TEST REPORT: 7191034331-CHM12-04-TSL: Subject
TEST REPORT: 7191034331-CHM12-04-TSL: Subject
TEST REPORT: 7191034331-CHM12-04-TSL: Subject
SUBJECT
CLIENT
30 May 2012
DESCRIPTION OF SAMPLE
DATE OF ANALYSIS
METHOD OF TEST
The test was conducted according to BS 6853:1999 Annex B, B.1 Mass Based Test Method –
NF X 70-100 (2006) Method:
Approximately 0.5 g of the sample was then used for the test in a stream of air at the air flow
rate of 120L/hr at 600oC for 20minutes in a tube furnace. A further 20minutes was used to
air-flush the apparatus once residue sample was removed from tube furnace.
Toxic fumes collected during the burning were analysed by the following methods:
a) Carbon Monoxide and Carbon Dioxide : Directly determined by Horiba Automotive Emission
Analyzer
b) Hydrogen Cyanide : By Pyridine – Pyrazalone Method
c) Others ions : By Ion Chromatography
RESULTS:
Table 1: The Toxic Fumes Results For “FiresafeTM Isophenic Foam” Sample
“FiresafeTM Isophenic Foam” IDLH Values
Toxic Fumes Generated Limits a
(mg/m3 of Fire Effluents)
(mg/m3)
1. Carbon Dioxide, Average <200 73000
(Carbon Dioxide, maximum) <200 -
Page 2 of 4
TEST REPORT: 7191034331-CHM12-04-TSL
07 JUN 2012
RESULTS (Cont’d)
1. The above results from the analysis of the toxic fumes generated from the specimen were found to
be below the IDLH Value of listed gases.
Remarks
The weighted summation index R for the sample tested was found to be within the requirement of 1.0
max when tested and assessed according to NF X 70-100 with R calculated in accordance with Annex
B of BS 6853:1999.
Page 3 of 4
TEST REPORT: 7191034331-CHM12-04-TSL
07 JUN 2012
Please note that this Report is issued under the following terms :
1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.
2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no
responsibility for the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information
supplied.
3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.
4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or results
furnished by TÜV SÜD PSB in any advertisements or sales promotion.
5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.
July 2011
Page 4 of 4