TEST REPORT: 7191034331-CHM12-04-TSL: Subject

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

TEST REPORT: 7191034331-CHM12-04-TSL

Date: 07 JUN 2012 Tel: +65 68851335 Fax: +65 67784301

Client’s Ref: Email: [email protected]


Note: This report is issued subject to the Testing and Certification Regulations of the TÜV SÜD Group and the General
Terms and Conditions of Business of TÜV SÜD PSB Pte Ltd. In addition, this report is governed by the terms set out
within this report.

SUBJECT

Evaluation of Toxic Fumes Generated From Material Sample During Burning

CLIENT

Izopoli Yapi Elemanlari Taahhut Sanayi ve Ticaret A.S.


Ciragan Caddesi No 97,
34347 Ortakoy
Istanbul, Turkey

Attn : Mr Emre Erhan Karabiyik

SAMPLE SUBMISSION DATE

30 May 2012

DESCRIPTION OF SAMPLE

A packet of foam sample labelled as follows was received.

1. Brand Name / Model Name : FireSafe TM


Type of Material : Isophenic foam

DATE OF ANALYSIS

01 Jun 2012 – 07 Jun 2012

METHOD OF TEST

1. Analysis of Pyrolysis and Combustion Gases Generated From the Sample

The test was conducted according to BS 6853:1999 Annex B, B.1 Mass Based Test Method –
NF X 70-100 (2006) Method:

1.1 Sample Preparation of Test Specimen


o
The sample was conditioned at 23 C and 50% Relative Humidity for 48hours and tested as
whole for the following tests.

Laboratory: Phone : +65-6885 1333 Regional Head Office:


TÜV SÜD PSB Pte. Ltd. Fax : +65-6776 8670 TÜV SÜD Asia Pacific Pte. Ltd.
No.1 Science Park Drive E-mail: [email protected] 3 Science Park Drive, #04-01/05
Singapore 118221 www.tuv-sud-psb.sg The Franklin, Singapore 118223
Co. Reg : 199002667R Page 1 of 4
TEST REPORT: 7191034331-CHM12-04-TSL
07 JUN 2012

METHOD OF TEST (Cont’d)

1.2 Generation of Pyrolysis and Combustion Gases

Approximately 0.5 g of the sample was then used for the test in a stream of air at the air flow
rate of 120L/hr at 600oC for 20minutes in a tube furnace. A further 20minutes was used to
air-flush the apparatus once residue sample was removed from tube furnace.

Toxic fumes collected during the burning were analysed by the following methods:
a) Carbon Monoxide and Carbon Dioxide : Directly determined by Horiba Automotive Emission
Analyzer
b) Hydrogen Cyanide : By Pyridine – Pyrazalone Method
c) Others ions : By Ion Chromatography

RESULTS:

Table 1: The Toxic Fumes Results For “FiresafeTM Isophenic Foam” Sample
“FiresafeTM Isophenic Foam” IDLH Values
Toxic Fumes Generated Limits a
(mg/m3 of Fire Effluents)
(mg/m3)
1. Carbon Dioxide, Average <200 73000
(Carbon Dioxide, maximum) <200 -

2. Carbon Monoxide, Average <200 1400


(Carbon Monoxide, maximum) <200 -

3. Hydrogen Fluoride. HF <5 25

4. Hydrogen Chloride, HCl <5 76

5. Hydrogen Bromide, HBr <5 101


b
6. Sulfur Dioxide, SO2 <5 270
c
7. Nitrogen Dioxide, NO2 <5 38

8. Hydrogen Cyanide, HCN <5 56


a
The values in Table 1 are the IDLH values of the listed gases (the concentration of the gas in the atmosphere which
for an exposure time of 30mins is immediately Dangerous to Life or Health) given in the NIOSH Guide [1].
b
Sulfur Dioxide includes Sulfur trioxide expressed as sulfur dioxide
c
Nitrogen dioxide includes nitric oxide expressed as nitrogen dioxide

Page 2 of 4
TEST REPORT: 7191034331-CHM12-04-TSL
07 JUN 2012

RESULTS (Cont’d)

1. The above results from the analysis of the toxic fumes generated from the specimen were found to
be below the IDLH Value of listed gases.

2. The weighted summation index, R, is less than 0.3.

Remarks
The weighted summation index R for the sample tested was found to be within the requirement of 1.0
max when tested and assessed according to NF X 70-100 with R calculated in accordance with Annex
B of BS 6853:1999.

MS TAN SER LING for DR LI SIHAI


TECHNICAL EXECUTIVE AVP / SENIOR CHEMIST
MICROCONTAMINATION DIAGNOSIS
CHEMICAL & MATERIALS

Page 3 of 4
TEST REPORT: 7191034331-CHM12-04-TSL
07 JUN 2012

Please note that this Report is issued under the following terms :

1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.

2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no
responsibility for the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information
supplied.

3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.

4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or results
furnished by TÜV SÜD PSB in any advertisements or sales promotion.

5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.

July 2011

Page 4 of 4