Distribution Relays Brochure - FULL
Distribution Relays Brochure - FULL
Distribution Relays Brochure - FULL
ABB is a global leader in Power and Automation The product offering includes a wide spectrum of
technologies that enable utility and industry technologies across the entire voltage range
customers to improve performance while lowering including indoor and outdoor circuit breakers, air
environmental impact. The ABB Group operates in and gas insulated switchgear, disconnectors,
around 100 countries and employs over 1,08,000 capacitor banks, reactive power compensators,
people. power transformers, distribution transformers,
instrument transformers, Compact Secondary
In India, ABB serves customers with a complete
Substations (CSS) and Ring Main Units (RMU).
range of power and automation technologies. The
company has a vast installed base, an extensive
manufacturing facilities and a countrywide marketing
and service presence. Advantage ABB
The Power Technologies division offers electric, gas 9 120 years of technology and innovation
and water utilities as well as industriaal and
commercial customers a wide range of products,
9 Unparalleled domain competence
systems and services for power generation, 9 Global experience
transmission amd distribution. ABB’s turnkey
9 Complete solution capabilities
solution capabilities in the sector range from bulk
power transmission, substations and complete 9 Large installed base
electrification to utility automation and distribution 9 Environment-friendly technologies
systems.
2 ABB
Innovative technology for complete protection of your
distribution systems
With a wide range of products and systems based on The products manufactured are approved by leading
electromechanical, static and numerical micro-processor based consultants in the electrical engineering field such as EIL,
platforms, ABB offers complete protection solutions for utility and MECON, PDIL, TCE, DCL, DESIN, HOLTAC, FISHNER
industry power distribution networks for improved performance, Technimont ICB, H&G, UDHE etc and are widely used by major
reliability and safety. utilities, industries and OEM’s.
ABB solutions include application engineering, testing &
commissioning, after sales service, troubleshooting and training.
Training facilities 5
Type of Relay
VHXm22_ /VHXm23 Instantaneous / Definite Time Under and Over Voltage Relay 8-9
RXPQ8n, PQ8n, PN8n, RXPQ8n High Speed Trip / No Volt Relay 32-33
SPAU130C Numerical three phase Under voltage and Over voltage relay 48-49
ABB 3
State of the art manufacturing facilities
Quality policy
Our quality policy is aimed at fulfilling customers
requirement in terms of quality, on time delivery and
services. All our products and services are seen as
an expression of quality, and each delivery is aimed
at creating a recommendation for further business.
4 ABB
Training facilities
ABB 5
InverseTime Overcurrent and Earth Fault Relay type ICM21_
Features
Single pole Electromechanical draw out design
Reliable, robust Ferraris measuring system without gearing
/ coupling
Range of current setting 1:4, adjustable in 7 steps
Plug-in active part, the CT connections being automatically
short-circuited when the relay is withdrawn.
Separate double-pole tripping relay with indicator, for high
contact rating
Temperature -compensated measuring system
Range of time setting 10-100%
Specification
CT input ( In ) : 1 or 5 Amp.
Setting range for IDMT unit ( Iset ) : Phase O/C - 50 - 200% x In Earth Fault - 10-40% or 20-80% x In
Setting range for Inst. Unit : 4-20 x Iset or 2.5-10 x Iset
Rated Frequency : 50 Hz
Permissible sustained current (Thermal withstand) : 2 x In continuous 100 x In for 1 Sec.
Pick up : 1.1 times of setting
Operating Time : As per IDMT characteristics conf. BS142
Reset current : > 0.9 x Iset
Reset time : 9.5 Sec
Max. Overrun : 0.02 Sec
Max. Error : ± 10% for 2 x I, ± 5% for 4 - 20 x I
CT Burden : 3.5 VA at Min. and 4.8 VA at Max.Setting
Number of Output Contacts : 2 NO or 1NO+1NC for ICM21NP & P 4 NO or 2 NO+2NC for ICM21KP
Output Contact rating : 10 Amp. Cont. & 30 Amp. Making
Rated Auxiliary Supply : 24, 30, 48, 110, 220,250 VDC
Burden on Aux. Supply : 3W
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -I Case
6 ABB
Wiring Diagrams
ICM21NP, ICM21BNP
ICM21KP, ICM21BKP
ICM21P, ICM21BP
ABB 7
Instantaneous / Definite Time Under and Over Voltage Relay type
VHXm22_ / VHXm23
Features
Single pole Static draw-out type design
Variable Voltage Settings
Used for U/V and O/V protection of Generator, Motor,
Capacitor Transformer
Built in timer with variable time delay settings
Hand reset flag for operation indication
Separate built in tripping output relay for high contact rating
Robust construction
Specification
PT input ( Un ) : 63.5V, 110V, 240V AC
Setting range for U/V VHXm22A / B : 40-80% of Un
Setting range for O/V VHXm23 A / B : 80-140% of Un
Operating time for Inst. VHXm22A / 23 A : < 60 mSec
Time Delay Range for VHXm22B / 23 B : 0.1-1Sec, 0.5-5Sec, 1-10 Sec
Rated Frequency : 50 Hz
Reset Ratio
for Over Voltage : > 90% x Un
for Under Voltage : < 110% x In
Max. Error : ± 5%
VT Burden : 0.5 VA
No. of Output Contact : 3 NO + 3 NC or 6NO
Output Contact rating : 5 Amp. Cont. & 25 Amp. Making
Rated Auxiliary Supply : 24, 30, 48, 110, 220 VDC
Burden on Aux. Supply : 8W /11W (quiescent / operation cond.)
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -I Case
8 ABB
Wiring Diagrams
ABB 9
Instantaneous Circulating Current Relay type IRXm
Features
Single pole Static draw-out type design
Sensitive High speed protection on internal faults
Operation largely immune to DC components and harmonics
Plug-in active part, the CT connections being automatically
short-circuited when the relay is withdrawn.
Used as Sensitive E/F, High Imp. Restricted E/F protection of
Transformer & Generator, High Imp. Differential protection of
Motor, Generator, Busbar
Also suitable for Sensitive definite time E/F when used
with timer
Specification
CT input ( In ) : 1 and 5 Amp.
Setting range : 0.05 - 50% x In ( 0.05 - 5% x In in 10 equal steps and 5 - 50% x In in 10
equal steps both setting ranges selectable at site )
Rated Frequency : 50 Hz
Permissible sustained current (Thermal withstand) : 4 x In continuous 100 x In for 1 Sec.
Pick up : 1.1 times of setting
Operating Time : < 25 mSec
Reset current : > 0.9 x Iset
Max. Error : ± 5%
CT Burden : < 0.5 VA
Number of Output Contacts : 2 NO + 1NC
Output Contact rating : 5 Amp. Cont. & 10 Amp. Making
Rated Auxiliary Supply : 24, 30, 48, 110, 220,250 VDC
Burden on Aux. Supply : 5.3 W Max.
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -I Case
Note : The external stabilizing resistor is supplied along with relay. The total impedance of the relay and series stabilising resistor is usually low enough to
prevent the CT developing voltages over 2 kV during max. internal faults, but in some applications a non-linear resistor is required to limit this voltage.
