Section 23 21 11 - Boiler Plant Piping Systems
Section 23 21 11 - Boiler Plant Piping Systems
Section 23 21 11 - Boiler Plant Piping Systems
PART 1 GENERAL
1.01 DESCRIPTION
A. All boiler plant piping systems, except plumbing and sanitary, including piping supports.
Piping located outside of the boiler plant building is not included except for gas regulator
and meter stations.
A. Entire installation shall comply with ASME Power Piping Code, ASME B31.1 and
appendices.
B. Boiler External Piping, as defined in the ASME Boiler and Pressure Vessel Code, Section
I, is required to be constructed and inspected in conformance with the ASME Code.
C. Mechanics shall be skilled in their work or trade. Welders on pressure vessels or piping
shall show evidence of qualification in accordance with the ASME Power Piping Code and
the ASME Boiler and Pressure Vessel Code. Certify that each welder has passed
American Welding Society (AWS) qualification tests for the welding processes involved,
and that certification is current. Each welder shall utilize a stamp to identify all work
performed by the welder. The Government reserves the right to reject any personnel
found unqualified in the performance of work for which they are employed.
1.04 SUBMITTALS
B. Piping:
3. Manufacturer.
3. Materials of construction.
4. Accessories.
23 21 11 - 1
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
A. All piping shall be stored and kept free of foreign material and shall be internally and
externally cleaned of all oil, dirt, rust and foreign material. Deliver and store valves and
pipe hangers in sealed shipping containers with labeling in place. Storage must be in dry,
protected location.
A. Steam service pressures are selected to provide optimum pressure to the facilities served
by the boiler plant. Main steam header pressure shall be controlled at 815 kPa (120 psi).
Maximum pressure capability of steam systems between boilers and through first
pressure reducing valve protected by a safety valve shall be governed by the
pressure/temperature relationship of the highest safety valve setting shown for the boilers.
C. Boiler feedwater systems between boiler feed pumps, economizers (if provided), and
boilers are designed for a normal maximum temperature of 138 degrees C (280 degrees
F), and emergency temperature of 213 degrees C (415 degrees F) (if economizers are
provided and economizer safety relief valve setting is 1896 kPa (275 psi)). Design
pressure is the greater of: boiler feed pump shut off head; or 1896 kPa (275 psi) set
pressure, plus accumulation, of economizer (if provided) relief valve.
D. Condensate collection and transfer systems to suction of boiler feed pumps are designed
for maximum temperatures to 100 degrees C (212 degrees F), and pressures 276 kPa
(40 psi). Vacuum return systems shall operate between 0 and 27 kPa (0 and 8 inch Hg)
vacuum and equivalent steam saturation temperatures.
E. Natural gas fuel systems are designed and materials and equipment are applied to
prevent failure under gas pressure of 100 kPa (15 psi) entering Government property. LP
gas systems for igniters (pilots) are designed for maximum LP tank pressure of 1725 kPa
(250 psig).
F. Fuel oil system pressures are determined by the requirements of the burners and fuel
trains. No. 2 oil systems are designed for maximum temperatures of 55 degrees C (130
degrees F), and pressures of 1025 kPa (150 psi).
G. Water service pressures are 545 kPa (80 psi) maximum. Systems are designed to
operate under conditions of maximum available pressure.
H. Drips, drains, blowdown, water sampling, and chemical treatment are designed, and
materials and equipment are applied in accordance with the maximum pressure and
temperature of the system with which they are associated.
I. Low pressure steam, condensate, vacuum and vents are designed for service pressures
and temperatures equivalent to 103 kPa (15 psi) saturated steam.
J. Compressed air systems are designed to accommodate a maximum pressure of 850 kPa
(125 psi).
K. Instrumentation and control piping shall be provided for the service and pressure
characteristics of the systems to which they are connected.
23 21 11 - 2
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
A. The publications listed below form a part of this specification to the extent referenced. The
publications are referenced in the text by the basic designation only.
