PCD
PCD
Girder spacing =
Top cover =
(includes ½ in. integral wearing surface)
Bottom cover =
Concrete density =
DECK THICKNESS
The specifications require that the minimum thickness of a concrete deck, excluding any provisions for grinding,
grooving and sacrificial surface, should not be less than 7 in. (S9.7.1.1). Thinner decks are acceptable if approved
by the bridge owner. For slabs with depths less than 1/20 of the design span, consideration should be given to
prestressing in the direction of that span in order to control cracking.
Most jurisdictions require a minimum deck thickness of 8 in., including the ½ inch integral wearing surface.
In addition to the minimum deck thickness requirements of S9.7.1.1, some jurisdictions check the slab thickness
using the provisions of S2.5.2.6.3. The provisions in this article are meant for slab-type bridges and their purpose is
to limit deflections under live loads. Applying these provisions to the design of deck slabs rarely controls deck slab
design.
Design of Deck
For this example, a slab thickness of 8 in., including the ½ inch integral wearing surface, is assumed. The integral
wearing surface is considered in the weight calculations. However, for resistance calculations, the integral wearing
surface is assumed to not contribute to the section resistance, i.e., the section thickness for resistance calculations
is assumed to be 7.5 in.
Minimum = 0.9
Maximum=1.2
Minimum = 0.65
Maximum = 1.5
It is not intended to maximize the load effects by applying the maximum load factors to some bays of the deck and
the minimum load factors to others. Therefore, for deck slabs the maximum load factor controls the design and the
minimum load factor may be ignored.
Dead loads represent a small fraction of the deck loads. Using a simplified approach to determine the deck dead
load effects will result in a negligible difference in the total (DL + LL) load effects. Traditionally, dead load positive
and negative moments in the deck, except for the overhang, for a unit width strip of the deck are calculated using
the following approach:
M = wl2/c
where:
M = dead load positive or negative moment in the deck for a unit width strip (k-ft/ft)
w = dead load per unit area of the deck (ksf) l = girder spacing (ft.)
c= constant, typically taken as 10 or 12
The dead load moments due to the self weight and future wearing surface are
calculated assuming c = 10.
Self weight of the deck = 8(150)/12 = 100 psf
Using the approximate method of deck analysis (S4.6.2), live load effects may be determined by
modeling the deck as a beam supported on the girders. One or more axles may be placed side by
side on the deck (representing axles from trucks in different traffic lanes) and move them
transversely across the deck to maximize the moments (S4.6.2.1.6). To determine the live load
moment per unit width of the bridge, the calculated total live load moment is divided by a strip
width determined using the appropriate equation from Table S4.6.2.1.3-1. The following
conditions have to be satisfied when determining live load effects on the deck:
Minimum distance from center of wheel to the inside face of parapet = 1 ft. (S3.6.1.3)
(Note: the “three lanes” situation never controls for girder spacings up to 16 ft.)
Fatigue need not be investigated for concrete slabs in multi-girder bridges (S9.5.3 and S5.5.3.1)
Resistance factors, j, for moment: 0.9 for strength limit state (S5.5.4.2)
1.0 for extreme event limit state (S1.3.2.1)
The reinforcement determined in this section is based on the maximum positive moment in the deck. For interior
bays of the deck, the maximum positive moment typically takes place at approximately the center of each bay. For
the first deck bay, the bay adjacent to the overhang, the location of the maximum design positive moment varies
depending on the overhang length and the value and distribution of the dead load. The same reinforcement is
typically used for all deck bays.
Factored loads
Live load
From Table SA4.1-1, for the girder spacing of 9’-9” (conservative):
Unfactored live load positive moment per unit width = 6.74 k-ft/ft
Maximum factored positive moment per unit width = 1.75(6.74) = 11.80 k-ft/ft
This moment is applicable to all positive moment regions in all bays of the deck (S4.6.2.1.1).
