pcs7 Readme - en US PDF
pcs7 Readme - en US PDF
pcs7 Readme - en US PDF
Overview 2
Notes on installation 3
SIMATIC
Notes on usage 4
Process Control System PCS 7 Software components on the
PCS 7 Readme V8.0 SP2 (online) SIMATIC PCS 7 DVD V8.0
5
incl. SP2 and changes to
PCS 7 V8.0 incl. SP1
07/2014
A5E31750585-AD
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified
personnel are those who, based on their training and experience, are capable of identifying risks and avoiding
potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in
this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
1 Security information......................................................................................................................................7
2 Overview.......................................................................................................................................................9
3 Notes on installation...................................................................................................................................11
3.1 General information.....................................................................................................................11
3.2 Type of delivery...........................................................................................................................13
3.2.1 Delivery package.........................................................................................................................13
3.2.2 Notes on the license contract for the SQL server........................................................................13
3.3 Hardware requirements...............................................................................................................14
3.3.1 PC hardware...............................................................................................................................14
3.3.1.1 Recommended PC hardware configuration................................................................................14
3.3.1.2 Compatibility matrix SIMATIC IPC and accessories for PCS 7 V8.0..........................................16
3.3.1.3 Network.......................................................................................................................................19
3.3.2 AS hardware................................................................................................................................20
3.3.2.1 HW versions................................................................................................................................20
3.4 Installation of the software, software requirements.....................................................................21
3.4.1 Software installation....................................................................................................................21
3.4.1.1 Requirements..............................................................................................................................21
3.4.1.2 Notes on installing the software..................................................................................................27
3.4.1.3 Notes on updating the software...................................................................................................29
3.4.2 MS Windows settings..................................................................................................................31
3.4.3 Installation of ES and OS on a single PC....................................................................................31
3.4.4 Installation of SIMATIC NET products.........................................................................................31
3.4.5 Use of the Media Redundancy Protocol (MPR) for PROFINET fieldbus.....................................32
3.4.6 Settings for standard network adapters (BCE and Softnet)........................................................33
3.4.6.1 Plant bus with TCP/IP protocol....................................................................................................33
3.4.6.2 BCE and time synchronization....................................................................................................33
3.4.7 Installation of SIMATIC BATCH products....................................................................................34
3.4.8 Installation of older versions of PCS 7 libraries...........................................................................34
3.4.9 Using antivirus software and whitelisting protection mechanisms...............................................34
3.4.10 Use of Multi-VGA graphics cards................................................................................................35
3.4.11 Using a DCF 77 client.................................................................................................................36
3.4.12 Shutting down Windows, standby mode / hibernation.................................................................36
3.4.13 SIMATIC Logon...........................................................................................................................36
3.4.14 Using smart card readers............................................................................................................37
3.4.15 Using Microsoft Office.................................................................................................................38
3.4.16 Ethernet settings.........................................................................................................................38
3.4.17 Changing the storage location for projects/multiprojects.............................................................39
3.4.18 Remote service and remote operation........................................................................................39
3.4.19 Modifying the internal authentication mechanism of the OS.......................................................40
3.4.20 Remote access to OS projects....................................................................................................41
3.4.21 Installation of WinAC software....................................................................................................41
3.5 Licensing.....................................................................................................................................42
3.5.1 PCS 7 licenses and quantity structures.......................................................................................42
You have received the software package, SIMATIC PCS 7 V8.0 incl. SP2.
SIMATIC PCS 7 is the future-oriented process control system used in the "Totally Integrated
Automation" concept by Siemens.
● Based on robust, industrial standard SIMATIC hardware and software components
● Modern, distributed system architecture
● Simple and quick system expansion and optimization in runtime
● Scalable from a small laboratory system to networks of plants
● For all applications: continuous and batch applications
● For all industries: process, production and hybrid sectors
● Efficient, plant-wide engineering
● Flexible and simple integration of field devices and drives based on PROFIBUS or
Foundation Fieldbus
● Homogeneously integrated safety technology, certified by the TÜV (German Technical
Inspectorate)
● Support for open source interfaces based on international standards such as OPC
● Increased availability through redundancy at all levels
● Modular structured and scalable batch system, SIMATIC BATCH
● Flexible route control system, SIMATIC Route Control
● 21 CFR Part 11 compliance
We hope that you enjoy using SIMATIC PCS 7 and have great success with it.
Your PCS 7 team
Note
It is vital that you use the information from the most recent version of the PCS 7 Readme
(online) before you begin the installation or use of PCS 7 V8.0 incl. SP2.
Each of the products comes with product-specific information in the form of readme files.
The information contained in these readme files also applies to using products in PCS 7.
Pre-installed manuals
Once you have installed PCS 7 on your computer, the following PCS 7 documentation is
immediately available:
● You can find this documentation in the section SIMATIC > Documentation or the product
information in the Start menu of Windows:
– PCS 7 - Catalog Overview (PDF)
– PCS 7 - Operating Instructions - OS Process Control (PDF)
– PCS 7 - Installation Manual - PC Configuration and Authorization (PDF)
– PCS 7 - Configuration Manual - Engineering System (PDF)
– PCS 7 - Configuration Manual - Operator Station (PDF)
You can also access this documentation at any time on the SIMATIC PCS 7 DVD 1/2 in the
folder "_Manuals\English" or "_Product_Information\English".
