Total Building COOLING Load Calculation

This document contains a cooling load calculation for a cafeteria dining space. It details the building components, their thermal properties, and solar gains to calculate the total cooling and dehumidification load over time throughout a day.

Uploaded by

Anamol
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
161 views169 pages

Total Building COOLING Load Calculation

This document contains a cooling load calculation for a cafeteria dining space. It details the building components, their thermal properties, and solar gains to calculate the total cooling and dehumidification load over time throughout a day.

Uploaded by

Anamol
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 169

COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Account Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 351.33 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor

brick 0.42 171.72


Partition
glass 1.01
Glass 1.01
Door
wood 0.38 28.92
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.8 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 158.00
q n CLF
People Qs 245.00 6 1.00
Ql 155.00 6
Equipment 1804.54
factor n CLF dT dw CFM
Ventilation Qs 1.10 6 1.00 17.00 15.00
Ql 0.68 6 100.24 15.00

Total
TOR
Latent
Sensible
CULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1591.07 1591.07 1591.07 1716.84 1842.62
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
Qs=U*A*dT

12.00 863.41 863.41 863.41 863.41 863.41


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 131.86 131.86 131.86 131.86 131.86
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
537.20 537.20 537.20 537.20 537.20
Qs=q*n*LCF , Ql=q*n
1470.00 1470.00 1470.00 1470.00 1470.00
930.00 930.00 930.00 930.00 930.00
1804.54 1804.54 1804.54 1804.54 1804.54
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1683.00 1683.00 1683.00 1683.00 1683.00
6134.69 6134.69 6134.69 6134.69 6134.69

Total 15145.8 15145.8 15145.8 15271.5 15397.3


TOR 1.26 1.26 1.26 1.27 1.28 125.1835
Latent 7064.7 7064.7 7064.7 7064.7 7064.7
Sensible 8081.1 8081.1 8081.1 8206.9 8332.6
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Cafeteria Dining Space Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 326.47 16.15 16.65 17.15 18.15 18.65
ESE 0.36 85.25 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 94.40 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 669.14 12.65 12.65 12.65 13.65 14.65
NNE 1.01 301.28 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 120.87 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 44.29 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor

brick 0.42 265.79


Partition
glass 1.01
Glass 1.01
Door
wood 0.38 26.59
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 301.28 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 120.87 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 44.29 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 1358.00
q n CLF
People Qs 245.00 20.00 1.00
Ql 155.00 20.00
Equipment
factor n CLF dT dw CFM
Ventilation Qs 1.10 20.00 1.00 17.00 15.00
Ql 0.68 20.00 100.24 15.00

Total
TOR
Latent
Sensible
LCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1887.53 1945.96 2004.40 2121.27 2179.71
562.33 608.11 653.89 699.67 730.19
0.00 0.00 0.00 0.00 0.00
523.83 506.93 523.83 540.72 591.42
3030.33 3030.33 3030.33 3269.89 3509.44
4107.98 4412.27 4716.57 4716.57 4412.27
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1648.11 1770.19 1892.27 1892.27 1770.19
603.91 648.65 693.38 693.38 648.65

Qs=U*A*dT

12.00 1336.39 1336.39 1336.39 1336.39 1336.39


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 121.26 121.26 121.26 121.26 121.26
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 5979.70 5813.60 5315.29 4650.88 3820.36
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2474.08 4835.70 7309.78 8996.65 9446.48
0.44 894.98 864.81 824.58 754.19 784.36
Qs=3.4*W*BF*CLF
4617.20 4617.20 4617.20 4617.20 4617.20
Qs=q*n*LCF , Ql=q*n
4900.00 4900.00 4900.00 4900.00 4900.00
3100.00 3100.00 3100.00 3100.00 3100.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
5610.00 5610.00 5610.00 5610.00 5610.00
20448.96 20448.96 20448.96 20448.96 20448.96

Total 61846.6 64570.4 67098.1 68469.3 68026.9


TOR 5.2 5.4 5.6 5.7 5.7 242.8682
Latent 23549.0 23549.0 23549.0 23549.0 23549.0
Sensible 38297.6 41021.4 43549.2 44920.3 44477.9
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Conference Hall Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 108.72 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 289.22 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 677.41
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 154.61
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 1350.00
q n CLF
People Qs 245.00 105.00 1.00
Ql 155.00 105.00
Equipment 1091.84
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 105.00 1.00 17.00 15.00
Ql 0.68 105.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
324.98 344.44 402.82 441.74 519.58
0.00 0.00 0.00 0.00 0.00
1309.79 1309.79 1309.79 1413.33 1516.87
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 3406.01 3406.01 3406.01 3406.01 3406.01


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 705.02 705.02 705.02 705.02 705.02
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
4590.00 4590.00 4590.00 4590.00 4590.00
Qs=q*n*LCF , Ql=q*n
25725.00 25725.00 25725.00 25725.00 25725.00
16275.00 16275.00 16275.00 16275.00 16275.00
1091.84 1091.84 1091.84 1091.84 1091.84
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
29452.50 29452.50 29452.50 29452.50 29452.50
### ### ### ### ###

