Remote I/O Module Data Acquisition Module DAM102 DAM124 Series

The user manual provides instructions for installing and operating the DAM Series data acquisition module. The DAM supports Modbus RTU protocol over RS485 and has models that offer various combinations of digital inputs, analog inputs, temperature sensors, and relay outputs. It is commonly used in industrial automation and remote monitoring applications to transmit sensor data via serial communication.

Uploaded by

arief
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
142 views11 pages

Remote I/O Module Data Acquisition Module DAM102 DAM124 Series

The user manual provides instructions for installing and operating the DAM Series data acquisition module. The DAM supports Modbus RTU protocol over RS485 and has models that offer various combinations of digital inputs, analog inputs, temperature sensors, and relay outputs. It is commonly used in industrial automation and remote monitoring applications to transmit sensor data via serial communication.

Uploaded by

arief
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Multi-Channel Isolation

Protection

Support Modbus RTU Protocol


over RS485 Serial Port

Used Widely in Industrial


Automation Control Systems

Remote I/O Module


Data Acquisition Module
DAM102 ~ DAM124 Series

DAM102~DAM124
User Manual
Ver 1.0

Date Issued: 2017-07-01


King Pigeon Hi-Tech. Co., Ltd.

www.GPRS-M2M.com
Remote I/O Module
Data Acquisition Module
Table of contents
1. Brief introduction -----------------------------------------------------------------------3
2. Safety Directions -----------------------------------------------------------------------3
3. Standard Packing list ------------------------------------------------------------------3
4. Mainly Features -------------------------------------------------------------------------3
5. Physical Layout and Installation Diagram-----------------------------------------4
6. Initialize/Reset the GSM unit --------------------------------------------------------6
7. Settings & Operations------------------------------------------------------------------7
8. Register Table List -------------------------------------------------------------10
9. Warranty ----------------------------------------------------------------------------10

This handbook has been designed as a guide to the installation and operation of DAM Series. Statements contained
in the handbook are general guidelines only and in no way are designed to supersede the instructions contained
with other products.

We recommend that the advice of a registered electrician be sought before any Installation work commences.
King Pigeon Hi-Tech.Co., Ltd, its employees and distributors, accept no liability for any loss or damage including
consequential damage due to reliance on any material contained in this handbook.

【UPGRADE HISTORY】
DATE FIRMWARE VERSION HARDWARE VERSION DESCRIPTION

Page 2 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
Model List
I/O Digital
Analog Input Temperature
Model Input Output
DAM102 2
DAM108 4
DAM104 2
DAM110 4
DAM106 2 2
DAM112 4 4
DAM114 2
DAM116 4
DAM118 2
DAM120 4
DAM122 2 2
DAM124 4 4
DIN: Digital input, Compatible with NC/NO/Pulse Counter/TTL;
DOUT: Relay output, Max: 3A/240VAC, Compatible with NC/NO/Pulse Counter/TTL;
AIN: Default: 4~20mA, 12 Bits ,Isolated; Optional:0~20mA/4~20mA/0-5V/0~10V;
Temperature: PT100,PT500, PT1000,CU50,CU100 or other PT Resistance Thermometer;
Protocol: Modbus RTU, with RS485 interface, *RS232 is optional;
Dimension: 70*88*30mm, support DIN RAIL Optional.

1. Brief introduction

The DAM with multi-channel for digital input, analog input, digital output (relay), analog output, and
temperature inputs. It can work with any RTU, SCADA, data monitoring, data loggers, PLC’s, process
controllers, instrumentation that supports Modbus RTU Protocol over RS485 serial port. and
transmit in ASCII data format to engineering units for control equipments. It is an industrial class,
high reliability, low-power consumption, high stability and high precision control module. Powered
up by 12VDC or 24VDC.

The DAM is used widely as an extension control module in of Base Transceiver Station, diesel
generator rooms, engine room, transformer substations, telecommunication equipment rooms,
power supply systems and so on.

The DAM with metal box, support standard 35mm DIN rail makes it easy to install in fields.