10 ABB
Wiring Diagrams
IRXm
ABB 11
Instantaneous Overcurrent and Earth Fault Relay type IKM2
Features
Single pole Electromechanical draw out design
Wide current setting range
Used to protect elect.installations & line systems against
short circuit.
Plug-in type active part, the CT connections being
automatically short-circuited when the relay is withdrawn.
Separate double-pole tripping contactor with indicator, for
high cont. rating
Also suitable for definite time operation when used with timer.
Robust construction
Specification
CT input ( In ) : 1 or 5 Amp.
Setting range for O/C : (50-200%) x 5 x In or (50-200%) x 10 x In
Setting range for E/F : (10-40%) x 5 x In or (10-40%) x 10 x In or (20-80%) x 5 x In or (20-80%) x 10 x In
Rated Frequency : 50 Hz
Permissible sustained current (Thermal withstand) : 2 x In continuous 100 x In for 1 Sec.
Pick up : 1.1 times of setting
Operating Time : Max. 70 mSec
Time Delay Range for DMT : 0.1-1Sec, 0.5-5Sec, 1-10 Sec ( with timer )
Reset current : 1.2-2.5 x Iset
Max. : ± 10%
CT Burden : 3.5 VA at Min. and 4.8 VA at Max.Setting
Number of Output Cont. : 2 NO or 1NO+1NC
Output Contact rating : 10 Amp. Cont. & 30 Amp. Making
Rated Auxiliary Supply : 24, 30, 48, 110, 220,250 VDC
Burden on Aux. Supply : 3W
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -I Case
12 ABB
Wiring Diagrams
KM2
ABB 13
Biased Transformer Differential Relay type RADSB
Features
Triple pole Static 2 winding differential relay for phase &
ground faults
Variable percentage restraint for external fault security and
on-load tap changer transformer protection
Second harmonic restraint from all three phases for inrush
security
Fifth harmonic restraint from all 3 phases for overexcitation
security
Harmonic restrained operating time 30 ms at 3 times pick-up
current
Unrestrained operation does not respond to dc offset and
can be set at 8, 13 or 20 times
Specification
CT input ( In ) : 1 or 5 Amp.
Restrained Operating Value Isr : 20, 25, 35, or 50% of In
Unrestrained Operating Value Isu : Reconnectible : 8, 13 and 20 of In
Rated Frequency : 50 Hz
Permissible sustained current (Thermal withstand) : 10 x In Cont. and 100 x In for 1 Sec. For 1A
20 x In Cont. and 250 x In for 1 Sec. For 5A
Operating Time : 30 ms at Id=3xIsr & 10-20 ms at Id=2xIsu
Max. Error : ± 5%
CT Burden : < 0.2 VA
Number of Output Cont. : 3 NO + 2CO
Output Contact rating : 5 Amp. Cont. & 10 Amp. Making
Rated Auxiliary Supply : 24, 30, 48, 110, 220,250 VDC
Burden on Aux. Supply : 10W /14W ( quiescent / operation cond. )
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : RHGX12 Case with Screw terminals
14 ABB
Wiring Diagrams
ABB 15
Frequency Relay type FCX103b
Features
Static design with High accuracy ( ± 0.03 Hz at 50 Hz )
1 to 4 independently adjustable tripping stages, two of which
can be rate of change df/dt
Wide setting range 39.1 to 65 Hz for U/F & O/F, 0.1 to 9.9
Hz/Sec for df/dt
Under voltage interlock ( 0.2 or 0.6 Un )
Largely insensitive to Harmonics and transients in the system
Digital measuring principle with resolution due to 1.25 MHz
quartz reference
Used for graded load shedding and protection of generators
to avoid damage to turbines and auxiliary drives.
Specification
PT input ( Un ) : 63.5, 110, 200, 220V AC
Setting range for U/F & O/F : 39.1 - 65 Hz in step of 0.1 Hz
Setting range for df/dt : 0.1 - 9.9 Hz / Sec in step of 0.1 Hz / Sec
Rated Frequency : 50 Hz
Operating time for U/F & O/F : 0.15-1.5 Sec or 0.5-5 Sec or 1-10 Sec or 0.3-3 Sec
Tripping delay for df/dt : 33 / 66 / 99 or 132 msec
Evaluation per period : 26 msec
Reset ratio : 100%
Reset time : 70 msec for U/F & 25 msec for O/F
Max. Error : ± 0.03 Hz for Freq. & ± 5% for timing
PT Burden : 11VA + 2VA / Stage in reset condition / 11VA + 6VA / Stage in tripped condition
Number of Output Cont. : 3 NO or 2 CO per stage
Output Contact rating : 10 Amp. Cont. & 20 Amp. Making
Rated Auxiliary Supply : 24, 30, 48, 110, 220,250 VDC
Burden on Aux. Supply : 6W+0.75W/additional stage in reset condition &
8W+1W/additional stage in tripped condition
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -II Case Horizontal
16 ABB
Wiring Diagrams
FCX 103b
FCX 103b
ABB 17
Voltage Earth Fault / Neutral Displacement Relay type UBX117
Features
Single pole Static draw-out type design
Built in filter with very high attenuation of 3rd and 5th
harmonics.
Used to detect stator earth faults of Generators and motors
equipped with high impedance groundings at star points.
Able to detect 95% of stator winding from machine terminal
towards its star point. Also suitable for capacitor bank
protection.
Definite time operation.
Specification
VT input ( Un ) : 110 or 240V AC
Setting range : 2.5 - 6% x Un or 5 - 12% x Un
Operating Time : 0.5 Sec
Rated Frequency : 50 Hz / 60 Hz
Reset ratio : 100%
PT Burden : 10 VA
Max. Error : ± 5%
Number of Output Contact : 3 CO
Output Contact rating : 5 Amp. Cont. & 10 Amp. Making
Rated Auxiliary Supply : 24, 30, 48 - 250 VDC
Burden on Aux. Supply : 1 W Max.
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -I Deep Case
18 ABB
Wiring Diagrams
UBX 117
ABB 19
Over Fluxing Relay type UFX132
Features
Single pole Static draw-out type design
Used to protect power transformer, generator transformer
against excessive flux ( over fluxing ). Also used to protect
generator from overfluxing during start-up and shutdown
when generator is not connected to network, during faulty
operation of voltage regulator. Also offers protection in the
event of sudden load shedding.
Definite time operation.
Specification
VT input ( Un ) : 110 V AC
Voltage Range : 2V - 400V
Frequency Range : 10 Hz - 100 Hz
Load Capacity : 4.5 x f
Setting Range : 0.1 - 4.0 V/Hz in step of 0.1
Operating Time ( time lag : 0.1-1Sec or 0.2-2Sec or 0.5-5 Sec or 1-10 Sec
Rated Frequency : 50 Hz
Permissible sustained voltage (Thermal : 100 x In for 1 Sec.
