Application Examples: Multi-Function Timer
Application Examples: Multi-Function Timer
Features
• Delayed ON, Interval (one shot) or symmetrical recycling
(OFF first or ON first)
16 18 A2 26 28
• Power ON LED flashes when unit is timing
• 5A/250VAC rating per relay contact
SUPPLY RELAY
TYPE VOLTAGE AC/DC CONTACTS
ORDERING
A-LINE CODE AT100 / 250 A D
Technical Specification
Time Time Setting: Time Range
Power Supply: Setting accuracy: 5% Scale
Selection
10 to 100% Selection:
sec, min, hrs
Repeatability: 0.5% 2 0.2 to 2 Sec, min, hrs
AC: 24, 250 (ie. 90-250) 400 (ie. 380-415) V ±15% 5 0.5 to 5 Sec, min, hrs
10 1 to 10 Sec, min, hrs
DC: 48, 60, 110 VDC ±10% 20 2 to 20 Sec, min, hrs
Description of Controls
back A1 15 L1: The red “Relay ON” LED illuminates when the relay is energised.
front
A-LINE AT100 L2: The green “Power ON” LED illuminates when power is supplied to the unit. The LED flashes
Multi-Function Timer
1
2
when the unit is timing. Before the relay switches, the flash rate increases.
3 S1
Function 4 S1: The Timing Function is set on S1.
L1 Position 1: Delayed ON Operation
sec.
Position 2: Interval (one shot) Operation
Range
min. S2 Position 3: Symmetrical Recycling, OFF Cycle First
hrs.
L2 10
Position 4: Symmetrical Recycling, OFF Cycle First
5 20
2 50 S3 S2: The Time Range is set on S2.
Scale
100 Sec Seconds
40% Min: Minutes
70% Hrs: Hours
10%
P1
Time Set 100%
S3: The Time Scale is set on P3. The time scales are 2, 5, 10, 20, 50 & 100.
front P1: The Time Setting is adjusted on P1. The time setting can be adjusted from 10% to 100% of the
back 16 18 A2 selected time. (The selected time is the time range multiplied by the time scale).
Operational Diagrams
Function 1 : Delayed ON Operation Function 3 : Symmetrical Recycling, OFF cycle first
Power ON Power ON
T T T T
Relay ON T T Relay ON T T T T
Power ON Power ON
T T T T T T
Relay ON Relay ON T T T T
T = Set time