What is Fuses
A fuse is a device that protects a circuit from an over current condition only. It has a fusible link directly heated
and destroyed by the current passing through it. A fuse contains a current- carrying element sized so that the
heat generated by the flow of normal current through it does not cause it to melt the element; however, when
an over current or short-circuit current flows through the fuse, the fusible link will melt and open the circuit.
A device that protects a circuit by fusing opens its current-responsive element when an over-current passes
through it. An over-current is either due to an overload or a short circuit condition.
The Underwriter Laboratories (UL) classifies fuses by letters e.g. class CC, T, K, G, J, L, R, and so forth. The
class letter may designate interrupting rating, physical dimensions, and degree of current limitation.
As per NEC and ANSI/IEEE standard 242 [2] – A current limiting fuse is a fuse that will interrupt all available
currents above its threshold current and below its maximum interrupting rating, limit the clearing time at rated
voltage to an interval equal to or less than the first major or symmetrical loop duration, and limit peak let-through
current to a value less than the peak that would be possible with the fuse replaced by a solid conductor of the
same impedance.
Fuse Construction:
The typical fuse consists of an element which is surrounded by filler and enclosed by the fuse body. The element
is welded or soldered to the fuse contacts (blades or ferrules).
The element is a calibrated conductor. Its configuration, mass and the materials employed are selected to
achieve the desired electrical and thermal characteristics.
The element provides the current path through the fuse. It generates heat at a rate dependent on its resistance
and the load current.
The heat generated by the element is absorbed by the filler and passed through the fuse body to the surrounding
air. The filler material, such as quartz sand, provides effective heat transfer and allows for the small element
cross-section typical in modern fuses.
The effective heat transfer allows the fuse to carry harmless overloads .The small element cross section melts
quickly under short-circuit conditions. The filler also aids fuse performance by absorbing arc energy when the fuse
clears an overload or short circuit.
When a sustained overload occurs, the element will generate heat at a faster rate than the heat can be passed to
the filler. If the overload persists, the element will reach its melting point and open. Increasing the applied current
will heat the element faster and cause the fuse to open sooner. Thus, fuses have an inverse time current
characteristic: that is, the greater the over current, the less time required for the fuse to open the circuit.
This characteristic is desirable because it parallels the characteristics of conductors, motors, transformers, and
other electrical apparatus. These components can carry low-level overloads for relatively long periods without
damage. However, under high-current conditions, damage can occur quickly. Because of its inverse time current
characteristic, a properly applied fuse can provide effective protection over a broad current range, from low-level
overloads to high-level short circuits.
Commonly used terms for Fuse
I2t (Ampere Square second): A measure of the thermal energy associated with current flow.I2t is equal to (I
RMS) 2 X t, where is the duration of current flow in seconds.A measure of thermal energy associated with current
flow. It can be expressed as melting I2t, arcing I2t or the sum of them as Clearing I2t. Clearing I2t is the total I2t
passed by a fuse as the fuse clears a fault, with t being equal to the time elapsed from the initiation of the fault to
the instant the fault has been cleared. Melting I2t is the minimum I2t required to melt the fuse element
Interrupting Rating (Abbreviated I.R.)Same as breaking capacity or short circuit rating. The maximum current a
fuse can safely interrupt at rated voltage. Some special purpose fuses may also have a ―Minimum Interrupting
Rating‖. This defines the minimum current that a fuse can safely interrupt. Safe operation requires that the fuse
remain intact. Interrupting ratings may vary with fuse design and range from 35 amperes AC for some 250V
metric size (5 x 20mm) fuses up to 200,000 amperes AC for the 600V industrial fuses (for example, ATDR
series).
Clearing I2t: The total I2t passed by a fuse as the fuse clears a fault, with being equal to the time elapsed from
the initiation of the fault to the instant the fault has been cleared.
Melting I2t: The minimum I2t required melting the fuse element.
Ampere Rating: The continuous current carrying capability of a fuse under defined laboratory conditions. The
ampere rating is marked on each fuse.
Available Fault Current: The maximum short-circuit current that can flow in an unprotected circuit.
Coordination: The use of over current protective devices that will isolate only that portion of an electrical system
that has been overloaded or faulted.
Current limiting Range: currents a fuse will clear in less than ½ cycles, thus limiting the actual magnitude of
current flow.
Element: A calibrated conductor inside a fuse that melts when subjected to excessive current. The element is
enclosed by the fuse body and may be surrounded by an arc quenching medium such as silica sand. The
element is sometimes referred to as a link.
