Easy UPS 3S User
Easy UPS 3S User
10–40 kVA
Operation
12/2017
www.schneider-electric.com
www.totalpowersolutions.ie
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
10–40 kVA
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Overview ......................................................................................................7
User Interface ............................................................................................7
Display Interface ...................................................................................9
Overview of Breakers in a Single UPS..........................................................9
Overview of Breakers in a Parallel System.................................................. 11
Operation Modes ......................................................................................12
Operation Procedures ..............................................................................16
Start Up a Single UPS in Normal Mode ......................................................16
Transfer a Single UPS from Normal Mode to Static Bypass Mode.................18
Transfer a Single UPS from Static Bypass Mode to Normal Mode.................18
Transfer a Single UPS from Normal Mode to Maintenance Bypass
Mode .......................................................................................................18
Transfer a Single UPS from Maintenance Bypass Mode to Normal
Mode .......................................................................................................20
Transfer a Parallel System from Normal Mode to Maintenance Bypass
Mode .......................................................................................................22
Transfer a Parallel System from Maintenance Bypass Mode to Normal
Mode .......................................................................................................23
Isolate a Single UPS from the Parallel System ............................................23
Start Up and Add a UPS to a Running Parallel System ................................24
Configuration .............................................................................................26
Register Your Easy UPS 3S ......................................................................26
Set the Display Language .........................................................................26
Set the Date and Time ..............................................................................27
Set the UPS Settings ................................................................................27
Set the Battery Settings.............................................................................28
Set the Life Cycle Monitoring .....................................................................28
Settings ...................................................................................................29
Tests............................................................................................................31
Perform a Battery Maintenance Test ..........................................................31
Perform a Battery Test ..............................................................................31
Maintenance ..............................................................................................32
Parts Replacement ...................................................................................32
Determine if you need a Replacement Part ...........................................32
Replace the Dust Filter..............................................................................32
Troubleshooting ........................................................................................34
View the Active Alarms..............................................................................34
Status and Alarm Messages ......................................................................34
990–91079-001 3
Important Safety Instructions — SAVE THESE
INSTRUCTIONS 10–40 kVA
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990–91079-001 5
Important Safety Instructions — SAVE THESE
10–40 kVA INSTRUCTIONS
Electromagnetic Compatibility
NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category C3 according to IEC 62040-2. This is a product for
commercial and industrial applications in the second environment - installation
restrictions or additional measures may be needed to prevent disturbances. The
second environment includes all commercial, light industry, and industrial
locations other than residential, commercial, and light industrial premises directly
connected without intermediate transformer to a public low-voltage mains
supply. The installation and cabling must follow the electromagnetic compatibility
rules, e.g.:
• the segregation of cables,
• the use of shielded or special cables when relevant,
• the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.
Safety Precautions
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by a Schneider Electric certified
engineer/partner.
Failure to follow these instructions will result in death or serious injury.
6 990–91079-001
Overview 10–40 kVA
Overview
User Interface
Keys
EPO
Only use the EPO button in case of emergency. When the EPO button is pushed,
the system turns off the rectifier and the inverter, and stops supplying the load
immediately.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS control circuit will remain active after the EPO has been pushed if
mains is available.
Failure to follow these instructions will result in death or serious injury.
990–91079-001 7
10–40 kVA Overview
Status LEDs
LED Status
A Rectifier Green : Rectifier is working correctly.
Flashing green : Rectifier is working correctly and mains is normal.
Red : Rectifier is inoperable.
Flashing red : Mains is unavailable.
OFF : Rectifier is off.
B Battery Green : Battery is charging.
Flashing green : Battery is discharging.
Red : Battery is inoperable.
Flashing red : Battery low voltage.
OFF : Battery and battery charger are normal, battery is not charging.
C Bypass Green : Load supplied by bypass source.
Red : Bypass source is unavailable or static bypass switch is inoperable.
Flashing red : Bypass voltage is out of tolerance.
OFF : Bypass source is normal.
D Inverter Green : Load supplied by inverter.
Flashing green : Inverter on, start, synchronization or standby (ECO mode) for at least
one module.
Red : Load not supplied by inverter, inverter is inoperable.
Flashing red : Load supplied by inverter, but an inverter alarm is present.
OFF : Inverter is off.
E Load Green : UPS output is on.
Red : Overload on UPS output for too long, or output has shorted, or no output power
present.
Flashing red : Overload on UPS output.
OFF : UPS output is off.
F Status Green : Normal mode.
Red : Inoperable status.
8 990–91079-001
Overview 10–40 kVA
Display Interface
Home Screen
Buttons
Power On/ Input and Output Battery UPS status Function Log Mute
Off bypass status status settings
status information information
information
BB Battery breaker
990–91079-001 9
10–40 kVA Overview
Rear View of the 20–30 kVA UPS Rear View of the 40 kVA UPS
10 990–91079-001
Overview 10–40 kVA
BB Battery breaker
990–91079-001 11
10–40 kVA Operation Modes
Operation Modes
Normal Mode
The UPS provides power to the connected load from mains. The UPS converts
mains to conditioned power for the connected load while recharging the batteries
(float or boost charge).
