Protection & Switchgear PDF
Protection & Switchgear PDF
1
INTRODUCTION
Presented by
C.GOKUL,AP/EEE
Velalar College of Engg & Tech , Erode
7
UNIT 1 Syllabus
• Importance of protective schemes for electrical
apparatus and power system
• Qualitative review of faults and fault currents
• Relay terminology – definitions
• Essential qualities of protection
• Protection against over voltages due to lightning and
switching - arcing grounds
• Ground wires
• surge absorber and diverters
• Power System Earthing – neutral Earthing Methods
{Peterson Coil}
• Basic ideas of insulation coordination.
8
Importance of protective
schemes for electrical
apparatus and power system
9
PROTECTION SYMBOL
two-winding
current transformer
transformer
two-winding
voltage transformer
transformer
generator capacitor
VS
Relay
VP
Relay Purpose
Isolate controlling circuit from controlled circuit.
Control high voltage system with low voltage.
Control high current system with low current.
Logic Functions
Advantages for Using
Protective Relays
• Detect system failures when they occur
and isolate the faulted section from the
remaining of the system.
• Mitigating the effects of failures after
they occur.
• Minimize risk of fire, danger to personal
and other high voltage systems.
CIRCUIT BREAKER
• Low voltage circuit breaker
• Magnetic circuit breaker
• Medium voltage circuit breaker
• High voltage circuit breaker
Battery bank
• Battery bank are called as
backbone of protection system
• Emergency use for power
system
Fuse
• Fuses are selected to allow passage of normal
current and of excessive current only for short
periods.
• It is used to protect the low voltage or current
rating devices
Lighting arrester
• A lightning arrester is a device used on
electrical power system to protect the
insulation damaging effect of lightning.
• All lighting arrester are earthed
What is Switchgear ?
• Switchgear is the combination of switches,
fuses or circuit breakers(CB) used to
control , protect & isolate electrical
equipment.
• It is used de-energize equipment & clear
faults.
Different elements of switchgear
• Circuit breaker • Load Breaking Switch LBS
Air ckt breaker ACB • By pass and changeover
Vacuumed ckt breaker VCB
switches
Oil filled ckt breaker OCB
SF6 Ckt Breaker • Isolators(switches)
• Fuses
• MCCB (Moulded Case Ckt
Breakers)
• MCB
(Miniature Circuit Breaker)
• RCCB
Residual current circuit breaker
Function wise categories
• Automatic & Manual operation
{ example: Circuit breaker ,MCB , MCCB }
•Insulation failure.
•Conducting path failure.
•Over voltages due to lightening or switching surges.
•Puncturing or breaking of insulators.
•Failure of conducting path due to broken conductors.
•Failure of solid insulation due to aging, heat, moisture,
overvoltage , accidental contact with earth or earth screens,
flash over voltages and etc.,
FAULT IN POWER SYSTEM
A power system fault may be defined as any
condition or abnormality of the system which
involves the electrical failure of primary
equipment such as generators, transformers,
busbars, overhead lines and cables and all other
items of plant which operate at power system
voltage.
Unsymmetrical fault
Faults in which not all the line currents are equal
and not all have the same phase.
Example (any one): single phase line to ground
fault (L-G), two phase to ground (LL-G) fault and
phase to phase (L-L) fault.
Abnormalities in Power
Systems
SLG 85
LL 8
DLG 5
3L 2 or less
Frequency of Fault Occurrence
Equipment % of Total
Overhead lines 50
Cables 10
Switchgear 15
Transformers 12
CTs and PTs 2
Control Equipment 3
Miscellaneous 8
SYMMETRICAL FAULT
(50%) •Icing
•Birds
•Tree branches
•Kite Strings
•Internal Overvoltage
Under ground Cable •Damage due to digging
(9%) • Insulation failure due to temperature rise
•Failure of Joints
(10%) •Overloading
48
Relays are electrical
switches that open or close
another circuit under certain
conditions.
Protective relays are devices which
monitor power system conditions and
operate to quickly and accurately isolate
faults or dangerous conditions. A well
designed protective system can limit
damage to equipment, as well as minimize
the extent of associated service
interruption.
Isolate controlling circuit from controlled circuit.
Control high voltage system with low voltage.
Control high current system with low current.
Logic Functions
Electromagnetic Relays (EMRs)
Microprocessor-based Relay
◦ Much higher precision and more reliable and durable.
◦ Capable of both digital and analog I/O.
◦ Higher cost
Detect system failures when they occur and
isolate the faulted section from the remaining of
the system.
Transducers
Power Circuit
(PT & CT) Relay
System Breaker
Sensitivity
Relaying equipment must be sufficiently sensitive
so that it will operate when required
Must discriminate normal from abnormal
conditions.
Selectivity
Performance of protective devices to select between
those conditions for which prompt operation and
those for which no operation, or time delay
operation is required.
Isolate faulted circuit resulting in minimum
interruptions.
Implemented through “Zone of Protection”
Speed
Remove a fault from the power system as quickly
as possible
Classification:
System Grounding
•The process of connecting some electrical part of the
power system to earth (i.e. soil) is called system
grounding.
Neutral
Earthing
Neutral Grounding
Connecting neutral point to earth (i.e. soil) either
directly or some circuit element
(e.g. resistance, reactance , Peterson coil etc.)
is called neutral grounding.