Tips: King Pigeon Hi-Tech.Co.,Ltd not only provides competitive prices, excellent quality but also
helps customers to solve technical problems, improve quality, reduce extra costs, and assist
customers to become more competitive. If our existing modules cannot meet your requirements,

Page 3 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
we also design and manufacture new models / products according to buyer's request. Any of your
requirements is always welcome!

Typically applications:

Server room, Warehouse, Drug store, Medicine center, Seafood storage, Aquarium, Supermarket, hospital, Hotel;
Weather Stations remote control and data logging, Transformer stations, BTS room, agriculture, Supervision and
monitoring alarm systems, etc.

2.Safety Directions
Safe Startup
Do not use the unit when using GSM/3G/4G equipment is prohibited or might bring disturbance or
danger.
Interference
All wireless equipment might interfere network signals of the unit and influence its performance.

3. Standard Packing List


DAM X 1; User Manual X 1.
Note: The package does not include any sensors and adapter.

Optional: 35mm Standard DIN rail fixed Bracket

4. 1Mainly Features
 Power supply with reverse polarity connection protection;
 32 bit MCU, reliable performance with in-built watchdog;
 Support relay outputs,7A@125VAC,5A@125VAC, 20A@14VDC; (DAM104/110/106/112 Only)
 LEDs for status indication makes it easy to program in filed;
 Support configure parameters, load/export profiles via PC;
 Wall mount or 35mm standard DIN rail Design, convenient installation,
 Metallic cover, small size, exterior dimension is L70*W88*H30mm.

Page 4 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
4. 2 Specifications
Item Reference Scope

DC Power Supply Standard Adapter: DC 12V/1A Range 9~36VDC


Power Consumption Standby:12V/50mA; WorkingMax.:12V/150mA Typically≤3W
Communication Protocol Modbus RTU
Modbus Address 1~247
Data Format n,8,1; e,8,1; o,8,1 or n,8,2
Communication Interface RS485
Baud Rate 1200, 2400, 4800, 9600, 115200 Bps
Output Response Time 100~200mS
Operation Temperature -20~70℃;
Isolated Type Input / Power / RS485 Serial port isolated
Exterior Dimension 70*88*30mm
Installation 35mm standard DIN rail(Optional) Wall mount (Default)
Net Weight 500g

5. Physical Layout and Installation Diagram


5.1 DAM Unit physical layout

LED Indicator Instruction


ON :Standby;
Flash: Data Transmission;
OFF: Power off.

5.2 Interface Instructions for installation


1) Connect External DC Power and Temperature & Humidity Sensor

Page 5 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
See below interface, please connect to the correct wires.

Interface Instruction
+ DC9~36V positive input, 1.5A, for power on the Unit;
DC IN 9~36V
– DC9~36V negative input, 1.5A, for power on the Unit;
+ DC9~36V positive output, 1.5A
DC Out 9~36V
– DC9~36V negative output, 1.5A
1+ Relay output 1;
1– Relay output 1;
2+ Relay output 2;
2– Relay output 2;
3+ Relay output 3;
Relay Output
3– Relay output 3;
4+ Relay output 4;
4– Relay output 4;
A RS485 A Port, used it to communicate with the device for Data Transfer
RS485
B RS485 B Port, used it to communicate with the device for Data Transfer
1~4 Digital input 1~4, connect to one wire of the wired Detector
Digital Input
GND Ground point; connect to another wire of the wired Detector
1~4 Analog input 1~4, the data wire of the analog transducer
Analog Input
GND Ground point; connect to GND wire of the analog transducer
1+
Data Wire of the PT100
1–
GND GND , Connect to PT-100 GND wire, (black wire or white wire)
2+
Data Wire of the PT100
2–
PT100 Resistance GND GND , Connect to PT-100 GND wire, (black wire or white wire)
Temperature
3+
Detector Input Data Wire of the PT100
3–
GND GND , Connect to PT-100 GND wire, (black wire or white wire)
4+
Data Wire of the PT100
4–
GND GND , Connect to PT-100 GND wire, (black wire or white wire)

2) Connect electrical device to Relay outputs.


The DAM unit (DAM104/110/106/112 Only) provides some relay outputs; it can be used for control different
device according to requirements. The connection diagram is below:

3) Connect to the PT-100 Temperature Sensor.

