0% found this document useful (0 votes)
170 views9 pages

Huanza Hydropower Project: Static Excitation System Calculation

This document provides calculations for the static excitation system for the Huanza Hydroelectric Project 2x46MW synchronous generators. It includes specifications for the excitation transformer, thyristor converter, field suppression components, field flashing components, excitation cables, and manufacturer information. The calculations determine components can meet the rated power system outputs and conditions under the project's ambient temperature and altitude conditions.

Uploaded by

Rubén Callata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
170 views9 pages

Huanza Hydropower Project: Static Excitation System Calculation

This document provides calculations for the static excitation system for the Huanza Hydroelectric Project 2x46MW synchronous generators. It includes specifications for the excitation transformer, thyristor converter, field suppression components, field flashing components, excitation cables, and manufacturer information. The calculations determine components can meet the rated power system outputs and conditions under the project's ambient temperature and altitude conditions.

Uploaded by

Rubén Callata
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

DETAIL DESIGN REPORT TITLE: NO: HZHPP-R/HDSL-406

Static Excitation System Calculation

OWNER:

HUANZA HYDROPOWER PROJECT

CONTRACTOR

中国上海外经(集团)有限公司
CHINA SHANGHAI (GROUP) CORPORATION FOR FOREIGN
ECONOMIC & TECHNOLOGICAL COOPERATION
DESIGNER

邯郸市水利水电勘测设计研究院
HANDAN INVESTIGATION & DESIGN INSTITUTE OF WATER
CONSERVANCY AND HYDROPOWER
SUBCONTRACTOR

国电南瑞科技股份有限公司
STATE GRID ELECTRIC POWER RESEARCH INSTITUTE
NARI Technology Development Co.,Ltd
REVISION
A
Huanza Hydroelectric Project 2×46MW
STATIC EXCITATION SYSTEM
CALCULATION

NARI Technology Development CO.,Ltd.

April 13, 2011


Huanza Hydroelectric Project 2×46MW

1、 Synchronous machine data:

Rated power PN 47.88 MW

Rated stator voltage UN 13.8 kV

Rated stator current IN 2356.7 A

Rated frequency FN 60 Hz

Rated power factor p.f. 0.85

Rated field current IFN 752 A

Rated field voltage UFN 193 V

No-load field current IFO 420 A

No-load field voltage UFO 73 V

2、 System output ratings and conditions:

Rated system continuous DC


827.2 A
output current

Rated system continuous DC


212.3 V
output voltage

System ceiling current 4000 A

System ceiling application


20 S
time

On load system ceiling voltage 580 V

Ambient temperature 45 °C

Altitude above sea level 3400 M

Type of AC connections Cables

Conductors material of AC Cu

2
Huanza Hydroelectric Project 2×46MW

connections

Type of DC connections Cables

Conductors material of DC
Cu
connections

Security factor for thyristors


2.75
blocking voltage

3、Excitation transformer data:


Excitation transformer supplied from:Supplied from machine terminals

Rated apparent power 550 KVA

Rated primary voltage 13800 V

No-load secondary voltage 460 V

Rated frequency 60 HZ

Excitation transformer calculation:


1) Rated secondary voltage
K uU fn
U2 
3 2
1 cos  min K r

Firing angle  min :=100

U fn
Rated field voltage : =193V

Field voltage multiple K u : = 3


Factor Kr : = 0.95

U2=193×3/1.264=458V (460V)

2)Rated secondary current

2
I2   K i I fn
3

3
Huanza Hydroelectric Project 2×46MW

Rated system continuous factor KI=1.1

I2=0.816×1.1×752=674.9A

3)Rated apparent power


S  3U 2 I 2
1.732×458×674.9=535368.5VA (550kVA )

4、Thyristor converter
Thyristor type 5STP09D2201
Thyristor blocking voltage 2200 V
Thyristor current 862 A
Current sharing factor 0.95
Rated continuous current output (pre-load) 1000 A
Rated ceiling current output (pre-load) 2000A(20S)
Formula:

VRRM、 VDRM≥2.75× 2 ×460V=1788.7V<2200V

2×752/2×0.95=791.6A

1.1×752=827.2A<1000A

2×752=1504A<2000A

5、Non linear field suppression


1)Field breaker
Field breaker type E1N-1000(ABB)
Arcing voltage 1000 V
Rated current 1000 A
Maximum breaking current capacity 20000 A

Formula:

4
Huanza Hydroelectric Project 2×46MW

S
I=
3  U  Uk  0.816

=550000/(1.732×460×6%×0.816)=14099.9A<20000A

Excitation transformer of short –circuit impedance UK=6%

2)Resistor
Resitor type ZNO
Total energy limit 0.6 MJ
Drop-out voltage 800 V
Nominal voltage of BOD element 1200 V

Formula:

W=1/2 ×Td0’×Rf×Xd’/ Xd×(2×Ifn)2 =0.5×6.874×0.2181×0.297/0.993×(2


×752)2 ×2=0.5×0.44840×2262016=507143.9J (0.6MJ)