Battery Mode
The UPS transfers to battery mode if the mains supply fails. The UPS provides
power to the connected load from the connected batteries for a finite period. When
the mains supply returns, the UPS transfers back to normal mode.
12 990–91079-001
Operation Modes 10–40 kVA
ECO Mode
In ECO mode the UPS is configured to use static bypass mode as the preferred
operation mode under predefined circumstances. The inverter is in standby in ECO
mode and in case of interruption to the mains, the UPS transfers to battery mode
and the load is supplied from the inverter.
990–91079-001 13
10–40 kVA Operation Modes
Auto-Restart Mode
The batteries will reach end of discharge if the interruption to the mains is longer
than the battery runtime. If the UPS is programmed to auto-restart after end of
discharge, the system will automatically restart after a delay when the mains
returns.
NOTICE
RISK OF EQUIPMENT DAMAGE OR LOAD DROP
In frequency converter mode the UPS cannot run in static bypass or
maintenance bypass mode. Before turning the UPS into frequency converter
mode, you must contact a Schneider Electric-certified partner to make sure
• the static switch input breaker SSIB and the maintenance bypass breaker
MBB are in the OFF (opened) position (Schneider Electric strongly
recommends to lock these with a padlock available from Schneider Electric)
• the cables are disconnected according to the instructions in the installation
manual
Failure to follow these instructions can result in equipment damage.
NOTICE
RISK OF LOAD DROP
When the unit output breaker UOB is opened while the UPS is in frequency
converter mode, the load will not be transferred, but will be dropped.
Failure to follow these instructions can result in equipment damage.
14 990–91079-001
Operation Modes 10–40 kVA
990–91079-001 15
10–40 kVA Operation Procedures
Operation Procedures
Start Up a Single UPS in Normal Mode
NOTE: When the UPS starts, the stored settings will be used.
NOTE: The log can be accessed during start-up.
16 990–91079-001
Operation Procedures 10–40 kVA
5. When the rectifier LED turns steady green, the inverter synchronizes with
bypass.
The LEDs on the user interface show as follows:
6. When the inverter LED turns steady green, the UPS transfers automatically
from static bypass mode to normal mode.
The LEDs on the user interface show as follows:
990–91079-001 17
10–40 kVA Operation Procedures
18 990–91079-001
Operation Procedures 10–40 kVA
Rear View of the 20–30 kVA UPS Rear View of the 40 kVA UPS
990–91079-001 19
10–40 kVA Operation Procedures
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Wait at least 5 minutes before removing the cover of the UPS after the
display has turned off to allow for the capacitors to fully discharged.
• Always measure for hazardous voltages on all terminals before working
on the UPS.
Failure to follow these instructions will result in death or serious
injury.
20 990–91079-001
Operation Procedures 10–40 kVA
Rear View of the 20–30 kVA UPS Rear View of the 40 kVA UPS
990–91079-001 21
10–40 kVA Operation Procedures
8. On the display select and then select Function > Clear alarm.
NOTE: The system will not transfer to normal mode before the
maintenance bypass cover has been reinstalled and the alarm has been
cleared.
9. After approximately 60 seconds, the UPS will automatically transfer to normal
mode.
The LEDs on the user interface show as follows:
1. On all UPS displays, select and then select Function > To bypass.
The parallel system will transfer to static bypass mode.
2. Turn the external maintenance bypass breaker Ext. MBB to the ON (closed)
position.
The load is now supplied via the external maintenance bypass breaker.
3. Turn the battery breakers BB of all UPSs to the OFF (open) position.
4. Turn the mains input breakers MIB and the bypass input breakers BIB of all
UPSs to the OFF (open) position.
5. Turn the system isolation breaker SIB to OFF (open) position.
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Wait at least 5 minutes before removing the cover of the UPS after the
display has turned off to allow for the capacitors to fully discharged.
• Always measure for hazardous voltages on all terminals before working
on the UPS.
Failure to follow these instructions will result in death or serious
injury.
22 990–91079-001
Operation Procedures 10–40 kVA
and then select Function > Clear alarm on all UPS displays.
5. Turn the mains input breakers MIB of all UPSs to the ON (closed) position.
The rectifier ramps up.
6. When the rectifier LED turns steady green, the inverter synchronizes with
bypass.
7. When the inverter LED turns steady green, the parallel system automatically
transfers from static bypass to normal mode.
