Subestación Iquitos: Test Object-Device Setting
Subestación Iquitos: Test Object-Device Setting
Subestación Iquitos: Test Object-Device Setting
Subestación Iquitos
Test Object-Device Setting
Station/Bay Information:
Station Name: Bahia de Transformador Bay Address: =F1.C01.CPM02
Station Address: Iquitos Tester: Manuel Corrales
Bay Name: T-03
Device Information:
Device Name: -BCU Serial Number: 1183390313
Device Model: SEL451 Setting List Number: EO_RevD
Device Address: =F1.C01.CPM02 Additional Info: www.indexum.com
Manufacturer: SCHWEITZER
Nominal Values:
Vnom: 57.735V Fnom: 60.000Hz V Primary: 60.000kV Debounce Time: 0ms
Inom: 1.000A Vdc: 0.000V I Primary: 800.000A
1. Medidas W1 (60.0kV)
Page 1
PW Series Relay Testing System
System Parameters:
Tprefault : 1.000 Vz Define : Vs Phi(Vz) : 0.0Deg
Fault : A-E Phi(Vz) Ref. : Phi(Va)
CT Polarity : Line |Vz| : 22.000V
Characteristic Curve
Test Setting
Inom: 1.000A Td: 0.090 Ipickup: 0.940
Page 2
PW Series Relay Testing System
Test Result
1.I=1.500*In,A-B
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.500A
2.I=2.000*In,A-B
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.000A
3.I=2.500*In,A-B
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.500A
4.I=3.000*In,A-B
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.000A
5.I=3.500*In,A-B
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.500A
Page 3
PW Series Relay Testing System
Settings Trip time Error ErrorAbs Results
0.100S 0.116S 0.016S Passed
6.I=4.000*In,A-B
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 4.000A
7.I=1.500*In,B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.500A
8.I=2.000*In,B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.000A
9.I=2.500*In,B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.500A
10.I=3.000*In,B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.000A
Page 4
PW Series Relay Testing System
Settings Trip time Error ErrorAbs Results
0.100S 0.118S 0.018S Passed
11.I=3.500In,B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.500A
12.I=4.000In,B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 4.000A
13.I=1.500*In,C-A
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.500A
14.I=2.000*In,C-A
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.000A
15.I=2.500*In,C-A
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.500A
Page 5
PW Series Relay Testing System
Settings Trip time Error ErrorAbs Results
0.100S 0.117S 0.017S Passed
16.I=3.000In,C-A
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.000A
17.I=3.500*In,C-A
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.500A
18.I=4.000*In,C-A
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 4.000A
19.I=1.500*In,A-B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.500A
20.I=2.000*In,A-B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.000A
Page 6
PW Series Relay Testing System
Settings Trip time Error ErrorAbs Results
0.828S 0.833S 0.6 0.005S Passed
21.I=2.500*In,A-B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.500A
22.I=3.000*In,A-B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.000A
23.I=3.500*In,A-B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.500A
24.I=4.000*In,A-B-C
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 4.000A
Page 7
PW Series Relay Testing System
System Parameters:
Tprefault : 0.500 Vz Define : Vs Phi(Vz) : 0.0Deg
Fault : A-E Phi(Vz) Ref. : Phi(Va)
CT Polarity : Line |Vz| : 22.000V
Page 8
PW Series Relay Testing System
Characteristic Curve
Test Setting
Inom: 1.000A Td: 0.130 Ipickup: 0.220
Test Result
1.I=0.500*In,A-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 0.500A
Page 9
PW Series Relay Testing System
Settings Trip time Error ErrorAbs Results
1.099S 1.109S 0.9 0.010S Passed
2.I=1.200*In,A-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.200A
3.I=1.900*In,A-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.900A
4.I=2.600*In,A-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.600A
5.I=3.300In,A-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.300A
6.I=0.500*In,B-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 0.500A
Page 10
PW Series Relay Testing System
Settings Trip time Error ErrorAbs Results
1.099S 1.111S 1.1 0.012S Passed
7.I=1.200*In,B-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.200A
8.I=1.900*In,B-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.900A
9.I=2.600*In,B-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.600A
10.I=3.300*In,B-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.300A
11.I=0.500*In,C-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 0.500A
Page 11
PW Series Relay Testing System
Settings Trip time Error ErrorAbs Results
1.099S 1.110S 1.0 0.011S Passed
12.I=1.200*In,C-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.200A
13.I=1.900*In,C-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 1.900A
14.I=2.600*In,C-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 2.600A
15.I=3.300*In,C-E
Prefault Voltage: 57.735V Prefault Frequency: 60.000Hz Angle: 75.000Deg
Prefault Current: 0.000A Fault Voltage: 50.000V Fault Frequency: 60.000Hz
Prefault Angle: 75.000Deg Fault Current: 3.300A
Page 12
PW Series Relay Testing System
Page 13