Unidades para Aire Acondicionado
Unidades para Aire Acondicionado
Unidades para Aire Acondicionado
Catalog 1108-7
Water Source Heat Pumps
Model CCH Standard Range
Model CCW Geothermal Range
Enfinity Horizontal Ceiling Water Source With Daikin Enfinity Water Source Heat
Heat Pumps Sizes 007-070 (1/2 to 6 Tons) Pumps, you benefit from:
Model WCCH (Standard Range: 55°F to 110°F) High efficiency, low operating costs.
Model WCCW (Geothermal Range: 30°F to 110°F) Easy, low cost design and installation.
Daikin Enfinity Horizontal Ceiling units are designed Standard or extended range/geothermal application
for use in multiple floor apartments, office buildings, flexibility.
hotels, nursing homes and other similar applications. Superior indoor air quality.
Enfinity™ water source heat pumps incorporate the
Quiet, reliable operation.
best of our past and the best of what’s new. Using
feedback from building owners, consulting engineers, Easy, low-cost maintenance and service.
contractors and service engineers, we designed Available in multiple unit sizes – 007 (1/2 ton, 2.6kW)
Enfinity products to give you maximum flexibility to through 070 (6 ton, 10.6kW)
design, install, operate and maintain the ideal water
source heat pump system for your building project. Units exceed ASHRAE 90.1 efficiency levels
And we incorporated non-ozone depleting R-410A R-410A Refrigerant, environmentally friendly with
refrigerant, which–along with high Energy Efficiency zero ozone depletion potential
Ratios (EER’s)–helps preserve our environment and
precious energy resources. Cupro-nickel Coaxial Coil
Optional extended 4-year parts warranty
Nomenclature
Enfinity™ Horizontal Ceiling Unit (Size 007 - 070)
W CCH 1 019 B E Y L S
Product Category Discharge Air
W = WSHP S = Straight
E = End
Product Identifier
WCCH = Ceiling Mounted/Standard Range
WCCW = Ceiling Mounted/Geothermal Return Air
L = Left
Design Series R = Right
1 = A Design
2 = B Design
3 = C Design Future
4 = D Design (None)
5 = E Design
Notes: For illustration purposes only. Not all options available with all models.
Please consult Daikin Sales Representative for specific availability.
* A 460 volt, 3-phase unit that utilize an ECM fan motor will need a 4-wire WYE voltage supply with 3 hot leads and a
neutral wire. To power the ECM motor with neutral and one hot for 277/60/1 voltage to the ECM motor.
Catalog 1108-7 Efinity Horizontal Water Source Heat Pumps Page 3 of 96
Features & Options
BACnet LonWorks
Communication Communication
MicroTech III Unit
Module Module
Controller
4. Blower Motor – Multi-speed, PSC type with thermal overload 7. MicroTech® III Unit Controller – Designed for flexibility, the
protection. The motor is isolated from the fan housing for main control board is used in standalone applications. A sepa-
minimum vibration transmission. Removable orifice ring al- rate LonWorks® or BACnet® communication module can be
lows easy removal of blower and motor. easily snapped onto the board to accommodate the building
automation system of your choice.
*ECM Motor (Optional) – available in unit sizes 015 to 070.
Programmed to make soft starts and stops to reduce stress Control Options
transmitted to the fan housing. They adjust their speed and
MicroTech III - Standalone
torque to deliver constant airflow over a wide range of external
static pressure MicroTech III - LonWorks Communication Module
5. Compressor – Mounted close to the access panel for maximum MicroTech III - BACnet Communication Module
serviceability and isolated from the bottom panel with rubber
isolators. Standard with massplate for quiet operation
Cabinet
Daikin Enfinity horizontal water source heat pumps are
available in five cabinet sizes, each with the lowest pos-
sible profile to conserve space. Figure 1 - Left Hand Figure 2 - Left Hand
Consistencies in shape, connection locations, parts and Return with End Return with Straight
assemblies throughout the five cabinets make layout, instal- Discharge Discharge
lation and service simple.
Cabinet Configurations – Right Hand
All water and electrical connections are made from the
front of the unit.
Low Design And Installation Costs Standard heavy-gauge steel mass-plate with visco
Four configurations for each unit size (left or right re-
elastic dampening material below the compressor helps
reduce noise emission in horizontal ceiling unit sizes
turn and straight or end discharge) allow you to specify
019-070.
units to fit space requirements and to design the system
using minimum ductwork and piping.
Easy, Low-Cost Maintenance
Five cabinet sizes, each with Daikin’s low-profile Easy access to the unit compressor (2-sides), fan and motor
design, make it easy to meet the space requirements of (1-side) and controls (end access).
your new construction or replacement application.
A removable orifice ring allows the blower and motor
Flush FPT water fittings allow easy, one-wrench con- to be removed without removing the blower housing or
nection of units and help reduce delays caused by ship- disconnecting the unit from the ductwork.
ping damage.
Removable orifice ring for easy blower and motor removal
Flexible control options that include standalone or
network operation with the building automation system Removable
of your choice using LonMark® or Alerton BACnet® Orifice Ring
communications.
Quiet Operation
Large fan wheel allows the fan motor to operate at
lower speed for quieter operation.
