Chapter 6 Screw Compressors
Chapter 6 Screw Compressors
Screw compressors are the most widely used compressors for industrial refrigeration
application in the world because of the favorable features of variable head and
variable volume characters. Screw compressor practically replaces almost all the
applications that used to the areas of reciprocating compressor in industrial
refrigeration in recent decade.
Screw compressor was invented long time ago. It was based on dry compression; that
is the compressor is with a set of timing gears to ensure that no contacts between the
twin rotors of the compressor. The earlier design screws were mostly used and still
being used for air and gas compression in oil refinery, petrochemical and gas
processing industries. It was not used by refrigeration industries due to various
difficulties including high cost.
Oil Injection (Oil Flooded) for screw compressor was invented in 1950’s. It
eliminated the timing gears, increasing the compression ratio and reducing the
discharge temperature for the compressor. But, it was still not good enough for
refrigeration application, because of oil carry over problem and lack of capacity
control capability for partial load operation.
The adaptation of the screw compressor for refrigeration duty was made possible
in1970’s after the new inventions plus the further improvements made to the screw
compressor. Those major invention and improvement were: The hydraulically
operated capacity control; economizer cycle improves compressor efficiency to a
point comparable to two-stage; improvements on compressor discharge oil filter,
variable Vi, better control by using microprocessor panel and etc.
There are two types of open oil flooded screw compressor available for industrial
refrigeration application do-day; one is the Twin-Rotor screw and the other is the
Single-Rotor screw. Twin-rotor screw is the most widely used compressor for
industrial refrigeration installations worldwide, particularly larger size installations.
FIG. 6.1 shows the typical construction of the twin-rotor screw compressor; FIG. 6.2
shows the typical Asymmetric Twin-Rotor Profile; some manufacturers use other
rotor profile such as 4+6 “A” or 5+7 “D” rotor profile or others. FIG. 6.3 is a typical
construction of Single-Rotor screw compressor.
The compressor shown in FIG. 6.1 is a bare screw compressor; it can not be used for
refrigeration. The screw compressor only can become useful if it is equipped with
other necessary subsystems becoming a “compressor unit” as shown in FIG. 6.4. A
typical “compressor unit” consists of other subsystems as the following:
- 60 -
Screw Compressor.
Driving Motor & Power Supply System.
Lubrication System.
Oil Reservoir & Oil Separation System.
Hydraulic System.
Oil Cooling & Filtering System.
Suction and Discharge Valves and Strainer.
Microprocessor Control Panel and Control System.
- 61 -
- 62 -
- 63 -
One of the terms that manufacturers commonly refer to is “Standard” such as
“Standard Unit”. “Standard Unit” is the scope of supply for the unit as defined by the
manufacturer. A Standard Unit for a screw compressor usually includes the
components shown in FIG. 6.1, except the main driver. The standard steel base for the
driver is designed to accept NEMA Standards motor and the unit is with single oil
filter, single oil cooler and NEMA-1 control panel. Extra cost might be imposed by
the maker for the items that is outside the scope of supply of the “Standard Unit”.
Therefore, it is recommended to check what exactly the scope of supply is with each
supplier.
The screw compressor used for industrial refrigeration is equipped with Hydraulic
Operator and Slide Vane capacity control mechanism; the slide vane is capable of
controlling the screw compressor for partial load operation down to 10% without
surge. FIG. 6.5 is a typical partial load performance curve chart for a screw
compressor.
The general compression ratio limit for screw compressor could be as high as 25:1.
However, the compressor efficiency is lower when the compression ratio is higher.
Other technical, application details and special feature for the screw compressor are as
the following:
Economizer:
One of the special features of screw compressor is to allow a side load connection to
the compressor casing; this feature makes economizer cycle possible for the
refrigeration system to improve the system efficiency. The capacity of the screw can
be increased by using the economizer and yet the driving power increase is relatively
small.
There are two types of economizer for the screw compressor; one is Flash
Economizer and the other is the Liquid Subcooling Economizer. The economizer
connection to the compressor casing is located by the compressor maker for the
optimum pressure for the economizer. The benefit of economizing is better when the
compression ratio of the compressor is higher.
FIG. 6.6 shows the flash type economizer using a vertical type flash intercooler which
is controlled by a liquid level valve. The flash gas returns to the side connection of the
compressor. The FIG. 6.7 is also a flash intercooler, but it is with a high pressure float
valve, the intercooling vessel serves as the combination of economizer and receiver.
The P-H diagram is the same for both flash economizing and is shown in FIG.. 6.8.
At the top of the FIG. 6.8 shown the compression cycle without economizer; where
the Refrigeration Effect δH is small. The Refrigeration Effect δH is greatly
increased when economizer is used.
- 64 -
TYPICAL PART LOAD CURVES
R-717 OR R-22
- 65 -
- 66 -
- 67 -
Liquid Subcooling Type Economizer:
FIG. 6.9 shows the Shell-and-Coil type economizer in a vertical type intercooler
which is controlled by a liquid level valve. The flash gas is returned to the side
connection of the compressor. The FIG. 6.10 shown is a DX type liquid subcooling
economizer. The P-H diagram for these two liquid subcooling (FIG. 6.9 and FIG. 6.10)
is the same and it is shown in FIG. 6.11.