6. A126-04(2009): Standard Specification for Gray Iron Castings for Valves, Flanges
and Pipe Fittings
8. A194/A194M-10: Standard Specification for Carbon and Alloy Steel Nuts for Bolts
for High-Pressure or High-Temperature Service, or Both
10. A216/A216M-08: Standard Specification for Steel Castings, Carbon, Suitable for
Fusion Welding, For High Temperature Service
12. A269-10: Standard Specification for Seamless and Welded Austenitic Stainless
Steel Tubing for General Service
16. B62-09: Standard Specification for Composition Bronze or Ounce Metal Castings
1. Boiler and Pressure Vessel Code: 2010 Edition with current Addenda
23 21 11 - 3
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
9. B16.22-2001: Wrought Copper and Copper Alloy Solder Joint Pressure Fittings
23 21 11 - 4
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
PART 2 PRODUCTS
A. Pipe: Carbon steel, ASTM A53 Grade B or ASTM A106 Grade B, seamless or electric
resistance welded (ERW). Schedule 40 for piping up to 862 kPa (125 psig) with welded
ends, Schedule 80 for piping with threaded ends and piping over 862 kPa (125 psig) with
welded ends. Standard weight permitted for pipe sizes 300 mm (12 inches) and above.
B. Joints:
C. Fittings:
1. Welded joints: Steel, ASTM A234, Grade B, ASME B16.9, same schedule as
adjoining pipe, all elbows long radius.
2. Threaded joints: Forged steel, ASME B16.ll, 13,790 kPa (2000 psi class; or
malleable iron, ASTM A47 or A197, ASME B16.3, 2050 kPa (300 psi) class.
3. Socket-welded joints: Forged steel, ASME B16.11, 13,790 kPa (2000 psi) class.
D. Unions on Threaded Piping: Forged steel, 13,800 kPa (2000 psi) class or 20,680 kPa
(3000 psi) class; or malleable iron, 2050 kPa (300 psi) on piping 50 mm (2 inches) and
under.
E. Flanges and Bolts: Forged steel weld neck, ASME B16.5, ASTM A105, 1025 kPa (150
psi) pressure class, except 2050 kPa (300 psi) class required adjacent to 1725 kPa (250
psi) and 2050 kPa (300 psi) class valves. Bolts shall be high strength steel ASTM A193,
Class 2, Grade B8. Nuts shall be ASTM A194.
A. Includes all gravity, drip return, pumped and vacuum systems. Does not include piping
system between boiler feed pumps and boilers.
B. Pipe: Carbon steel, ASTM A53 Grade B or ASTM A106 Grade B, seamless or ERW,
Schedule 80.
C. Joints:
D. Fittings:
1. Welded joints: Steel, ASTM A234, Grade B, ASME B16.9, same schedule as
adjoining pipe.
23 21 11 - 5
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
2. Threaded joints: Forged steel, ASME B16.ll, 13,790 kPa (2000 psi class; or
malleable iron, ASTM A47 or A197, ASME B16.3, 2050 kPa (300 psi) class.
3. Socket-welded joints: Forged steel, ASME B16.11, 13,800 kPa (2000 psi) class.
E. Unions on Threaded Piping: Forged steel, 13,800 kPa (2000 psi) class or 20,680 kPa
(3000 psi) class; or malleable iron, 2050 kPa (30 psi). On piping 50 mm (2 inches) and
under.
F. Flanges: Forged steel weld neck, ASTM A105, ASME B16.5, 1025 kPa (150 psi).
A. Provide threaded dielectric unions for pipe sizes 50 mm (2 inches) and under. For 65 mm
(2-1/2 inches) and above, provide copper and steel flanges electrically isolated at gasket
and by sleeves at bolts. Fittings on cold water and soft water lines shall be rated for 690
kPa (100 psi), 27 degrees C (80 degrees F). Fittings on steam condensate lines shall be
rated at 510 kPa (75 psi), 120 degrees C (250 degrees F). Fittings on other services shall
be rated for the maximum pressure and temperature conditions of the service.