Heavy gauge cabinet construction and vibration isolated
hanger brackets minimize noise and vibration.
Three quiet compressor selections (depending on volt-
age and size variations) including rotary (sizes 007 to
015), reciprocating (sizes 019 to 024) and scroll com-
pressors (sizes 030 to 070).
An optional factory provided 2" filter rack is avail- Fan Housing Protrudes Through the Cabinet for
able where high indoor air quality is required. A 2" Connection of Flexible Duct
construction-type filter is included. The filter rack can
be mounted for left hand or right hand filter removal
by rotating it 180 degrees. Two thumb screws allow
easy removal of the access door for quick filter changes
without using a tool.
Unit Hangers
Drain Pan
Daikin horizontal heat pumps come standard with a
ABS plastic, corrosion-resistant plastic drain pan to pro-
mote good indoor air quality. The pan is double sloped for
positive draining to reduce the occurrence of standing water
and microbial growth.
Compressor
Daikin Enfinity water source heat pumps are designed
around the most advanced compressors in the industry. A
wide variety of compressor types are used to offer the best
system design for the dedicated refrigerants and tonnage.
This allows Daikin Enfinity water source heat pumps to
deliver rated capacity with low noise levels.
Rotary compressor are used in unit sizes 007 to 015.
Unit sizes 019 to 024 use a Reciprocating type compressor.
Unit sizes 030 to 070 use a scroll compressor.
Scroll
Compressor
Rotary
Compressor
Reciprocating
Compressor
MicroTech III The MicroTech III unit controller is Each unit controller is factory programmed, wired, and Unit-mounted
a standalone microprocessor-based tested for complete control of single zone, standalone or wall-mounted
control board conveniently located operation of your Daikin Water Source Heat Pump. thermostat
in the unit control box for accessibil-
ity. The board is designed to provide
standalone control of a Water Source
Heat Pump using a wall thermostat or
a wall mounted temperature sensor.
Each unit controller is factory pro-
(Standalone) grammed, wired, and tested. For added
Unit Controller functionality.
LonWorks The MicroTech III unit controller can Designed to be linked with a centralized building LonMark 3.4
accept a plug-in LonWorks commu automation system (BAS) through a LonWorks com
nication module to provide network munications network for centralized scheduling and
communications and added functional- management of multiple heat pumps.
ity to easily integrate with an existing
BAS. The communication module can
Communication be factory- or field-installed and is
Module tested with all logic required to monitor
and control the unit.
BACnet The MicroTech III unit controller can Designed to be linked with a centralized building BACnet
accept a plug-in BACnet commu automation system (BAS) through a BACnet com-
nication module to provide network munications network for centralized scheduling and
communications and added functional- management of multiple heat pumps.
ity to easily integrate with an existing
BAS. The communication module can
be factory- or field-installed and is
Communication tested with all logic required to monitor
and control the unit.
Module
Each Enfinity Horizontal Water Source Heat Pump can The MicroTech III Unit Controller with LonWorks or
be equipped with a LonWorks or BACnet communication BACnet Communication Module orchestrates the following
module. The LonWorks module is LonMark 3.4 certified unit operations:
and designed to communicate over a LonWorks communi- Enable heating and cooling to maintain space
cations network to a Building Automation System (BAS). temperature setpoint based on a room sensor setting
The BACnet module is designed to communicate over a
BACnet MS/TP communications network to a building Enable fan and compressor operation
automation system. Both controllers are microprocessor- Monitors all equipment protection controls
based and can be factory or field-installed.
Monitors room and discharge air temperatures
The control modules are programmed and tested with
all the logic required to monitor and control the unit. Op- Monitors leaving water temperature
tional wall sensors may be used with the communication Relays status of all vital unit functions
modules to provide limited local control of the Horizontal
An amber, on-board status LED indicates the status of the
Water Source Heat Pump. The MicroTech III unit controller
monitors water and air temperatures and passes information MicroTech III LonWorks or BACnet module.
to the communication module. The module communicates The MicroTech III unit controller with communication
with the BAS, to provide network control of the Water module includes:
Source Heat Pump. ■ Return Air Temperature sensor (RAT) (field-installed)
■ Discharge Air Temperature sensor (DAT)
MicroTech III LonWorks Communication Module (field-installed)
The LonWorks communication module is designed for ■ Leaving Water Temperature sensor (LWT)
units that are integrated into a LonWorks communication
network for centralized scheduling and management of CAUTION
multiple heat pumps.
When an optional wall-mounted room temperature sensor is
connected to the unit controller, the Return Air Temperature
(RAT) sensor must not be installed. A wall-mounted room
temperature sensor and the return air temperature sensor
must not be connected simultaneously or the unit will not
operate properly.
Condensate
Drain (P Trap)
Optional
Field Installed Vent
1 1/2"
1 1/2"
(38mm)
(38mm)
Flexible Supply Condensate
Duct Collar Hose Trap
Flexible Connector
Acoustic/Thermal
Lining
Diffuser
Ductwork Supported
Independent of Unit
Flexible Connector
Return Air Intake Acoustic/Thermal
Located Lining 10ft. (3 meters)
Away from the
Unit Blower
Return Air
Heating Refrigeration Cycle
When the wall thermostat calls Thermal
Expansion Valve Water to Refrigerant
for HEATING, the reversing valve Heat Exchanger
directs the flow of the refrigerant, a
hot gas, from the compressor to the
air-to-refrigerant heat exchanger coil.