Disadvantages:
By adjusting the value of R, the arcing grounds can be minimized.
It improves the stability
Less interference
Minimize hazards
(iii) Reactance grounding
•In this system, a reactance is inserted between the neutral and ground
•The purpose of reactance is to limit the earth fault current.
Disadvantages :
(i) In this system, the fault current required to operate the protective device
is higher than that of resistance grounding for the same fault conditions.
(ii) High transient voltages appear under fault conditions.
Presented by C.GOKUL,AP/EEE Velalar College of Engg & Tech , Erode
If inductance L of appropriate value is connected in
parallel with the capacitance of the system, the fault
current IF flowing through L will be in phase
opposition to the capacitive current IC of the system.
If L is so adjusted that
I L = IC
then resultant current in the fault will be zero. This
condition is known as Resonant Grounding.
When the value of L of arc suppression coil is
such that the fault current IF exactly balances the
capacitive current IC , it is called resonant grounding.
•An arc suppression coil (also called Peterson coil) is an iron-cored coil
connected between the neutral and earth.
•The reactor is provided with tappings to change the inductance of the
coil.
•By adjusting the tappings on the coil, the coil can be tuned with the
capacitance of the system i.e. resonant grounding can be achieved.
• Suppose line to ground fault occurs in the line B at point
F. The fault current IF and capacitive currents IR and IY will
flow as shown in Fig
• Note that IF flows through the Peterson coil (or Arc
suppression coil) to neutral and back through the fault. The
total capacitive current IC is the phasor sum of IR & IY
as shown in phasor diagram in Fig.
• The voltage of the faulty phase is applied across the arc
suppression coil. Therefore, fault current IF lags the faulty
phase voltage by 90°.
• The current IF is in phase opposition to capacitive
current IC [See Fig].
By adjusting the tappings on the Peterson coil, the
resultant current in the fault can be reduced. If inductance
of the coil is so adjusted that IL= IC , then resultant current
in the fault will be zero.
v. Voltage Transformer Earthing
In this method of neutral earthing , the primary of a
single-phase voltage transformer is connected
between the neutral and the earth as shown in Fig
A low resistor in series with a relay is connected
across the secondary of the voltage transformer. The
voltage transformer provides a high reactance in the
neutral earthing circuit and operates virtually as an
ungrounded neutral system.
Advantages:
•Arcing grounds are reduced.
•Transient overvoltage are reduced
Protection against
over voltages due to
lightning and
switching
Protection Against Over Voltage Due
to Lightning & Switching
During Operation , PS equipments such as Generator,
transformer, Tx.lines may subject to Over Voltage.
OV occurs due to Lightning, opening of CB & so on.
Causes Of OV
Internal Cause
External Cause
• Lightning
External • Tree falls on
Tx.lines causes SC
• Insulation Failure
Internal •
•
Resonance
Arching Ground
• Switching Surges
Types of Over Voltages
*Power Frequency OV
* Switching OV
* Lightning OV
Power Frequency OV
Does not have damaging effects like switching or
lightning surges
Mainly due to
Ground faults
Loose connection
Switching OV
Also known as Switching surge or over voltage transient
Sudden rise of voltage for a very short duration in PS
network is known as transient voltage or voltage surge
An electrical transient appears, if there is sudden change
in the state of energy in PS network. This sudden change
is due to
i. Closing a Switch
ii. Opening a Switch
iii. Occurrence of fault in system
Note:
Surge Diverter : Diverts the Surge to earth
Surge Absorber : Absorbs the Surge energy
Types of Surge Absorber
Characteristics of
lightning arrestor should
be correlated with
equipment isolation
The insulation of the line
lightning arrestor &
equipment should be
coordinated.
Curve A relates to Protective
device
Curve B – equipment to be
protected
Protective device must have
insulation characteristics
which must be lie below the
insulation characteristics of
instrument to be protected.
A perfect insulation coordination must
satisfy the following conditions:
The insulation should withstand both operating
voltage & voltage surges
2
RELAY
Presented by
C.GOKUL,AP/EEE
Velalar College of Engg & Tech , Erode
1
2
UNIT 2 Syllabus
• Electromagnetic relays
(attracted armature , solenoid, balanced beam)
• over current relay
• directional relay
• non-directional relay
• distance relay
(Impedance , Reactance, admittance(mho))
• negative sequence relay
• differential relay
(current , voltage, biased beam)
• under frequency relay
• Introduction to static relays 3
Relay Overview
4
What are Relays?
8
Electromagnetic Attraction Relays
(i) Attracted armature type relay
(ii) Solenoid type relay
(iii) Balanced beam type relay
Induction Relays / Electromagnetic
induction
(i) Induction type overcurrent Relay (Non Directional
Relay)
(ii) Induction Cup Relay (Directional Relay)
9
1. Attracted Armature Type Relays
13
(iii) Balanced beam type relay
• It consists of an iron armature fastened to a
balance beam. Under normal operating
conditions , the current through the relay coil is
such that the beam is held in the horizontal
position by the spring.
• When a fault occurs, the current through the
relay coil becomes greater than the pickup value
and the beam is attracted to close the trip circuit.
This causes the opening of the circuit breaker to
isolate the faulty circuit.