2.04 VALVES – GATE, GLOBE, PLUG, CHECK, BALL, BUTTERFLY, VENT COCKS
A. Valves for particular services are generally specified as Type Numbers. The Type
Numbers are defined below. All valves of the same type shall be the products of a single
manufacturer. Comply with MSS SP045, MSS SP080, and ASME B31.1. Design valves
for the service fluids and conditions. Pressure-temperature ratings listed are minimum
requirements. Packing and gaskets shall not contain asbestos.
1. Gate Valves:
a. Type 101: Cast steel body ASTM A216 WCB, rated for 1025 kPa at 260
degrees C (150 psi at 500 degrees F), 11-1/2 to 13 percent chromium
stainless steel flexible wedge and hard faced (stellite) or nickel copper
alloy seats, 1025 kPa (150 psi) ASME flanged ends, OS&Y, rising stem,
bolted bonnet.
b. Type 102: Cast iron body ASTM Al26 Class B, rated for 1725 kPa (250
psi) saturated steam, 3440 kPa (500 psi) WOG, bronze wedge and
seats, 1725 kPa (250 psi) ASME flanged ends, OS&Y, rising stem, bolted
bonnet, renewable seat rings.
23 21 11 - 6
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
c. Type 103: Cast iron body ASTM Al26 Class B, rated for 850 kPa (125
psi) saturated steam, 1375 kPa (200 psi) WOG, bronze or bronze faced
wedge and seats, 850 kPa (125 psi) ASME flanged ends, OS&Y, rising
stem, bolted bonnet, renewable seat rings.
d. Type 104: Bronze body ASTM B6l, rated for 1375 kPa (200 psi) saturated
steam, 2750 kPa (400 psi) WOG, bronze wedges and Monel or stainless
steel seats, threaded ends, rising stem, union bonnet.
e. Type 105: Forged steel body ASTM A105, rated for 2050 kPa at 216
degrees C (300 psi at 420 degrees F) minimum, Class 4130 kPa (600
psi) or Class 5500 kPa (800 psi), hardened stainless steel or stellite
wedge and seats, threaded ends, OS&Y, rising stem, bolted bonnet.
C. Steam above 100 kPa (15 psi), all valves in steam pressure reducing stations:
A. Provide an engineered piping support system with all hangers, supports and anchors
designed and located by experienced technical pipe support specialists, utilizing piping
system design and analysis software. The system design must be completely
documented and submitted for review.
B. All pipe hangers and supports, and selection and installation shall comply with MSS SP-
58, SP-69, SP-89, SP-90, SP-127.
C. All pipe hanger and support devices must be in compliance with specified MSS SP-58
type numbers, have published load ratings, and be products of engineered pipe support
manufacturers.
D. All pipe stresses and forces and moments on connecting equipment and structures shall
be within the allowances of the ASME B31.1 code, applicable building codes, and
equipment manufacturer’s design limits.
E. Piping that expands and contracts horizontally including steam, steam condensate, boiler
feed, condensate transfer, shall be supported by roller or sliding type hangers and
23 21 11 - 7
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
supports except when long vertical hanger rods permit sufficient horizontal movement
with the vertical angles of the rods less than 4 degrees.
F. Piping that expands and contracts vertically including steam, steam condensate, boiler
feed, condensate transfer, shall be supported by engineered variable spring and spring
cushion hangers. Utilize MSS SP-69 selection requirements and guidelines. Vibration
isolator hanger types are not permitted.
G. Piping system anchors shall be engineered and located to control movement of piping
that is subject to thermal expansion.
1. Piping system design and analysis software shall be current state of the art that
performs B31.1 Code analyses, and shall be utilized to analyze pipe movement
and deflection, pipe stresses, pipe support forces and moments, and for selection
of pipe support types and sizes.