Reset ratio : > 98%
PT Burden : 4 VA
Max. Error : ± 3%
Number of Output Contact : 3 CO
Output Contact rating : 5 Amp. Cont. & 10 Amp. Making
Rated Auxiliary Supply : 30, 48 - 250 VDC
Burden on Aux. Supply : 3 W Max.
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -I Deep Case
20 ABB
Wiring Diagrams
UFX 132 - C
ABB 21
Power Directional Relay type PPX 111-R
Features
Three Phase Static relay in modular construction
2 or 3 Phase Power measurement
Operating ranges for all three phases individually adjustable
Reconnectable from maximum power ( over power ) to
minimum power ( under power ) measurement
Can be used for active or reactive power measurement.
Used as reverse power, Low forward power relay and
power oscillation relay up to slip frequencies of about 2 Hz,
in which power flow between network and generator
oscillates i.e. generator falls out of step and swings between
motor and generator operation
Specification
CT input ( In ) : 1 or 5 Amp.
PT input ( Un ) : 110/√3, 110, 240/√3, 240V AC
Setting range : 0.5 - 100% x PN ( Rated Power )
Timer Setting range : 0.5 - 5 Sec in steps of 0.5 Sec 5 - 50 Sec in steps of 5.0 Sec
Permissible sustained current / voltage ( Thermal withstand) : 4 x In continuous, 100 x In for 1 Sec. 2 x Un continuous
Characteristic angle : 0 or 90 degree electrical
Measurement of power : up to factor of cos θ = 0.005
Rated Frequency : 50 Hz
Reset ratio : 0.6-0.95 dependent on set operating value
Max. Error : ± 5%
CT Burden : < 0.5 VA
PT Burden : < 0.15 VA
Number of Output : 3 CO for tripping T1 & T2 stage each
Output Contact rating : 10 Amp. Cont. & 30 Amp. Making
Rated Auxiliary Supply : 24, 48, 110, 220 V DC
Burden on Aux. Supply : 6W
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : 19" Rack Mounting
22 ABB
Wiring Diagrams
PPX 111-R
ABB 23
Rotor Earth Fault Relay type IWX + YWX
Features
Single / Two Stage Static relay in modular construction
Adjustable pick up value in ohms ( fault resistance )
Adjustable trip delay
Simple testing facility
Bridge form assuring the impedance of the insulation, with a
band pass filter at the output for the test frequency and low
pass filter with good attenuation of the higher harmonics.
Used for detection of earth faults on the rotor windings of
turbo alternator synchronous motors.
Specification
AC Aux. Input for YWX111 : 110V, 230V AC
Fault Resistance setting : 0 - 5000 ohms
Time Delay setting : 0.5 - 5 Sec
Reset ratio : 100%
Excitation operating volt. : 1.0 kV DC Max.
Rated Frequency : 50 Hz or 60 Hz
Max. Error : ± 5%
Burden on Aux. AC of YWX : 1.1 VA
No. of Output Contact : 2 CO for Stage 1 & 3 CO for Stage 2
Output Contact rating : 5 Amp. Cont. & 25 Amp. Making
Rated Auxiliary Supply : 24, 110, 220 V DC
Burden on Aux. Supply : 8W /11W (quiescent / operation cond.)
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : 19” rack mounting
24 ABB
Wiring Diagrams
IWX+YWX
ABB 25
Fuse Failure Relay type UVT92m
Features
Three Phase Static draw out design
Reliable and Fast operation
Sensitivity down to 2.5 VA load on PT Secondary
No continuous drain on DC auxiliary supply
Used for monitoring the fuses continuously against blowing
out / rupturing and inadvertent removals. The relay can be
used to give blocking signals to voltage operated
protection schemes such as distance, under impedance
and under voltage to avoid mal operation.
Also can be used for alarming purpose in synchronizing
circuits.
Hand reset LED for operation indication.
Operating time less than 15 msec
Specification
PT input ( Un ) : 110V AC
Operating time : 15 msec or less
Rated Frequency : 50 Hz
PT Burden : 0.5 VA per phase
Permissible sustained current (Thermal withstand) : 2 x In continuous 100 x In for 1 Sec.
Number of Output : 2 NO or 1NO+1NC or 2 NC
Output Contact rating : 10 Amp. Cont. & 20 Amp. Making
Rated Auxiliary Supply : 30, 110, 220 V DC
Burden on Aux. Supply : 3W
Max. Error : ± 5%
Max. load impedance allowable in series : 2000 ohms
Insulation : 2.0 kV as per IEC 60255-5
Case Size : Size -I Deep Case
26 ABB
Wiring Diagrams
UVT 92m
ABB 27
Trip Circuit Supervision Relay type TCS / RXTCS
Features
Static design
Continuous supervision of complete trip circuit independent
of the circuit breaker position.
Detects faults in the supervised circuits, such as loss of
voltage, circuit breakage, contact degeneration in
connections and resistivity increases in wires, contacts
and coils.
Low measuring current enables use in sensitive or high
resistance circuit
Operation delayed to avoid spurious signals, for instance,
on circuit breaker operation
Very low burden on auxiliary source
Galvanic isolation between auxiliary source and supervised
circuit.
Also available in combiflex version
Specification
Rated voltage ( Uaux ) : 24, 30, 48, 110, 220,250 V DC
Pick-up and Drop-off current at rated voltage : 0.3 - 0.7 mA
Operate ( drop-off ) time at rated voltage : 0.6 - 0.7 Sec
Burden on Aux. Supply : 3.5 W Max.
Burden on supervised circuit : 0.7 W Max.
No. of Output Contact : 1 NO + 1 NC + 2CO
Output Contact rating : 5 Amp. Cont. & 10 Amp. Making for 3 Sec
Max. Error : ± 5%
Supervision in condition : suitable for supervision in both breaker Pre closed and post closed
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -1/2 Case for TCS, 2U x 6C Size for RXTCS mounted in combiflex
case as per requirement
28 ABB
Wiring Diagrams
TCS
RXTCS
ABB 29
Voltage Operated Auxiliary Relay type CV2
Features
Electromechanical design with Compact Size
High degree of reliability, even when it has been idle for long
time
Mechanical operation indicator
High contact rating
2 or 4 Nos. contacts with double interruption
Three mounting variants - Flush, Plug in base and sheet
metal base
Wide range of voltage
Lower power consumption
Specification
Rated voltage ( Uaux ) : 24, 30, 48, 110, 220, 250 V DC, 110, 240V AC for CV2AJ & CV2A2J model
Pick-up voltage ( % Un ) : < 75%
Drop-off voltage ( % Un ) : > 15%
Operate time at Un : 20 - 35 msec
Operating range : -20% to +10% of Un
Burden on Aux. Supply : 3.0 W for DC & 2.5VA for AC
No. of Output Contact : 2NO / 1 NO+1 NC for 1 element relay 4NO / 2NO+1NC / 3NO+1NC for 2 element
Output Contact rating : 10A continuous & 30A making current.
