Welcome to choose Automatic Tank Gauging (ATG) System of Windbell Company. You are strongly
The installation and maintenance of the products must be done by the qualified technicians.
Safety Instruction
The ATG system is installed in gas station and oil depot, please read safety instructions for
explosion protection.
The products are prohibited to be installed in explosion proof area over its own Ex-proof grade.
The console and printer must be installed in safe area, such as office.
Safety Warning
The tank must have earth busbar, and the earth must be safe and reliable.
Please check all the materials according to the list. If anything missed, please contact the local
representative or distributor directly. You can also find the contact information of Windbell in this
manual.
Warranty Card
After installation, please send the filled Warranty card to Service Department of Windbell by email
In the constant effort to improve our product, we reserve the right to make construction or design
1. Summary
This automatic tank gauging system is mainly consists of smart console and magnetostrictive probe.
It can monitor oil product level, water level and temperature in real time; and display inventory data,
alarm information and leak detection information; and automatically generate history report for future
inquiry.
International graphic touch screen and user-friendly icon, makes it is easy for new user.
Smart console (please see below) is a powerful operation platform, the data processing and record
center, can communicate with probe by RS485, and also offer safety and reliable power to probe.
It consists of TFT colorful touch screen, core processing CPU, safety barriers and power module.
Display and operating screen is 8’’ size, 800*600 resolutions. The CPU which composed of the
advanced embedded processor and peripheral circuit is the control center of the whole tank gauge
system. The safety barrier is intrinsic safe parts, offer safety power to probe.
1
SS160Plus Smart Console User Manual
System Features
International graphic touch screen.
Real time monitoring oil product level, water level,
density, volume and temperature.
Monitor up to 12 tanks at one compact unit
(Standard monitor 6 tanks).
Automatic alarm and release alarm.
Automatically generate delivery report, inventory
report, alarm report and leak detection report.
Automatically generate tank volume chart.
Support TCP/IP.
Support programmable leak detection test PLD.
Support external GSM message module ( Option).
Support import & export tank volume chart, very
convenient.
Security password for authorization.
Language optional among English (default),
Spanish, Portuguese.
Support connect to Submersible Pump Console
SS160-EM02.
Open communication protocol, can connect to the
central control system of mainstream fuel
dispensers, totally satisfy management demand of
oil retail companies.
2
SS160Plus Smart Console User Manual
2. Installation
Safety warning
3
SS160Plus Smart Console User Manual
2.2 Electrical Wiring Diagram of ATG System
The cable from probe must be correctly connect to relevant safety barrier inside console. The shielding
of cable must connect to PE of safety barrier. The safety barrier also must connect to grounding
reliably. As fig. below:
Safety Warning
Grounding terminal of safety barrier should connect to ground reliably by more than 6
mm²multi-core copper cable.
4
SS160Plus Smart Console User Manual
When console need to be connected with PC management system and printer, please take out PC line
and printer line (which both RS232 serial lines) from console packing box, plug them into relevant
port.
Safety Warning
After installation, check carefully whether each part is normal. If ok, power on the complete system.
Name Qty
Power cable 1
Communication
2
cable RS232
Fixed plate 1
Expansion bolt 4
PG9 6
Spare fuse 1
Keys 2
Spare Battery 1
5
SS160Plus Smart Console User Manual
3. Operation
Monitoring Screen (Home page)
After power on, the system will automatically access to the monitoring interface.
① If initialized operation, the tank information is blank, please click “Setup” button to set up
System (detail operation please see relevant introduction). At first login, no need password,
please double click OK button to enter into Setup screen.
② If need inquire detail information of each tank, please directly click the graphic of tank.
If there is no operation on screen for about 5 minutes, console will automatically switch to the screen
saver. That time, the screen is black, but program is still working continuously. The screen will light
again if touched.
Probe ID = Manufacturing code of probe
P = Product level (Fuel level)
W = Water level
T = Average temperature, take from 5 sensors
V = Volume in stock, default including water volume
EV = Empty volume
WV = Water volume
V20 = Compensation volume at standard 20℃
D = Density
T1……T5 = Temperature sensor 1….5
6
SS160Plus Smart Console User Manual
3.1 Alarm
When alarm beep, for example, Water high (W H), Product low low(P LL), Product
low (P L), Product high (P H), Product high high (P HH), Temperature high (T H),
Temperature low (T L), click this to release alarm, then beep stop.
3.2 Printer
Click this button at homepage, will print the current data of available tanks
3.3 Setup
When need to set up system information or amend configuration, please click this
button.
3.4 Shift
Click this button when shift, there will show a dialog box “Shift Confirm”, choose”
Yes” to confirm shift, system will create a shift report automatically.
There are 4 tanks information displayed on screen, if inquire tanks information more
than 4, like tank 5 an 6, just click this button to view.
3.6 Reports
When need to inquire reports information, click this button to enter into report page,
When need to inquire if there is any leakage of tank, click this button to see leak
detection screen.
7
SS160Plus Smart Console User Manual
4. System Setup
4.1 System Setting Interface
Introduction
Input company code
Note: the company code and petrol station serial code are used for transmit data to head-office
software.
8
SS160Plus Smart Console User Manual
Introduction
Click to choose oil name
9
SS160Plus Smart Console User Manual
Introduction
Status: Choose “Valid” or “Invalid”, to enable or disable a tank.
Auto leak: Choose “Yes” or “No” to start or stop automatic leak detection function.
Leak time: Input the starting time of automatic leak detection test.
Water flag: Choose “Included” or not at Water Flag which mean cross volume include water or
not.