For the comparison, the P-H diagram shown at the top of the FIG. 6.11 is the
compression cycle without economizer; the Refrigeration Effect δH is small. The
Refrigeration Effect δH is greatly increased when liquid subcooling economizer is
used.
Oil Pump:
The purpose of using oil pump is to supply oil injection for the rotors and shaft seal,
to cool the compressor, to lubricate the bearings and for the hydraulic operator.
There are three types of compressor design when comes to the use of oil pump:
1) Some compressor design needs full time oil pump for the compressor operation.
2) Some compressor design only requires the oil pump to be operated for the
start-up and shut-down. This type of oil pump is the auxiliary oil pump. The oil
pump is not in operation after the compressor starts up.
3) Some compressor design can start up the compressor without the auxiliary oil
pump and is able to utilize the system pressure differential from the oil reservoir
to other parts of the compressor for the positive oil flow; no oil pump at all.
Oil pump is usually required if the system pressure differential is too small or when
the compressor is used for booster duty or low stage application.
Oil Separator:
Oil injects into the screw compressor to lubricate the rotating parts and to cool the
compressor. The oil absorbs a lot of heat; the oil vapor is mixed with the refrigerant
gas when leave the compressor. The oil is to be removed as much as possible through
an oil separator-filter before it goes to condenser and evaporator.
The oil separator is a standard component for the screw compressor for industrial
refrigeration application. FIG. 6.12 is a typical three-stage oil separator structure for
the screw compressor. The oil separator also serves as the oil reservoir. Most the oil
separators of modern design screw compressors are equipped with Coalescent Filters
inside of the oil separator for better oil separation efficiency. The oil carry over rate
could be 3 PPM to 10 PPM depending on the operating conditions if Coalescent Filter
is used.
Most Standard Units supplied by the manufacturers are with a horizontal oil separator
as shown in FIG. 6.13. Vertical oil separator with floor mounted compressor might be
required as special arrangement if the driving motor is too heavy or a special driver
such gas engine, steam turbine or gas turbine is being used.
- 68 -
- 69 -
- 70 -
- 71 -
Oil Cooling & Oil Cooler:
The oil temperature in the oil separator is relatively high and therefore, it is to be
cooled down by oil cooler (except the liquid injection oil cooling) to an acceptable
temperature level before it is re-injected back to the compressor. There are several
types of oil cooling methods available:
Oil is cooled by water through a shell-and-tube heat exchanger as shown in FIG. 6.14.
FIG. 6.15 shows the relative position between the oil cooler and the oil circuit of the
screw compressor.
The major disadvantage of using water cooled oil cooler is that maintenance and
service are required for the heat exchanger because of water problem. The big
advantage is that a portion of the total heat rejection from the compressor is removed
by water from the oil cooler to the cooling tower. The condenser heat rejection load is
therefore smaller (see Heat Rejection for Condenser Selection).
Liquid injection oil cooling is that a small amount of refrigerant liquid from high
pressure receiver is injected into the screw compressor just before the discharge port
of the compressor. The liquid refrigerant evaporated and the mixture of the oil and the
refrigerant vapor is cooled down to an acceptable temperature. This type of
arrangement is shown in FIG. 6.16. The amount of liquid to be injected is control by a
thermostatic expansion valve. The FIG. 6.17 shows the typical arrangement of a screw
compressor with liquid injection oil cooling.
The advantage of using liquid injection oil cooling is low cost and very little
maintenance is required. The disadvantages are capacity and power consumption
penalties. It is generally about 7 to 9% in capacity reduction and also resulting in high
power consumption rate. Sometimes, the liquid injection method might not be feasible
for low head or high suction temperature applications.
Thermosyphone oil cooling is the method using refrigerant to cool the oil, but without
penalizing the capacity or power consumption of the compressor.
FIG. 6.18 is the typical thermosyphone oil cooler arrangement. The thermosyphone oil
cooler is a shell-and-tube heat exchanger. The oil flow through the shell side and
refrigerant is through the tube side. The refrigerant liquid is supplied to the
thermosyphone oil cooler from the thermosyphone receiver by gravity force. Portion
of the liquid is vaporized to cool the oil in the heat exchanger; the bubbling mixture of
liquid/vapor is circulated back to the thermosyphone receiver. The oil temperature
returning to the compressor is regulated by a three-way thermostatic valve as
indicated.
- 72 -
- 73 -
- 74 -
- 75 -
Dual Oil Coolers and Dual Oil Filters:
A lot of oil is circulated for the screw compressor. Oil flow is considered as the blood
line for the screw compressor operation. For industrial process refrigeration
application, the compressor is required to operate year round without being shut down.