Max. Error : ± 5%
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -1/2 Case for Flush mounting, Size -PB1 mounting for CV2DRN, CV2DN,
Size -SM1 mounting for CV2DRM, CV2DM
30 ABB
Wiring Diagrams
ABB 31
High Speed Trip / No Volt Relay type RXPQ8n, PQ8n, PN8n, RXPQ8n
Features
Electromechanical design with Compact Size
High degree of reliability, even when it has been idle for
long time
Mechanical operation indicator
High contact rating
7 Nos. contacts with double interruption
4 mounting variants - Flush, Plug in, Sheet metal base and
combiflex
Wide range of voltage
Lower power consumption
Specification
Rated voltage ( Uaux ) : 24, 30, 48, 110, 220,250 V DC, 110, 240V AC for flush mounted models
Pick-up voltage ( % Un ) : < 80% for P8n & PN8n, < 70% for PQ8n
Drop-off voltage ( % Un ) : > 4% for P8n & 20% for PN8n
Operate time at Un : 20-30mSec for P8N & PN8N and 12-15mSec for PQ8n
Operating range : -20% to +10% of Un for P8n & PN8, -30% to +10% of Un for PQ8n
Burden on Aux. Supply : 9.0 W for DC & 7.5VA for AC
No. of Output Contact : 7NO, 6NO+1NC, 5NO+2NC, 4NO+3NC
Output Contact rating : 5A continuous & 50A making for 0.5 Sec
Max. Error : ± 5%
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size -1/2 Case for Flush mounting, Size -PB1 mounting for P8nAHXS Size -SM1 mounting for P8 /
PN8nAH2YS 2U x 12C Size for RXPQ/RXP8 mounted in combiflex case as per requirement
32 ABB
Wiring Diagrams
P8nAHXS
ABB 33
Bistable Relay type PSU6n, PSU14n, RXPSU6n, RXPSU14n
Features
Electromechanical design with Compact Size
High degree of reliability, even when it has been idle for
long time
Mechanical operation indicator for PSU14 & RxPSU14 relay
High contact rating
6 or 14 Nos. contacts with double interruption
Three mounting variants - Plug in base, sheet metal base
and combiflex
Wide range of voltage
Lower power consumption
Specification
Rated voltage ( Uaux ) : 24, 30, 48, 110, 125, 220, 250 V DC
Pick-up voltage ( % Un ) : < 80%
Operate time at Un : 20 - 40 msec
Operating range : -20% to +10% of Un
Burden on Aux. Supply : 65 W
No. of Output Contacts for PSU14n : 7NO+7NC, 8NO+6NC, 9NO+5NC, 10NO+4NC, 11NO+3NC,
and RXPSU14n 12NO+2NC, 13NO+ 1NC or 14NO
No. of Output Contacts for PSU6n and RXPSU6n : 3NO+3NC, 4NO+2NC, 5NO+ 1NC or 6NO
No. of Output Contacts for PSU14nX : 4NO+3NC, 5NO+2NC, 6NO+1NC, or 7NO
Output Contact rating : 5 A continuous & 50 A making for 0.5 Sec
Max. Error : ± 5%
Insulation : 2.0 kV as per IEC 60255-5
mpulse : 5.0 kV as per IEC 60255-5
Case Size : Size -PB2 mounting for PSU6nX, PSU14nX
: Size -PB3 mounting for PSU14n2X, Size -SM2 mounting for PSU6n2Y
Size -SM3 mounting for PSU14n4Y
34 ABB
Wiring Diagrams
ABB 35
Time Delay ( Delay on Pick Up ) Relay type SSX90m6C2J
Features
Static design with Compact Size
Used for Protection, Control of industrial systems
Pick up delay function
Wide range of continuously adjustable time setting
High repetition accuracy
Indication by hand-reset flag
Multiple 6 Nos. output contacts
Specification
Rated voltage ( Uaux ) : 24, 30, 110, 220, 250 V DC
Operating range : -20% to +10% of Un
Time Delay range : 0.1-1.0 Sec, 0.3-3.0 Sec, 0.5-5.0 Sec, 1.0-10.0 Sec, 3.0-30.0 Sec,
6.0-60.0 Sec, 12.0-120.0 Sec, 30-300 Sec
Burden on Aux. Supply : 7W / 13W ( quiescent / operation cond. )
Accuracy Setting : ± 10 msec or ± 5% of setting which ever is greater at Un
Accuracy Repeat : < 1.0% or ± 5 msec which ever is higher
No. of Output Contacts : 3NO + 3NC, 6NO
Output Contact rating : 5 A continuous & 50 A making for 0.5 Sec
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size - 1/2 deep case
36 ABB
Wiring Diagrams
SSX90m6C2J
ABB 37
Time Delay ( Delay on Drop Off ) Relay type SRX90m5C2J
Features
Static design with Compact Size
Used for Protection, Control of industrial systems
Drop off delay function
Wide range of continuously adjustable time setting
High repetition accuracy
Indication by hand-reset flag
Multiple 6 Nos. output contacts
Specification
Rated voltage ( Uaux ) : 24, 30, 110, 220, 250 V DC
Operating range : -20% to +10% of Un
Time Delay range : 0.1-1.0 Sec, 0.3-3.0 Sec, 0.5-5.0 Sec,
1.0-10.0 Sec, 3.0-30.0 Sec, 6.0-60.0 Sec, 12.0-120.0 Sec, 30-300 Sec
Burden on Aux. Supply : 7W / 13W ( quiescent / operation cond. )
Accuracy Setting : ± 10 msec or ± 5% of setting which ever is greater at Un
Accuracy Repea : < 1.0% or ± 5 msec which ever is higher
No. of Output Contacts : 3NO + 2NC
Output Contact rating : 5 A continuous & 50 A making for 0.5 Sec
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case Size : Size - 1/2 deep case
38 ABB
Wiring Diagrams
SRX90m5C2J
ABB 39
Numerical combined Overcurrent and Earth Fault Relay type NI 40/ 41
Model NI 40, NI 41
ANSI 51/ 51N, 50/ 51/ 50N/ 51N
Function Numerical three phase over current and earth fault
relay without instantaneous element (NI 40).
Numerical three phase over current and earth fault
relay with instantaneous element (NI 41).
For protection of feeders, transformers, capacitors
of utility power plant & industry against short circuit
& earth fault.