Note
Timeliness of online documents
Documents available online may be more up-to-date than the version of documents installed
with PCS 7 Setup. The statements in documents available online should therefore be given
priority over installed documents.
Information on modified documents
In order to keep yourself informed about changes to the PCS 7 Readme and the other PCS
7 documentation, we recommend that you subscribe to the newsletter in the Industry Online
Support:
● Internet link (http://support.automation.siemens.com)
3.3.1 PC hardware
Parameters OS client
Basic PC (see catalog) SIMATIC IPC427C / IPC427D
Processor Intel Core2 Duo / Intel Core i7-3517UE
Work memory (RAM) 2.0 - 4.0 GB
Hard disk >=250 GB HDD SATA or >=50 GB Solid State disk SATA
Partition size C:\ 50GB HDD (Windows XP)
C:\ 100GB HDD ( Windows 7)
C:\ 35GB SSD ( Windows 7 + Windows XP)
Network adapter/communications ● 2 x RJ45 on-board Gigabit Ethernet
interfaces ● without PROFINET or PROFIBUS interface
Special features Without fan
Purpose Approved for OS/Batch client operation only
We recommend the following configuration for Box / Microbox components (the higher the
quality of the equipment, the better):
Note
Please note the following:
● In the case of multiproject engineering, it is beneficial for the engineering stations if you
use PCs with high clock-pulse rates, large main memories and hard disks, and high-speed
disk drives. In addition to the Microsoft recommendation of "15% free space", we
recommend that you reserve at least 2 GB of free space (depending on the size of the
project) on the system partition.
● 1): Central engineering station with server operating system (not with Windows Server
2008 SP2 Standard Edition 32-bit); CAS (Central Archive Server, with Windows Server
2003 R2 SP2 Standard Edition MUI 32-bit only)
● If the Process Historian and central archive server (CAS with large quantity structure) is
used in conjunction with large volumes of data, we recommend you use the premium
server found in the PCS 7 Add-on catalog.
Additional information
● Catalog ST PCS 7 for V8.0
● Add on catalog ST PCS 7 for V8.0
3.3.1.2 Compatibility matrix SIMATIC IPC and accessories for PCS 7 V8.0
PCS 7 V8.0 MLFB Windows 7 SP1 Windows 7 SP1 Windows Server Windows Server
Ultimate 32-bit Ultimate 64-bit 2008 SP2 2008 R2 SP1
Standard Edition Standard Edition
32-bit 64-bit
RACK IPC
IPC547B 6ES7650-0N...-.... - - - -
IPC547C 6ES7660-0....-.... X - X -
IPC547D 6ES7660-3....-.... - X - X
IPC547E 6ES7660-4....-.... - X - X
IPC647C 6ES7660-1....-.... - X - X
IPC647D 6ES7660-5....-.... - X - X
IPC847C 6ES7660-2....-.... - X - X
IPC847D 6ES7660-6....-.... - X - X
BOX IPC
IPC627B, BOX 416, 6ES7650-2P...-0YX0 - - - -
BOX RTX (RTX 6ES7650-2Q...-0YX0
2008)
IPC627C, BOX with/ 6ES7650-4A...-.... X - - -
without RTX 2010
Microbox
IPC427B, AS RTX 6ES7654-0UE12-0XX0 - - - -
(RTX 2008)
IPC427C, AS RTX 6ES7654-0UE13-0XX0 - - - -
(RTX 2010)
IPC427C, OS 6ES7650-0RG..-.... X - - -
clients
IPC427D, OS 6ES7650-0UG..-.... - X - -
clients
CPs
CP1613 A1 6GK1161-3AA00 - - - -
CP1613 A2 6GK1161-3AA01 X X X X
CP1623 6GK1162-3AA00 X X X X
CP1628 6GK1162-8AA00 - X - X
PCS 7 V8.0 MLFB Windows 7 SP1 Windows 7 SP1 Windows Server Windows Server
Ultimate 32-bit Ultimate 64-bit 2008 SP2 2008 R2 SP1
Standard Edition Standard Edition
32-bit 64-bit
Accessories
Redundant terminal 6ES7652-0XX01-1XF0 - - - -
bus adapter
package PCI
Redundant terminal 6ES7652-0XX01-1XF1 X X X X
bus adapter
package PCIe
BOX IPC
IPC627B, BOX 416, 6ES7650-2P...-0YX0 X - -
BOX RTX (RTX 6ES7650-2Q...-0YX0
2008)
IPC627C, BOX with/ 6ES7650-4A...-.... X - -
without RTX 2010
Microbox
IPC427B, AS RTX 6ES7654-0UE12-0XX0 - - X
(RTX 2008)
IPC427C, AS RTX 6ES7654-0UE13-0XX0 - - X
(RTX 2010)
IPC427C, OS clients 6ES7650-0RG..-.... X - -
IPC427D, OS clients 6ES7650-0UG..-.... - - -
CPs
CP1613 A1 6GK1161-3AA00 X X -
CP1613 A2 6GK1161-3AA01 X X -
CP1623 6GK1162-3AA00 X X -
CP1628 6GK1162-8AA00 - - -
Accessories
Redundant terminal 6ES7652-0XX01-1XF0 X X -
bus adapter
package PCI
Redundant terminal 6ES7652-0XX01-1XF1 X X -
bus adapter
package PCIe
3.3.1.3 Network
Network configuration
The network for the PCS 7 systems must be isolated via switches, routers or gateways in such
a way that no external interference can affect the PCS 7 network.