Note:
Please do not forget to click “save” button after setup.
When you want to delete one tank, firstly click tank at left table, and then click “Delete”.
Click to setup probe ID, alarm values, oil offset and water offset.
10
SS160Plus Smart Console User Manual
Introduction
Input tank serial number, please refer to the tank setup.
OHH alarm indicates that the oil product is likely to overfill, stop filling now.
OH alarm indicates that the oil product level high, keep your eyes on filling.
OL alarm indicates that the fuel is not enough, please make purchase order.
OLL alarm indicates that nearly no fuel inside this tank, need to close this tank now.
WHH alarm indicates that too much water inside tank, need to remove water out.
Input probe ID, please ensure the right ID, each probe have the sole ID which same as the
If need to calibrate oil level and water level, please measure the oil level and water level by dip
stick, input the measured value in O value and W value, console program will automatically
calculate the result and display on O offset and W offset. Please note that all the unit is mm.
Note:
Please do not forget to save above information after input.
If you want to delete one of the probes, click the relevant tank at left table, click “Delete” button
is ok.
Click to input tank volume table or input tank data to generate a new table.
volume table Up and Down. Click delete if need to delete this table.
If you want to amend one point of tank table, choose this point data at table, input new value,
click “Update” to save the new data, click “Delete” to delete this point data.
If tanks in petrol station have same specification, input one tank table, click “Copy to” and choose the
desired tank number, then click “save” button. That way, you can easily and fast input another one tank
volume table.
11
SS160Plus Smart Console User Manual
Click the table, choose one line, and then input the height and relevant volume data.
After input all the data, click “Save” to save tank volume table. See the picture below.
Click “Gen” button to calculate and simulate the whole tank size, and automatically generate a
new tank volume table. When the operation is finished, please click the “save” button.
12
SS160Plus Smart Console User Manual
Choose the tank in Tank No. item, click “Search” to display this tank’s volume table. Insert Flash
Click “Import” button to import tank volume table from flash disk to console.
Click “Export” button to download the tank volume table from console to flash disk.
13
SS160Plus Smart Console User Manual
Click “Tank No.” to choose relevant tank, click “Start” button to check thecommunication. If
probe data displayed on the left table, it means the communication is OK.
Connect to one probe, and click “Get ID” button, then Probe ID of this probe will be displayed on
screen.
Set password
Choose different authorization for different users, and click “save” button after setup.
14
SS160Plus Smart Console User Manual
General interface:
“Printer Setup”.
default is “General”.
data by network.
15
SS160Plus Smart Console User Manual
Copy the latest version and save at the root directory of flash disk, insert flash disk in USB port
Click “Update” to start, When the progress bar show 100%, the update is finished.
16
SS160Plus Smart Console User Manual
Insert flash disk in USB port, click “ Import Setup” will import the console configuration from
flash disk to console; click “Export Setup” will export console configuration into flash disk.
Insert flash disk in USB port, click “Backup Setup” to back up console data into flash disk; click
Click “Calibration Screen”, and then restart console. When the console work again, will
automatically start screen calibration progress, please click the 5 calibration points at screen as
Insert flash disk in USB port, Click “Update Language” can change operating language.
Click “Clear Report” to clear the reports you want to delete, see this picture below.
Input password, this password is for starting console, screen saver and reports inquiry.
Choose “Yes” at “Boot Password”, it means user should input this password when starting console.
Choose “Yes” at “Screen Protection Password”, it means user should input this password to stop
Choose “Yes” at “View Report Password”, it means user should input this password to search
reports.
17
SS160Plus Smart Console User Manual
Input the right value of current time at Year, Month, Date, Hour, Minute, Second, and click “Save”
18
SS160Plus Smart Console User Manual
4.14 GSM Setup (Optional)
Input mobile phone number of the receiver at Phone, can input 2 different mobile phone numbers,
Center number is the message center number. Eg: In china, the country code is 86, and the
message center number at Zhengzhou city of China Mobile (one of the Mobile operator in China)
If you want receive a message when there is an alarm of tank, or a delivery of tank, or a shift at
19
SS160Plus Smart Console User Manual
Measure range of density floater:
Gasoline: 0.70 ~ 0.74; 0.74 ~ 0.78(g/cm3); Diesel: 0.80 ~ 0.84; 0.84 ~ 0.89 (g/cm3)
Measure liquid density by density gauge, record the result 0.7405g/cm3. Put probe into this liquid,
click button “Get Height”, system will automatically calculate the height balance between density
floater and oil floater, and display the balance value at” 1st Diff H”.
Input the density value measured by density gauge 0.7405g/cm3 in“1st Density”.
Click “Save” button to store the above configuration.
Put probe into another liquid, measure liquid density by density gauge, the result is 0.775g/cm3,
input the density value 0.775 g/cm3 in “2nd Density”
Click ”Calculate” to calculate density coefficient, the result will be displayed at “Correction
factor”
When setup is finished, put probe into oil tank, system will automatically start to measure the current
density of oil, please see home page, “D” is Density.
Note:
Customer should offer the density range of measured liquid when order. The correction coefficient of
density will preset before delivery out of factory, users can install probe and start use directly.
If the density of liquid has changed, and is different with the original density offered to manufacturer,
And if the density measured by ATG is different from the density value measured by density gauge,
20
SS160Plus Smart Console User Manual
21
SS160Plus Smart Console User Manual
5.System Reports
Input the start date and end date to set a search scope, then system will show you the result soon.
Value means the oil product level when alarm was activated.