Total 190237.2 190256.6 190315.0 190457.5 190638.9


TOR 15.9 15.9 15.9 15.9 15.9 85.12203
Latent 123632.0 123632.0 123632.0 123632.0 123632.0
Sensible 66605.1 66624.6 66683.0 66825.4 67006.8
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Control Room Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 392.32
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 22.09
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 210.00
q n CLF
People Qs 245.00 2.00 1.00
Ql 155.00 2.00
Equipment 716.54
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 2.00 1.00 17.00 15.00
Ql 0.68 2.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 1972.58 1972.58 1972.58 1972.58 1972.58


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 100.72 100.72 100.72 100.72 100.72
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
714.00 714.00 714.00 714.00 714.00
Qs=q*n*LCF , Ql=q*n
490.00 490.00 490.00 490.00 490.00
310.00 310.00 310.00 310.00 310.00
716.54 716.54 716.54 716.54 716.54
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
561.00 561.00 561.00 561.00 561.00
2044.90 2044.90 2044.90 2044.90 2044.90

Total 6909.7 6909.7 6909.7 6909.7 6909.7


TOR 0.6 0.6 0.6 0.6 0.6 364.7029
Latent 2354.9 2354.9 2354.9 2354.9 2354.9
Sensible 4554.8 4554.8 4554.8 4554.8 4554.8
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room General Enquiry Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 108.72 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 289.22 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 116.04 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 26.59 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 678.00
Partition
glass 1.01 54.89
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 116.04 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 26.59 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 328.00
q n CLF
People Qs 245.00 4.00 1.00
Ql 155.00 4.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 4.00 1.00 17.00 15.00
Ql 0.68 4.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
603.29 583.83 603.29 622.75 681.13
1309.79 1309.79 1309.79 1413.33 1516.87
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1582.14 1699.33 1816.53 1816.53 1699.33
362.55 389.41 416.27 416.27 389.41

Qs=U*A*dT

12.00 3408.98 3408.98 3408.98 3408.98 3408.98


12.00 665.27 665.27 665.27 665.27 665.27
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2375.05 4642.14 7017.18 8636.53 9068.36
0.44 537.29 519.18 495.03 452.77 470.89
Qs=3.4*W*BF*CLF
1115.20 1115.20 1115.20 1115.20 1115.20
Qs=q*n*LCF , Ql=q*n
980.00 980.00 980.00 980.00 980.00
620.00 620.00 620.00 620.00 620.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1122.00 1122.00 1122.00 1122.00 1122.00
4089.79 4089.79 4089.79 4089.79 4089.79

Total 18771.4 21144.9 23659.3 25359.4 25827.2


TOR 1.6 1.8 2.0 2.1 2.2 166.3614
Latent 4709.8 4709.8 4709.8 4709.8 4709.8
Sensible 14061.6 16435.1 18949.5 20649.6 21117.4
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Office Metal Worksho Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 105.00 16.15 16.65 17.15 18.15 18.65
ESE 0.36 41.33 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 124.86 13.50 14.50 15.50 15.50 14.50
ESE 1.01 155.00 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 401.14
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 25.11
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 124.86 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 155.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 249.00
q n CLF
People Qs 245.00 7.00 1.00
Ql 155.00 7.00
Equipment 1192.54
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 7.00 1.00 17.00 15.00
Ql 0.68 7.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
607.08 625.87 644.67 682.26 701.05
272.65 294.84 317.04 339.24 354.03
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1702.43 1828.53 1954.64 1954.64 1828.53
2113.43 2269.98 2426.53 2426.53 2269.98
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 2016.94 2016.94 2016.94 2016.94 2016.94


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 114.50 114.50 114.50 114.50 114.50
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 2478.10 2409.27 2202.76 1927.41 1583.23
0.44 3374.37 2999.44 2624.51 2374.55 1874.65
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
846.60 846.60 846.60 846.60 846.60
Qs=q*n*LCF , Ql=q*n
1715.00 1715.00 1715.00 1715.00 1715.00
1085.00 1085.00 1085.00 1085.00 1085.00
1192.54 1192.54 1192.54 1192.54 1192.54
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1963.50 1963.50 1963.50 1963.50 1963.50
7157.14 7157.14 7157.14 7157.14 7157.14

Total 26639.3 26519.1 26261.4 25795.8 24702.7


TOR 2.2 2.2 2.2 2.1 2.1 113.7794
Latent 8242.1 8242.1 8242.1 8242.1 8242.1
Sensible 18397.1 18277.0 18019.2 17553.7 16460.6
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Office Wood workshop Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 131.06 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 84.22 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 424.82
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 25.11
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 84.22 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 143.00
q n CLF
People Qs 245.00 5.00 1.00
Ql 155.00 5.00
Equipment 596.27
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 5.00 1.00 17.00 15.00
Ql 0.68 5.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
391.78 415.24 485.62 532.53 626.37
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1148.32 1233.38 1318.44 1318.44 1233.38
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 2136.00 2136.00 2136.00 2136.00 2136.00