Deck weight
1.25(0.93) = 1.16 k-ft/ft
Future wearing surface
1.5(0.28) = 0.42 k-ft/ft
Dead load + live load design factored positive moment (Strength I limit state)
MDL+LL= 11.8 + 1.16 + 0.42
= 13.38 k-ft/ft
For rectangular section behavior, the depth of the section in compression, c, is determined using Eq. S5.7.3.1.1-4:
𝐴𝑝𝑠 𝑓𝑝𝑢 +𝐴𝑠 − 𝐴′𝑠 𝑓′𝑦
C = 𝑓𝑝𝑢
0.85𝑓′𝑐 𝑏1 𝑏+𝑘𝐴𝑝𝑠
𝑑𝑝
where:
Aps = area of prestressing steel
fpu = specified tensile strength of prestressing steel
fpy = yield strength of prestressing steel
As = area of mild steel tension reinforcement
A¢s = area of compression reinforcement
fy = yield strength of tension reinforcement
f¢y = yield strength of compression reinforcement
b = width of rectangular section
dp = distance from the extreme compression fiber to the centroid of the prestressing
tendons
c = distance between the neutral axis and the compressive face
ß1 = stress block factor specified in S5.7.2.2
For reinforced concrete sections (no prestressing) without reinforcement on the compression side of the section,
the above equation is reduced to:
As f y
c = 0.85 fc¢ b 1 b
k’ = Mu/(bd2)
𝑓𝑐′ 2𝑘′
r = 0.85( 𝑓𝑦 )(1.0 - √1.0 − 0.85𝑓′𝑐)
AS = rde
A different method to determine the required area of steel is based on using the above equation for “a” and “c” with
the Eq. S5.7.3.2.2-1 as shown below. The nominal flexural resistance, Mn, may be taken as:
Mn = Apsfps(dp – a/2) + Asfy(ds – a/2) – A¢sf¢y(d¢s – a/2) + 0.85f¢c(b – bw)b1hf(a/2 – hf/2)
(S5.7.3.2.2-1)
where:
fps = average stress in prestressing steel at nominal bending resistance specified in Eq. S5.7.3.1.1-1 (ksi)
ds = distance from extreme compression fiber to the centroid of nonprestressed tensile reinforcement
d's = distance from extreme compression fiber to the centroid of compression reinforcement
b= width of the compression face of the member
bw = web width or diameter of a circular section
hf = compression flange depth of an I or T member
For rectangular reinforced concrete sections (no prestressing) without reinforcement on the compression side of
the section, the above equation is reduced to:
Mn = ASfy(ds-a/2)
From the equations for “c” and “a” above, substituting for:
𝐴𝑠 𝑓𝑦
A = cb1 = 0.85𝑓′ in the equation for Mn above yields:
𝑐𝑏
𝑓𝑦 2
Mn = ASfy(ds-a/2) = fydsAs – (1.7𝑓𝑐′𝑏)As2
Only As is unknown in this equation. By substituting for b = 12 in., the required area of reinforcement per unit width
can be determined by solving the equation.
Both methods outlined above yield the same answer. The first method is used throughout the following
calculations.
For the positive moment section:
de = effective depth from the compression fiber to the centroid of the tensile force in the tensile
reinforcement (in.)
= 0.00688
Therefore,
Required As = rde = 0.00688(6.19) = 0.0426 in2/in.
Required #5 bar spacing with bar area 0.31 in2 = 0.31/0.0426 = 7.28 in.
b1 = ratio of the depth of the equivalent uniformly stressed compression zone assumed in the
strength limit state to the depth of the actual compression zone
= 0.85 for f¢c = 4 ksi (S5.7.2.2)
= 0.78/0.85 = 0.918 in.
dc = thickness of concrete cover measured from extreme tension fiber to center of bar located closest
thereto (in.)