Features Specification
Numerical microprocessor based cost efficient NI40 NI41
feeder protection relay CT INPUT (IN) 1A or 5 A CT INPUT (IN) 1A or 5 A
3-phase low set O/C stage (IDMT or DMT) OVER CURRENT Stage I> OVER CURRENT Stage I>
3-Phase high set O/C stage (DMT or Inst) STAGE STAGE
a) Current range for I> 50-200%x In b) Current range for I> 50-200%x In
Earth fault protection - Low set stage (IDMT or
c) Operate time range 0.05 - 64 Sec d) Operate time range at
DMT)
at DMT mode for I> DMT mode for I> 0.05 - 64 Sec
Earth fault protection - High set stage (DMT or
e) Time-Current Normal Inverse f) Time-Current Normal Inverse
Inst) Characteristics at Very Inverse Characteristics at Very Inverse
Low set stage have option of choosing four inverse mode for I> Extreme Inverse inverse mode for I> Extreme Inverse
inverse time characteristics curve Long time Inverse Long time Inverse
Measurement of 3 phase current in primary or g) Time multiplier k for 0.05, 0.1-1.0 h) Time multiplier k for 0.05, 0.1-1.0
secondary terms IDMT IDMT
Measurement of Neutral current in primary or i) Current range for I>> - j) Current range for I>> 50-4000% x In
secondary terms k) Operate time range - l) Operate time range for 50 mSec
for Inst mode I>> Inst mode I>>
Last five fault data recording
m) Operate time range n) Operate time range at
16x2 Alpha Numeric LCD display with backlit
at DMT mode for I>> - DMT mode for I>> 0.05 - 64 Sec
Indication LED's for Supply ON, Alarm/Trip, RATED VOLTAGE 18-80 V DC or RATED FREE VOLTAGE 18-80 V DC or
Internal Relay Failure 80-265 V AC/DC 80-265 V AC/DC
Display of fault cause indication RATED FREQUENCY 50 Hz RATED FREQUENCY 50 Hz
Extensive relay internal supervision monitoring THERMALWITHSTAND 4xI THERMAL WITHSTAND 4 x In
relay hardware and software (Continuous) (Continuous)
Normally open heavy duty output contact CT BURDEN <0.5VA CT BURDEN <0.5VA
Two changeover signaling output contacts NUMBER OF OUTPUT 1 NO heavy duty, NUMBER OF OUTPUT 1 NO heavy duty,
CONTACTS 2 Nos. NO 2 Nos. NO
Low burden on current transformer
Signaling & Signaling &
Degree of protection IP54
1 No C/O for 1 No C/O for
Design confirming to requirements of IEC 60255 / Internal relay Internal relay
IS 3231 standards failure failure
Design immune to any kind of electromagnetic OUTPUT CONTACT 5A cont and 30A 5A cont and 30A
interference RATING for 0.5 sec for for 0.5 sec for
heavy heavy
Used for feeder, transformer and backup
protection duty and 5A cont duty and 5A cont
and 10A for and 10A for
0.5 sec for 0.5 sec for
Signaling contact. Signaling contact.
40 ABB
Wiring Diagrams
Connection diagram for three phase Numerical overcurrent and earth fault relay type NI 40/41 with residual connection
of CT’s for earth fault.
ABB 41
Numerical combined Overcurrent and Earth Fault Relay type
SPAJ140C
Model SPAJ140C
Ansi 50, 51, 50N, 51N, 50LBB
Function Combined three phase over current and earth-fault
relay with instantaneous highset stage with built in
circuit breaker failure protection
Features Specification
Numerical microprocessor relay with CT input ( In ) : 1 or 5 Amp.
communication facility Over current stage Stage I> Stage I>>
a) Start current at DMT : 50% - 500% x In 50% - 4000% x In &
3 phase Low set O/C stage with definite time
b) Start current at IDMT : 50% - 250% x In –
or IDMT characteristic.
c) Operate time at DMT : 0.05…300 s 0.04…300 s
3 phase high set O/C stage with
d) Operate time at Instantaneous : 40 ms
instantaneous or definite time characteristic.
e) Time/current characteristic at : Extremely Inverse –
Low set earth fault stage with definite time or inverse mode Very Inverse –
IDMT characteristic. Normal Inverse –
High set earth fault stage with instantaneous or Long time Inverse –
definite time characteristic. RI type inverse –
Low set stage have option of choosing six inverse RXIDG type inverse –
or definite time characteristics - four standard f) Time multiplier k for IDMT : 0.05…1.0 –
inverse time curves as per IEC and BS. Two g) Retardation time : < 30 msec
specific inverse time characteristics called RI & h) Reset ratio, typically : 0.96
RXIDG. i) Operation accuracy : ± 3% of set value ± 3% of set value
Integrated circuit breaker failure protection. Rated frequency : 50 Hz
Permissible sustained : 4 x In continuous
Possibilities for two sets of relay settings.
current (Thermal withstand ) : 100 x In for 1 Sec.
Memory of fault history for previous five
Number of output : 2 NO Heavy Duty, 3 NO Signalling &
numbers faults.
contacts 1 CO for internal relay failure
2 Heavy duty capable of direct breaker
Output contact rating : 5 A Cont. & 30 A make for 0.5 Sec for
tripping & 4 signalling contacts heavy duty & 5 A cont. & 10 A make for
High system reliability and availability due to 0.5 sec for signalling contact
continuous self-supervision. Earth fault stage Stage Io> Stage Io>>
Digital display for measured and recorded a) Start current : 10% - 80% x In 10% - 1000% x In &
values and status information. b) Operate time at DMT : 0.05…300 s 0.05…300 s
Ample programming, blocking and routing c ) Operate time at Instant. : - 50 ms
possibilities. d) Time/current characteristic at : Extremely Inverse –
Very high degree of protection IP54. inverse mode Very inverse –
Normal inverse –
High immunity to electrical and
Long time inverse –
electromagnetic interference.
RI type inverse –
Dual current input rating 1A and 5A
RXIDG type inverse –
Extremely low VA burden on current e) Time multiplier k for IDMT : 0.05…1.0 –
transformer f) Retardation time : < 30 msec
High accuracy of the order 2% due to high g) Reset ratio, typically : 0.96
sampling rate. h) Operation accuracy : ± 3% of set value ± 3% of set value
Used for feeder, transformer & back up CT Burden : < 0.5 VA
protections Rated auxiliary supply : 18-80V DC or 80-265V AC / DC
Long life time -MTBF > 200 years based on Burden on aux. supply : 4W / 6W ( quiescent / operation cond. )
delivery and fault statistics. Number of binary input : 1 No.
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case size : SPACOM 100 size case
42 ABB
Wiring Diagrams
ABB 43
Numerical Composite Motor Protection Relay type SPAM150C
Model SPAM150C
Ansi 49,14, 48, 51, 50, 51n, 46, 37
Function Comprehensive multifunctional motor protection
relay
Features Specification
Numerical microprocessor multifunctional CT input ( In ) : 1 or 5 Amp
relay with communication. Thermal overload
a) Full load current ( I@ ) : 50% - 150% x In
3 Phase thermal overload protection, motor
b) Weighting factor ( P ) : 20 - 100%
overload pre-alarm
c ) Cooling time multiplier ( Kc ) : 1 - 64 x Th
3 phase high set O/C stage with d) Thermal prior alarm level ( Qa) : 50 - 100% x Qt
Instantaneous or DMT for S/C protn. e) Motor restart inhibit level ( Qt ) : 20 - 80% x Qt
Negative phase sequence, loss of phase & Locked rotor / stalling
single phasing protection with Inverse a) Start up current Is : 1.0 - 10 x In
characteristic, b) Start up time ts : 0.3 - 80 Sec
c ) Operation principle : Definite time or thermal stress
Sensitive earth fault protection
I2 x t
Lock rotor / stalling protection Inst. phase overcurrent (S/C)
Under current protection for loss of load a) Start current I>> : 50 - 2000% x In or Infinite
Cumulative start up counter and restart b) Operate time t>> : 0.04…30.0 s
inhibit function Rated frequency : 50 Hz
CT Burden : < 0.5 VA
Measurement principle based on 3 phase
Permissible sustained cur- : 4 x In continuous
RMS measurement to consider the effect of
Rent (Thermal withstand ) : 100 x In for 1 Sec.
harmonics in thermal image resulting in to
Number of output : 2 No heavy duty, 3 No signalling
better protection.