2. Each support for piping 60 mm (2-1/2 inches) and above shall be completely
engineered to include location, type and size, hot and cold loads and movement.
Submit layout drawings showing precise support locations and submit individual
drawings for each support assembly showing all components, sizes, loadings.
4. Obtain permissible loadings (forces and moments) for equipment nozzles (pipe
connections) from the manufacturer of the boilers, the feedwater deaerator and
any other equipment as necessary. Professional structural engineer shall verify
capability of building structure to handle piping loads.
5. The project drawings may show locations and types of resilient supports including
rollers and springs, and may also show special supports including anchors,
guides and braces. Comply with the drawing requirements unless it is determined
that piping may be overstressed or supports overloaded. Refer conflicts to the
PM/COR.
6. Variable spring hangers conforming the MSS SP-58, Type 51, shall support all
piping that expands vertically from thermal effects which may include connected
equipment, such as boilers. Spring rates must be selected to avoid excessive
load transfer to the connected equipment as the piping expands vertically.
Vibration-type spring isolators are not acceptable. Light duty spring hangers, MSS
SP-58, Type 48, may be utilized on loads of 90 kg (200 lb) or less, and vertical
movement of 3 mm (0.125 inches) or less. Spring cushion hangers, MSS SP-58,
Type 49, may be utilized for vertical movement of 3 mm (0.125 inches) or less.
7. Locate supports to permit removal of valves and strainers from pipelines without
disturbing supports.
23 21 11 - 8
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
8. If equipment and piping arrangement differs from that shown on the drawings,
support locations and types shall be revised at no cost to the Government.
2. Upper Attachments to Building Structure: Types 18, 20, 21, 22, 23, 29 and 30.
3. Roller Supports: Types 41, 43 and 46. Provide vertical adjustment for Type 41
with threaded studs and nuts adjacent to the roller.
a. Type 51 variable spring, with Type 3 pipe clamp or Type 1 clevis. Type 53
variable spring trapeze may also be used. Locate Type 51 variable spring
within 300 mm (1 foot) above pipe attachment. Attach rod to top of
variable spring with Type 14 clevis.
b. Typical features of variable spring hangers include spring rates under 150
lb/in, enclosed spring, load and travel indicator, sizes available with load
capabilities ranging from 50 lb to multiples of 10,000 lb.
6. Light Duty Spring Hanger Assembly: Type 48 light duty spring, with Type 3 pipe
clamp or Type 1 clevis. Locate Type 48 light duty spring within 300 mm (1 foot)
above pipe attachment.
11. Roller Guides: Type 44. Construct guides to restrain movement perpendicular to
the long axis of the piping. All members shall be welded steel.
12. Trapeze Supports: May be used where pipes are close together and parallel.
Construct with structural steel channels or angles. Bolt roller supports to steel to
support piping subject to horizontal thermal expansion. Attach other piping with U-
bolts.
13. Pipe Covering Protection Saddles: Type 39. Provide at all support points on
insulated pipe except where Type 3 pipe clamp is provided. Insulation shields are
not permitted. Refer to Section 23 07 11 – HVAC and Boiler Plant Insulation.
14. Sliding Supports: Type 35. Welded steel attachments to pipe and building
structure with Teflon or graphite sliding surfaces bonded to the attachments.
23 21 11 - 9
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
A. Non-asbestos, designed for the service conditions. On steam service utilize 3 mm (1/8
inch) thick Class 300 spiral-wound with Type 304 stainless steel and mica/graphite filler
and carbon steel gauge ring.
PART 3 EXECUTION
A. The piping arrangement shown is a design based on currently available equipment. The
plans show typical equipment to scale and show practical arrangement. Modification will
be necessary during construction, at no additional cost to the Government, to adapt the
equipment layout and piping plans to the precise equipment purchased by the Contractor.
Accessibility for operation and maintenance must be maintained.