Air to
There, the heat is removed by the Refrigerant
Water In
air passing over the surfaces of the Heat
coil and the hot gas condenses and Exchanger Water Out
Coil
becomes a liquid. The liquid then Sensing
flows through a thermal expansion Bulb and
Capillary
valve to the water-to-refrigerant heat Tube
exchanger. The liquid then evaporates
and becomes a gas, at the same time Compressor
absorbing heat and cooling the water.
The refrigerant then flows as a low
pressure gas through the reversing Blower
Boiler/Tower Application
Water Loop
Rated in Accordance with ISO Standard 13256-1
PSC & ECM Motor
PSC Fan Motor ECM Fan Motor
Unit Airflow Waterflow
Voltage Cooling Heating Cooling Heating
Size
CFM L/S GPM L/S Btuh EER Btuh COP Btuh EER Btuh COP
115-60-1
007 300 142 2.2 0.14 8000 11.8 10700 4.2 n/a n/a n/a n/a
208/230-60-1
115-60-1
009 300 142 2.3 0.14 8800 12.9 11800 4.6 n/a n/a n/a n/a
208/230-60/1
208/230-60-1
012 400 189 3.0 0.19 12900 12.7 15800 4.3 n/a n/a n/a n/a
265/277-60-1
630 208/230-60-1
015 297 3.8 0.24 15700 16.0 18100 5.2 16000 17.6 18100 5.6
500* 265/277-60-1
208/230-60-1
019 630 297 5.3 0.33 21000 14.9 23600 4.8 20900 15.7 23700 5.1
265/277-60-1
208/230-60-1
265/277-60-1
024 800 378 6.2 0.39 24700 14.4 28400 4.7 24700 14.7 28500 4.9
208/230-60-3
460-60-3
208/230-60-1
265/277-60-1
030 1000 472 7.6 0.48 30400 15.3 36200 5.0 30500 15.9 36100 5.3
208/230-60-3
460-60-3
208/230-60-1
265/277-60-1
036 1200 566 9.0 0.57 35800 15.2 42500 4.9 36000 16.0 42400 5.2
208/230-60-3
460-60-3
208/230-60-1
208/230-60-3
042 1400 661 10.7 0.68 43000 15.0 50700 5.0 43000 15.5 51600 5.2
460-60-3
575-60-3
208/230-60-1
208/230-60-3
048 1600 755 12.3 0.78 48400 14.1 57100 4.7 48700 15.6 57700 5.2
460-60-3
575-60-3
208/230-60-1
208/230-60-3
060 2000 944 15.2 0.96 59500 14.6 69400 4.9 59700 15.5 69300 5.2
460-60-3
575-60-3
208/230-60-3
070* 2330 944 18.0 1.14 460-60-3 n/a n/a n/a n/a 71300 12.7 88100 4.2
575-60-3
Ground Loop
Rated in Accordance with ISO Standard 13256-1
Ground Source
Rated in Accordance with ISO Standard 13256-1
CFM L/S GPM L/S Btuh EER Btuh COP Btuh EER Btuh COP
115-60-1
007 300 142 2.2 0.14 10200 20.1 9100 3.8 n/a n/a n/a n/a
208/230-60-1
115-60-1
009 300 142 2.3 0.14 10800 21.8 9800 4.1 n/a n/a n/a n/a
208/230-60/1
208/230-60-1
012 400 189 3.0 0.19 14700 19.2 13300 3.7 n/a n/a n/a n/a
265/277-60-1
630 208/230-60-1
015 297 3.8 0.24 18000 25.8 14700 4.4 18200 29.3 14700 4.7
500* 265/277-60-1
208/230-60-1
019 630 297 5.3 0.33 25400 23.6 19800 4.4 25300 25.0 19900 4.6
265/277-60-1
208/230-60-1
265/277-60-1
024 800 378 6.2 0.39 29600 22.8 23500 4.3 29600 23.5 23600 4.4
208/230-60-3
460-60-3
208/230-60-1
265/277-60-1
030 1000 472 7.6 0.48 33500 22.8 29500 4.2 33600 23.9 29500 4.6
208/230-60-3
460-60-3
208/230-60-1
265/277-60-1
036 1200 566 9.0 0.57 40700 23.2 36000 4.4 40900 25.0 35900 4.5
208/230-60-3
460-60-3
208/230-60-1
208/230-60-3
042 1400 661 10.7 0.68 47500 22.1 42200 4.3 47000 22.7 42800 4.5
460-60-3
575-60-3
208/230-60-1
208/230-60-3
048 1600 755 12.3 0.78 54200 20.7 48100 4.4 54600 24.1 48700 4.6
460-60-3
575-60-3
208/230-60-1
208/230-60-3
060 2000 944 15.2 0.96 61200 20.5 59300 4.1 61300 22.1 59200 4.7
460-60-3
575-60-3
208/230-60-3
070* 2330 944 18.0 1.14 460-60-3 n/a n/a n/a n/a 77600 17.7 73400 3.8
575-60-3
ECM Motor
Compressor Fan Motor Total Unit Minimum Minimum Maximum
Unit Size Voltage/Hz/Ph
RLA LRA FLA FLA Voltage Circuit Amps Fuse Size
Note: *All 460-60-3 units require 4-wire power, which includes a neutral wire. ECM motors 460-60-3 volt units require a
265 volt power supply. Both a hot AND a neutral wire are required to obtain proper fan motor voltage. Therefore, 4-
wires with a wye type wiring arrangement is required.