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 114.50 114.50 114.50 114.50 114.50
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1909.10 2055.95 1958.05 1615.39 1125.88
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
486.20 486.20 486.20 486.20 486.20
Qs=q*n*LCF , Ql=q*n
1225.00 1225.00 1225.00 1225.00 1225.00
775.00 775.00 775.00 775.00 775.00
596.27 596.27 596.27 596.27 596.27
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1402.50 1402.50 1402.50 1402.50 1402.50
5112.24 5112.24 5112.24 5112.24 5112.24

Total 15296.9 15552.3 15609.8 15314.1 14833.3


TOR 1.3 1.3 1.3 1.3 1.2 109.9308
Latent 5887.2 5887.2 5887.2 5887.2 5887.2
Sensible 9409.7 9665.0 9722.6 9426.8 8946.1
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Seminar Hall Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 246.19 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 544.87
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 110.43
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 1025.00
q n CLF
People Qs 245.00 30.00 1.00
Ql 155.00 30.00
Equipment 1091.84
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 30.00 1.00 17.00 15.00
Ql 0.68 30.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1114.93 1114.93 1114.93 1203.07 1291.20
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 2739.60 2739.60 2739.60 2739.60 2739.60


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 503.56 503.56 503.56 503.56 503.56
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
3485.00 3485.00 3485.00 3485.00 3485.00
Qs=q*n*LCF , Ql=q*n
7350.00 7350.00 7350.00 7350.00 7350.00
4650.00 4650.00 4650.00 4650.00 4650.00
1091.84 1091.84 1091.84 1091.84 1091.84
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
8415.00 8415.00 8415.00 8415.00 8415.00
30673.44 30673.44 30673.44 30673.44 30673.44

Total 60023.4 60023.4 60023.4 60111.5 60199.6


TOR 5.0 5.0 5.0 5.0 5.0 204.9202
Latent 35323.4 35323.4 35323.4 35323.4 35323.4
Sensible 24699.9 24699.9 24699.9 24788.1 24876.2
COOLING LOAD CALCULATION

Floor Ground Design condition DBT(F) WBT(F)


Room Staff Room Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 224.52 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 132.32 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 203.88 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 92.65 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 401.81
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 26.59
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 203.88 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 92.65 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 544.00
q n CLF
People Qs 245.00 19.00 1.00
Ql 155.00 19.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 19.00 1.00 17.00 15.00
Ql 0.68 19.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1298.11 1338.30 1378.49 1458.86 1499.05
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
734.24 710.56 734.24 757.93 828.98
0.00 0.00 0.00 0.00 0.00
2779.95 2985.88 3191.80 3191.80 2985.88
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1263.24 1356.81 1450.38 1450.38 1356.81
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 2020.32 2020.32 2020.32 2020.32 2020.32


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 121.26 121.26 121.26 121.26 121.26
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 4046.58 3934.18 3596.96 3147.34 2585.32
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1896.32 3706.45 5602.77 6895.72 7240.51
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
1849.60 1849.60 1849.60 1849.60 1849.60
Qs=q*n*LCF , Ql=q*n
4655.00 4655.00 4655.00 4655.00 4655.00
2945.00 2945.00 2945.00 2945.00 2945.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
5329.50 5329.50 5329.50 5329.50 5329.50
19426.51 19426.51 19426.51 19426.51 19426.51

Total 48365.6 50379.4 52301.8 53249.2 52843.7


TOR 4.0 4.2 4.4 4.4 4.4 124.814
Latent 22371.5 22371.5 22371.5 22371.5 22371.5
Sensible 25994.1 28007.9 29930.3 30877.7 30472.2
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Cafeteria Dining Space Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 400.349 16.15 16.65 17.15 18.15 18.65
ESE 0.36 202.3615 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 125.73 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 697.62 12.65 12.65 12.65 13.65 14.65
NNE 1.01 442.6805 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 89.54885 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 145.41401 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 247.5699
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 442.68 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 89.55 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 145.41 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 1936.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
2314.70 2386.36 2458.02 2601.35 2673.01
1334.81 1443.47 1552.14 1660.81 1733.26
0.00 0.00 0.00 0.00 0.00
697.67 675.17 697.67 720.18 787.69
3159.29 3159.29 3159.29 3409.04 3658.78
6035.95 6483.06 6930.16 6930.16 6483.06
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1221.00 1311.44 1401.89 1401.89 1311.44
1982.72 2129.59 2276.46 2276.46 2129.59

Qs=U*A*dT

12.00 1244.78 1244.78 1244.78 1244.78 1244.78


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 8786.11 8542.05 7809.88 6833.64 5613.35
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1832.92 3582.52 5415.44 6665.16 6998.41
0.44 2938.32 2839.27 2707.21 2476.11 2575.15
Qs=3.4*W*BF*CLF
6582.40 6582.40 6582.40 6582.40 6582.40
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 80704.4 82953.1 84809.0 85375.7 84364.6


TOR 6.7 6.9 7.1 7.1 7.0 273.933
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 51268.2 53516.9 55372.8 55939.5 54928.4
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Deputy Director office Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 100.14 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 95.33 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 95.33 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 218.00
q n CLF
People Qs 245.00 6.00 1.00
Ql 155.00 6.00
Equipment 358.27
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 6.00 1.00 17.00 15.00
Ql 0.68 6.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
578.98 596.91 614.83 650.68 668.61
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1299.85 1396.14 1492.43 1492.43 1396.14
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 0.00 0.00 0.00 0.00 0.00