= 1.3125 in. < (2 + ½ bar diameter) in. OK
A = area of concrete having the same centroid as the principal tensile reinforcement and bounded by the
surfaces of the cross-section and a straight line parallel to the neutral axis, divided by the number of
bars (in2)
2(1.3125)(7)
18.375 in2
Dead load + live load service load positive moment = 7.95 k- ft/ft
b. Dead load
Factored dead load moments at the design section for negative moment:
Dead weight
1.25(0.93) = 1.16 k-ft/ft
Future wearing surface
1.5(0.28) = 0.42 k-ft/ft
Dead Load + live load design factored negative moment = 1.16 + 0.42 + 7.37 = 8.95 k-ft/ft
= distance from compression face to centroid of tension reinforcement (in.) = total thickness – top
cover – ½ bar diameter
Assume #5 bars; bar diameter = 0.625 in., bar area = 0.31 in2
= 8 – 2 ½ – ½ (0.625) = 5.19 in.
Required area of steel = 0.0339 in2/in.
Required spacing = 0.31/0.0339 = 9.15 in.
Use #5 at 9 in. spacing
As indicated earlier, checking the minimum and maximum reinforcement is not expected to control in deck slabs.
Transformed section properties may be calculated as done for the positive moment section in Design Step 4.8.
Refer to Figure 4-5a for the section dimensions and location of the neutral axis. The calculations are shown below.
Maximum dead load + live load service load moment = 5.42 k- ft/ft
n=8
Itransformed = 43.83 in4
LONGITUDINAL REINFORCEMENT
Bottom distribution reinforcement (S9.7.3.2)
Negative Moment Region, I.e., Over the Intermediate Support Of the Girder
For simple span precast girders made continuous for live load: design according to S5.14.1.2.7
(Notice that for continuous steel girders, this reinforcement is designed according to S6.10.3.7.)
The required reinforcement area is determined during girder design. See Section 5.6 for the calculations for this
reinforcement.
Provided reinforcement area = 14.65 in2
Use #6 bars at 5.5 in. spacing in the top layer
As ³ 0.11Ag/fy (S5.10.8.2-1)
where:
Ag = gross area of the section (in2)
12(7.5)
90 in2/ft. width of deck
As req = 0.11(90/60)
= 0.165 in2/ft. width of deck
This area should be divided between the two surfaces, As req per surface = 0.0825 in2/ft. width of deck.
Assuming longitudinal reinforcement is #4 bars at 12 in. spacing:
As provided = 0.2 in2/ft. width of deck > 0.0825 in2/ft .width of deck required. OK
Design of Superstructure
LIVE LOAD DISTRIBUTION FACTORS
(S4.6.2.2)
The AASHTO-LRFD Specifications allow the use of advanced methods of analysis to determine the live
load distribution factors. However, for typical bridges, the specifications list equations to calculate the
distribution factors for different types of bridge superstructures. The types of superstructures covered by
these equations are described in Table S4.6.2.2.1-1. From this table, bridges with concrete decks
supported on precast concrete I or bulb-tee girders are designated as cross-section “K”. Other tables in
S4.6.2.2.2 list the distribution factors for interior and exterior girders including cross-section “K”. The
distribution factor equations are largely based on work conducted in the NCHRP Project 12-26 and have
been verified to give accurate results compared to 3-dimensional bridge analysis and field measurements.
The multiple presence factors are already included in the distribution factor equations except when the
tables call for the use of the lever rule. In these cases, the computations need to account for the multiple
presence factors. Notice that the distribution factor tables include a column with the heading “range of
applicability”. The ranges of applicability listed for each equation are based on the range for each
parameter used in the study leading to the development of the equation. When the girder spacing exceeds
the listed value in the “range of applicability” column, the specifications require the use of the lever rule
(S4.6.2.2.1). One or more of the other parameters may be outside the listed range of applicability. In this
case, the equation could still remain valid, particularly when the value(s) is(are) only slightly out of the
range of applicability. However, if one or more of the parameters greatly exceed the range of applicability,
engineering judgment needs to be exercised.
Article S4.6.2.2.2d of the specifications states: “In beam-slab bridge cross-sections with
diaphragms or cross-frames, the distribution factor for the exterior beam shall not be taken less than that
which would be obtained by assuming that the cross-section deflects and rotates as a rigid cross-section”.