15
Balanced beam type relay 16
Induction cup
structure
17
• An induction motor, except that the rotor iron is
stationary, rotor conductor portion being free to rotate.
• Moving element is a hollow cylindrical rotor which
turns on its axis. The rotating field is produced by two
pairs of coils wound on four poles as shown.
• The rotating field induces currents in the cup to provide
the necessary driving torque.
18
• If φ1 and φ2 represent the fluxes produced by
the respective pairs of poles, then torque
produced is proportional to Φ1 Φ2 sin α .
• Where α is the phase difference between two
fluxes.
• Induction cup structures are more efficient
torque producers than either the shaded-pole or
watt hour meter structures.
ADVANTAGES:
• type of relay has very high speed
• operating time less then 0.1 second.
19
Induction type
overcurrent Relay
(Non Directional Relay)
20
• This type of relay works on the induction
principle and initiates corrective measures
when current in the circuit exceeds the
predetermined value.
• These relays are used on a.c. circuits only and
can operate for fault current flow in either
direction.
• The actuating source is a current in the circuit
supplied to the relay from a current transformer.
21
22
Constructional details
• It consists of a metallic (aluminum) disc which is free to
rotate in between the poles of two electromagnets.
• The upper electromagnet has a primary and a secondary
winding. The primary is connected to the secondary of a
C.T. in the line to be protected and is tapped at intervals.
• The secondary winding is energized by induction from
primary and is connected in series with the winding on
the lower magnet. The controlling torque is provided by
a spiral spring.
• The spindle of the disc carries a moving contact which
bridges two fixed contacts (connected to trip circuit).
• This angle can be adjusted to value between 0° to 360°
23
Operation
• The driving torque on the aluminium disc is set up
due to the induction principle. This torque is opposed by
the restraining torque provided by the spring.
• Under normal operating conditions, restraining
torque is greater than the driving torque produced by
the relay coil current. Therefore, the aluminium disc
remains stationary.
• If the current in the protected circuit exceeds the
pre-set value, the driving torque becomes greater than
the restraining torque. Consequently, the disc rotates
and the moving contact bridges the fixed contacts when
the disc has rotated through a pre-set angle. The trip
circuit operates the circuit breaker which isolates the
faulty section. 24
DIRECTIONAL
RELAY
25
Induction relays are two types
Operation:
from the diagram we can conclude that we have two flux
quantities: φ1 & φ2 .
always φ1 lags V by 90 0
φ2 inphase with current I
Due to phase difference between two flux quantities
i.e., α = 90-θ
Φ1 α V & φ2 α I
Hence T = φ1 φ2 sin α
= φ1 φ2 sin(90-θ)
= VI COS θ
= POWER
Hence the relay activated only when there is a
specific direction of power flow
when power flows in normal direction both driving
torque and restraining torque twists in same direction
and relay does not operates.
when the power flow is in reverse direction,
driving torque and restraining torque acts in opposite
direction and relay operates.
•Therefore CB operates and disconnects faulty section.
DIRECTIONAL OVER CURRENT RELAY:
T = V I COS θ
i.e., the directional power relay is not suitable for short circuit
conditions.
Construction:
1) Directional element :
Operation :
If a ground fault occurs on the alternator winding as shown in fig 16 b. the two
secondary currents will not be equal and the current flows through the operating coil
of the relay, causing the relay to operate. The amount of current flow through the
relay will depend upon the way the fault is being fed.
Disadvantages
The impedance of the pilot cables generally
causes a slight difference between the currents at the
two ends of the section to be protected, then the small
differential current flowing through the relay may
cause it to operate even under no fault conditions.
It’s called percentage differential relay because the ratio of differential operating
current to average restraining current is a fixed percentage.
It’s called bias relay because restraining known as biased coil produces the bias
force. Fig 17 a, shows the schematic arrangements of biased beam relay. It is
essentially an over current balanced beam type relay with an additional restraining
coil. The restraining coil produces a bias force in the opposite direction to the
operating force.
Under normal and through load conditions, the bias
force due to restraining coil is greater than operating
force. Therefore, the relay remains inoperative.
When an internal fault occurs, the operating
force exceeds the bias force. Consequently the
trip contacts are closed to open the circuit
breaker.
70
Principle of operation
• The essential components of static relays are shown in
figure below. The output of CT and PT are not suitable
for static components so they are brought down to
suitable level by auxiliary CT and PT. Then auxiliary CT
output is given to rectifier.
• Rectifier rectifies the relaying quantity i.e., the output
from a CT or PT or a Transducer.
71
• The rectified output is supplied to a measuring
unit comprising of comparators, level detectors,
filters, logic circuits.
• The output is actuated when the dynamic input
(i.e., the relaying quantity) attains the threshold
value. This output of the measuring unit is
amplified by amplifier and fed to the output unit
device, which is usually an electromagnetic one.
• The output unit energizes the trip coil only when
relay operates.
72
Advantages of Solid State Relay
• Low Weight
• Arc less switching
• Static Relay burden is less than electromagnetic type
of relays. Hence error is less.
• Fast response.
• Long life
• Less power consumption
• More Accurate compared to electromechanical Relay
73
University 2 mark Questions:
• Mention the principle of directional relay
• State the function of protective relays
• List out the types of fuses
• State the function of under frequency relay
• Define under frequency relay
• Mention the advantages of static relay
• List out the types of distance relay.