Page 6 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
The DAM unit (DAM118/120/122/124 Only) provides some resistance temperature input; it can be used for
monitoring the temperature according to requirements.

6.1 Initialize/Reset the DAM unit


The Unit can be reset to factory default once mistake programmed. Please follow below steps to initialize it. After
initialized, the parameters will set as factory default.
1) Power on the Unit
2) Press and hold the RESET button for 5 seconds,;
3) Loose the RESET Button.
4) When the status LED flashing, then Reboot the unit then recovery to factory default settings, and will enter to
work mode.

6.2 Testing the DAM unit


1) Please refer to the above mentioned wiring connection to finish the connection.
Please only power on the DAM unit before you’re sure the connection are correct.
After connected to the power, the Status LED indicator will ON.

2) Default setting: Address 1, baud rate 9600bps, data format: n,8,1.


Users can change the settings by configuration software.

3) Connect to RS485 interface.


The host should provide the RS485 interface, if no RS485 port, please use the RS232 to RS485 converter. We
recommend the user use the isolated RS485 to improve the reliability.
In the RS485 interface, all of the A+ should connect together, and the B- connects together, too. Also, the GND
should connect together then connect to the Communication GND.
The RS485 network usually allow to connect maximum 32 device. if the device more than 32, then please use
the RS485 repeater to extend it. The RS-485 network should use the shield twist cable, the shield should connect to
GND independently.
The RS485 network communication distance maximum is 1200m, when the communication baud rate is high
will cause the communication distance short, in this case, please use the RS485 repeater.
At the end of the RS485 network, if the communication quality is not good then usually should connect a
120~300Ω/0.25W termination resistors. If the communication quality is good then no need to connect this resistor.

7. Settings & Operations


The DAM is user-friendly design. The user can setup it by the PC Configuration through RS485/232 interface, the
communication protocol is Modbus RTU, for the Register Address, please refer to Chapter 8.
Tips!
1) Please power on to check the LEDs status according to above mentioned LED Definitions, keep switch
on it during the programming.
2) The PC Configuration in the CD, please click it to run it. Also can download from www.GPRS-M2M.com
under DAM page directly.

Start to Configure:
Step1: Install the Configurator

Page 7 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
The Configurator in the CD or download from www.GPRS-M2M.com, then installs it on the computer.

Step2: Connection
Please only power on the DAM unit before you’re sure the connection are correct.

Step3: Connect the DAM to the PC by RS485/232/USB Cable. And connect the external DC Power to
DC Power Ports, Power on, and switch on the device, see below:

Step4: Install RS485/232/USB Drvier


Install the Driver to the computer. When successful, it can be found out at the device manager of the XP or
Windows 7 or Win8/Win10. Also, please download the driver from the Supplier website of the RS485/232/USB
cable.

Step5: Run the Configurator (Compatible with Windows XP/7/8/10)


Tips: In some computer, it required download net framework 4.0 while installation, then please click “Yes” to go
to Microsoft website to download this service pack.

Step5: Choose the correct "COM port", then click "open Com port", and select the model number
or search the model automatically, after that, then can start to programming.

8. Modbus Register Tables: (The register is used for the Modbus RTU protocol)
8.1 Modbus Register Tables for DAM104/110/106/112:
Table 1:Digital output definition, function code 01/05/0F
Address Definition Data Description
st
0000H DO1 1 digital output:=1 triode close,=0 open.
0001H DO2 2nd digital output:=1 triode close,=0 open.
0002H DO3 3rd digital output:=1 triode close,=0 open.
0003H DO4 4th digital output:=1 triode close,=0 open.

Table 2: Digital Input definition, function code 02


Address Definition Data Description
st
0000H DI1 1 digital input,=0 (0~0.5VDC) short/close,=1 (3~30VDC) Open/no signal.
0001H DI2 2nd digital input,=0 (0~0.5VDC) short/close,=1 (3~30VDC) Open/no signal.
0003H DI3 3rd digital input,=0 (0~0.5VDC) short/close,=1 (3~30VDC) Open/no signal.
0004H DI4 4th digital input,=0 (0~0.5VDC) short/close,=1 (3~30VDC) Open/no signal.
Remark: If the digital input=0, it means closed, if digital input=1, it means open or no signal.