You can find recommendations for this in the document:
● PCS 7 Security Concept PCS 7 & WinCC (Basic)
The document is available for download under the Entry ID 60119725 in the Industry Online
Support:
3.3.2 AS hardware
3.3.2.1 HW versions
Documentation on hardware
The versions of the AS hardware components that are approved for PCS 7 V8.0 incl. SP2 are
described in the manual "PCS 7 - Released Modules". This document is located on the website
for SIMATIC PCS 7 Technical Documentation:
● Internet link (www.siemens.com/pcs7-documentation)
Time synchronization
● These CPU types can only be synchronized using the NTP method when using the internal
ETHERNET/PROFINET interface. We recommend that you use the central SICLOCK TC
400 system clock. For the previous CPU types, we continue to recommend that you use
the SIMATIC mode.
● You can find notes on SICLOCK TC 100 / TC 400 in the function manual "PCS 7 – Time
synchronization".
This document is located on the website for SIMATIC PCS 7 Technical Documentation:
– Internet link (www.siemens.com/pcs7-documentation)
3.4.1.1 Requirements
Note
Released processor architectures
Only the x64 platform is used for processor architectures which support 64-bit memory
addressing.
Systems with Intel Itanium CPU architecture (IA64) are not supported.
Not all configurations are suitable for every operating system. The following table shows the
relationship of the most common configurations of PCS 7 to the operating systems. Before
performing the installation, refer to the product-specific readme files to ensure that the product
being installed is suitable for the desired operating system.
XP Emb. Std. Windows 7 Windows 7 Server 2003 2008 Server 2008 Server
2009 SP1 (32 Bit) SP1 (64Bit) SP2 (32Bit) SP2 (32Bit) R2 SP1
XP Prof. SP3 Server 2003 (64Bit)
(32Bit) R2 SP2
(32Bit)
ES X X X X
OS- Single Station X X X X
ES/OS-Single Station X X X X
OS-Server X X X
OS-Client X X X X X
Web-Server X1 X X X
Web-Client X X X X X
CAS X
Process Historian X
Information Server X X X X X
PCS 7 BOX X
PCS 7 RTX X
OS-Client Microbox X
PCS 7 AS RTX Microbox X
PCS 7 AS RTX S7 mEC X
Information on installing the operating system based on Windows Server 7 or Windows Server 2008
If the operating system for PCS 7 has not been installed on the PC station yet, reinstall the
PC. This requires the operating system to be changed. The use of tools such as Windows
Easy Transfer to transfer data and settings between different operating systems or to perform
a direct upgrade from Windows Vista to Windows 7 has not been approved.
The use of the following features of the new operating system generation has not been
approved for PCS 7:
● XP mode (only available with Windows 7)
● HomeGroup (only available with Windows 7)
● Parental Control (only available with Windows 7 Ultimate)
● Windows Defender
● Bit Locker
● Fast User Switching (The use of this feature can be disabled by the administrator via a
group policy. You can find additional information on the procedure on the SIMATIC PCS 7
DVD 1/2 in the folder _Manuals\English "PCS 7 - PC Configuration and Authorization.pdf"
in the section "How to disable user switching")
It is always advisable that only alphanumeric characters are used for the computer name. You
should choose a name consisting of uppercase Latin letters (A-Z) and digits (0-9) only, starting
with a letter and containing a maximum of 15 characters.
Security settings
You can find information about the security settings in the "_Manuals\English" folder on the
SIMATIC PCS 7 DVD 1/2 in the sections "Security settings for the PC configuration" and
"Firewall" of the "PCS 7 - PC Configuration and Authorization.pdf" file.
Settings need to be made in the registry, the DCOM configuration and the exception list of the
Windows firewall for the PCS 7 software to operate correctly.
Before the installation begins, the "Setup - System Settings" dialog appears. There, the system
settings to be changed are listed. To continue the setup, you need to agree to the change to
these system settings.
Note
Please note the following:
● The settings must be applied again if the work environment changes (domains,
workgroups) using the menu command Start > Program Files > Siemens Automation >
Security Controller > Repeat Settings . Start the Security Controller after the PC has been
added to the domain and rebooted. Remember that the Windows services that are
required for the Security Controller are not immediately available after Windows logon. If
the tool is started without entries,restart it after a brief interval.
● The settings in the exception list of the Windows firewall are applied to the area of the
local network (subnet). If your PC stations are located in different networks (subnets), you
need to change this area.
● If you need to make individual changes to any of the firewall settings, they should be
adapted afterwards.