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 1892.11 1839.55 1681.87 1471.64 1208.85
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
741.20 741.20 741.20 741.20 741.20
Qs=q*n*LCF , Ql=q*n
1470.00 1470.00 1470.00 1470.00 1470.00
930.00 930.00 930.00 930.00 930.00
358.27 358.27 358.27 358.27 358.27
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1683.00 1683.00 1683.00 1683.00 1683.00
6134.69 6134.69 6134.69 6134.69 6134.69

Total 15088.1 15149.8 15106.3 14931.9 14590.8


TOR 1.3 1.3 1.3 1.2 1.2 173.1729
Latent 7064.7 7064.7 7064.7 7064.7 7064.7
Sensible 8023.4 8085.1 8041.6 7867.2 7526.1
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Director's Office Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 118.8643 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 102.17 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 105.8862 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 127.7461 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 224.7504
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 105.89 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 127.75 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 278.00
q n CLF
People Qs 245.00 5.00 1.00
Ql 155.00 5.00
Equipment 358.27
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 5.00 1.00 17.00 15.00
Ql 0.68 5.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
687.24 708.51 729.79 772.34 793.62
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
566.95 548.66 566.95 585.24 640.10
0.00 0.00 0.00 0.00 0.00
1443.76 1550.70 1657.65 1657.65 1550.70
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1741.82 1870.84 1999.87 1999.87 1870.84
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 1130.05 1130.05 1130.05 1130.05 1130.05


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 2101.58 2043.20 1868.07 1634.56 1342.68
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2614.75 5110.65 7725.41 9508.19 9983.60
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
945.20 945.20 945.20 945.20 945.20
Qs=q*n*LCF , Ql=q*n
1225.00 1225.00 1225.00 1225.00 1225.00
775.00 775.00 775.00 775.00 775.00
358.27 358.27 358.27 358.27 358.27
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1402.50 1402.50 1402.50 1402.50 1402.50
5112.24 5112.24 5112.24 5112.24 5112.24

Total 20104.3 22780.8 25496.0 27106.1 27129.8


TOR 1.7 1.9 2.1 2.3 2.3 130.8441
Latent 5887.2 5887.2 5887.2 5887.2 5887.2
Sensible 14217.1 16893.6 19608.7 21218.9 21242.6
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Lecture Room 1 Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0.00 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 0.00 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 265.65 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0.00 13.50 14.50 15.50 15.50 14.50
ESE 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 76.64 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 174.15
Partition
glass 1.01
Glass 1.01
Door
wood 0.45 53.18
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 76.64 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 410.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1203.06 1203.06 1203.06 1298.17 1393.27
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1044.97 1122.38 1199.78 1199.78 1122.38

Qs=U*A*dT

12.00 875.62 875.62 875.62 875.62 875.62


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 287.20 287.20 287.20 287.20 287.20
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1548.61 1496.41 1426.81 1305.01 1357.21
Qs=3.4*W*BF*CLF
1394.00 1394.00 1394.00 1394.00 1394.00
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 48927.2 48952.4 48960.2 48933.5 49003.4


TOR 4.1 4.1 4.1 4.1 4.1 100.4898
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 19491.0 19516.2 19524.0 19497.3 19567.2
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Lecture Room 2 Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0.00 16.15 16.65 17.15 18.15 18.65
ESE 0.36 247.41 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 0.00 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0.00 13.50 14.50 15.50 15.50 14.50
ESE 1.01 94.88 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 174.15
Partition
glass 1.01
Glass 1.01
Door
wood 0.45 53.18
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 94.88 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 410.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
1631.97 1764.84 1897.70 2030.56 2119.13
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1293.68 1389.50 1485.33 1485.33 1389.50
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 875.62 875.62 875.62 875.62 875.62


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 287.20 287.20 287.20 287.20 287.20
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2065.53 1836.03 1606.52 1453.52 1147.52
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
1394.00 1394.00 1394.00 1394.00 1394.00
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 50121.7 50120.9 50120.1 50099.9 49786.7


TOR 4.2 4.2 4.2 4.2 4.1 98.16427
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 20685.5 20684.7 20683.9 20663.7 20350.5
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Lecture Room 3 Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0 16.15 16.65 17.15 18.15 18.65
ESE 0.36 52.09733 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 0 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 142.72 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0 13.50 14.50 15.50 15.50 14.50
ESE 1.01 143.8058 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 0 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42
Partition
glass 1.01
Glass 1.01
Door
wood 0.45 53.18448
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 143.81 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 489.00
q n CLF
People Qs 245.00 38.00 1.00
Ql 155.00 38.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 38.00 1.00 17.00 15.00
Ql 0.68 38.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
343.64 371.62 399.59 427.57 446.22
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
646.33 646.33 646.33 697.42 748.52
0.00 0.00 0.00 0.00 0.00
1960.79 2106.04 2251.28 2251.28 2106.04
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 0.00 0.00 0.00 0.00 0.00