B. All piping shall be installed parallel to walls and column centerlines (unless shown
otherwise). Fully coordinate work of each trade to provide the designed systems without
interference between systems. All piping shall be accurately cut, true, and beveled for
welding. Threaded piping shall be accurately cut, reamed and threaded with sharp dies.
Copper piping work shall be performed in accordance with best practices requiring
accurately cut clean joints and soldering in accordance with the recommended practices
for the material and solder employed.
D. Valves shall be located and stems oriented to permit proper and easy operation and
access to valve bonnet for maintenance of packing, seat and disc. Valve stems shall not
be below centerline of pipe. Refer to plans for stem orientation. Where valves are more
than 2100 mm (7 feet) above the floor or platform, stems shall be horizontal unless shown
otherwise. Gate and globe valves more than 3 m (10 feet) above floor or platform, shall
have chain wheel and chain for operation from floor or platform. Provide hammer-blow
wheel on any valve that cannot be opened or tightly closed by one person. Steam line
gate and butterfly type isolation valves 750 mm (3 inch) pipe size and above shall have
factory or field-fabricated 20 mm or 25 mm (3/4 or one inch) globe-valved warm-up
bypasses if the steam line length is 6 m (20 feet) or longer.
23 21 11 - 10
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
H. Do not install any piping within 600 mm (2 feet) of water tube boiler side or top casings.
3.02 WELDING
A. The contractor is entirely responsible for the quality of the welding and shall:
1. Conduct tests of the welding procedures used by his organization, determine the
suitability of the procedures used, determine that the welds made will meet the
required tests, and also determine that the welding operators have the ability to
make sound welds under standard conditions.
3. Perform all welding operations required for construction and installation of the
piping systems.
B. Qualification of Welders: Rules of procedure for qualification of all welders and general
requirements for fusion welding shall conform to the applicable portions of ASME B31.1,
and AWS B2.1, and also as outlined below.
C. Examining Welder: Examine each welder at job site, in the presence of the Project
Manager (PM), to determine the ability of the welder to meet the qualifications required.
Test welders for piping for all positions, including welds with the axis horizontal (not rolled)
and with the axis vertical. Each welder shall be allowed to weld only in the position in
which he has qualified and shall be required to identify his welds with his specific code
marking signifying his name and number assigned.
D. Examination Results: Provide the PM with a list of names and corresponding code
markings. Retest welders who fail to meet the prescribed welding qualifications. Disqualify
welders, who fail the second test, for work on the project.
E. Beveling: Field bevels and shop bevels shall be done by mechanical means or by flame
cutting. Where beveling is done by flame cutting, surfaces shall be thoroughly cleaned of
scale and oxidation just prior to welding. Conform to specified standards.
F. Alignment: Utilize split welding rings or approved alternate method for joints on all pipes
above 50 mm (two-inches) to assure proper alignment, complete weld penetration, and
prevention of weld spatter reaching the interior of the pipe.
G. Erection: Piping shall not be split, bent, flattened or otherwise damaged before, during, or
after installation. If the pipe temperature falls to 0 degrees C (32 degrees F) or lower, the
pipe shall be heated to approximately 38 degrees C (100 degrees F) for a distance of 300
mm (one foot) on each side of the weld before welding, and the weld shall be finished
before the pipe cools to 0 degrees C (32 degrees F).
1. The PM may require up to ten percent of the welded piping joints to be examined
using radiographic testing. If defective welds are discovered the PM may require
examination of all pipe joint welds.
23 21 11 - 11
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
3. Comply with ASME B31.1. Furnish a set of films showing each weld inspected, a
reading report evaluating the quality of each weld, and a location plan showing
the physical location where each weld is to be found in the completed project.
The PM/COR reserves the right to review all inspection records.
I. Defective Welds: Replace and reinspect defective welds. Repairing defective welds by
adding weld material over the defect or by peening will not be permitted. Welders
responsible for defective welds must be requalified.