& Contacts 1 CO for internal relay failure
Memory of fault history for previous faults. Output contact rating
2 Heavy duty capable of direct breaker a) for heavy duty contact : 5 A continuous & 30 A make for 0.5 sec
tripping & 4 Signalling contacts b) for signalling contact : 5 A continuous & 10 A make for 0.5 sec
Earth fault unit
High system reliability and availability due to
a) Start current I0> : 1.0 - 100% x In
continuous self-supervision
b) Operate time t0> : 0.05…30.0 s
Digital display for measured and recorded Negative phase sequence / incorrect phase sequence
values and status information a) Start current ∆I : 10…40% x IL or
Ample programming, blocking and routing b) Operate time ∆T : 20…120 s
possibilities. c ) Operation characteristic : Inverse time
Very high degree of protection IP54. d) Operate time at single phasing : 1 sec
e) Operate time at Incorrect phase : 600 msec
High immunity to electrical and
Under current unit
electromagnetic interference. a) Start current I< : 30…80% of Iθ or off
Dual current input rating 1A and 5A b) Operation inhibit level : <12% of Iθ
Extremely low VA burden on current c ) Operate time t< : 2…600 sec
transformer Cumulative start-up time counter unit
a) Restart inhibit level : 5…500 sec
High accuracy of the order 2% due to high
b) Countdown rate : 2…250 s/h
sampling rate.
Rated auxiliary supply : 18-80V DC or 80-265V AC / DC
Used for large & medium sized breaker & Burden on aux. supply : 4W / 6W ( quiescent / operation cond.)
contactor controlled LT / HT motors Number of binary input : 1 No.
Long life time -MTBF > 200 years based on Insulation : 2.0 kV as per IEC 60255-5
delivery and fault statistics. Impulse : 5.0 kV as per IEC 60255-5
Case size : SPACOM 100 size case
44 ABB
Wiring Diagrams
ABB 45
Numerical Capacitor Bank Protection relay type SPAJ160C
Model SPAJ160C
Ansi 46,49,37,62,51N
Function Comprehensive multifunctional capacitor bank
protection relay
Features Specification
Numerical microprocessor multifunctional relay CT Input ( In ) : 1 and 5 Amp.
with communication. Overload stage Ib>
3 phase 2 stage overload protection with one a)Start current Ib> : 30 - 150% x In
Inverse time characteristics and other with b)Operation characteristic : Inverse ANSI
definite time characteristics
c )Time multiplier k : 0.2 - 2.0
2 Stage phase unbalance protection with one
Overload stage Ia>
Inverse time characteristics and other with
definite time characteristics a)Start current Ia> : 80-120% x Ib
Undercurrent protection for detection of capacitor b)Operation characteristic : Definite time
disconnection. Reconnection time with wide c )Operate Time : 0.5 - 100 min
setting range Undercurrent stage I<
Compensation for natural unbalance current a)Start current I< : 10 - 70% x In
Memory of fault history for previous faults. b)Operate time : 1 - 100 Sec
2 Heavy duty capable of direct breaker tripping & c )Reconnection inhibit time trec : 0.5 - 100 min
4 signalling contacts Rated Frequency : 50 Hz
High system reliability and availability due to Number Of output : 2 No heavy duty, 3 No signalling &
continuous self-supervision
Contacts 1CO for internal relay failure
Digital display for measured and recorded values Output contact rating
and status information
a)for Heavy duty contact : 5 A continuous & 30 A make for 0.5 sec
Ample programming, blocking and routing
b)for signalling contact : 5 A continuous & 10 A make for 0.5 sec
possibilities.
Phase unbalance ∆ I 1>
Very high degree of protection IP54.
a)Start current ∆I 1> : 1.0 - 100% x ∆In
High immunity to electrical and electromagnetic
b)Operate time t∆1 : 1.0 - 300 sec at definite time
interference.
Phase unbalance ∆ I 2>
Dual current input rating 1A and 5A
a)Start current ∆I 2> : 2.0 - 80% x ∆In
Extremely low VA burden on current transformer
b)Time multiplier k∆2> : 0.1 - 1.0 at Inverse time
High accuracy of the order 2% due to high
c )Shortest possible operate time : ~100 ms
sampling rate.
Unbalance compensation
Used for large & medium sized breaker &
contactor control LT / HT motors a) Compensation current ∆I CS : 0.0 - 20% x ∆I n*
Operation accuracy : ±3% of set value
Long life time -MTBF > 200 years based on
delivery and fault statistics. CT Burden : < 0.5 VA
Used to protect capacitor bank intended for Permissible sustained cur- : 4 x In continuous
reactive power compensation and filtering of the rent (Thermal withstand ) : 100 x In for 1 sec.
harmonics. Rated auxiliary supply : 18-80V DC or 80-265V AC / DC
Burden on aux. supply : 4W / 6W ( quiescent / operation cond. )
Number of binary input : 1 No.
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case size : SPACOM 100 Size Case
46 ABB
Wiring Diagrams
ABB 47
Numerical three phase Under voltage and Over voltage relay type
SPAU130C
Model SPAU130C
Ansi 27+2 , 59+2
Function Three phase under voltage and over voltage relay
type SPAU130C
Features Specification
Numerical microprocessor relay with PT Input ( Un ) : 100, 110 V AC
communication facility Over Voltage Protection
Combined over voltage and under voltage a) Start voltage U> : 80 - 160% x Un
protection relay
b) Start time, preset values : 0.1 sec or 30 sec
3 Phase definite time or inverse time over voltage
c ) Operate time at definite time operation: 0.05 - 100 sec
stage
characteristic
3 Phase definite time under voltage stage
d) Time multiplier k> at inverse time : 0.05 - 1.00
Control input for blocking the function of the
e) Reset time, typically : 60 ms
undervoltage stage by means of an external
control signal f) Drop-off/pick-up ratio, typically : 0.97
Automatic blocking of the undervoltage stage on g) Operation accuracy : ±3% of set value
loss of energizing voltage Rated Frequency : 50 Hz
Memory of fault history for previous fault. PT Burden : < 0.5 VA
2 Heavy duty capable of direct breaker tripping & Number of output : 2 NO heavy duty, 3 No signalling &
3 signalling contacts
Contacts : 1 CO for internal relay failure
High system reliability and availability due to
Output contact rating
continuous self-supervision.
a) for heavy duty contact : 5 A continuous & 30 A make for 0.5 Sec
Digital display for measured and recorded values
and status information. b) for signalling contact : 5 A Continuous & 10 A make for 0.5 Sec
Under voltage protection
Ample programming, blocking and routing
possibilities. a) Start voltage U< : 40 - 120% x Un
Very high degree of protection IP54. b) Start time, preset values : 0.1 sec or 30 sec
High immunity to electrical and electromagnetic c ) Operate time : 1 - 120 sec
interference. d) Reset time, typically : 60 ms
Dual PT input rating 100V and 110V AC e) Drop-off/pick-up ratio : 1.03
Extremely low VA burden on voltage transformer f) Operation accuracy : ±3% of set value
High accuracy of the order 2% due to high Permissible sustained : 4 x In continuous
sampling rate.
voltage (Thermal withstand) : 100 x In for 1 sec.