• Define negative sequence relay.
74
University 2 mark Questions:
• State the merits of static relay
• List out the applications of static relays.
• Compare Static and Electromagnetic relay.
• A relay is connected to 400/5 ratio current
transformer with current setting of 150%.
Calculate the Plug Setting Multiplier when
circuit carries a fault current of 4000 A.
75
University 16 mark Questions:
• Electromagnetic relay (15)
• Distance relay (15)
• Under frequency relay (8)
• Static relay-Introduction (8)
• Negative sequence relay (8)
• Directional relay (16)
• MHO relay (8)
76
UNIT
3
Apparatus Protection
Presented by
C.GOKUL,AP/EEE
Velalar College of Engg & Tech , Erode
1
UNIT 3 Syllabus
2
Introduction
The two major items of equipment in a
power system are the generators and transformers.
They have very high chance of fault occurrence
and usually takes much time and money to repair
the damage.
Fault and Abnormal
Conditions
Generator : Over Current, Over Voltage, Under Voltage, Under
Frequency, Unbalanced Current, Loss of Excitation, Reverse Power,
Winding Inter turn Fault, Winding Earth Fault etc.
3 6
52
5 87B
1 50/51
52
87B
50/51
2 4 CT REQUIREMENTS FOR
OVERLAPPING ZONES
G
Zones of Protection
3
5 1 - Bus Protection
2 - Generator Protection
3 - Subtrans Line Protection
1
4 - Feeder Protection
5 - Transformer Protection
2
G 4
Feeder Protection
Fault
G
Bus Protection
Fault
G
Transformer Protection
Fault
G
Sub transmission Line Protection
Fault
G
Generator Protection
Fault
G
Faults occurring in Transformers
Open-Circuit faults
Earth faults
Phase-to-Phase faults
Inter-Turn faults
Overheating
Factors in choosing Protective Gear
for a Transformer
Type of Transformer
Size of the Transformer
Type of Cooling
System where used
Importance of service for which it is required
Transformer Relaying Scheme
1. Buchholz Protection
Also known as gas accumulator relay, commonly used on
all oil-immersed transformer provided with conservator.
Working Principle:
Whenever a fault occur inside the transformer, the
oil of the tank gets overheated and gases are generated.
The heat generated by the high local current causes the
transformer oil to decompose and produce gas which can
be used to detect the winding faults
Buchholz Protection
2. Core-Balance Leakage Protection
This system is used to provide protection
against earth faults on high voltage winding.
When earth fault occurs, the sum of the three
currents is no longer zero and a current is induced in
the secondary of the CT causing the trip relay to
operate and isolate the transformer from the bus-bars.
core-balance protection cannot provide
protection against overload
3. Combined Leakage and Overload
Protection
The core-balance protection cannot provide protection
against overload. It is usual practice to provide
combined leakage and overload protection for
transformer.
The earth relay has low current setting and
operates under earth faults only.
The overload relays have high current setting it
arranged to operate against faults between the phases
In this system, two overload relay and one earth relay
are connected. The two overload relays are sufficient to
protect against phase to phase faults.
The trip contacts of overload relays and earth fault
relay are connected in parallel. Therefore the
energizing of either one of them, the circuit breaker
will tripped.
Transformer Protection
Overheating
Normal maximum working temp. = 95 °C
8-10 °C rise will reduce the life of the transformer.
Overcurrent
Fuses for distribution transformer
Overcurrent relaying for 5MVA and above
Characteristics:
– Must be below the damage curve
– Must be above magnetizing inrush
Conclusion
Open-circuit faults, earth faults, phase-to-phase faults,
inter-turn faults and overheating are the fault that are
likely occur in a transformer
Relays control output circuits of a much higher power.
Safety is increased
Protective relays are essential for keep equipment from
being damaged.
Introduction
• Generator ? Sources ?
Generator is the most precious/valuable
equipment in PP which actually converts the
mechanical energy of turbine into electricity.
Various relays are used to detect
abnormalities and whenever fault conditions
appear, they can give warning alarms to trip the
unit automatically.
• Rotor
– Two stage relay:
a) Alarm b) Trip
– Over voltage in the rotor.
ABNORMAL OPERATING CONDITIONS:
Which affects the generator
• Negative Phase sequence
• Loss of Excitation
• Over fluxing protection
• Reverse power
• Over-speeding
• Pole slipping/ Out of Step
EARTH FAULT:
• When fault current flows through earth return
path, the fault is called Earth Fault.
• Possible causes are
(a) Insulation failure,
(b) due to over heating (Failure of water/air
circulation through stator conductor).
• Earth fault may occur between any phase
conductor and core.
• It is usually practice to limit the earth fault
current to avoid damage to the stator.
STAND BY EARTH FAULT:
• This protection is practically protects 95% of
generator winding. Therefore a current setting
of 5% of in to be set.
• E/F current is generally limited to about
15/20Amps.
• Earth fault current of even 100A for few seconds
can cause external damage. So the earth fault is
restricted to 100Amps. By providing NGR of
63.5 ohms at 11KV Voltage Level.
• This is a Back-Up protection.
100% STATOR EARTH FAULT:
• In this protection, where neutral voltage measurement is
made at generator terminals, (By Broken Delta), the third
harmonic voltage element is used.