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 287.20 287.20 287.20 287.20 287.20
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 3130.67 2782.81 2434.96 2203.06 1739.26
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
1662.60 1662.60 1662.60 1662.60 1662.60
Qs=q*n*LCF , Ql=q*n
9310.00 9310.00 9310.00 9310.00 9310.00
5890.00 5890.00 5890.00 5890.00 5890.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
10659.00 10659.00 10659.00 10659.00 10659.00
38853.02 38853.02 38853.02 38853.02 38853.02

Total 72743.3 72568.6 72394.0 72241.2 71701.9


TOR 6.1 6.0 6.0 6.0 6.0 81.05646
Latent 44743.0 44743.0 44743.0 44743.0 44743.0
Sensible 28000.2 27825.6 27651.0 27498.1 26958.8
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Lecture Room 4 Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 0 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 287.18 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 0 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 71.90292 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 174.1493
Partition
glass 1.01
Glass 1.01
Door
wood 0.45 53.18448
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 71.90 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 432.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1300.56 1300.56 1300.56 1403.37 1506.18
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
980.40 1053.02 1125.64 1125.64 1053.02

Qs=U*A*dT

12.00 875.62 875.62 875.62 875.62 875.62


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 287.20 287.20 287.20 287.20 287.20
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1452.91 1403.94 1338.64 1224.36 1273.34
Qs=3.4*W*BF*CLF
1468.80 1468.80 1468.80 1468.80 1468.80
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 48939.2 48962.8 48970.2 48958.7 49037.9


TOR 4.1 4.1 4.1 4.1 4.1 105.8604
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 19503.0 19526.6 19534.0 19522.5 19601.7
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Lecture Room 5 Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0.00 16.15 16.65 17.15 18.15 18.65
ESE 0.36 290.06 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 0.00 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0.00 13.50 14.50 15.50 15.50 14.50
ESE 1.01 69.03 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 174.15
Partition
glass 1.01
Glass 1.01
Door
wood 0.45 53.18
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 69.03 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 432.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
1913.26 2069.02 2224.78 2380.54 2484.38
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
941.19 1010.90 1080.62 1080.62 1010.90
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 875.62 875.62 875.62 875.62 875.62


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 287.20 287.20 287.20 287.20 287.20
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1502.73 1335.76 1168.79 1057.48 834.85
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
1468.80 1468.80 1468.80 1468.80 1468.80
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 49562.5 49621.0 49679.5 49724.0 49535.5


TOR 4.1 4.1 4.1 4.1 4.1 104.3489
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 20126.3 20184.8 20243.3 20287.8 20099.3
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Leisure Room (North) Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 302.29 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 147.20723 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 234.2227
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 147.21 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 278.00
q n CLF
People Qs 245.00 4.00 1.00
Ql 155.00 4.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 4.00 1.00 17.00 15.00
Ql 0.68 4.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1369.00 1369.00 1369.00 1477.22 1585.44
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
2007.17 2155.85 2304.53 2304.53 2155.85

Qs=U*A*dT

12.00 1177.67 1177.67 1177.67 1177.67 1177.67


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2974.55 2874.29 2740.60 2506.64 2606.91
Qs=3.4*W*BF*CLF
945.20 945.20 945.20 945.20 945.20
Qs=q*n*LCF , Ql=q*n
980.00 980.00 980.00 980.00 980.00
620.00 620.00 620.00 620.00 620.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1122.00 1122.00 1122.00 1122.00 1122.00
4089.79 4089.79 4089.79 4089.79 4089.79

Total 15285.4 15333.8 15348.8 15223.1 15282.9


TOR 1.3 1.3 1.3 1.3 1.3 217.3461
Latent 4709.8 4709.8 4709.8 4709.8 4709.8
Sensible 10575.6 10624.0 10639.0 10513.3 10573.1
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Leisure Room (south) Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 89.34046 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0 13.50 14.50 15.50 15.50 14.50
ESE 1.01 0 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 145.3128 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 0 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 0 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 470.1676
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 145.31 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 304.00
q n CLF
People Qs 245.00 4.00 1.00
Ql 155.00 4.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 4.00 1.00 17.00 15.00
Ql 0.68 4.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
267.07 283.06 331.03 363.02 426.98
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1981.34 2128.11 2274.87 2274.87 2128.11
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 2364.00 2364.00 2364.00 2364.00 2364.00


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 3294.00 3547.39 3378.46 2787.23 1942.62
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
1033.60 1033.60 1033.60 1033.60 1033.60
Qs=q*n*LCF , Ql=q*n
980.00 980.00 980.00 980.00 980.00
620.00 620.00 620.00 620.00 620.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1122.00 1122.00 1122.00 1122.00 1122.00
4089.79 4089.79 4089.79 4089.79 4089.79

Total 15751.8 16167.9 16193.8 15634.5 14707.1


TOR 1.3 1.3 1.3 1.3 1.2 225.2719
Latent 4709.8 4709.8 4709.8 4709.8 4709.8
Sensible 11042.0 11458.2 11484.0 10924.7 9997.3
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Maker Space(North) Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 214.0668 16.15 16.65 17.15 18.15 18.65
ESE 0.36 391.1309 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 1395.30 12.65 12.65 12.65 13.65 14.65
NNE 1.01 216.4897 13.50 14.50 15.50 15.50 14.50
ESE 1.01 521.6487 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 168.91589 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 213.84
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 25.11
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 216.49 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 521.65 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 168.92 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 2884.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment 477.60
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1237.67 1275.99 1314.31 1390.94 1429.26
2579.96 2790.00 3000.03 3210.07 3350.09
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
6318.88 6318.88 6318.88 6818.39 7317.91
2951.84 3170.49 3389.15 3389.15 3170.49
7112.68 7639.55 8166.41 8166.41 7639.55
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
2303.17 2473.77 2644.38 2644.38 2473.77