Water Source Heat Pump Operating Temperature Limits (For Continuous Duty)
Entering Air °F Entering Water °F
Operating
Minimum Maximum Standard Range Extended Range
Mode
DB WB DB WB Minimum Maximum Minimum Maximum
Cooling 65 55 85 71 55 110 50 110
Ambient 50 – 100 – – – – –
Heating 50 – 80 – 55 90 20 90
Ambient 50 – 85 – – – – –
Notes: In the heating mode, the sum of the entering air + entering water must be ≥ 100°F.
MINIMUM WATER FLOW = 1.5 GPM/Ton.
Maximum and minimum values may not be combined. If one value is at maximum or minimum, the other two
conditions may not exceed the normal condition for standard units. Extended range units may combine any two
maximum conditions, but not more than two, with all other conditions being normal conditions.
Percent of Nominal Airflow
105 110 115 120 125 130 135 140 145 150
Total Cooling Capacity 1.004 1.011 1.017 1.024 1.031 1.038 1.045 1.052 1.059 1.066
Sensible Cooling Capacity 1.024 1.048 1.073 1.098 1.122 1.147 1.171 1.196 1.220 1.245
kW - Cooling 1.010 1.019 1.027 1.036 1.044 1.053 1.061 1.070 1.078 1.087
Total Heat of Rejection 1.006 1.014 1.021 1.029 1.036 1.044 1.051 1.059 1.066 1.074
Total Heating Capacity 1.007 1.017 1.027 1.036 1.046 1.055 1.065 1.074 1.084 1.094
kW - Heating 0.998 0.995 0.992 0.990 0.987 0.984 0.981 0.979 0.976 0.973
Total Heat of Absorption 1.008 1.018 1.028 1.038 1.048 1.058 1.068 1.078 1.088 1.098
Percent of Nominal Airflow
155 160 165 170 175 180 185 190 195
Total Cooling Capacity 1.0731.079 1.086 1.093 1.100 1.107 1.114 1.121 1.128
Sensible Cooling Capacity 1.2691.294 1.318 1.343 1.367 1.392 1.417 1.441 1.466
kW - Cooling 1.0951.104 1.113 1.121 1.130 1.138 1.147 1.155 1.164
Total Heat of Rejection 1.0811.089 1.096 1.104 1.111 1.119 1.126 1.134 1.141
Total Heating Capacity 1.1031.113 1.122 1.132 1.141 1.151 1.161 1.170 1.180
kW - Heating 0.9710.968 0.965 0.962 0.960 0.957 0.954 0.952 0.949
Total Heat of Absorption 1.1081.118 1.128 1.138 1.149 1.159 1.169 1.179 1.189
Propylene Glycol
10% 20% 30% 40% 50%
Cooling Capacity 0.9900 0.9800 0.9700 0.9600 0.9500
Heating Capacity 0.9870 0.9750 0.9620 0.9420 0.9300
Pressure Drop 1.0700 1.1500 1.2500 1.3700 1.4200
Methanol
10% 20% 30% 40% 50%
Cooling Capacity 0.9980 0.9720 – – –
Heating Capacity 0.9950 0.9700 – – –
Pressure Drop 1.0230 1.0570 – – –
Ethanol
10% 20% 30% 40% 50%
Cooling Capacity 0.9910 0.9510 – – –
Heating Capacity 0.9950 0.9600 – – –
Pressure Drop 1.0350 0.9600 – – –
Page 72 of 96
Physical Data (in inches)
Unit Size 007 009 012
Fan Wheel - D x W 6.3 x 6.0 6.3 x 6.0 6.2 x 7.4
Standard PSC Motor Horsepower 1/8 1/8 1/8
Coil Face Area (Sq. Ft.) 0.97 1.11 1.53
Overall Unit Dimensions
Coil Rows 3 3 4
Size 007, 009 = 20"W x 34"L x 11.50"H
Refrigerant Charge (oz.) 17 oz. 19 oz. 31.5 oz.
1" Filter, (Qty.) Size (In.) (1)10 x 20 (1)10 x 20 (1)10 x 26 Size 012 = 20"W x 40"L x 11.50"H
Water Connections, FPT 1/2 1/2 1/2
Condensate Connections, FPT 3/4 3/4 3/4 Dimensions are approximate
Weight, Operate (Lbs.) 98 99 115
Weight, Shipping (Lbs.) 130 130 145 Right and left hand return determined by
facing the water connection side of the unit.