Page 8 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
Table 3: Holding register definition, function code:03/10H
Address Definition Data Description
9C40H Mod Device Model number
9C41H Ver Version
Above mentioned items are READ ONLY, below mentioned items can READ and WRITE.
9C42H ADDR Device Address; 1~247; 0 is the broadcast address.
COM setting: high-order 8 bytes reserved.
The low-order bytes low 3 bytes baud rate:
0:115200;1:57600;2:38400; 3:19200; 4:9600;5:4800;6:2400;7:1200
The lowest 3rd~7th bytes in the low-order bytes is data format:
00 stands for 10bits,equal to n,8,1;
9C43H COM1
50 stands for 11bits, Even-parity check: e,8,1;
58 stands for 11bits, Odd Parity Check: o,8,1;
20 stands for 11 bits, non parity,
2 is stop bit,n,8,2;
default is 4, equal to 9600bps. (9600,8.N.1)
DO1 output type control: BIT15=1 :
Pulse Output control; BIT15=0 : TTL.
9C44H DO1-PUL
Low-order 8 byte: Pulse Width(time): 1~250 = 0.1~25.0 seconds; Default
value: 10 (one second)
9C45H DO2-PUL DO2 output type control, detail description as same as above DO1.
9C46H DO3-PUL DO3 output type control, detail description as same as above DO1.
9C47H DO4-PUL DO4 output type control, detail description as same as above DO1.
Low-order 4 byte is the Pulse Counter:
BIT0=1, Enable the DI1 as a Pulse Counter, =0: Disable
DI Pulse
9C48H BIT1=1, Enable the DI2 as a Pulse Counter, =0: Disable
Counter
BIT2=1, Enable the DI3 as a Pulse Counter, =0: Disable
BIT3=1, Enable the DI4 as a Pulse Counter, =0: Disable
Low-order 2 byte is the additional function when the power failure:
Function for BIT0=1: Save the pulse counter value;
9C49H Power BIT0=0 : Don’t save the pulse counter value;
Failure BIT1=1 : Keep the relay status;
BIT1=0 : Don’t keep the relay status.

Address Definition Data Description


st
9C4AH DI1_Cnt 1 DI 32 bytes pulse counter; 4 bytes, MSB first
9C4BH
9C4CH DI2_Cnt 2nd DI 32 bytes pulse counter; 4 bytes, MSB first
9C4DH
9C4EH DI3_Cnt 3rd DI 32 bytes pulse counter; 4 bytes, MSB first
9C4FH
9C50H DI4_Cnt 4th DI 32 bytes pulse counter; 4 bytes, MSB first
9C51H