Fast acting Fuse: This is a fuse with no intentional time-delay designed into the overload range. It is sometimes
referred to as a ―single-element fuse‖ or ―non-delay fuse.‖
Fault Current: Short-circuit current that flows partially or entirely outside the intended normal load current path of
a circuit component. Values may be from hundreds to many thousands of amperes.
1. Ferrule: copper mounting terminals of fuses with amp ratings up to 60 amperes. The cylindrical terminals at each
end of a fuse fit into fuse clips.
Current limiting Fuse: A fuse that meets the following three conditions:
1. 1. interrupts all available over currents within its interrupt rating.
1. 2. Within its current limiting range, limits the clearing time at rated voltage to an interval equal to, or less than, the
first major or symmetrical current loop duration.
1. 3. Limits peak let-through current to a value less than the available peak current. The maximum level of fault
current that the fuse has been tested to safely interrupt.
Arcing timeThe amount of time from the instant the fuse link has melted until the over current is interrupted, or
cleared.
Clearing time The total time between the beginning of the over current and the final opening of the circuit at rated
voltage by an over current protective device. Clearing time is the total of the melting time and the arcing time.
Fast acting fuse A fuse which opens on overload and short circuits very quickly. This type of fuse is not designed
to withstand temporary overload currents associated with some electrical loads. UL listed or recognized fast
acting fuses would typically open within 5 seconds maximum when subjected to 200% to 250% of its rated
current.IEC has two categories of fast acting fuses:
1. F= quick acting, opens 10x rated current within 0.001 seconds to 0.01 seconds
1. FF = very quick acting, opens 10x rated current in less than 0.001 seconds
Overload Can be classified as an over current which exceeds the normal full load current of a circuit by 2 to 5
times its magnitude and stays within the normal current path.
Resistive load An electrical load which is characterized by not drawing any significant inrush current. When a
resistive load is energized, the current rises instantly to its steady state value, without first rising to a higher value.
RMS Current The R.M.S. (root mean square) value of any periodic current is equal to the value of the direct
current which,flowing through a resistance, produces the same heating effect in the resistance as the periodic
current does.
Short circuit An over current that leaves the normal current path and greatly exceeds the normal full load current
of the circuit by a factor of tens, hundreds, or thousands times.
Time delay fuse A fuse with a built-in time delay that allows temporary and harmless inrush currents to pass
without operating, but is so designed to open on sustained overloads and short circuits. UL listed or recognized
time delay fuses typically open in 2 minutes maximum when subjected to 200% to 250% of rated current. IEC has
two categories of time delay fuses:
1. T= time lag, opens 10x rated current within 0.01 seconds to 0.1 seconds
1. TT = long time lag, opens 10x rated current within 0.1 seconds to 1 second
Voltage rating A maximum open circuit voltage in which a fuse can be used, yet safely interrupt an over current.
Exceeding the Voltage rating of a fuse impairs its ability to clear an overload or short circuit safely.
Over current A condition which exists in an electrical circuit when the normal load current is exceeded. Over
currents take on two separate characteristics-overloads and short circuits.
Threshold Current: The magnitude of symmetrical RMS available current at the threshold of the current-limiting
range, where the fuse becomes current-limiting when tested to the industry standard.
Threshold ratio: A threshold ratio is a relationship of threshold current to a fuse‘s continuous current rating.
Threshold Ratio = Fuse Threshold Current / Fuse Continuous Current.
CLASS RK5 65
CLASS RK1 30
CLASS J 30
CLASS CC 30
A current limiting fuse may be current limiting or may not be current limiting. The current limiting characteristic
depends on the threshold ratio and available fault current.
Let‘s consider an example of 1500 kVA radial service feeding a fusible switchboard with 2000 amps class L fuses.
As per ANSI C 57 [3] standard, a typical impedance value for this size of a transformer is 5.75%; this value is a
key factor in calculating the short circuit current.
All utility‘s network provides a specific fault current at a specific location which depends on various factors, e.g.;
cable lengths, cable size, X/R ratio and etc. If we ignore this limitation and assume that there is an unlimited fault
current available from a utility, then let‘s calculate short circuit current from a 1500 kVA transformer at 480 volts
The formula to calculate short circuit current (Isc)
ISC = (KVA X 10,000) / (1.732 X VOLT X %Z).
ISC = 1500 X 10,000 / 1.732 X 480 X 5.75
ISC = 31378.65 Amp.
Type of Fuse:
A fuse unit essentially consists of a metal fuse element or link, a set of contacts between which it is fixed and a
body to support and isolate them. Many types of fuses also have some means for extinguishing the arc which
appears when the fuse element melts. In general, there are two categories of fuses.