Catalog 1108-7
Dimensional Data
Size 007, 009, 012 – Right Hand Return, End and Straight Discharge
Catalog 1108-7
Physical Data (in inches)
Unit Size 007 009 012
Fan Wheel - D x W 6.3 x 6.0 6.3 x 6.0 6.2 x 7.4
Standard PSC Motor Horsepower 1/8 1/8 1/8
Coil Face Area (Sq. Ft.) 0.97 1.11 1.53
Coil Rows 3 3 4 Overall Unit Dimensions
Refrigerant Charge (oz.) 17 oz. 19 oz. 31.5 oz.
Size 007, 009 = 20"W x 34"L x 11.50"H
1" Filter, (Qty.) Size (In.) (1)10 x 20 (1)10 x 20 (1)10 x 26
Size 012 = 20"W x 40"L x 11.50"H
Water Connections, FPT 1/2 1/2 1/2
Condensate Connections, FPT 3/4 3/4 3/4
Weight, Operate (Lbs.) 98 99 115 Dimensions are approximate
Weight, Shipping (Lbs.) 130 130 145
Right and left hand return determined by
facing the water connection side of the unit.
Page 73 of 96
Dimensional Data
Size 015, 019, 024 – Left Hand Return, End and Straight Discharge
Page 74 of 96
Physical Data (in inches)
Unit Size 015 019 024
Fan Wheel - D x W 9.5 x 7.1 9.5 x 7.1 9.5 x 7.1
Standard PSC Motor Horsepower 1/3 1/3 1/3
Coil Face Area (Sq. Ft.) 2.75 2.75 2.75
Coil Rows 3 3 3
Overall Unit Dimensions =
Refrigerant Charge (oz.) 43 oz. 45 oz. 40.5 oz.
1" Filter, (Qty.) Size (In.) (1)18 x 24 (1)18 x 24 (1)18 x 24
20"W x 42"L x 19"H
Water Connections, FPT 1/2 1/2 1/2
Condensate Connections, FPT 3/4 3/4 3/4 Dimensions are approximate.
K Z
Weight, Operate (Lbs.) 195 195 195 Straight
Weight, Shipping (Lbs.) 214 214 214 Right and left hand return Discharge
determined by facing the water Position
1"
connection side of the unit.
1" P
1" Removable
9"
Access Panel
Y to Compressor L
V N C Removable A
R
Return Air - Filter Access Panel 11"
End Discharge View Water Supply
Condensate Drain Straight Discharge View
Connection
Dimensional Data (in inches)
Dimensions
Unit Size
A B C D E F G H J K L M N P R T U V W Y Z
015 9.22 3.00 1.45 14.93 2.91 7.12 3.15 2.15 4.10 22 15.43 3.60 1.25 42 3.73 2.03 8.30 20 42 19 17.5
019 9.22 3.00 1.45 14.93 2.91 7.12 3.15 2.15 4.10 22 15.43 3.60 1.25 42 3.73 2.03 8.30 20 42 19 17.5
024 9.22 3.00 1.45 14.93 2.91 7.12 3.15 2.15 4.10 22 15.43 3.60 1.25 42 3.73 2.03 8.30 20 42 19 17.5
Catalog 1108-7
Dimensional Data
Size 015, 019, 024 – Right Hand Return, End and Straight Discharge
Catalog 1108-7
Physical Data (in inches)
Unit Size 015 019 024
Fan Wheel - D x W 9.5 x 7.1 9.5 x 7.1 9.5 x 7.1
Standard PSC Motor Horsepower 1/3 1/3 1/3
Coil Face Area (Sq. Ft.) 2.75 2.75 2.75
Coil Rows 3 3 3 1"
Refrigerant Charge (oz.) 43 oz. 45 oz. 40.5 oz. Overall Unit Dimensions =
1" Filter, (Qty.) Size (In.) (1)18 x 24 (1)18 x 24 (1)18 x 24 20"W x 42"L x 19"H
Water Connections, FPT 1/2 1/2 1/2
Condensate Connections, FPT 3/4 3/4 3/4 Dimensions are approximate.
Weight, Operate (Lbs.) 195 195 195
Z K
Weight, Shipping (Lbs.) 214 214 214 Right and left hand return
determined by facing the water Straight Discharge Position
connection side of the unit. 1"
P 1"
Water Line
Return Low
Voltage Voltage W 1" B
E
T
Removable 9" F
L Access Panel
D Y
to Compressor
9" F
H G
N V A
C Return Air - Filter Duct Collar
R 11"
Water Blower Housing Assembly Converts from
Condensate Drain
Supply Connection Straight Discharge to End Discharge End Discharge View Straight Discharge View
Page 75 of 96
Dimensional Data
Size 030, 036 – Left Hand Return, End and Straight Discharge
Page 76 of 96
Physical Data (in inches)
Unit Size 030 036
Fan Wheel - D x W 9.5 x 7.1 9.5 x 7.1
Standard PSC Motor Horsepower 1/3 1/2 1"
Coil Face Area (Sq. Ft.) 3.43 3.43 Overall Unit Dimensions =
Coil Rows 3 3
21"W x 46"L x 20"H
Refrigerant Charge (oz.) 48 oz. 49 oz.