● If you use the Windows Server 2008 SP2 (32-bit) operating system and install network
adapters at a later point in time (e.g. install CP-drivers with the setup from SIMATIC NET),
when you are finished check your custom firewall settings and enter them once again if
necessary.
● The settings in the exception list of the Windows firewall are made when the Windows
firewall is disabled.
Additional information
PCS 7 Security Concept PCS 7 & WinCC (Basic) function manual
The document is available for download under the Entry ID 60119725 in the Industry Online
Support:
● Download link (http://support.automation.siemens.com/WW/view/en/60119725)
Security patches
You can find information on the use of the latest Microsoft security patches in the Industry
Online Support under Entry ID 18490004:
● Internet link (http://support.automation.siemens.com/WW/view/en/18490004)
Also read the latest information about malware/viruses/trojans in the SIMATIC WinCC /
SIMATIC PCS 7 environment under Entry ID 43876783:
● Internet link (http://support.automation.siemens.com/WW/view/en/43876783)
Hyper-Threading Technology
Hyper-Threading has been approved for PCS 7.
OPC XML DA
OPC XML DA has not been released.
Example:
Create a network copy of the two SIMATIC PCS 7 DVDs with the following structure:
● …\PCS7_Vxx\
– DVD_1\
– DVD_2\
Installation
There are two possible ways to install PCS 7:
● Install a previously saved image of the operating system (PCS 7 must not be installed in
this image). You can then install PCS 7 on this image.
● Install the operating system, and then install PCS 7.
You can find detailed information about the installation requirements and procedure in the
"PCS 7 - PC Configuration and Authorization.pdf" document located in the "_Manuals\English"
folder on the SIMATIC PCS 7 DVD 1/2.
Steady state
During the installation of the PCS 7 software, the system must be in steady state.
Therefore, make sure that no updates are being performed for antivirus software or the
Windows Software Update Services (WSUS) during the installation. You can ensure this by
temporarily disabling the corresponding options in each program.
bit version of the Windows Server 2008 operating system, you must follow the instructions on
the Microsoft support page 2745448:
● Internet link (http://support.microsoft.com/kb/2745448)
Software update with utilization of new functions from the PCS 7 Advanced Process Library
A software update of the Advanced Process Library (APL) V7.1.x to V8.0x with utilization of
new functions can only be performed with an AS STOP.
Computer reboot
If you use the "Update" function in the PCS 7 setup, we recommend you reboot the PC before
performing the installation.
During the software update, there may be some instances when a message appears prompting
you to reboot your PC. Reboot the PC. The installation is then automatically continued. You
can ignore the warning "At least one service or driver failed during system startup. Use Event
Viewer to examine the event log for details" that may appear with a reboot. The installation will
proceed correctly.
General information
You can find information about the settings on the SIMATIC PCS 7 DVD 1/2 in the folder
_Manuals\English in the document "PCS 7 - PC Configuration and Authorization.pdf".
Windows XP XP Prof. SP3 Windows 7 Server 2003 2008 Server 2008 Server
Emb. Std. (32Bit) SP1 (32 Bit) SP2 (32Bit) SP2 (32Bit) R2 SP1 (64Bit)
2009 Windows 7 Server 2003
SP1 (64Bit) R2 SP2 (32Bit)
SIMATIC NET X X
SOFTNET-IE RNA
V8.2
3.4.5 Use of the Media Redundancy Protocol (MPR) for PROFINET fieldbus
Network topologies
It is absolutely necessary to operate the PROFINET fieldbus ring with MRP (Media
Redundancy Protocol) when using rings with PROFINET. The HSR (High Speed Redundancy)
protocol and MRP cannot be used simultaneously in the same ring. The PROFINET fieldbus
ring may only consist of devices that support MRP functionality.
The following Industrial Ethernet switches support the MRP function:
● SCALANCE X-200 as of Firmware-Version V4.0
● SCALANCE X-200 IRT as of Firmware-Version V4.0
● SCALANCE X-300 as of Firmware-Version V3.0
● SCALANCE X-400 as of Firmware-Version V3.0
HSR MRP
High Speed Redundancy Media Redundancy Protocol
Separate terminal and plant bus X -
Common terminal and plant bus X -
PROFINET fieldbus - X
The following Whitelisting software has been tested for compatibility with PCS 7 V8.0 incl.
SP2:
● McAfee Application Control V6.1
You can find information on "Whitelisting protection mechanisms" in the Industry Online
Support under Entry ID 49382928:
● Internet link (http://support.automation.siemens.com/WW/view/en/49382928)
Detailed information is available on the SIMATIC PCS 7 DVD 1/2 in the folder _Manuals
\English in chapter "How to activate a multi-VGA graphics card" of document "PCS 7 PC
Configuration and Authorization".
SIMATIC Logon
The term "SIMATIC Logon Admin Tool" has been replaced by "SIMATIC Logon Role
Management".
The Microsoft Office applications Word, Excel, and Access can be used in process mode on
PCS 7 OS and BATCH clients. However, their use may result in significantly reduced
performance in some situations. Office must not be used in process mode on any other
operator stations and BATCH stations.