Qs=U*A*dT

12.00 1075.19 1075.19 1075.19 1075.19 1075.19


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 114.50 114.50 114.50 114.50 114.50
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 4296.78 4177.43 3819.36 3341.94 2745.17
0.44 11356.34 10094.53 8832.71 7991.50 6309.08
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 3413.21 3298.16 3144.75 2876.30 2991.35
Qs=3.4*W*BF*CLF
9805.60 9805.60 9805.60 9805.60 9805.60
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
477.60 477.60 477.60 477.60 477.60
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 95617.1 95285.4 94676.6 93875.7 91473.3


TOR 8.0 7.9 7.9 7.8 7.6 365.5392
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 66180.9 65849.2 65240.4 64439.5 62037.1
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Maker Space S Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0 16.15 16.65 17.15 18.15 18.65
ESE 0.36 160.3823 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 141.0072 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 341.35 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0 13.50 14.50 15.50 15.50 14.50
ESE 1.01 300.3131 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 300.3131 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 0 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 99.9752 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 198.8955
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 24.9938
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 300.31 0.27 0.24 0.21 0.19 0.15
SSW 66.05 300.31 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 99.98 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 1102.00
q n CLF
People Qs 245.00 13.00 1.00
Ql 155.00 13.00
Equipment 358.27
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 13.00 1.00 17.00 15.00
Ql 0.68 13.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
1057.91 1144.03 1230.16 1316.28 1373.70
421.51 446.75 522.47 572.95 673.92
0.00 0.00 0.00 0.00 0.00
1545.85 1545.85 1545.85 1668.05 1790.25
0.00 0.00 0.00 0.00 0.00
4094.77 4398.09 4701.40 4701.40 4398.09
4094.77 4398.09 4701.40 4701.40 4398.09
0.00 0.00 0.00 0.00 0.00
1363.16 1464.14 1565.11 1565.11 1464.14

Qs=U*A*dT

12.00 1000.05 1000.05 1000.05 1000.05 1000.05


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 113.97 113.97 113.97 113.97 113.97
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 6537.85 5811.42 5084.99 4600.71 3632.14
0.44 6807.61 7331.27 6982.16 5760.28 4014.74
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2020.15 1952.06 1861.27 1702.38 1770.47
Qs=3.4*W*BF*CLF
3746.80 3746.80 3746.80 3746.80 3746.80
Qs=q*n*LCF , Ql=q*n
3185.00 3185.00 3185.00 3185.00 3185.00
2015.00 2015.00 2015.00 2015.00 2015.00
358.27 358.27 358.27 358.27 358.27
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
3646.50 3646.50 3646.50 3646.50 3646.50
13291.82 13291.82 13291.82 13291.82 13291.82

Total 55301.0 55849.1 55552.2 53946.0 50872.9


TOR 4.6 4.7 4.6 4.5 4.2 238.0463
Latent 15306.8 15306.8 15306.8 15306.8 15306.8
Sensible 39994.2 40542.3 40245.4 38639.2 35566.1
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Office Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 265.76 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 66.62861 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 183.5193
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 26.59224
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 66.63 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 134.00
q n CLF
People Qs 245.00 5.00 1.00
Ql 155.00 5.00
Equipment 358.27
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 5.00 1.00 17.00 15.00
Ql 0.68 5.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1203.55 1203.55 1203.55 1298.69 1393.84
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
908.48 975.78 1043.07 1043.07 975.78

Qs=U*A*dT

12.00 922.74 922.74 922.74 922.74 922.74


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 121.26 121.26 121.26 121.26 121.26
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1346.34 1300.95 1240.44 1134.55 1179.93
Qs=3.4*W*BF*CLF
455.60 455.60 455.60 455.60 455.60
Qs=q*n*LCF , Ql=q*n
1225.00 1225.00 1225.00 1225.00 1225.00
775.00 775.00 775.00 775.00 775.00
358.27 358.27 358.27 358.27 358.27
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1402.50 1402.50 1402.50 1402.50 1402.50
5112.24 5112.24 5112.24 5112.24 5112.24

Total 13831.0 13852.9 13859.7 13848.9 13922.2


TOR 1.2 1.2 1.2 1.2 1.2 116.0201
Latent 5887.2 5887.2 5887.2 5887.2 5887.2
Sensible 7943.7 7965.6 7972.4 7961.7 8034.9
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Audiotorium Hall Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 0.00 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 1214.17 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 0.00 13.50 14.50 15.50 15.50 14.50
ESE 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 0.00 13.50 14.50 15.50 15.50 14.50
Roof 0.46 5026.00 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 3113.49
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 344.74
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 5026.00
q n CLF
People Qs 245.00 250.00 1.00
Ql 155.00 250.00
Equipment 2132.46
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 250.00 1.00 17.00 15.00
Ql 0.68 250.00 100.24 15.00