1" Filter, (Qty.) Size (In.) (1)19 x 27 (1)19 x 27
Water Connections, FPT 3/4 3/4
Dimensions are approximate. Straight Z
K Discharge
Condensate Connections, FPT 3/4 3/4 A
Position
Weight, Operate (Lbs.) 225 223 Right and left hand return
Weight, Shipping (Lbs.) 244 242 determined by facing the water
1"
connection side of
the unit.
1" P
1"
Removable Removable
D F
Y Access Panel Access Panel
F to Compressor
L
G
H M J
Catalog 1108-7
Dimensional Data
Size 030, 036 – Right Hand Return, End and Straight Discharge
Catalog 1108-7
Physical Data (in inches)
Unit Size 030 036
Fan Wheel - D x W 9.5 x 7.1 9.5 x 7.1
Standard PSC Motor Horsepower 1/3 1/2 1"
Coil Face Area (Sq. Ft.) 3.43 3.43
Coil Rows 3 3
Overall Unit Dimensions = 21"W x 46"L x 20"H
Refrigerant Charge (oz.) 48 oz. 49 oz.
1" Filter, (Qty.) Size (In.) (1)19 x 27 (1)19 x 27 Dimensions are approximate.
Water Connections, FPT 3/4 3/4 Z
Condensate Connections, FPT 3/4 3/4 Right and left hand return determined by facing K
A
Weight, Operate (Lbs.) 225 223 the water connection side of the unit. Straight Discharge Position
Weight, Shipping (Lbs.) 244 242
1"
P 1"
Removable
D Access Panel L Y F
to Compressor F
Page 77 of 96
Dimensional Data
Size 042, 048, 060, 070 – Left Hand Return, End and Straight Discharge
Page 78 of 96
Physical Data (in inches)
Unit Size 042 048 060 070
Fan Wheel - D x W 12.9 x 11.1 12.9 x 11.1 12.9 x 11.1 12.9 x 11.1 1"
Standard PSC Motor Horsepower 1/2 3/4 3/4 3/4
Coil Face Area (Sq. Ft.) 4.43 4.43 6.11 6.11
Overall Unit Dimensions =
Coil Rows 3 3 3 3
28"W x 52"L x 23"H
Refrigerant Charge (oz.) 60.0 oz. 55.0 oz. 74.0 oz. 64.0 oz.
1" Filter, (Qty.) Size (In.) (2)16 x 22.5 (2)16 x 22.5 (2)22 x 22 (2)22 x 22
Water Connections, FPT 3/4 3/4 3/4 3/4 Dimensions are approximate.
Z
Condensate Connections, FPT 3/4 3/4 3/4 3/4 Straight
Right and left hand return K Discharge
Weight, Operate (Lbs.) 293 298 332 332
Position
Weight, Shipping (Lbs.) 314 319 351 351 determined by facing the water
connection side of 1"
the unit.
1" P
Blower Housing Assembly Converts from Straight
Discharge to End Discharge Low Water Water
Line
Voltage Return Supply
1" W Voltage
E A
C
F
Removable
L Access Panel D
Y to Compressor
F
Catalog 1108-7
Dimensional Data
Size 042, 048, 060, 070 – Right Hand Return, End and Straight Discharge
Catalog 1108-7
Physical Data (in inches)
Unit Size 042 048 060 070
Fan Wheel - D x W 12.9 x 11.1 12.9 x 11.1 12.9 x 11.1 12.9 x 11.1
Standard PSC Motor Horsepower 1/2 3/4 3/4 3/4
Coil Face Area (Sq. Ft.) 3.43 3.43 6.11 6.11
1"
Coil Rows 3 3 3 3
Refrigerant Charge (oz.) 60.0 oz. 55.0 oz. 74.0 oz. 64.0 oz. Overall Unit Dimensions =
1" Filter, (Qty.) Size (In.) (2)16 x 22.5 (2)16 x 22.5 (2)22 x 22 (2)22 x 22 28"W x 52"L x 23"H
Water Connections, FPT 3/4 3/4 3/4 3/4
Condensate Connections, FPT 3/4 3/4 3/4 3/4 Dimensions are approximate.
Weight, Operate (Lbs.) 293 298 332 332
Z
Weight, Shipping (Lbs.) 314 319 351 351 Right and left hand return 1" K
determined by facing the water Straight Discharge Position
connection side of the unit.
F
D Removable L
Access Panel Y
to Compressor
Page 79 of 96
Dimensional Data
Standard 1" Filter Rack – Left Hand Return, End Discharge Standard 1" Filter Rack – Right Hand Return, End Discharge
D
D
C B B C*
A A
E
E
Dimensions (inches)
Unit size
A B C D E
007, 009 20.17 8.88 1.90 1.56 1.25
012 26.17 8.88 1.90 1.56 1.25
015, 019, 024 24.00 17.02 1.76 1.06 1.39
030, 036 27.32 18.01 1.63 1.06 1.63
042, 048 32.07 21.54 1.63 1.06 2.16
060, 070 44.20 20.97 1.63 1.06 2.16
Dimensions (inches)
Unit size D E
A B C
007, 009 8.22 21.43 9.55 21.53 2.06
012 8.22 27.42 9.55 27.42 2.06
015, 019, 024 16.29 25.15 17.62 25.15 2.06
030, 036 17.23 30.75 18.56 30.75 2.06
042, 048 20.28 34.75 21.61 34.75 2.06
060, 070 20.22 46.9 21.54 46.9 2.06
Features
• Hardwired
System Configurations:
• Two-stage heat / two-stage cool
button press
Room temperature sensors provide electronic sensing
Terminations: of room temperatures at interior wall locations. All sensor
• +R, -C, W1, Y1, W2, Y2, G, O, S1, S2
models feature a thermistor (10kΩ), a green LED for unit
status and tenant override button. Setpoint adjustment
Optional Remote Sensor potentiometer, heat and fan mode switches are optional
Part No. 667720401 – Used with Thermostat(s) 668375301 & features.