Direct axis open circuit transient time constant Td0’:6.874S


Direct axis synchronous reactance Xd:0.993
Direct axis transient reactance (unsat.) Xd’:0.297
Field resistance Rf:0.2181Ω

5
Huanza Hydroelectric Project 2×46MW

6、Field flashing components


Field flashing components designed 5%-10% for of no load field current
DC Field flashing components
Limiting resistor value 4 Ohm
Field flashing breaker type CZT-40/DC110V
Rectifier type ZP50A/500V
Formula:
IL=6% IFO=25.2A
RL=U/IL=11O/25.2=4.37Ω (4Ω)
6、Excitation Cables
1)Type of AC connections
Cables type YJV-3*185*1KV
Formula:
I1=1.1*IFN*0.816=674.9A
Current capacity j=2.0A/mm2
NA=S/185= I1/2.0/185=674.9/2/185=1.8
There are two cables connected per-phase
2)Type of DC connections
Cables type YJV-1*185*1KV
Formula:
I1=1.1* IFN =1.1*752A=827.2A
j=2.0A/mm2
NA=S/185= I1/2.0/185=827.2/2/185=2.2
There are three cables connected with both anode and minus pole.

6
Huanza Hydroelectric Project Bid Forms
REQUEST FOR PROPOSAL

EXCITATION SYSTEM

1) MANUFACTURE

(a) Manufacturer NARI Technology Development Limited Company


(b) Place of manufacture Add : No.1 Chuangye Rd, NanJing, China

(b) Manufacturing standard IEEE Std 421.1 IEEE Standard Definitions for
Excitation Systems for Synchronous Machines

IEEE Std 421.3 IEEE Standard for High-Potential


Test Requirements for Excitation Systems for
Synchronous Machines

IEEE Std C50.13 IEEE Standard for Cylindrical-Rotor


50 Hz and 60 Hz Synchronous Generators Rated 10
MVA and Above

IEEE Std 421.4 IEEE Guide for the Preparation of


Excitation System Specifications.

ANSI/IEEE C37.18 IEEE Standard Enclosed Field


Discharge Circuit Breakers for Rotating Electric
Machinery – Description

IEC 60076-3 Ed Power transformers - Insulation levels


dielectric tests and externa

IEC 60099-1 Ed Non-Linear Resistor Type Gapped


Surge Arresters for a.c. Systems

IEC 60099-4 Ed Surge arresters - Part 4: Metal-oxide


surge arresters without gaps for a.c. systems

2) REQUIRED CHARACTERISTICS

(a) Excitation type Digital static thyristor, type NES5100


(b) Rated field current 752A
(c) Field forcing current - not less than 827.2A
o
(d) Voltage to circulate rated field current (120 C) 193V
(e) Maximum field voltage 580V

3) CHARACTERISTICS OF REQUIRED EQUIPMENT

(a) Excitation system rating FWL/B-46MW


(b) Transformer rated power 550kVA
(c) Transformer secondary Volts 460V
(d) Transformer rated secondary amps. 690A
(e) Percentage Impedance 0.04
(f) Interwinding shield F class
(g) Over voltage factor. 2~3
(h) Vector group Yd11
(i) Number of three-phase bridges 2
(j) Current rating with all bridges in service 2000A
(k) Current rating with one bridge out of service 1000A
(l) Cooling system Fans
(m) Thyristor maker/type 5STP09D2201
(n) Continuous rated current 862A
(o) Maximum half-cycle current Ifsm NA
(Max.surge peak forward current for 1800 sine wave;no
voltage reapplied after surge)

EXCITATION SYSTEM 1 of 2 February 2002


Huanza Hydroelectric Project Bid Forms
REQUEST FOR PROPOSAL

EXCITATION SYSTEM

3) CHARACTERISTICS OF REQUIRED EQUIPMENT (cont'd)

(p) Protective fuse type/rating 107RSM-800V/1000A-8


(q) Peak inverse voltage 2200
(r) Surge protection - AC side Resistance- Capacitance to protect
(s) Surge protection - DC side High energy zinc oxide
(t) Field current breaker location In the de-excitation cubicle
(u) Maker and type E2N 1000
(v) Continuous rated current 1000A
(w) Interrupting capacity 15kA
(x) Field flashing requirements current/time < 30A, 8s
(y) Voltage regulator make/type NARI Technology Development Limited Company ,
NES5100

(zz) Digital/analogue Digital


(aa) Number of independent channels 2
AC sampling, regulation calculation, SCR control
(bb) Channel function angle output, signal and protection output,etc.
(cc) Auto-man follow-up Have
(dd) Dedicated firing sets
(ee) Adjustment range Volts (auto) 10% - 130%
(ff) Adjustment range field current (manual) 10% - 130%
(gg) Limiters
- V/hz Yes
- over voltage Yes
- over excitation Yes
- stator overcurrent Yes
- sub excitation Yes
(hh) PSS type NES-PSS-ⅡB
(ii) PSS reference value Power signal and frequency signal

EXCITATION SYSTEM 2 of 2 February 2002