1. Low voltage fuses.
2. High voltage fuses.
Usually isolating switches are provided in series with fuses where it is necessary to permit fuses to be replaced or
rewired with safety.
In absence of such isolation means, the fuses must be so shielded as to protect the user against accidental
contact with the live metal when the fuse is being inserted or removed.
The fuse carrier is a separate part and can be taken out or inserted in the base without risk, even without
opening the main switch. If fuse holder or carrier gets damaged during use, it may be replaced without replacing
the complete unit.
The fuse wire may be of lead, tinned copper, aluminum or an alloy of tin lead.
The actual fusing current will be about twice the rated current. When two or more fuse wire are used, the wires
should be kept apart and a de rating factor of 0.7 to 0.8 should be employed to arrive at the total fuse rating.
The specification for re wire able fuses are covered by IS: 2086-1963. Standard ratings are 6, 16, 32, 63, and
100A.
A fuse wire of any rating not exceeding the rating of the fuse may be used in it that is a 80 A fuse wire can be
used in a 100 A fuse, but not in the 63 A fuse. On occurrence of a fault, the fuse element blows off and the circuit
is interrupted. The fuse carrier is pulled out, the blown out fuse element is replaced by new one and the supply
can is resorted by re-inserting the fuse carrier in the base.
Though such fuses have the advantage of easy removal or replacement without any danger of coming into the
contact with a lie part and negligible replacement cost but suffers from following disadvantages:
1. Unreliable Operations.
2. Lack of Discrimination.
3. Small time lag.
4. Low rupturing capacity.
5. No current limiting feature.
6. Slow speed of operations.
The breaking or rupturing capacity is of the order of 4k A for 2 and 4 ampere fuses the 16k A for 63 A fuses.
D-type cartridge fuse have none of the drawbacks of the re wire able fuses. Their operation is reliable.
Coordination and discrimination to a reasonable extent and achieved with them.
The usual fusing factor for the link fuses is 1.45. the fuses for special applications may have as low as a fusing
factor as 1.2.
The specification for medium voltage HRC link fuses are covered under IS: 2202-1962.
It can be replaced on a live circuit at no load with the help of a special insulated fuse puller.
Fuse Class:
(1) Class L, fuses
They provide a minimum time delay of 4 seconds at 500% of their rated current to handle harmless inrush
currents, plus they are 20% more current limiting than any other Class L fuse.
That means optimal over current protection for service entrances, large motors, feeders and other circuits.
Range from 601 to 6000 amperes, 600V AC, 300kA
I.R., and an exclusive 500V DC, 100kA I.R., through 3000A.
Features
Fastest operation under short circuit conditions
Most current limiting for lowest peak let-thru current
Replaces all older Class L fuses
Pure silver links for long fuse life
AC and DC ratings
High-grade silica filler for fast arc quenching
Applications
Mains and feeders
Large motors
Lighting, heating and general loads
Power circuit breaker backup
UPS DC links, battery disconnects and other DC applications
Application notes
Mains and feeders — Can size at 100% of expected full load, unless equipment manufacturers specify
Motor starters — Consult your motor control manufacturer‘s recommendations.
Lighting, heating and general loads — Can size at 100% to 125%, depending on load make-up.
Transformers — Due to the high inrush currents that can be experienced with transformers, size fuse to carry 12
times transformer full load for 0.1 second and 25 times full load for 0.01 second.
½ 2 1 0.8
7.5 22 11 9
10 28 14 11
15 42 21 17
20 54 27 22
25 68 34 27
Fuse Ratings
Fuses with an A-C voltage rating may be applied at system voltages below the fuse voltage rating, but not at
voltages above the fuse voltage rating.
The other A-C fuse ratings remain the same at applied voltages below the fuse voltage rating.
A-C rated fuses should not be applied in D-C voltage circuits unless D-C application ratings are provided by the
fuse manufacturer.
Except for some special purpose fuses, D-C ratings are not usually shown on fuse labels.
The operating frequency (Hertz) will affect fuse characteristics in various ways.
Time/Current Curves will not shift and fuse ratings will not change from 1-100 Hertz in normal applications. If
ferrous hardware is used to mount the fuses, eddy current heating could alter the ratings.
Above 100 Hertz, ―skin effect‖ could alter the fuses‘ rating characteristics. This effect must be analyzed on an
individual application basis.
Source: http://electricalnotes.wordpress.com/2011/04/21/fuse/