668375401
Sensor Kit Part Numbers
The fast, easy solution for temperature sensing problems. Feature
669529001 669529101 669529201
• For tamper prone areas Tenant Override
Yes Yes Yes
• Poor airflow areas Button
SPT Adj. Pot No Yes Yes
• Troubled applications
Status LED Yes Yes Yes
• Foam gasket prevents drafts through Fan and No
1
Yes
2
Yes
wall opening Mode Switches
• Mounts to standard 2" x 4" outlet box Notes:
23/4"W x 41/2"H 1 55º to 95°F (13º to 35ºC)
0 to 10 K ohm
Potentiometer
3.75"
4.59"
Mode Control Tenant Override
Slide Switch Momentary Push Button Switch
Temperature
Sensor Terminals
Temperature
Sensor Terminals
Non-Programmable, Auto or Manual Changeover Two Stage Heat/Two Stage Cool, Night
Setback and Override Feature
1 Circuit (Part No. 668375401)
MicroTech III Unit Control Board
Low Voltage Terminal Strip (Circuit 1)
TB2
Thermostat
24VAC Common C Terminals
Tenant Override O -
C
Fan G +
R
Cool 1 Y1 W1
Cool 2 Y2
Y1
Heat 1 W1
W2
Heat 2 W2
Y2
Alarm Output A
G
24VAC R
O
Override (Optional)
Note: An additional conductor is required between "O" terminals for the override feature to work.
Thermostat
Remote Sensor
S1 S2
S1 S2
Wire 2
Wire 1
Cut R12 from
circuit board
Table B
208V RED
230V ORG
Legend
Item Description
C1 Capacitor-Compressor
C2 Capacitor-Fan
CC Compressor - Contactor
CM Compressor - Motor
COS Condensate Overflow Sensor
DAT Discharge Air Temp Sensor
EWT Entering Water Temp Sensor
HP High Pressure Switch
ISO-NO Isolation Valve - Normally Open
LED1 LED Annunciator / Harness
LP Low Pressure Switch
SLTS Suction Line Temp Sensor
LWT Leaving Water Temp Sensor
MIII MicroTech III Main Board
R1 Relay - Fan Motor
RAT Return Air Temp Sensor
RV Reversing Valve Solenoid
TB1 Power Terminal Block
X1 Primary 24VAC Transformer
_____ Standard Unit Wiring
_ _ _ _ Optional Wiring (by others)
Notes:
1. Main board jumpers:
JP3 Geothermal
Transformer:
Unused wire to be capped.
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT), Discharge Air (DAT) and Return Air (RAT) Temperature
sensors are shipped or are field installed on units configured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access
panel of the unit.
Page 88 of 96 Enfinity Horizontal Water Source Heat Pumps Catalog 1108-7
Typical Wiring Diagrams
MicroTech III Unit Controller with PSC Motor – 208/230/460/575-60-3 Unit Sizes 024-060
Drawing No. 668991202
Legend
Table B Item Description
208V RED C1 Capacitor-Compressor
230V ORG C2 Capacitor-Fan
460V BLK/RED CC Compressor - Contactor
575V BLUE CM Compressor - Motor
COS Condensate Overflow Sensor
DAT Discharge Air Temp Sensor
EWT Entering Water Temp Sensor
HP High Pressure Switch
ISO-NO Isolation Valve - Normally Open
LED1 LED Annunciator / Harness
LP Low Pressure Switch
SLTS Suction Line Temp Sensor
LWT Leaving Water Temp Sensor
MIII MicroTech III Main Board
R1 Relay - Fan Motor
RAT Return Air Temp Sensor
RV Reversing Valve Solenoid
TB1 Power Terminal Block
X1 Primary 24VAC Transformer
_____ Standard Unit Wiring
_ _ _ _ Optional Wiring (by others)
Notes:
1. Main board jumpers:
JP3 Geothermal
Transformer:
Unused wire to be capped.
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT), Discharge Air (DAT) and Return Air (RAT) Temperature
sensors are shipped or are field installed on units configured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access
panel of the unit.
MicroTech III Unit Controller with ECM Motor – 208/230-60-3 Unit Sizes 024-070
Drawing No. 910104890
Table B
208V RED
230V ORG
Legend
Item Description
CC Compressor - Contactor
CM Compressor - Motor
COS Condensate Overflow Sensor
HP High Pressure Switch
ISO-NO Isolation Valve - Normally Open
LED1 LED Annunciator / Harness
LP Low Pressure Switch
SLTS Suction Line Temp Sensor
LWT Leaving Water Temp Sensor
MIII MicroTech III Main Board
RAT Return Air Temp Sensor
RV Reversing Valve Solenoid
X1 Transformer
_____ Standard Unit Wiring
_ _ _ _ Optional Wiring (by others)
Notes:
1. Main board jumpers:
JP3 Geothermal
Transformer:
Unused wire to be capped.