Total
TOR
Latent
Sensible
CALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
3629.52 3846.85 4498.86 4933.53 5802.88
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
83057.16 106176.76 124672.44 140856.16 150104.00
Qs=U*A*dT

12.00 15654.62 15654.62 15654.62 15654.62 15654.62


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 1572.01 1572.01 1572.01 1572.01 1572.01
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
17088.40 17088.40 17088.40 17088.40 17088.40
Qs=q*n*LCF , Ql=q*n
61250.00 61250.00 61250.00 61250.00 61250.00
38750.00 38750.00 38750.00 38750.00 38750.00
2132.46 2132.46 2132.46 2132.46 2132.46
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
70125.00 70125.00 70125.00 70125.00 70125.00
255612.00 255612.00 255612.00 255612.00 255612.00

Total 548871.2 572208.1 591355.8 607974.2 618091.4


TOR 45.7 47.7 49.3 50.7 51.5 101.9894
Latent 294362.0 294362.0 294362.0 294362.0 294362.0
Sensible 254509.2 277846.1 296993.8 313612.2 323729.4
COOLING LOAD CALCULATION

Floor First Design condition DBT(F) WBT(F)


Room Training Hall Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 447.17 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 440.24 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 44.18 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 501.46
Partition
glass 1.01
Glass 1.01
Door
wood 0.45 25.11
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 440.24 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 44.18 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 630.00
q n CLF
People Qs 245.00 17.00 1.00
Ql 155.00 17.00
Equipment 3582.70
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 17.00 1.00 17.00 15.00
Ql 0.68 17.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
2025.09 2025.09 2025.09 2185.17 2345.26
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
6002.73 6447.37 6892.02 6892.02 6447.37
602.33 646.94 691.56 691.56 646.94

Qs=U*A*dT

12.00 2521.34 2521.34 2521.34 2521.34 2521.34


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 135.59 135.59 135.59 135.59 135.59
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 9011.07 17612.55 26623.62 32767.53 34405.91
0.44 892.63 862.54 822.42 752.21 782.30
Qs=3.4*W*BF*CLF
2142.00 2142.00 2142.00 2142.00 2142.00
Qs=q*n*LCF , Ql=q*n
4165.00 4165.00 4165.00 4165.00 4165.00
2635.00 2635.00 2635.00 2635.00 2635.00
3582.70 3582.70 3582.70 3582.70 3582.70
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
4768.50 4768.50 4768.50 4768.50 4768.50
17381.62 17381.62 17381.62 17381.62 17381.62

Total 55865.6 64926.2 74386.5 80620.2 81959.5


TOR 4.7 5.4 6.2 6.7 6.8 101.6314
Latent 20016.6 20016.6 20016.6 20016.6 20016.6
Sensible 35849.0 44909.6 54369.8 60603.6 61942.9
COOLING LOAD CALCULATION

Floor Second Design condition DBT(F) WBT(F)


Room Cafeteria Dining Space Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 133.60 16.15 16.65 17.15 18.15 18.65
ESE 0.36 202.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 678.04 12.65 12.65 12.65 13.65 14.65
NNE 1.01 273.70 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 164.77 13.50 14.50 15.50 15.50 14.50
Roof 0.46 1536.57 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 654.45
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 273.70 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 164.77 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 1537.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
772.44 796.36 820.27 868.10 892.02
1334.81 1443.47 1552.14 1660.81 1733.26
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
3070.66 3070.66 3070.66 3313.40 3556.13
3731.96 4008.41 4284.85 4284.85 4008.41
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
2246.65 2413.07 2579.49 2579.49 2413.07
25392.59 32460.81 38115.39 43063.14 45890.43
Qs=U*A*dT

12.00 3290.55 3290.55 3290.55 3290.55 3290.55


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 5432.36 5281.46 4828.76 4225.17 3470.67
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 3329.45 3217.22 3067.58 2805.72 2917.94
Qs=3.4*W*BF*CLF
5225.80 5225.80 5225.80 5225.80 5225.80
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 96401.0 103781.5 109409.2 113890.7 115972.0


TOR 8.0 8.6 9.1 9.5 9.7 168.5782
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 66964.8 74345.3 79973.0 84454.5 86535.8
COOLING LOAD CALCULATION

Floor Second Design condition DBT(F) WBT(F)


Room Leisure Room (north) Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 302.30 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 147.21 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 234.23
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 147.21 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 278.00
q n CLF
People Qs 245.00 4.00 1.00
Ql 155.00 4.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 4.00 1.00 17.00 15.00
Ql 0.68 4.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1369.03 1369.03 1369.03 1477.25 1585.47
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
2007.17 2155.85 2304.53 2304.53 2155.85

Qs=U*A*dT

12.00 1177.69 1177.69 1177.69 1177.69 1177.69


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2974.55 2874.28 2740.59 2506.64 2606.91
Qs=3.4*W*BF*CLF
945.20 945.20 945.20 945.20 945.20
Qs=q*n*LCF , Ql=q*n
980.00 980.00 980.00 980.00 980.00
620.00 620.00 620.00 620.00 620.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1122.00 1122.00 1122.00 1122.00 1122.00
4089.79 4089.79 4089.79 4089.79 4089.79