• First earth fault very near to neutral produces negligible
current as driving voltage is nearly zero. But if a 2nd
earth fault occurs at machine terminal, line to ground
fault is not limited by NGR. The resulting fault current
can be high. Hence, the 1st E/F very near to neutral has
to be detected early and isolated.
• All generators produce continuous current of 3rd
harmonic voltage. Under normal condition, 3rd
harmonic voltage is present. If there is a fault near
neutral, the amount of 3rd harmonic voltage comes
down and this is used for detection.
STATOR EARTH FAULT PROTECTION
Generator
Red
Yellow
Blue
CT Relay
Neutral Earth
Resistance
ROTOR EARTH FAULT:
• Since rotor circuits operate ungrounded, a single earth
fault is caused by insulation failure due to moisture,
ageing of insulation or vibration of rotor etc. But
existence of single ground fault increases the chance of a
second ground fault. The occurrence of second earth
fault can cause fault current flows. This results
unsymmetrical flux distribution. The air gap flux is
badly distorted. The rotor is displaced enough to rub
stator leading to severe vibrations and can damage the
bearing.
• Although a machine can continuously run on a single
earth fault but second rotor earth fault, if allowed to
occur, should be detected immediately and generator
should be tripped.
DIFFERENTIAL PROTECTION
• Differential protection is very reliable method for stator
winding phase to phase fault. In this, currents on both
sides of the generator are compared.
• Under normal condition or for a fault outside of the
protected zone, current i1s is equal to current i2s.
Therefore, the currents in the CTs secondary's are also
equal, i1s=i2s and no current flows through the current
relays.
• If a fault develops inside of the protected zone, current
i1s and i2s are no longer equal, therefore i1s and i2s are
not equal and therefore a current flowing in the current
relay.
Negative Phase Sequence Protection:
• When the generator is connected to a balanced load, the phase
currents are equal in magnitude and displaced electrically by 120°.
The ATs wave produced by the stator currents rotate synchronously
with the rotor and no eddy currents are induced in the rotor parts.
• If there is an unbalanced loading of the generator, and then the
stator currents have a –ve sequence component. The stator field due
to these –ve sequence currents rotates at synchronous speed but in a
direction opposite to the direction of the field structure on the rotor.
Thus, the –ve sequence stator armature mmf rotates at a speed –Ns,
while the rotor field speed is +Ns. There is a relative velocity of 2Ns
between the two.
• These causes double frequency currents, of large amplitude to be
induced in the rotor conductors and iron part. So both the eddy
currents as well as the hystersis losses increase due to these double
frequencies induced currents in the rotor.
• Unbalanced loading affects ;(a) Rotor heating (b) Severe vibration &
heating of stator.
FIELD FAILURE PROTECTION:
• Acts as an Induction Generator.
• Possible Causes;
– AVR Fault
– Tripping of Field C.B.
– Open circuit or Short circuit occurring in the D.C. circuit.
– PMG failure
• In normal condition, generator when running shares the reactive
demand of the system. If excitation fails, synchronous generator runs at
a super-synchronous speed, draws reactive power from the power
system instead of supplying the Qe. In case, the other generators can’t
meet the requirement of reactive power, this shall result in large voltage
drop which may ultimately result in instability.
• In this case, slip becomes –Ve result in slip frequency currents. Rotor
gets heated up due to induced currents in the rotor winding, core or
damage the winding if this condition is sustained. Stator heats up due to
high stator currents due to increase in reactive current from the system.
• By monitor (i) Field current, If
(ii) Phase current & voltage.
REVERSE POWER PROTECTION:
• This protection is provided to protect against motoring.
• A generator is expected to supply active power to the connected system in
normal operation. If the generator primover fails, a generator that is connected
in parallel with another source of electrical supply will to begin to motor. This
reversal of power flow due to loss of prime mover can be detected by reverse
power element.
• Possible Causes:
• When immediately after Synchronising control valves are not operated which
may happen due to some fault in the system or some delay by the operating
personnel.
• In case of sudden closure of stop valves or control valves when the generator
unit is still connected to the grid.
• Reverse power operation is harmful to the turbine since without steam flow in
the turbine. If the turbine continues to rotate, it will result in heating of turbine
blades due to churning action. However, the period for the turbine to overheat
may vary from a few seconds to minutes depending upon the turbine &
operating conditions.
OVER FLUXING PROTECTION:
• Fundamental Voltage- Flux relation:
V = 4.44 * N * f * ø
V/f = 4.44 * N * ø
= K * ø = K * B/A
• V/f is a measure of flux in machine. That means, over fluxing can occur if
the ratio of voltage to frequency exceeds certain limits. High voltage or low
frequency, causing a rise in the V/f ratio, will produce high flux densities in
the magnetic core of the generator. This could cause the core of the machine
to saturate & stray flux to be induced in the unlamilated components that
have not designed to carry flux. The resulting eddy currents in the solid
components e.g. core bolts & clamps and end of core laminations can cause
rapid overheating and damage.
POSSIBLE CAUSES:
• AVR failure
• Load rejection under manual AVR control
• Excessive excitation with Generator Offline.
• Decreasing Speed with operator tries to maintain rated stator voltage.
• AUTO to Manual transfer of AVR.