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT) and Discharge Air (DAT) Temperature sensors are
shipped or are field installed on units configured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls access
panel of the unit.
MicroTech III Unit Controller with ECM Motor – 208/230-60-1 Unit Sizes 015-060
Drawing No. 919194871
Table B
208V RED
230V ORG
Legend
Item Description
C1 Capacitor-Compressor
CC Compressor - Contactor
CM Compressor - Motor
COS Condensate Overflow Sensor
DAT Discharge Air Temp Sensor
EWT Entering Water Temp Sensor
HP High Pressure Switch
ISO-NO Isolation Valve - Normally Open
LED1 LED Annunciator / Harness
LP Low Pressure Switch
SLTS Suction Line Temp Sensor
LWT Leaving Water Temp Sensor
MIII MicroTech III Main Board
R1 Relay - Fan Motor
RAT Return Air Temp Sensor
RV Reversing Valve Solenoid
X1 Transformer
_____ Standard Unit Wiring
_ _ _ _ Optional Wiring (by others)
Notes:
1. Main board jumpers:
JP3 Geothermal
Transformer:
Unused wire to be capped.
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT) and Discharge Air (DAT) Temperature sensors are
shipped or are field installed on units configured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls
access panel of the unit.
Table B
460V/N BLK/RED
Legend
Item Description
CC Compressor - Contactor
CM Compressor - Motor
COS Condensate Overflow Sensor
HP High Pressure Switch
ISO-NO Isolation Valve - Normally Open
LED1 LED Annunciator / Harness
LP Low Pressure Switch
SLTS Suction Line Temp Sensor
LWT Leaving Water Temp Sensor
MIII MicroTech III Main Board
RAT Return Air Temp Sensor
RV Reversing Valve Solenoid
X1 Transformer
_____ Standard Unit Wiring
_ _ _ _ Optional Wiring (by others)
Notes:
1. Main board jumpers:
JP3 Geothermal
Transformer:
Unused wire to be capped.
Note: The gray tinted areas in the wiring diagram; Leaving Water (LWT) and Discharge Air (DAT) Temperature sensors are
shipped or are field installed on units configured with a communication module.
*Wiring diagrams are typical. For the latest drawing version refer to the wiring diagram located on the inside of the controls
access panel of the unit.
Units shall be configured in one of the following airflow ar- Refrigerant metering shall be regulated by a thermostatic
rangements: expansion valve (TXV) only. Reversing valve shall be four-
■ Left Return/End Discharge way solenoid activated refrigerant valve, which fails in the
■ Left Return/Straight Discharge cooling “dominant” operation. Safety controls include a
■ Right Return/End Discharge high-pressure switch, a low-pressure switch (sizes 015 to
■ Right Return/Straight Discharge 070 only) and a low refrigerant temperature sensor. Refrig-
erant gauge access fittings shall be factory installed on high
Units shall have a factory-installed 1" duct flange on the
and low pressure refrigerant lines to facilitate field service.
discharge of the blower and must have a minimum of two ac-
Activation of any safety switch shall prevent the compressor
cess panels, one for the compressor compartment and one for
from operating. Units shall be capable of being reset only by
the blower compartment. Unit shall have an insulated panel
interrupting the power supply to the unit. Unit shall not be
separating the blower compartment from the compressor
able to be reset from the wall thermostat.
compartment. Units are to ship with heavy metal brackets,
rubber isolators, fasteners and washers to suspend and isolate Drain Pan
the unit from the building. The condensate pan shall be constructed of high impact
IAQ, ABS plastic to prevent corrosion and sweating. The bot-
Cabinets shall have separate openings and knockouts for
tom of the drain pan shall be sloped on two planes to provide
entrance of line voltage and low voltage control wiring. Sup-
complete drainage of water from the pan. The water source
ply and return water connections shall be brass FPT fittings
heat pump unit shall be supplied with standard solid-state
and shall be securely mounted flush to the cabinet corner post
electronic condensate overflow protection.
allowing for connection to a flexible hose without the use of a
back-up wrench. Unit shall have a high-density polyethylene Fan and Motor Assembly
plastic “dual-sloped” drain pan with a drain connection being Unit sizes 007-070 shall have a direct drive centrifugal
flush mounted to the unit casing. It is the installing contractor’s fan. The fan housing shall have a removable orifice ring to
responsibility to provide sufficient clearance so that units can facilitate fan motor and fan wheel removal. The fan housing
be easily removed for servicing. shall protrude through the cabinet to facilitate field supply
duct connection. The standard fan motor shall be PSC type
isolated from the fan housing and shall have internal thermal
overload protection.
Console Units
3/4 to 11/2 Ton
Enfinity Vertical &
Horizontal Units
1/2 to 6 Ton
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high
priority. For training information on all Daikin HVAC products, please visit us at
www.DaikinApplied.com and click on training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-
430285Y. To find your local Daikin Representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To
find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.