This provision was added to the specifications because the original study that developed the distribution
factor equations did not consider intermediate diaphragms. Application of this provision requires the
presence of a sufficient number of intermediate diaphragms whose stiffness is adequate to force the cross
section to act as a rigid section. For prestressed girders, different jurisdictions use different types and
numbers of intermediate diaphragms. Depending on the number and stiffness of the intermediate
diaphragms, the provisions of S4.6.2.2.2d may not be applicable. For this example, one deep reinforced
concrete diaphragm is located at the midspan of each span. The stiffness of the diaphragm was deemed
sufficient to force the cross-section to act as a rigid section, therefore, the provisions of S4.6.2.2.2d apply.
Notice that the AASHTO Standard Specifications express the distribution factors as a fraction of wheel
lines, whereas
Notice that fatigue in the prestressing steel need not be checked for conventional prestressed
girders (S5.5.3) when maximum stress in the concrete at Service III limit state is taken according
to Table S5.9.4.2.2-1. This statem ent is valid for this example. The fatigue distribution factors are
calculated in the following sections to provide the user with a complete reference for the
application of the LRFD distribution factors.
Required information:
AASHTO Type I-Beam (28/72)
Noncomposite beam area, Ag = 1,085 in2
Noncomposite beam moment of inertia, Ig = 733,320 in4
Deck slab thickness, ts = 8 in.
Span length, L = 110 ft.
Girder spacing, S = 9 ft. - 8 in.
Modulus of elasticity of the beam, EB = 4,696 ksi (S5.4.2.4)
Modulus of elasticity of the deck, ED = 3,834 ksi (S5.4.2.4)
C.G. to top of the basic beam = 35.62 in.
C.G. to bottom of the basic beam = 36.38 in.
Design Step Calculate n, the modular ratio between the beam and the deck.
5.1.1
n = EB/ED (S4.6.2.2.1-2)
4,696/3,834
1.225
Design Step Calculate eg, the distance between the center of gravity of the noncomposite beam and
the deck. Ignore the thickness of the haunch in determining eg. It is also possible to ignore the
integral wearing surface, i.e., use ts = 7.5 in. However the difference in the distribution factor will
be minimal.
eg = NAYT + ts/2
= 35.62 + 8/2
= 39.62 in.
Calculate the moment distribution factor for an interior beam with two or more design lanes loaded
using Table S4.6.2.2.2b-1.
Design Step According to S4.6.2.2.2e, a skew correction factor for moment may be applied for bridge
skews greater than 30 degrees. The bridge in this example is skewed 20 degrees, and, therefore,
no skew correction factor for moment is allowed.
Calculate the moment distribution factor for an interior beam with one design lane loaded using
Table S4.6.2.2.2b-1.
For single- lane loading to be used for fatigue design, remove the multiple presence factor of 1.2.
DM = 0.542/1.2
= 0.452 lane (3)
1.047
Design Step Calculate the shear distribution factor for an interior beam with two or more design lanes 5.1.7
loaded using Table S4.6.2.2.3a-1.
0.2 + (9.667/12) – (9.667/35)2
0.929 lane
DV = 1.047(0.929)
= 0.973 lane (4)
Design Step Calculate the shear distribution factor for an interior beam with one design lane loaded 5.1.8 using
Table S4.6.2.2.3a-1.
DV = 0.36 + (S/25.0)
= 0.36 + (9.667/25.0)
= 0.747 lane
DV = 1.047(0.747)
= 0.782 lane (5)
For single-lane loading to be used for fatigue design, remove the multiple presence factor of 1.2.
DV = 0.782/1.2
= 0.652 lane (6)
Design Step From (1) and (2), the service and strength limit state moment distribution factor for the
interior girder is equal to the larger of 0.796 and 0.542 lane. Therefore, the moment distribution
factor is 0.796 lane.
From (3):
From (4) and (5), the service and strength limit state shear distribution factor for the interior girder
is equal to the larger of 0.973 and 0.782 lane. Therefore, the shear distribution factor is 0.973 lane.
From (6):
Calculate the moment distribution factor for an exterior beam with two or more design 5.1.11 lanes using Table
S4.6.2.2.2d-1.