If it is the case, some of the users request that compressor unit is to be fitted with dual
oil filters with a change over valve; this arrangement allows the switching of the oil
flow to the stand-by filter while the other filter is being service and cleaned. Dual oil
coolers with a change over valve also might be requested by the user for the same
reason if water cooled oil cooler is used.
When the refrigerant gas is compressed by the screw compressor, the gas pressure is
increased while its volume is reduced. The internal compression ratio which occurs in
the compressor prior to discharge and the discharge pressure of the compressor are
governed by the location of the discharge port. For a fixed Vi design compressor, the
length of the sliding vane is fixed and the discharge port is tailored at the time when the
compressor is manufactured.
The fixed (or the built-in) pressure ratio of the screw compressor is presented by the
formulas as the following:
Pd
Pi = -------------------------- (1)
Ps
- 76 -
- 77 -
- 78 -
The term of "Built-in Volume Ratio (Vi)" is more frequently used than the built-in
pressure ratio for the screw compressor. The Vi is defined as the following:
Vd
Vi = - ---------------------------------- (2)
Vs
From the Gas Law of thermodynamic, the built-in volume ratio is related to the built-in
pressure ratio as the following:
P x V k = Constant
or
Therefore:
P2 (V1) k
= --------------------------- (5)
P1 (V2) k
Pd (Vs) k
= -- -------------------- (6)
Ps (Vd) k
k
Pd Vs
= ---- -------------------------------- (7)
Ps Vd
Pd
= Vi k ----------------------------------- (8)
Ps
- 79 -
The selection of the size (length) of slide vane is in accordance with the design
compression ratio for the compressor. See FIG. 6.21, a shorter slide vane is selected if the
design compression ratio is small (low Vi), otherwise, a longer slide vane will be
selected if the compression head is high (high Vi). The Vi is fixed once the length of the
slide vane is selected for the compressor. The slide vane is selected at the time when the
compressor is made in accordance with the design compression ratio.
The Vi becomes a constant once the slide vane length is given, this is referred to as a fix
Vi. From the formula (9), the characteristics of the screw compressor with this fixed Vi
are as the following:
(a) The discharge pressure of the compressor is always constant if the suction
pressure is controlled at the set point for the refrigeration system.
(b) The internal compression ratio of the screw compressor is always constant no
matter how the external system pressure ratio changes. The internal pressure
ratio of the compressor will not be able to match the external pressure ratio of
the refrigeration system.
(c) The screw compressor internal discharge pressure is not changed in despite of
the pressure change in the condenser.
Both the adiabatic efficiency and the volumetric efficiency are fixed when the
compressor is given a fixed Vi. A screw maker usually provides several sizes of slide
vane available for the selection. For example, the sizes of slide vane to represent Vi of
2.33, 3.0, 3.6 and 4.6 are shown in FIG. 6.22. As indicated earlier, a low compression
ratio uses a shorter sliding vane which is having a lower Vi and high compression ratio is
logically to choose a longer sliding vane which is having a high Vi for better power
consumption. Once a screw compressor is supplied with a specific built-in Vi, this Vi
slide vane cannot be altered because it is determined by the geometrical shapes of the
axial and radial outlet ports.
Once the compressor is supplied with a fixed Vi, for example Vi = 3.0, the compressor
characteristic curve is fixed and the efficiency curve is following the curve "B" of the
FIG. 6.22. The peak optimum efficiency of a screw compressor having Vi of 3.0 is at the
compression ratio of 3.2. The compressor can be operated at any other compression ratio.
However, the compressor shall operate at lower efficiency with higher power
consumption.
- 80 -
- 81 -
- 82 -
- 83 -
A hydraulic controllers “A” and “B” are used to control the slide valve and slide stop
separately as shown in FIG. 6.23(C). This allows the compressor Vi to be adjusted during
operation and matching the compression discharge pressure precisely as required for the
refrigeration system. The stepless control is automatically controlled by the
microprocessor control panel for all the operational range and conditions. Thus, the
maximum peak volumetric and adiabatic efficiencies of the compressor are maintained
over all the operational ranges. Therefore, the efficiency curve of a variable Vi
compressor is the line of (X)-(Y), which is at the top of the peak efficiencies of all fixed
Vi curves as shown in FIG. 6.24. The power consumption of a variable Vi compressor is
the best at all the partial load conditions. A variable Vi compressor is able to take the
advantages of both reduce capacity and reduce head during any partial load operation;
also the percent of partial load efficiency is actually increased. There, the annual power
consumption evaluation is improved in accordance with the formula shown in FIG. 4-4.
Control Panel:
Most standard unit is with a computer type microprocessor control panel with display
and keyboard. It provides automatic control for the continuous operation of the unit or
even the refrigeration system; to control slide vane to maintain suction pressure or
temperature at a set point; to control the variable Vi for the maximum efficiency. The
control panel also can provide self-diagnoses and self-check constantly and continuously
against the pre-set safety operation set points of the unit. The control penal can
communicate with a building automation system. Most panels are with NEMA-1
enclosure as standard from most makers in the world. But, it can be specially modified to
suit any electrical code requirement.
- 84 -
- 85 -