Various Industry Motor Applications
Fan, Blower
Pump, Compressor
Conveyor
Mixer
Cranes
Types of Fault in Motors
External Fault Internal Fault
Mechanical Load Bearing Failure
Unbalance Supply Winding phase and
Voltage earth fault
Single Phasing
Phase Reversal
Motor Protection Summary
THERMAL OVERLOAD
SHORT CIRCUIT
EARTH FAULT
UNBALANCE
BLOCKED ROTOR/STALLING PROTECTION
Thermal Stress Causes Motor Failure
Most of the motor failure contributors and failed motor components are related to motor overheating.
Thermal stress potentially can cause the failure of all the major motor parts: Stator, Rotor, Bearings,
Shaft and Frame.
Thermal Overload
•Consider a motor is as homogenous body
•Developing heat at constant rate.
•Dissipating heat at constant rate.
Heat disspation is proportional to temperature
rise
T = KIR (1-e
2 –t/τ)
Overload Protection - Thermal Model
• Main Factors and Elements Comprising
the Thermal Model are:
• Overload Pickup Level
• Overload Curve
• Cooling Time Constants
• Hot/Cold Stall Time Ratio
THERMAL OVERLOAD cont……
Motor running
Time in sec
Starting
time :10s
Sh or t- cir cuit
elem ent
Current
293 A 1370 A 1720 A (Amperes)
SHORT CIRCUIT PROTECTION
What is:-It happens when motor circuits are energized, but motor rotor is not
rotating. It is also called locked rotor.
Effects:
This will result in excessive currents flow given the same load. This will cause
thermal damage to the motor winding and insulation.
Motor Protection Stalling
Required for
IDMT RELAYS :
These relays have inverse characteristic and the operating time decreases as the
magnitude of current increases.
t = TMS X K/((I/In)^n – 1)
t = RELAY OPERATING TIME
I = FAULT CURRENT
n = CONSTANT
K = CONSTANT
In = RELAY PLUG SETTING ( PICK UP )
TMS = TIME MULTIPLIER SETTING
Pilot Relays
Why needed:-Overcome diffculties of overcurrent
Relay ie
•Coordination
•Excessive fault clearance times
Principle:-
•Measurement of current at each end feeders
•Transmission of information
•No time and current gradation required
•Supervision facility.
•Merz price Circulating scheme
Bus Bar Protection
87B
86B
86B
86B
BUS 2
BUS 1
Busbar Protection
TRIPS AND
LOCKS-OUT ALL 87B 87B
BREAKERS
CONNECTED TO
BUS 1 86B
TRIPS AND
LOCKS-OUT ALL
BREAKERS
CONNECTED TO
BUS 2
BUS 2
BUS 1
Busbar Protection
BUS 2
86B1
87B1
87B2
• Distance Protection
• Over Current Protection
• Differential Protection.
• Main and Back up Protection
Distance Relay Protection
4
Theory of circuit
interruption
Presented by
C.GOKUL,AP/EEE
Velalar College of Engg & Tech , Erode
1
UNIT 4 Syllabus
2
The ARC
The electric arc constitute a basic ,indispensable and active
element in the process of current interruption.
By increase of
temperature resulting
into thermo ionic
emission
Maintenance of Arc
High temperature of the medium around the contacts
caused by high current densities, with high temp the
kinetic energy gained by moving electrons increased.
The field strength or volt. gradient which increases
the kinetic energy of the moving electrons and
increases the chances of detaching electrons from
neutral molecule.
An increase in mean free path-the distance through
which the electron moves freely.
Methods of Arc Extinction
High resistance method
a. cooling of arc
b. increasing the arc length
c. reducing the cross section of arc
d. splitting of arc
Low resistance or current zero interruption
a. Lengthening of the gap
b.increasing the pressure in the vicinity of the arc
c. Cooling
d. Blast Effect
Phenomenon of arc extinction
Energy Balance or Cassie Theory
This theory states that if the rate of heat
dissipation between the contacts is greater
then the rate at which heat is generated ,the
arc will be extinguished ,otherwise it will
restrike.
Recovery rate or Slepian’s Theory
This theory states that if the rate at which
the ions and electrons combine to form or
replaced by neutral molecules.
Restriking Voltage & Recovery Voltage
The transient voltage which appears across the breaker contacts
at the instant of arc being extinguished is known as restriking
voltage.
The power frequency rms voltage ,which appears across the
breaker contacts after the arc is finally extinguished and
transient oscillation die out is called recovery voltage.
Arc Extinction
Arc Voltage:
The Voltage drop
across the arc is
called Arc Voltage.
Arc Quenching: ( C.B )
• The Arc Produced not only delays the
current interruption process but it also generates
enormous heat which may cause damage to the
system or to the circuit breaker itself.
• Therefore main problem in a C.B is to
extinguish the arc within the shortest possible
time so the heat generated by it may not reach a
dangerous value.
ARC PHENOMENON
During arcing period, the current flowing between the
contacts depends upon the resistance. The greater
resistance smaller the current that flows between the
contacts.
The arc resistance depends upon
i) Degree of ionisation ( Arc resistance increases with the
decrease in number of ionised particles b/w the contact )
ii) Length of Arc ( Arc resistance increases with the
length of arc )
iii) Cross section of Arc ( Arc resistance increases with
the decrease in X- section of the arc )
The factors that are responsible for
maintenance of arc between the
contacts are:
i) Potential Difference between the
contacts.
ii) ionised particles between the
contacts.