You can find information on the compatibility of SIMATIC PCS 7 in the Industry Online Support
under Entry ID 2334224:
● Internet link (http://support.automation.siemens.com/WW/view/en/2334224)
RDP
Use of the Remote Desktop Protocol (RDP) is permitted only for remote maintenance of PCS 7
OS clients. In addition, no server services (e.g. WebNavigator server, DataMonitor server,
OPC server) are permitted to be active on these computers.
The reason for this lies in the handling of remote desktop sessions by the Microsoft operating
system.
The RealVNC software should be used for remote access to other computers in a distributed
PCS 7 system (for example, OS servers, CAS, engineering stations).
VNC
The "RealVNC" Enterprise Edition software is approved for use for remote service access as
of PCS 7 V8.0.
You can find the RealVNC edition suitable for your PCS 7 version in the regularly updated
Entry ID 2334224 in the Industry Online Support:
● Internet link (http://support.automation.siemens.com/WW/view/en/2334224)
CAUTION
During remote access to a PCS 7 Operator Station via RealVNC, the remote operator has
the possibility of accessing the operating system level of the local PCS 7 Operator Station
(OS). The local operator of the OS thus also has the opportunity - for example via Windows
Explorer opened by the remote operator - to access the operating system level of the local
OS at the same time as the remote operator.
You can find more information about the use of "RealVNC" in PCS 7 plants in the Industry
Online Support under Entry ID 55422236:
General information
Starting with PCS 7 V7.1 SP3, the PCS 7 OS works with a modified internal authentication
mechanism. Certain security settings will be modified accordingly on the SQL Server and in
the project databases. These changes are carried out automatically during installation and
when you initially open an OS project.
Install a copy of PCS 7 as of V7.1 SP3 on all OS stations of your plant so that all components
of your OS system operate with the modified authentication function.
Launch the "SIMATIC Rights" tool with administrator privileges immediately on completion of
this installation. The tool is available in the "Additional_Products\SimaticRights\" folder on your
SIMATIC PCS 7 DVD 2/2. Run the tool with double-click on "SimaticRights.exe". Select the
path that contains your STEP 7, PCS 7, or WinCC project folders from the "Storage location".
Confirm with "OK". Run the tool for all paths that contain STEP 7, PCS 7, or WinCC projects.
All users must have been assigned to the "SIMATIC HMI" user group. This rule also applies
users who want to open the OS projects remotely. Access by members of the "SIMATIC HMI"
user group to the OS database has been restricted to the necessary minimum authorizations
(read/write). Unrestricted access to the OS database is granted as usual only to users who
have Windows administrator privileges.
Add users who only need read access to the OS database to the "SIMATIC HMI VIEWER"
group.
Members of the Windows user group "SIMATIC HMI" should not also be members of the
Windows user group "SQLServer2005MSSQLUser$<Computername>$WINCC".
Members of this user group have administrator privileges on the SQL Server. Remove all
Windows users who only need restricted access to the OS database from this group.
The user "SA" (System Administrator) of the SQL Server is deactivated during installation.
The "WinCCAdmin" and "WinCCConnect" user names have been removed from the OS
database in order to improve access security. These user names can no longer be used to
access the OS database. Application using their own SQL user name and password are not
affected by this change.
3.5 Licensing
Note
Installation of the AS RT PO licenses
Select the appropriate AS RT PO license installation for your engineering environment:
1. AS RT PO license installed on the local engineering PC
Install the AS RT PO license(s) in sufficient numbers on the engineering PC. The favorites
list in the Automation License Manager (see menu "File > Settings") must not contain
entries or the PCs listed do not have AS RT PO licenses.
2. AS RT PO license installed on a license server
Install the AS RT PO license(s) in sufficient number on the license server PC. The favorites
list in the Automation License Manager (see menu "File > Settings") must contain the
name of the license server PC. The local engineering PC must not have an AS RT PO
license.
4.1.3 ET 200S
Note
After using PLCSIM, it may be necessary to re-establish the real connection and recompile
the changes made to relevant AS including the real connection to the OS.
OS connections with a simulated WinAC Controller (WinLC RTX or WinAC Slot) are not
possible. See the notes on simulation of a WinAC Controller in the PLCSIM Readme.
4.1.5 Changing the address range of HART modules in ET 200iSP/ET 200M leads to
address displacements
If HART auxiliary variables are configured retrospectively for HART modules, this leads to an
enlargement of the address field required for these modules. The I/O field may therefore be
redefined. In doing this, the ability to make configuration changes in RUN is lost. Note that
your project may need to be adapted (symbol tables, CFC charts).
We recommend configuring the modules with a "CiR" address placeholder in the address range
of the HART auxiliary variables during configuration. This ensures that the max. address range
is used and avoids address displacement.
4.1.7 Configuration in RUN (CiR) with FM 350-1, FM 350-2, FM 355, FM 355-2, CP 341
The modules FM 350-1, FM 350-2, FM355, FM 355-2 and CP 341 are CiR-compatible, which
means that a configuration in RUN can be used so that they can be plugged or pulled via (hot-
swapped) when the AS is in RUN.
Note the following about these modules when configuring in operating mode RUN:
● FM 350-1 and FM 350-2, CP 341:
Changing the module parameters when the CPU is in operating mode RUN resets the
module and is equivalent to restarting the module.