8. Turn the battery breakers BB of all UPSs to the ON (closed) position.
The LEDs on the user interfaces show as follows:
1. On the display select and then select confirm to power off the UPS.
2. Turn the battery breaker(s) BB of the UPS to the OFF (open) position.
3. Turn the mains input breaker MIB of the UPS to the OFF (open) position.
990–91079-001 23
10–40 kVA Operation Procedures
4. Turn the bypass input breaker BIB of the UPS to the OFF (open) position.
5. Turn the external unit output breaker Ext. UOB of the UPS to the OFF (open)
position.
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
• Wait at least 5 minutes before removing the cover of the UPS after the
display has turned off to allow for the capacitors to fully discharged.
• Always measure for hazardous voltages on all terminals before working
on the UPS.
Failure to follow these instructions will result in death or serious
injury.
24 990–91079-001
Operation Procedures 10–40 kVA
4. When the rectifier LED turns steady green, the UPS transfers to static bypass
mode.
The LEDs on the user interface show as follows:
5. When the inverter LED turns steady green, the UPS automatically transfers
from static bypass to normal mode and joins the running parallel system.
The LEDs on the user interface show as follows:
990–91079-001 25
10–40 kVA Configuration
Configuration
Register Your Easy UPS 3S
1. When prompted for registration, go to www.schneider-electric.com/
contactsupport to find your local service contact number.
26 990–91079-001
Configuration 10–40 kVA
NOTICE
RISK OF EQUIPMENT DAMAGE
Only trained personnel following the required training course may undertake
modifications to UPS system parameters.
Failure to follow these instructions can result in equipment damage.
3. Set the nominal input voltage (phase-neutral), the nominal output voltage
(phase-neutral), and the nominal frequency.
990–91079-001 27
10–40 kVA Configuration
NOTICE
RISK OF EQUIPMENT DAMAGE
Only trained personnel following the required training course may undertake
modifications to UPS system parameters.
Failure to follow these instructions can result in equipment damage.
3. Set the battery number, the battery capacity, and the battery charge
percentage.
NOTICE
RISK OF EQUIPMENT DAMAGE
Only trained personnel following the required training course may undertake
modifications to UPS system parameters.
Failure to follow these instructions can result in equipment damage.
28 990–91079-001
Configuration 10–40 kVA
Settings
Setting Default Value Available Settings
Input frequency 50 Hz 60 Hz
Output frequency 50 Hz 60 Hz
Output phase 3 1
United number 1 1 to 4
System ID 0 0 to 3
990–91079-001 29
10–40 kVA Configuration
System restart mode after end of discharge Normal bypass only/ no output
Battery maintenance period 1440 days (48 months) 100 to 3000 days
Battery AH 20 1 to 30000
Auto boost period 2160 hours (3 months) 720 to 30000 hours, available when auto
boost is enabled
Auto maintenance discharge period 6480 hours (9 months) 720 to 30000 hours, available when auto
maintenance is enabled
Critical battery temperature 45 ℃ 25 ℃ to 70 ℃
30 990–91079-001
Tests 10–40 kVA
Tests
Perform a Battery Maintenance Test
Prerequisite:
• The bypass supply must be within specifications.
• The battery capacity must be above 25%.
The battery maintenance test is used to test the condition of the batteries.
During the battery maintenance test, the system transfers to battery mode and
discharges the batteries until the battery low voltage alarm is reached.
990–91079-001 31
10–40 kVA Maintenance
Maintenance
Parts Replacement
Determine if you need a Replacement Part
To determine if you need a replacement part, contact Schneider Electric and follow
the procedure below so that the representative can assist you promptly:
1. In the event of an alarm condition, scroll through the alarm lists, record the
information, and provide it to the representative.
2. Write down the serial number of the unit so that you will have it easily
accessible when you contact Schneider Electric.
3. If possible, call Schneider Electric from a telephone that is within reach of the
display so that you can gather and report additional information to the
representative.
4. Be prepared to provide a detailed description of the problem. A representative
will help you solve the problem over the telephone, if possible, or will assign a
return material authorization (RMA) number to you. If a module is returned to
Schneider Electric, this RMA number must be clearly printed on the outside of
the package.
5. If the unit is within the warranty period and has been started up by Schneider
Electric, repairs or replacements will be performed free of charge. If it is not
within the warranty period, there will be a charge.
6. If the unit is covered by a Schneider Electric service contract, have the
contract available to provide information to the representative.
32 990–91079-001
Maintenance 10–40 kVA
990–91079-001 33
10–40 kVA Troubleshooting
Troubleshooting
View the Active Alarms
Buzzer
NOTE: The buzzer turns on as soon as an alarm condition is detected. The
buzzer makes two short beeps and a long beep for general system alarms. The
buzzer makes a continuous beep for critical alarms. It can be turned off by
34 990–91079-001
Troubleshooting 10–40 kVA
990–91079-001 35
10–40 kVA Troubleshooting
36 990–91079-001
Troubleshooting 10–40 kVA
990–91079-001 37
10–40 kVA Troubleshooting
38 990–91079-001
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com