Methods of Arc Interruption
• There are two methods of Arc Interruption
or Extinction are
i) High resistance interruption
ii) Current zero interruption
High resistance interruption
The arc resistance can be increased by
cooling, lengthening, reducing x- section
and splitting the arc.
It is employed for low power AC and DC
circuit breakers.
Current zero interruption
There are two theories to explain the zero
current interruption of the arc.
i) Recovery rate theory(Slepain’s Theory)
ii) Energy balance theory(Cassie’s Theory)
Recovery rate theory
Energy balance theory
Arc Extinction in oil Circuit Breaker
In this method the arc is elongated and splitted by arc splitters. These are
made with plates of resin bonded fiber gas. These are placed perpendicular
to arc and arc is pulled into them by electromagnetic forces.
c) Cooling of Arc :
It causes recombination of ionized particles. Cooling remove the heat from
the Arc. Efficient cooling may be obtained by gas blast directed along Arc .
This method is used for Arc Extinction in A.C circuit breakers. In this method
the resistance kept low until current is zero.
The rapid increase of dielectric strength of the medium near current zero
can be achieved by
1)Lengthening of Arc
2)Cooling
3)Blast effect
Refer Book
How is dc breaking done?
•B circuit breaker.
•Assuming CB “B” breaks the current I
(=E/R)
ARC CHARACTERISTICS
The diff equn of the ckt is,
L(di/dt)+Ri+eb=E
L(di/dt)=(E – Ri)-eb(i)=∆e
∆e negative:
Current will decrease
∆e positive:
When?
This occurs when an unloaded long transmission
line or a capacitor bank is switched off.
•Considering a electrical circuit of a simple power system
•C L line capacitance
TRANSIENT VOLTAGE ACROSS THE GAP
OF THE CIRCUIT BREAKER WHEN THE
CAPACITIVE CURRENT IS INTERRUPTED
At the instant M
The capacitive current is 0.
System voltage is maximum
If interruption occurs
Capacitor CL remains charged at the maximum value of
system voltage.
Value of Vc.
5
CIRCUIT BREAKERS
Presented by
C.GOKUL,AP/EEE
Velalar College of Engg & Tech , Erode
2
UNIT 5 Syllabus
Types of circuit breakers
1. Air Blast circuit breaker
2. Vacuum circuit breaker
3. Oil circuit breaker
4. SF6 circuit breaker
Comparison of Airblast,Vacuum,Oil,SF6
Testing of circuit breakers.
Types Of Circuit Breakers
Oil Circuit Breakers
Disadvantages:
Slower operation , takes about 20 cycles for arc
quenching.
It is highly inflammable , so high risk of fire.
High maintenance cost.
2. VACCUM CIRCUIT BREAKER
It is designed for medium voltage
range (3.3-33kv).
This consists of vacuum of pressure
(1*10-6) inside arc extinction chamber.
The arc burns in metal vapour when
the contacts are disconnected.
At high voltage , it’s rate of dielectric
strength recovery is very high.
Due to vacuum arc extinction is very
fast.
The contacts loose metals gradually
due to formation of metal vapours.
Advantages:
Free from arc and fire hazards.
Low cost for maintenance & simpler mechanism.
Low arcing time & high contact life.
Silent and less vibrational operation.
Due to vacuum contacts remain free from corrosion.
No byproducts formed.
Disadvantages:
High initial cost due to creation of vacuum.
Surface of contacts are depleted due to metal vapours.
High cost & size required for high voltage breakers.
3. AIR BLAST CIRCUIT BREAKERS
This operates using high velocity blast of air which
quenches the arc.
It consists of blast valve , blast tube & contacts.
Blast valve contains air at high pressure.
Blast tube carries the air at high pressure & opens the
moving contact attached to spring.
There is no carbonization of surface as in VCB.
Air should be kept clean & dry to operate it properly.
Types
(i) Axial-blast type (ii)Cross-blast type (iii)Radial-blast type
Advantages:
High speed operation as compared to OCB.
Ability to withstand frequent switching.
Facility for high speed reclosure.
Less maintenance as compared to OCB.
Disadvantages:
Little moisture content prolongs arcing time.
Pressure should be checked frequently for frequent
operation.
Risk of fire hazards due to over voltages.
It can’t be used for high voltage operation due to
prolonged arc quenching.
4. SF6 CIRCUIT BREAKERS
It contains an arc interruption chamber containing SF6 gas.
In closed position the contacts remain surrounded
by SF6 gas at a pressure of 2.8 kg/cm2 .
During opening high pressure SF6 gas at 14 kg/cm2 from its
reservoir flows towards the chamber by valve mechanism.
SF6 rapidly absorbs the free electrons in the arc path to
form immobile negative ions to build up high dielectric
strength.
It also cools the arc and extinguishes it.
After operation the valve is closed by the action of a set of
springs.
Absorbent materials are used to absorb the byproducts and
moisture.
Advantages:
Very short arcing period due to superior arc quenching
property of SF6 .
Can interrupt much larger currents as compared to other
breakers.
No risk of fire.
Low maintenance, light foundation.
No over voltage problem.
There are no carbon deposits.
Disadvantages:
SF6 breakers are costly due to high cost of SF6.