● FM 355 and FM 355-2:
Bumpless channel-specific changes to module parameters when the CPU is in operating
mode RUN are possible to a limited extent; refer to the documentation of the FM modules.
4.1.9 ET 200pro
The use of ET 200pro with CP 443-5 Extended is only approved with the
6GK7 443-5DX04-0XE0 module, firmware version V6.4 or later.
The modules from the ET 200pro series must be configured in DPV1 mode in HW Config. In
DPV0 mode, no interrupts are sent to the PCS 7 diagnostic blocks.
Shared Device
The use of PROFINET Shared Device with PCS 7 V8.0 incl. SP2 is not supported.
CIR functionality
If you would like to use the CIR functionality on the PROFIBUS master system for S7-400 PN/
DP CPU with firmware <= V6.0.2 (6ES7414-3EM06-0AB0 and 6ES7416-3ES06-0AB0), you
cannot configure PROFIBUS and PROFINET I/O simultaneously for the internal interfaces.
4.2.9 Download
When a "Download" performed from an ES to an OS, the Windows user logged on to the ES
must be known on the target station and a member in one of the following groups there: At
least "Superuser", "SIMATIC HMI" "SIMATIC NET", "SIMATIC Batch" and required SIMATIC
Route Control "RC_..." groups. In addition, the user also needs full access rights for the folder
into which the project should be downloaded. This includes the sharing and security settings.
4.2.11 F-monitoring time of F modules and F field devices after Y Link/DP-PA Link
By extending the calculation of the monitoring times for updating the reserve, it is possible as
of PCS 7 V7.1 SP1 to consider F-monitoring times of F modules and F field devices after Y
Link/DP-PA Link.
Note
When you activate the option "Calculate F modules after Y Link" you will change the CRC
for the F module configuration. You will have to compile the F program once again.
You may have to adjust the F monitoring times of the affected F modules and F field devices
prior to the calculation.
Use the Excel file "s7ftime" to determine the F monitoring times for F modules after Y Link
and F field devices on PROFIBUS-PA.
SIMATIC S7 F systems: execution times of fail-safe blocks, runtime of F shutdown group,
monitoring and reaction times.
Entry ID 22557362:
● Internet link (http://support.automation.siemens.com/WW/view/en/22557362)
● All configured devices and the employed F-drivers must support PROFIsafe V2 mode
● The version of S7 F Configuration Pack used must be >= V5.5 SP9 + Upd1
Note the following before the first compilation of the hardware configuration:
● For the fail-safe operation on PROFINET, be sure to use only fail-safe modules that are
listed in the "PCS 7 V8.0" module filter under PROFINET IO -> I/O -> ET200M.
● Be sure to use a version >= V1.3 of the F-system library in your project. If you have not yet
used F-blocks in your project, place at least one F-block from the F-library version >= V1.3
within a CFC (for example, F-channel drivers).
For this reason, a running Sybase server is an essential requirement. After the installation of
STEP 7, this Sybase server runs in the context of the logged-on user and is started
automatically when the user logs on.
For certain applications in multi-user operation, it may be necessary to maintain the project
data on a central server computer and process the data from several client computers.
For the required Sybase server to run on the central server computer, a user must also be
logged on to the central server computer in accordance with the specification above.
To remove this requirement, you can set up the Sybase server as a service with the application
"setsybserv.exe".
Procedure
To set up the ES as a service, you need to proceed as follows:
● Start the "setsybserv.exe" application with advanced rights (run as administrator) in the
following directory:
– For 32-bit operating systems: "%CommonProgramFiles%\Siemens\S7UBTOOX\"
– For 64-bit operating systems: "%CommonProgramFiles(x86)%\Siemens\S7UBTOOX\"
● You will see the currently valid setting in the dialog box. By selecting the other option, you
can switch between the two configurations "Sybase server as service" and "Sybase server
as user application".
● Then, set up the access rights for the shared folder in which you will make your project data
available on the central server computer for multi-user operation:
– Insert the user "SYSTEM" in the share permissions and allow "full access"
● Restart the computer in order for the settings to take effect.
Note
Operation of the dialog "Configure SIMATIC Workstation"
With the "Sybase server as service" configuration, the "Configure SIMATIC Workstation"
dialog can no longer be operated in the context of a logged-on user.
4.3.1 Diagnostic alarms for digital input modules SM 321-7BH00 and SM 321-7BH01
When using digital input module SM 321-7BH01 HF, the channel-related diagnostic interrupt
takes place for each individual channel.
4.3.4 Using the PCS 7 Advanced Process Library V8.0 + SP2 and software update for
PCS 7 V8.0 incl. SP2
A software update to PCS 7 V8.0 incl. SP2 with utilization of new functions requires an AS
stop and a complete compilation if you are using V7.1.x of the PCS 7 Advanced Process Library
(APL) in your project.
You can find additional information in the readme file PCS 7 Advanced Process Library V8.0
+ SP2.
Note
If a LAN cable is connected to a PC station and the associated LAN partner is not available
in the network or is switched off, you cannot activate automatic switchover using Setup. If
you turn on the LAN partner after the frame setup of the LAN partners, you will see the
message "Limited or no connectivity" after starting the PC station. Manually assign a TCP/IP
address for the network card (CP 1613/1623) to avoid this message.