DM = eDMInterior
e = 0.77 + de/9.1
where de is the distance from the centerline of the exterior girder to the inside face of the
curb or barrier.
e = 0.77 + 1.83/9.1
= 0.97
DM = 0.97(0.796)
= 0.772 lane (7)
Design Step Calculate the moment distribution factor for an exterior beam with one design lane using 5.1.12 the lever
rule as per Table S4.6.2.2.2d-1.
DM = [(3.5 + 6) + 3.5]/9.667
= 1.344 wheels/2
= 0.672 lane (8) (Fatigue)
Notice that this value does not include the multiple presence factor, therefore, it is adequate for
use with the fatigue limit state. For service and strength limit states, the multiple presence factor
for a single lane loaded needs to be included.
DM = 0.672(1.2)
= 0.806 lane (9) (Strength and Service)
Design Step Calculate the shear distribution factor for an exterior beam with two or more design lanes 5.1.13
loaded using Table S4.6.2.2.3b-1.
DV = eDVinterior
where:
e = 0.6 + de/10
= 0.6 + 1.83/10
= 0.783
DV = 0.783(0.973)
= 0.762 lane (10)
Design Step Calculate the shear distribution factor for an exterior beam with one design lane loaded
using the lever rule as per Table S4.6.2.2.3b-1. This value will be the same as the moment
distribution factor with the skew correction factor applied.
DV = 1.047(0.672)
= 0.704 lane (11) (Fatigue)
DV = 1.047(0.806)
= 0.845 lane (12) (Strength and Service)
Notice that S4.6.2.2.2d includes additional requirements for the calculation of the distribution
factors for exterior girders when the girders are connected with relatively stiff cross-frames that
force the cross-section to act as a rigid section. As indicated in Design Step 5.1, these provisions
are applied to this example; the calculations are shown below.
Design Step Additional check for rigidly connected girders (S4.6.2.2.2d) 5.1.15
The multiple presence factor, m, is applied to the reaction of the exterior beam (Table S3.6.1.1.2-
1)
m1 = 1.20 m2 = 1.00
m3 = 0.85
where:
= eccentricity of a design truck or a design land load from the center of gravity of the pattern
of girders (ft.)
= horizontal distance from the center of gravity of the pattern of girders to each girder (ft.)
Xext = horizontal distance from the center of gravity of the pattern to the exterior girder (ft.)
R = 1.2(0.477)
= 0.572 (Strength)
Add the multiple presence factor of 1.0 for two lanes loaded:
R = 1.0(0.776)
= 0.776 (Strength)
Add the multiple presence factor of 0.85 for three or more lanes loaded:
R = 0.85(0.899)
= 0.764 (Strength)
Design Step From (7) and (9), the service and strength limit state moment distribution factor for the
exterior girder is equal to the larger of 0.772 and 0.806 lane. Therefore, the moment distribution
factor is 0.806 lane.
From (8):
Additional Multiple
check for lanes NA 0.776 NA 0.776
rigidly loaded
connected
Single lane
girders NA 0.572 NA 0.572
loaded
Tables in
Single lane
S4.6.2.2.2 0.452 0.672 0.652 0.704
loaded
Additional Multiple
check for lanes NA NA NA NA
rigidly loaded
connected
Single lane
girders NA 0.477 NA 0.477
loaded
Calculate the dead load of the bridge superstructure components for the controlling
interior girder. Values for the exterior girder have also been included for reference. The
girder, slab, haunch, and exterior diaphragm loads are applied to the noncomposite
section; the parapets and future wearing surface are applied to the composite section.
Interior girder
Girder weight
where:
Ag = beam cross-sectional area (in2)
= 1,085 in2
g = unit weight of beam concrete (kcf)
= 0.150 kcf
DCgirder
(I) = (1,085/144)(0.150)
= 1.13 k/ft/girder
Girder weight
3.521 + ½(9.667)
8.35 ft.
Thickness = 4 in.