Used for over / under voltage protection of Motor,
Rated auxiliary supply : 18-80V DC or 80-265V AC / DC
Capacitor banks and Feeder protections Feeder
protections Burden on aux. supply : 4W / 6W (quiescent / operation cond.)
Long life time -MTBF > 200 years based on Number of binary input : 1 No.
delivery and fault statistics. Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case size : SPACOM 100 Size Case
48 ABB
Wiring Diagrams
ABB 49
Numerical High impedance Protection Relay type SPAE010 / 011
Features Specification
Numerical Microprocessor relay Energizing input ( Un ) : 50, 100, 200 V AC
High impedance type differential current earth- Setting ranges
fault protection. a) Voltage setting range, U>/Un : 0.4 - 1.2 x Un
Required stabilizing resistors built-in into the relay b) Operating current : 9…27 mA
Short total operating time together and high c ) Operating time : 17 - 80 ms
stability
d) Drop-off time : 120 ms
2 Heavy duty capable of direct breaker tripping &
e) Drop-off/pick-up ratio : 0.8
2 Signalling contacts
CT Burden : < 0.5 VA
High system reliability and availability due to
continuous self-supervision. Permissible sustained vol. : 1.3 x Un continuous
Note : The external stabilising resistor is supplied along with relay. The total impedance of the
relay and series stabilising resistor is usually low enough to prevent the CT developing voltages
over 2 kV during max. internal faults, but in some applications a non-linear resistor is required to
limit this voltage.
Wiring Diagrams
Features
Numerical microprocessor relay with Earth fault unit comprising of 2 stages - low, high
communication facility set stage
Integrated two winding transformer differential, Phase discontinuity unit for protection against
three phase Overcurrent and multi configurable phase unbalance
ear th fault relay. Integrated circuit breaker failure protection.
Three phase transformer differential module: 5 alarm channels for transformer mechanical
Biased differential protection stabilized against faults like buchchholtz, wdg temp etc.
unwanted operations at faults occurring outside Possibilities for two sets of relay settings.
the protected area and at transformer inrush.
Memory of fault history for previous five numbers
Second harmonic restraint for prevention of faults.
unwanted trip during T/R inrush.
2 Heavy duty contact capable of direct breaker
Fifth harmonic restraint for prevention of tripping & 4 signalling contacts
unwanted trip during T/R Over excitation.
High system reliability and availability due to
Interposing CTs can be avoided as CT ratio continuous self-supervision.
matching and vector group matching can be
Digital display for measured and recorded values
programmed in the relay
and status information.
Sensitive phase current and phase angle displays
Ample programming, blocking and routing
facilitate checking of energizing circuit
possibilities.
connections and vector group matching.
Very high degree of protection IP54.
In built disturbance recording facility is available.
High immunity to electrical and electromagnetic
Restricted earth fault and stand by earth fault
interference.
module :
Dual current input rating 1A and 5A
Four programmable operating principle for earth
fault on LV & HV side as: Extremely low VA burden on current transformer
- Neutral current principle, - high impedance High accuracy of the order 2% due to high
principle, - Stabilized differential current principle, sampling rate.
- zero sequence current principle Used for feeder, transformer & back up
CT Ratio matching protections
In built disturbance recording facility is available. Long life time -MTBF > 200 years based on
delivery and fault statistics.
Back up Over current and Earth fault module :
52 ABB
Specification
CT Input ( In ) : 1 and 5 Amp.
∆I>
Stabilized differential current stage 3∆
a) Basic start ratio P/In : 05 - 50%
b) Starting ratio setting S : 10 - 50%
c ) Second turning point I2tp/In of curve : 1.0 - 3.0
d) Harmonics blocking ratio Id2f/Id1f : 07 - 20%
e) Harmonics blocking ratio Id5f/Id1f : 10 - 50%
f) Harmonics deblocking ratio Id5f/Id1f : 10 - 50%
g) Operate time at 1.5-4 x operate value : < 40 msec
h) Operate time at 4 x operate value : < 30 msec
∆ I>
Instantaneous differential current stage 3∆
a) Start ratio Id/In>> : 05-30%
b) Operate time at 1.1-2.6 x Id/In>> : < 35 msec
c ) Operate time at 2.6 x Id/In>> : < 30 msec
CT Ratio correction range on HV : 0.40 - 1.50 x I1/In
CT ratio correction range on LV : 0.40 - 1.50 x I2/In
Restricted & stand by earth fault stages
a) Operating principle : Stabilized differential principle.
High Impedance differential principle.
Neutral current principle
b) Basic start ratio on HV side P1/In : 5…50%
c ) Operate time on HV side t01> : 0.03…100 s
d) Basic start ratio on LV side P2/In : 5…50%
e) Operate time setting on LV side t02> : 0.03…100 s
Rated frequency : 50 Hz
Permissible sustained cur- : 4 x In continuous
rent (thermal withstand ) : 100 x In for 1 sec.
Number of output contacts : 4No heavy duty, 5No signalling &
Output contact rating
a) for heavy duty contact : 5 A continuous & 30 A make for 0.5 Sec
b) for signalling contact : 5 A continuous & 10 A make for 0.5 Sec
Over current stage : Stage I> Stage I>> Stage I>>>
a) Start current at DMT : 50% - 500% x In 50% - 4000% x In & $
b) Start current at IDMT : 50% - 250% x In – –
c ) Operate time at DMT : 0.05…300 s 0.04 - 300 s 0.04 - 300 s
d) Operate time at instantaneous : – 40 ms 40 ms
e) Time/current characteristic at : Extremely inverse – –
inverse mode Very inverse – –
Normal inverse – –
Long time inverse – –
RI type inverse – –
RXIDG type inverse – –
f) Time multiplier k for IDMT : 0.05…1.0 – –
g) Retardation time : < 30 msec – –
h) Reset ratio, typically : 0.96 – –
Earth fault stage Stage Io> Stage Io>> Stage I>>>
a) Start current : 10% - 80% x In 10-1000%xIn 10-100%xIn
b) Operate time at DMT : 0.05…300 s 0.04 - 300 s 1-300 s
c ) Operate time at instant. : – – –
d) Time/current characteristic at : Extremely inverse – –
inverse mode Very inverse – –
Long time inverse – –
RI type inverse – –
RXIDG type inverse – –
e) Time multiplier k for IDMT : 0.05…1.0 – –
f) Retardation time : < 30 msec – –
g) Reset ratio, typically : 0.96 0.96 0.9
CT Burden : < 0.5 VA – –
Rated auxiliary supply : 18-80V DC or 80-265V AC / DC
Burden on aux. supply : 10W / 15W ( quiescent / operation cond. )
Number of binary input : 5 Nos.