4.4.8 Controls
Using controls from third-party suppliers may lead to errors such as performance problems or
system blockage. The user of the software must assume responsibility if problems are caused
by third-party controls. We highly recommend that you run a system test to ensure safe
operation before putting them into use.
4.4.17 Consistency between the plant hierarchy and the Picture Tree Manager for SFC
visualization
To prevent delays during the start of OS Runtime and during SFC operation on the OS client,
you need to ensure the following:
● all areas of the plant hierarchy (PH) that contain SFC charts must also be created by name
in the WinCC Picture Tree Manager.
OS areas which should not be available for selection in WinCC Runtime can be configured as
invisible via the OS project editor.
4.5.1 Compiling and loading BATCH with the "Compile and Download Objects" function
Note that when you modifying projects, compiling and loading should always be performed in
the following sequence: AS, OS, BATCH.
4.6.2 Canceling the module redundancy for HART modules of ET 200M and ET 200iSP
remote IOs
In order to cancel the module redundancy set in the hardware configuration (HWC), you need
to adhere to the following procedure:
1. Delete the module in question and then compile the hardware project
2. Remove the deleted module from the process device plant view or network view
3. Configure the module again in HWC
This ensures that the redundancy is removed correctly.
Note
There must be sufficient free hard disk space on the central archive server. The “Archives”
folder must contain at least twice the memory required for the sum of all the configured
individual OS segments.
The central archive server is only released for the Windows Server 2003 (Standard Edition) +
SP2 or Windows Server 2003 R2 (Standard Edition) + SP2 operating system.
Installation requirements:
● StoragePlus: Windows XP SP3, Windows Server 2003 (Standard Edition) + SP2 or
Windows Server 2003 R2 (Standard Edition) + SP2
● Central archive server: Windows Server 2003 (Standard Edition) + SP2 or Windows Server
2003 R2 (Standard Edition) + SP2
● Microsoft Internet Information Services (IIS) and installed Message Queuing
● With Windows Server 2003 (Standard Edition) + SP2 or Windows Server 2003 R2
(Standard Edition) + SP2, the server function "Application Server (IIS, ASP.net)" must be
enabled. Information on this is available in the document "PCS 7 - PC Configuration and
Authorization.pdf" on the SIMATIC PCS 7 DVD in the folder "_Manuals\English".
Install the Central Archive Server or StoragePlus from the SIMATIC PCS 7 DVD with the
appropriate installation package.
If a redundant OS server pair with connected central archive server/StoragePlus is completely
deactivated, on reactivation, the server deactivated last must be activated first.
If the project is connected to a central archive server or if there is no link to the connected OS
servers, a message will appear on these OS servers indicating that there are problems with
the connection to the central archive server. The message can be confirmed by clicking "OK";
otherwise the notice closes automatically when the connection to the central archive server is
activated or returns.
Software update
Before you update the CAS software (SW update installation), you must disconnect any *.SPB
(StoragePlus Backup) databases that may be connected to the project. The databases are
checked and disconnected using the StoragePlus Administration Console (SPB databases
originate in CAS/Storage Plus PCS 7 < V7.0 or prior to/equal to V1.1.1).
Note:
If you still need the values archived in the SPB databases for display, you must to reconnect
these SPB databases after the update.
You may see an error message during the update:
Displaying messages
You can display reports on messages using the Information Server. If there are formatting
instructions for components of the comment dialog in the message texts (for example,
computer name, logged-on user, comments), they are currently not filled out.
4.12 OpenPCS 7
Project languages
If you have project languages other than Western European Languages (code page Windows
– 1252), an OPC A&E Client may only use the languages “German” or “English”, as offered
by the OpenPCS 7 OPC server.
Example:
● WinCC und BATCH Server are running on server (A) .
● The full function of the redundant partner server (B) is achieved when WinCC and BATCH
Server are running on server (B) and the runtime data of WinCC and BATCH are
synchronized.
Automatic restart of the affected server is only performed when this full functionality is achieved.
Requirements
● Use of a PCS 7 OS (multi-station) redundant system, SIMATIC BATCH and SIMATIC Route
Control.
● You must make the following configuration settings on the server systems:
– Automatic Windows logon (not relevant for servers in WinCC service mode)
– Automatic start of the PCS 7 server applications
● Deactivate the "Display Shutdown Event Tracker".
Proceed as follows:
Call via Start > Run...: Enter "gpedit.msc"
In the "Group Policy" dialog: Select Computer Configuration > Administrative Templates >
System and open the properties of the "Display Shutdown Event Tracker". Select
"Disabled".
● Before a PCS 7 server application is exited, an availability check is carried out on the
relevant redundant partner server. The aspect of the data synchronization is not taken into
account in the availability check.
If the partner server is not fully functional, the user is informed of this status and can proceed
accordingly.
The availability check is only carried out in service mode if a user is logged on.
Additional information
You can find more detailed information in the corresponding application descriptions (manual
and readme for PCS 7 OS, SIMATIC BATCH, SIMATIC Route Control, SIMATIC NET).