SF6 gas has to be reconditioned after every operation of the
breaker, additional equipment is required for this purpose.
Comparison of Circuit Breakers
18
CONCLUSION:
Therefore, we conclude that circuit breaker is
the most essential part of the electrical
networks as it protects every device from
damage. It helps us to detect the fault and area
affected by it. Nowadays vacuum and SF6
circuit breakers are widely used due to their
reliable and fast operations.
Testing of circuit
breaker
Necessary of Testing of circuit
breaker:-
Why "Testing of Circuit Breaker" is Necessary?
A Circuit Breaker should be capable of carrying, making, and
breaking under normal and abnormal conditions. In any power
system circuit breaker has to withstand power frequency over
voltages and transient over voltages due to switching and
lightning.
The performance of a circuit breaker under normal and abnormal
conditions can be verified by performing different type of tests
on circuit breakers. The main purpose of testing of circuit
breakers is to confirm if circuit breaker is able to work on
particular voltage and current ratings or not.
There are mainly two tests classified:
1) Type test
2) Routine Test
1) Type Tests:
The purpose of type tests is to prove design features and
the quality of circuit breaker. Type tests are not conducted
on each circuit breaker. This is done to prove the
capabilities and to confirm the rated characteristics of the
circuit breakers.
2)Routine Tests:
A three phase transformer of 220/11000 Line Volts is Connected in star / delta. The protective
transformers on 220 V side have a current ratio of 600/5. What should be the current transformer
ratio on 11000 V side? (8)
MAY 2010
A star connected, 3 phase, 10 MVA, 6.6kV alternator has a per phase reactance of 10%. It is
protected by a Merz-Price circulating current protection which is set to operate for fault currents
not less than 175 A. Calculate the value of earthing resistance to be provided in order to ensure
that only 10% of the alternator winding remains unprotected. (16)
For a 132KV system, the reactance up to the fault location and bushing capacitance are 3 ohms
and 0.015µF respectively. Calculate the maximum value of RRRV. (8)
In a 132kV system, the reactance and capacitance up to the location of the circuit breaker is 5O
and 0.02µF respectively. A resistance of 500 O is connected across the contacts of the circuit
breaker. Determine
(i) natural frequency of oscillations (4)
(ii) frequency of damped oscillations (4)
(iii) critical value of resistance (4)
(iv) the value of resistance which will give frequency of damped oscillations
which is equal to 1/4th the natural frequency (4)
Website References
• www.slideshare.net
• www.scribd.com
• www.slideworld.com
• www.nptel.ac.in
• http://opencourses.emu.edu.tr/
• http://engineeringppt.blogspot.in/
• http://www.pptsearchengine.net/
• www.4shared.com
1
UNIT-1 References
• Power System Protection Fundamentals by Dr. Youssef A.
Mobarak
• PROTECTION & RELAY SCHEMES
• Earthing by Er. Satnam Singh Lecturer(Electrical engg.) GPC
Mohali (Khunimajra)
• ET 601 – POWER SYSTEM PROTECTION
• POWER SYSTEM PROTECTION by Chandra Bhushan Singh
• EE 445 Course Presentation
Power System Protection by Mohammed AL-Zeer
• SURGE DIVERTER by NEHA KARDAM & FARHEEN KHAN
• INTRODUCTION TO SWITCHGEAR by R.J.Phansalkar
• Symmetrical Components I by Dave Angell Idaho Power
UNIT-2 References
• Introduction to Protection Relay by Ir.S.Gopinath
• Protective Relays by Dr.Latif Shaikh
• GOVERNMENT COLLEGE OF ENGG.,CHANDRAPUR
PROTECTIVE RELAY
• Electrical Relays by Ben Oman
• Protection and Relay Schemes by Chris Fraser &
Amanda Chen Wang
• Protective Relay by Bhagawan Prasad,Chartered
Engineer
UNIT-3 References
• TRANSFORMER PROTECTIONS by S.Balamurugan
• Motor Protection Principles
• TRANSFORMER PROTECTION
• GENERATOR, TRANSFORMER, MOTOR AND TRANSMISSION LINE
PROTECTION PROTECTIONS
• GENERATOR PROTECTION by ABU SAMAH ABU HASAN,INSTITUT
LATIHAN SULTAN AHMAD SHAH,TENAGA NASIONAL BERHAD
MALAYSIA
• Protection of Transmission Lines by Rohini Haridas
• Generator Protection & Switchgear by Bhushan Kumbhalkar
• Fundamentals of Transformer Protection by Bhuvanesh Oza
• Transformer protection ELE304
• TRANSFORMER PROTECTION - USAID
• MOTOR PROTECTION by R.J. Phansalkar R&D , C&S Electric
UNIT-4 References
• interruption of capacitive current by A.Janani
EEE,SREC
• Dc circuit breaking by A.Janani EEE,SREC
• PRESENTATION ON CIRCUIT BREAKER Er. by
Rahul Sharma
• CIRCUIT BREAKERS by AUROSISH
PANI,Electronics and Electrical Engineering,7th
Sem. ,Roll no-07452
UNIT-5 References
• CIRCUIT BREAKER by RAVIVARMA A/L
RAMANATHAN 18746 PCS
• CIRCUIT BREAKERS
• Testing of circuit breakers