Insulation : 2.0 kV as per IEC 60255-5
Impulse : 5.0 kV as per IEC 60255-5
Case size : SPACOM 300 Size Case
ABB 53
Wiring Diagram SPAD346C
54 ABB
Station Automation COM 600
Features Specification
Standard web - browser with diagnostic COM 605 COM 610 COM 615
information & web HMI user management Connectivity
3 phase 2 stage overload protection with one Master Protocols
Inverse time characteristics and other with
SPA, IEC 61850-8-1 client, IEC 60870-5-103,
definite time characteristics
Modbus (RTU), LON (ABB Lag)
The station automation COM 600 series is a
dedicated system for the automation of utility and Slave Protocol
industrial Substation. IEC 60870-5-101, IEC 60870-5-104,
COM 600 is a dedicated system for providing DNP 3.0 Serial & LAN/WAN
inter operability between industrial or utility SMPT server for local time synchronisation
substation IED's and local or higher level Support for remote parameter setting and
systems, such as a local operator interfaces or
disturbance file uploaded with ABB
higher-level network control centers (NCC) or
protection and control devices from
Distributed control systems (DCS).
microSCADA Pro
The COM 600 series includes three products:
the control and monitoring unit COM605, the Control and Monitoring
communication gateway COM610 and the station Communication diagnostics
computer COM615
Configuration and administration
Each COM600 product is optimized for ABB
Single line diagram and busbar coloring
protection and control devices and can be easily
integrated with them. COM600 also facilitates for Parameter setting
integration of third party devices. Status monitoring and control
The innovative industrial design and extended Disturbance data upload
communication capabilities make them ideal for
harsh and demanding environment real-time Events and alarm list
process information is critical. Measurements
COM600 has an embedded design with no System Supervision
moving parts, so it is maintenance free.
Software
The design is compact enough to fit in low
voltage compartment of switchgear, saving both HMI through Web server functionality
space and money. Future proof - supporting IEC 61850 standards
The various communication interfaces included Efficient configuration supporting
minimize the need for external media converters. IEC 61850-6 (SCL)
Electrical and optical interfaces are available in Unified protocol mapping based upon
COM 600 products. IEC 61850-7
The control and monitoring unit COM 605 Remote configuration and administration
provides connectivity to the protection and
control devices of a substation. Hardware
The communication gateway COM 610 provides Communication ports : 2 x LAN (RJ-45 copper),
easy and powerful connectivity from the 4 x RS-232 (one can be configured as
protection and control devices of a substation, RS-485; 2-wire),
with monitoring and control functionality, and the
Other ports: VGA output, 4 x USB,
connection to NCC.
audio output for audio alarm
Station computer COM 615 provides full station
Optional cards: RS-232/485 (4 ports) or
automation functionality combines the features
LAN (2 ports, RJ-45 copper) or
and functionality of the control and monitoring unit
fiber optic LAN (1 port) or LON (1 Port)
COM 605 and communication gateway COM 610.
Communication over IEC61850 protocol is Wide range power supply
available for smooth interoperation. 24 - 220v DC(internal), 220v AC (external)
ABB 55
Station Automation COM 600
Utility Application
Industry Application
56 ABB
Mounting details and case dimensions
Size - I Case
Dimensions
Legend:
A a : Terminals M5
Ir : Mounting frame
Ge : Earthing lug
Ob : Fixing screw
Dimensions for mounting
Side View
ABB 57
Size - II Case ( Horizontal )
Dimensions
58 ABB
Size 1/2 Case Deep
Dimens ions
Ob
Aa ø6
a
7
Ls
8
126 - 0
+1
140±0.3
9
1
10
158
2
11 12 13 14
3
4
5
6
7
+1
92 - 0
170 55 102
Cutout Db
Rear view Side view Front view
Rear view Side view Front view Cutout
1/2’S’ casemounting.
1/2’S’ case mounting.
50
Ø4.5 (2 holes)
36
Required space
Required space
for mounting
for mounting
6
86
100
86
50
= =
100
Legend:
Legend
A a : Terminals
Aa : Terminals
Db : Mounting hole
Db : Mounting hole
Ls : Operation signal
External resistor's
External details
resistor’s details Ls : Operation signal
Ob : Mounting screw
Ob : Mounting screw
ABB 59
Spacom series case - 100
60 ABB
Combiflex RHGX - 4 Case, 8 Case, 12 Case, 20 Case
Upper View
Overall Cutout
Type of Case Dimensions (in mm) Dimensions (in mm)
L L1 L2 L3 L4
RHGX4 132 110 135.5 112+1.0 190+1.0
RHGX8 216 194 219.5 196+1.0 190+1.0
RHGX12 300 278 303.5 280+1.0 190+1.0
RHGX20 468 446 471.5 448+1.0 190+1.0
ABB 61
COMBIFLEX relay mounting 6C
Dimensions
Dimensions
Combiflex mounting
Dimensions
Dimensions
Legend
Aa: Terminals
Db: Mounting hole
E01:Cut-out for rear wiring.
Sheet-metal base mounting. *: Space for removing hood.
Ls: Operation signal
Ob: Fixing screw
Plug-in base (PB2)
Dimensions
Plug-in relay(PB3)
REX 521
This feeder protection relay is designed for protection,
control, measuring and supervision in distribution
networks and for protection of
large or medium-size three-phase a.c. motors in circuit
breaker controlled motor drives.
REF 542plus
This switchbay protection and control unit combines
measurement, monitoring, protection, control and
self diagnostics in one package.
66 ABB
REA 101, 103, 105 and 107
The REA Arc Protection System provides
your substation with comprehensive
protection against arc faults.
REM 610
The motor protection relay REM 610 is primary
targeted at protecting large asynchronous low-
voltage motors and small and medium-sized high-
voltage asynchronous motors.
REF 610
The protection relay REF 610 is primarily targeted at
the protection of incoming and outgoing feeders in
distribution substations. REF 610 is also used as
back-up protection for motors, transformers and
generators, in utility and industry applications.
REU 610
ABB 67
ABB Limited Regional Marketing Offices:
Distribution Automation
Maneja,
North South Central West
Vadodara 390 013, India.
Tel: +91 265 2604385 No.14, Mathura Road Embassy Star, 1st Floor 4th & 5th Floor ABB House
+91 265 2604386 P.O. Amar Nagar No. 8, Palace Road Maruti Heights Dr. S B Path
Fax:+91 265 2638922 Faridabad 121 003 Vasanth Nagar Aamanaka, G E Road Ballard Estate
E-mail: [email protected] Tel: +91 129 2275592, Bangalore 560 052 Raipur 492 099 Mumbai 400 038
2279627, 5049000 Tel: +91 80 22949779 Tel: +91 771 4701016 Tel: +91 22 56318231 – 39
Fax: +91 129 2279692/5019 Fax: +91 80 22949808 Fax: +91 22 56318276/77