J. Electrodes: Electrodes shall be stored in a dry heated area, and be kept free of moisture
and dampness during the fabrication operations. Discard electrodes that have lost part of
their coating.
A. All butt-welded piping shall be welded at circumferential joints, flanges shall be weld neck
type; slip-on flanges, screwed flanges may be applied only with written approval of the
PM.
C. Gaskets and bolting shall be applied in accordance with the recommendations of the
gasket manufacturer and bolting standards of ASME B31.1. Strains shall be evenly
applied without overstress of bolts. Gaskets shall cover entire area of mating faces of
flanges.
D. Screw threads shall be made up with Teflon tape except gas and oil piping joints shall
utilize specified joint compound.
A. Piping size changes shall be accomplished by use of line reducers, reducing ell, reducing
tee. Apply eccentric reduction in all piping requiring continuous drainage; steam,
condensate, vacuum, blowdown. Concentric reduction may be applied in run of piping
involving pressure water systems except at pump inlets. Use concentric increasers where
flow is in direction of increased size. Eccentric reduction, top flat, at all pump connections.
A. Coordinate support locations with building structure prior to erection of piping. Also refer
to approved Shop Drawings of equipment and approved piping layout and hanger layout
drawings when locating hangers. Arrangement of supports shall facilitate operating,
servicing and removal of valves, strainers, and piping specialties. Hanger parts must be
marked at the factory with a numbering system keyed to hanger layout drawings. Layout
drawings must be available at the site.
23 21 11 - 12
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
C. Expansion Fasteners and Power Set Fasteners: In existing concrete floor, ceiling and wall
construction, expansion fasteners may be used for hanger loads up to one-third the
manufacturer's rated strength of the expansion fastener. Power set fasteners may be
used for loads up to one-fourth of rated load. When greater hanger loads are
encountered, additional fasteners may be used and interconnected with steel members
combining to support the hanger.
D. Special Supports:
E. Spring Hangers: Locate spring units within one foot of the pipe, breeching or stack
attachment except in locations where spring assemblies interfere with pipe insulation.
Adjust springs to loads calculated by hanger manufacturer.
A. Flush all piping sufficiently to remove all dirt and debris. Fill piping completely. Velocity
shall be equivalent to that experienced during normal plant operation at maximum loads.
During flushing, all control valves, steam traps and pumps must be disconnected from the
system. After cleaning is complete, remove, clean and replace all strainer baskets and
elements. Reconnect all equipment. Provide safe points of discharge for debris blown
from pipes.
3.08 TESTING
A. Testing of piping components is not required prior to installation. Valves and fittings shall
be capable of withstanding hydrostatic shell test equal to twice the primary design service
pressure except as modified by specifications on fittings, ASME B16.5. This test capability
is a statement of quality of material. Tests of individual items of pipe, fittings or equipment
will be required only on instruction of PM and at Government cost.
B. After erection, all piping systems shall be capable of withstanding a hydrostatic test
pressure of 1.5 times design pressure, as stipulated in ASME B31.1. Hydrostatic tests will
be required only on boiler external steam piping, utilizing water as the test medium.
Hydrostatic tests will be required on other piping when operating tests described are
23 21 11 - 13
Demolish Building 162 Phase 1&2 674-11-110
Central Texas Veterans Health Care System Temple, Texas
1. All steam piping prior to insulation shall be subjected to steam at final operating
pressure. Inspect all joints for leaks and workmanship. Corrections shall be made
as specified.
2. Make corrections and retests to establish systems that have no leaks. Replace or
recut any defective fittings or defective threads. Soldered material shall be
thoroughly cleaned prior to resoldering. Back welding of threads will not be
permitted.
D. Generally, insulation work should not be performed prior to testing of piping. Contractor
may, at own option and hazard, insulate piping prior to test, but any damaged insulation
shall be replaced with new quality as specified for original installation at Contractor's cost
and time.
END OF SECTION
23 21 11 - 14