Page 9 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
8.2 Modbus Register Tables for DAM118/120/122/124:
Table 1: Holding register definition, function code:03/06/10H
Address Definition Data Description
9C40H Mod Device Model number
9C41H Ver Version
9C42H AdVal[1] 1st PT100 ADC_Value ,range:0-65535, for adjust the temperature
9C43H AdVal[2] 2nd PT100 ADC_Value ,range:0-65535, for adjust the temperature
9C44H AdVal[3] 3rd PT100 ADC_Value ,range:0-65535, for adjust the temperature
9C45H AdVal[4] 4th PT100 ADC_Value ,range:0-65535, for adjust the temperature
9C46H AdVal[5] 1st AIN ADC_Value , range:0-65535, for adjust at site
9C47H AdVal[6] 2nd AIN ADC_Value , range:0-65535, for adjust at site
9C48H AdVal[7] 3rd AIN ADC_Value , range:0-65535, for adjust at site
9C49H AdVal[8] 4th AIN ADC_Value , range:0-65535, for adjust at site
9C4AH AI1 The 1st Analog Input:
1. If enable the Max/Min, then will calculate the real value of the
sensors.
2. If there is no Max/Min:
a) 0~10000 correspond to 0~10V
b) 0~10000 correspond to 0~5V
c) 0~10000 correspond to 0~20mA
d) 0~10000 correspond to 4~20mA
9C4BH AI2 2nd Analog Input, detail description as same as above AI1.
9C4CH AI3 3rd Analog Input, detail description as same as above AI1.
9C4DH AI4 4th Analog Input, detail description as same as above AI1.
9C4EH PT1 1st channel for measuring the temperature, unit :0.1℃ Int, the
actualvalue=DATA/10, unit:℃
9C4FH PT2 2nd channel for temperature, detail description as same as above PT1.
9C50H PT3 3rd channel for temperature, detail description as same as above PT1.
9C51H PT4 4th channel for temperature, detail description as same as above PT1.
Abovementioned items are READ ONLY, below mentioned items can READ and WRITE.
9C52H ADDR Device Address; 1~247; 0 is the broadcast address.
9C53H COM1 COM setting: high-order 8 bytes reserved.
The low-order bytes low 3 bytes baud rate:
0:115200;1:57600;2:38400; 3:19200; 4:9600;5:4800;6:2400;
7:1200
The lowest 3rd~7th bytes in the low-order bytes is data format:
00 stands for 10bits,equal to n,8,1;
50 stands for 11bits, Even-parity check: e,8,1;
58 stands for 11bits, Odd Parity Check: o,8,1;
20 stands for 11 bits, non parity,
2 is stop bit,n,8,2;
Default is 4, equal to 9600bps. (9600,8.N.1)
9C54H AIMode1 Analog input model1 setting, low-order 2 bytes
0:0-5V;
1:0-10V;
2:0-20mA ;

Page 10 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0


Remote I/O Module
Data Acquisition Module
3:4-20mA;
Highest order byte b7=1 is enable the Max/Min;
0= disable
9C55H AIMode2 AIN 2 Setting, as same as the AIMode1
9C56H AIMode3 AIN 3 Setting, as same as the AIMode1
9C57H AIMode4 AIN 4 Setting, as same as the AIMode1
9C58H AdMax1 AIN1 Max Range, default: 5000
9C59H AdMax2 AIN2 Max Range, default: 5000
9C5AH AdMax3 AIN3 Max Range, default: 5000
9C5BH AdMax4 AIN4 Max Range, default: 5000
9C5CH AdMin1 AIN1 Min Range, default: 0
9C5DH AdMin2 AIN2 Min Range, default: 0
9C5EH AdMin3 AIN3 Min Range, default: 0
9C5FH AdMin4 AIN4 Min Range, default: 0
9C60H Pt_0C[1] 1st PT100 input calibrated values in 0℃
Remark: To testing the PT100 in 0℃,or connect to a 100R resistance to
get the ADC_Value, then use this value to adjust the accuracy,
Default:4500
9C61H Pt_0C[2] 2nd PT100 input calibrated values in 0℃
9C62H Pt_0C[3] 3rd PT100 input calibrated values in 0℃
9C63H Pt_0C[4] 4th PT100 input calibrated values in 0℃
9C64H Pt_50C[1] 1st PT100 input calibrated values in 50℃
1st PT100 input calibrated values in 50℃
Remark: To testing the PT100 in 50℃,or connect to a 100R resistance to
get the ADC_Value, then use this value to adjust the accuracy.
9C65H Pt_50C[2] 2nd PT100 input calibrated values in 50℃
9C66H Pt_50C[3] 3rd PT100 input calibrated values in 50℃
9C67H Pt_50C[4] 4th PT100 input calibrated values in 50℃
Remark: If the PT100 temperature sensor cannot measuring the correct value, then need to adjust it,
for 0℃(Pt_0Cx) and 50℃(Pt_50Cx).

9.Warranty
1) This system is warranted to be free of defects in material and workmanship for one year.
2) This warranty does not extend to any defect, malfunction or failure caused by abuse or misuse
by the Operating Instructions. In no event shall the manufacturer be liable for any alarm system
altered by purchasers
The End!
Any questions please help to contact us feel free.
Http://www.GPRS-M2M.com

Page 11 of 11 King Pigeon Hi-Tech. Co., Ltd. Ver 1.0