer

Model Equipment model number

Design Criteria
Code ASME Sec. 8 Engineering code stamp

Horizontal Cylinder Vessel shape and orientation

Vacuum Full Rated for vacuum

Tangent Select reference point for length/height (and for liquid levels and elevation for vertical vessels)

Ltan-tan 6 ft Vessel tangent-to-tangent length (or height), including length of any straight flange on head

D 4.5 ft Diameter

Elliptical Head type

No Vessel is liquid-full?

Hgrade bottom 6 ft Height above grade of vessel bottom (bottom of lower head for vertical vessels)

Hgrade 6 ft Height above grade of vessel bottom (bottom of lower head for vertical vessels)
normal 30 in Normal liquid level from bottom of vessel (bottom of lower head for vertical vessels)
Hl bottom
[ Basis = 2.5 ft ]

Hl
normal 2.5 ft Normal liquid level from bottom of vessel (bottom of lower head for vertical vessels)

high 42 in High (alarm) liquid level from bottom of vessel (bottom of lower head for vertical vessels)
Hl bottom
[ Basis = 3.5 ft ]
high 3.5 ft High (alarm) liquid level from bottom of vessel (bottom of lower head for vertical vessels)
Hl
select High (Alarm) Liquid Level Liquid level for use in wetted surface area (fire exposure - liquid vaporization)
Hl

Hl 3.5 ft Selected liquid level


low 12 in Low (Alarm) liquid level from bottom of vessel (bottom of lower head for vertical vessels)
Hl bottom
[ Basis = 1 ft ]
low 1 ft Low (alarm) liquid level from bottom of vessel
Hl

Tdesign 150 °F Design temperature [ Basis = 609.67 °R ]


rate Unknown US gal/min Fill rate
Vfill
rate Unknown US gal/min Empty rate
Vempty

Process Parameters
PMAWP 175 psig Maximum working pressure

Pop 40 psig Normal operating pressure


max 110 °F Maximum operating temperature [ Basis = 569.67 °R ]
Top

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570816/d... 7/19/2019
Equipment Data Sheet - ID # D-509 ~ - iPRSM / AECOM Page 2 of 4

Top 110 °F Normal operating temperature [ Basis = 569.67 °R ]

Environment Factor
Fenv Calc No Insulation Environmental factor calculation method

Fenv 1 Environmental factor

Rselect API 521 Adequate Select absorption rate

R 21000 Btu/hr-ft² Heat absorption rate from fire

Calculation Requirements
method API 521 Method of calculation for wetted area
Awet

Awet 93.489 ft² Wetted area

No Select to override plant setting for increase of wetted area for piping (fire exposure - liquid
vaporization)

Awet
% incr 0% Percentage increase of wetted area for piping (fire exposure - liquid vaporization)

piping 0 ft² Wetted area of piping


Awet
vessel 93.489 ft² Wetted area of vessel
Awet

Hfire 25 ft Plant level fire height

No Select to override plant setting for increase of exposed area for piping (fire exposure - gas
expansion)
% incr 0% Percentage increase of exposed area for piping (fire exposure - gas expansion)
Aexp
vessel 128.72 ft² Exposed area of vessel
Aexposed
piping
Aexposed 0 ft² Exposed area of piping

Aexposed 128.72 ft² Exposed area

Volume Calculations
full 892.29 US gal Full vessel volume
Volvessel
high
Volvessel 751.66 US gal Volume of liquid at high (alarm) level

low 140.64 US gal Volume of liquid at low (alarm) level


Volvessel
norm 511.35 US gal Volume of liquid at normal liquid level
Volvessel
unfilled
Volvessel high 140.64 US gal Unfilled volume of vessel at high (alarm) level

unfilled 380.95 US gal Unfilled volume of vessel at normal liquid level


Volvessel
norm

Unknown min Calculated fill time from high liquid level [ Basis = Unknown sec ]

Unknown min Calculated empty time from low liquid level [ Basis = Unknown sec ]

Wetted Area Formula

: liquid level from bottom of vessel used in analysis


: head depth
: radius
: vessel tangent-to-tangent length/height

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570816/d... 7/19/2019
Equipment Data Sheet - ID # D-509 ~ - iPRSM / AECOM Page 3 of 4

: effective liquid level (level used to compute wetted area)


: liquid level angle in radians
a function used to determine the wetted area for a filled or partially filled 2:1 elliptical horizontal head.

Exposed Area Formula

: liquid level from bottom of vessel used in analysis


: head depth
: radius
: vessel tangent-to-tangent length/height
: effective liquid level (level used to compute wetted area)
: liquid level angle in radians
a function used to determine the wetted area for a filled or partially filled 2:1 elliptical horizontal head.

Full Volume Formula

High Level Volume Formula

Low Level Volume Formula

https://i05.iprsm.com/iprsm/aecom.x/$Download/repo/file/serve.p//equip/005570816/d... 7/19/2019