DChaunch = [42(4)/144](0.150)
= 0.175 k/ft/girder
Notice that the haunch weight in this example is assumed as a uniform load along the full length of
the beam. This results in a conservative design as the haunch typically have a variable thickness
that decreases toward the middle of the span length. Many jurisdictions calculate the haunch load
effects assuming the haunch thickness to vary parabolically along the length of the beam. The
location of the minimum thickness varies depending on the grade of the roadway surface at bridge
location and the presence of a vertical curve. The use of either approach is acceptable and the
difference in load effects is typically negligible. However, when analyzing existing bridges, it may
be necessary to use the variable haunch thickness in the analysis to accurately represent the
existing situation
Concrete diaphragm weight
For this example, arbitrarily assume that the thickness of the diaphragm is 10 in. The diaphragm
spans from beam to beam minus the web thickness and has a depth equal to the distance from
the top of the beam to the bottom of the web. Therefore, the concentrated load to be applied at the
locations above is:
According to the S4.6.2.2.1, the parapet weight may be distributed equa lly to all girders in the
cross section.
Weight/ft2
Width
DWFWS
(I)
Exterior Girder
Weight/ft2
Width
0.030 k/ft2
slab width – parapet width
0.030 k/ft2 8.35 – 1.6875
9.667 ft.
6.663 ft.
0.030(9.667)
0.030(6.663)
0.290 k/ft/girder
0.200 k/ft/girder
Notice that some jurisdictions divide the weight of the future wearing surface equally between all
girders (i.e. apply a uniform load of 0.26 k/ft to all girders). Article S4.6.2.2.1 states that permanent
loads of and on the deck may be distributed uniformly among the beams. This method would also
be acceptable and would minimally change the moments and shears given in the tables in Design
Step 5.3.
UNFACTORED AND FACTORED LOAD EFFECTS
Summary of loads
The dead load moments and shears were calculated based on the loads shown in Design
Step 5.2. The live load moments and shears were calculated using a generic live load
analysis computer program. The live load distribution factors from Design Step 5.1 are
applied to these values.
(ft.) (k-ft) (k-ft) (k-ft) (k-ft) (k-ft) (k-ft) (k-ft) (k-ft) (k-ft)
0 47 0 0 0 0 0 0 0 0
Based on the analysis results, the interior girder controls the design. The remaining
sections covering the superstructure design are based on the interior girder analysis. The
exterior girder calculations would be identical.
The distance from the neutral axis to the compression face of the member may be
determined as follows:
+ - A ¢f ¢ - 0.85 ß f ¢ (b - b )h
Aps f
pu As f y s y 1 c w f
c =
f
pu
0.85 fc¢ ß1 bw + k A ps
dp
- A¢ f
+ ¢
Aps f
pu As f y sy
c =
f
pu
0.85 fc¢ ß1 b + k A ps dp
T-sections where the neutral axis lies in the flange, i.e., “c” is less than the slab thickness,
are considered rectangular sections.
72 + 7.5
79.5 in.
= 6.73(270)/[0.85(4)(0.85)(111) + 0.28(6.73)(270/74.5)]
5.55 in. < structural slab thickness = 7.5 in.
The assumption of the section behaving as a rectangular section is correct.
Notice that if “c” from the calculations above was greater than the structural slab thickness (the integral
wearing surface is ignored), the calculations for “c” would have to be repeated assuming a T-section
behavior following the steps below:
Assume the neutral axis lies within the precast girder flange thickness and calculate “c”. For this
calculation, the girder flange width and area should be converted to their equivalent in slab
concrete by multiplying the girder flange width by the modular ratio between the precast girder
concrete and the slab concrete. The web width in the equation for “c” will be substituted for using
the effective converted girder flange width. If the calculated value of “c” exceeds the sum of the
deck thickness and the precast girder flange thickness, proceed to the next step. Otherwise, use
the calculated value of “c”.
Assume the neutral axis is below the flange of the precast girder and calculate “c”. The term “0.85
f¢cb1(b – bw)” in the calculations should be broken into two terms, one refers to the contribution of
the deck to the composite section flange and the second refers to the contribution of the precast
girder flange to the composite girder flange.