See also
SIMATIC PCS 7 Technical Documentation (www.siemens.com/pcs7-documentation)
_Product Information
Automation License Manager V5.2 V5.3 V5.3 + Upd1
STEP 7 Basis V5.5 + SP3 V5.5 + SP3 + Upd4 V5.5 + SP3 + Upd7
CFC V8.0 + SP2 + Upd2 V8.0 + SP4 + Upd1 V8.0 + SP4 + Upd4
S7-SCL V5.3 + SP6 + Upd1 n.a. V5.3 + SP6 + Upd1
SFC V8.0 + Upd1 n.a. V8.0 + Upd1
TH V8.0 + SP1 V8.0 + SP1 + Upd1 V8.0 + SP1 + Upd3
IEA-PO V8.0 + SP1 V8.0 + SP2 + Upd1 V8.0 + SP2 + Upd2
PCS 7 Basis Library V8.0 + SP1 V8.0 + SP1 + Upd3 V8.0 + SP1 + Upd4
PCS 7 Advanced Process V8.0 + SP1 V8.0 + SP2 + Upd1 V8.0 + SP2 + Upd2
Library
VersionCrossManager V7.1 + SP3 n.a. V7.1 + SP3
Version Trail V8.0 V8.0 + Upd1 V8.0 + Upd1
PCS 7 PID Tuner V8.0 + SP1 n.a. V8.0 + SP1
DOCPRO V5.4 + SP2 n.a. V5.4 + SP2 + Upd1
PLCSIM V5.4 + SP5 + Upd1 n.a. V5.4 + SP5 + Upd1
SIMATIC WinCC V7.2 V7.2 + Upd5 V7.2 + Upd7
WebNavigator V7.2 V7.2 + Upd5 V7.2 + Upd7
DataMonitor V7.2 V7.2 + Upd5 V7.2 + Upd7
StoragePlus V7.2 n.a. V7.2 + Upd1
Process Historian V8.0 + SP1 V8.0 + SP1 + Upd3 V8.0 + SP1 + Upd4
Information Server V8.0 + SP1 V8.0 + SP1 + Upd3 V8.0 + SP1 + Upd4
OpenPCS 7 V8.0 + SP1 V8.0 + SP1 + Upd2 V8.0 + SP1 + Upd4
SFC Visualization V8.0 + SP1 V8.0 + SP1 + Upd3 V8.0 + SP1 + Upd5
AS-OS-Engineering V8.0 + SP1 V8.0 + SP1 + Upd2 V8.0 + SP1 + Upd4
PV InsInfo Server V8.0 n.a. V8.0 + Upd1
PCS 7 Basis Faceplates V8.0 + SP1 V8.0 + SP1 + Upd1 V8.0 + SP1 + Upd3
PCS 7 Advanced Faceplates V8.0 + SP1 V8.0 + SP2 + Upd1 V8.0 + SP2 + Upd2
SIMATIC NET PCSW V7.1 + SP6 n.a. V7.1 + SP6 + Upd1
V8.2 + SP2 n.a. V8.2 + SP2 + Upd3
SIMATIC Management V8.0 + SP1 V8.0 + SP1 + Upd2 V8.0 + SP1 + Upd2
Console
SIMATIC Management Agent V8.0 + SP1 V8.0 + SP1 + Upd2 V8.0 + SP1 + Upd2
SIMATIC BATCH V8.0 + SP1 V8.0 + SP1 + Upd5 V8.0 + SP1 + Upd8
SIMATIC BATCH BLOCKS V8.0 + SP1 V8.0 + SP1 + Upd1 V8.0 + SP1 + Upd3
SIMATIC Logon V1.5 + SP1 + Upd2 V1.5 + SP1 + Upd3 V1.5 + SP2
SIMATIC PDM V8.0 + SP2 V8.0 + SP2 + Upd2 V8.0 + SP2 + Upd2
SIMATIC PCS 7 DVD PCS 7 V8.0 incl. SP1 PCS 7 V8.0 SP1 PCS 7 V8.0 incl. SP2
SW components Update 1
Sonstiges :
PKZIP V12.4 n.a. V12.4
DotNetFramework V2.0 SP2, V3.0 SP2, V3.5 SP1, n.a. V2.0 SP2, V3.0 SP2, V3.5 SP1,
V4.0 V4.0
.NET Framework
The .NET Framework versions required by PCS 7 are installed automatically by the PCS 7
system setup.
S7-F Systems
S7 F Systems V6.0 (only for operating systems based on Windows XP and Windows Server
2003) and V6.1 SP1 have been tested for compatibility with PCS 7 V8.0 incl. SP2.
You can find additional current information on S7 F systems on the Internet at:
● Internet link (http://support.automation.siemens.com/WW/view/en/26091594/130000)
You can find the manual on configuring and programming S7 F/FH systems on the Internet at:
● Internet link (http://support.automation.siemens.com/WW/view/en/2201072)
For S7 F systems, use S7 F ConfigurationPack >= V5.5 SP9 + Upd1.
You can find more information about the F Configuration Pack on the Internet at:
● Internet link (http://support.automation.siemens.com/WW/view/en/15208817)