Total 15285.4 15333.8 15348.8 15223.1 15282.9


TOR 1.3 1.3 1.3 1.3 1.3 217.3456
Latent 4709.8 4709.8 4709.8 4709.8 4709.8
Sensible 10575.6 10624.0 10639.0 10513.3 10573.1
COOLING LOAD CALCULATION

Floor Second Design condition DBT(F) WBT(F)


Room Leisure Room (south) Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 110.72 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 123.93 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 300.85 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 480.07
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 123.93 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 301.00
q n CLF
People Qs 245.00 3.00 1.00
Ql 155.00 3.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 3.00 1.00 17.00 15.00
Ql 0.68 3.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
730.33 789.78 849.24 908.70 948.33
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1689.77 1814.94 1940.11 1940.11 1814.94
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
4971.70 6355.61 7462.73 8431.47 8985.04
Qs=U*A*dT

12.00 2413.78 2413.78 2413.78 2413.78 2413.78


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2697.95 2398.17 2098.40 1898.56 1498.86
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
1023.40 1023.40 1023.40 1023.40 1023.40
Qs=q*n*LCF , Ql=q*n
735.00 735.00 735.00 735.00 735.00
465.00 465.00 465.00 465.00 465.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
841.50 841.50 841.50 841.50 841.50
3067.34 3067.34 3067.34 3067.34 3067.34

Total 18635.8 19904.5 20896.5 21724.9 21793.2


TOR 1.6 1.7 1.7 1.8 1.8 172.8519
Latent 3532.3 3532.3 3532.3 3532.3 3532.3
Sensible 15103.4 16372.2 17364.2 18192.5 18260.8
COOLING LOAD CALCULATION

Floor Second Design condition DBT(F) WBT(F)


Room Maker Room N Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 246.41 16.15 16.65 17.15 18.15 18.65
ESE 0.36 676.10 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 1475.75 12.65 12.65 12.65 13.65 14.65
NNE 1.01 184.15 13.50 14.50 15.50 15.50 14.50
ESE 1.01 236.68 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 123.20 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 215.33
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 23.62
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 184.15 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 236.68 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 123.20 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 2884.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment 597.00
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1424.67 1468.78 1512.88 1601.10 1645.21
4459.66 4822.72 5185.79 5548.85 5790.90
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
6683.23 6683.23 6683.23 7211.55 7739.87
2510.89 2696.88 2882.87 2882.87 2696.88
3227.13 3466.18 3705.23 3705.23 3466.18
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1679.83 1804.26 1928.70 1928.70 1804.26

Qs=U*A*dT

12.00 1082.68 1082.68 1082.68 1082.68 1082.68


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 107.71 107.71 107.71 107.71 107.71
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 3654.92 3553.40 3248.82 2842.72 2335.09
0.44 5152.55 4580.04 4007.54 3625.87 2862.53
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 2489.45 2405.53 2293.65 2097.85 2181.76
Qs=3.4*W*BF*CLF
9805.60 9805.60 9805.60 9805.60 9805.60
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
597.00 597.00 597.00 597.00 597.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 85449.0 85647.7 85615.4 85611.4 84689.4


TOR 7.1 7.1 7.1 7.1 7.1 404.2264
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 56012.8 56211.5 56179.2 56175.2 55253.2
COOLING LOAD CALCULATION

Floor Second Design condition DBT(F) WBT(F)


Room Maker Room South Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 213.13 16.15 16.65 17.15 18.15 18.65
ESE 0.36 361.66 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 605.48 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 471.46 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 227.71 13.50 14.50 15.50 15.50 14.50
Roof 0.46 2106.90 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 201.34
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 23.62
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 471.46 0.27 0.24 0.21 0.19 0.15
SSW 66.05 0.00 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 227.71 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 2107.00
q n CLF
People Qs 245.00 15.00 1.00
Ql 155.00 15.00
Equipment 358.20
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 15.00 1.00 17.00 15.00
Ql 0.68 15.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1232.23 1270.38 1308.53 1384.82 1422.97
2385.56 2579.78 2773.99 2968.20 3097.67
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
2742.04 2742.04 2742.04 2958.80 3175.56
0.00 0.00 0.00 0.00 0.00
6428.41 6904.59 7380.77 7380.77 6904.59
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
3104.80 3334.79 3564.77 3564.77 3334.79
34817.58 44509.32 52262.71 59046.93 62923.62
Qs=U*A*dT

12.00 1012.33 1012.33 1012.33 1012.33 1012.33


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 107.71 107.71 107.71 107.71 107.71
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 10263.82 9123.39 7982.97 7222.69 5702.12
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 4601.20 4446.11 4239.31 3877.42 4032.51
Qs=3.4*W*BF*CLF
7163.80 7163.80 7163.80 7163.80 7163.80
Qs=q*n*LCF , Ql=q*n
3675.00 3675.00 3675.00 3675.00 3675.00
2325.00 2325.00 2325.00 2325.00 2325.00
358.20 358.20 358.20 358.20 358.20
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
4207.50 4207.50 4207.50 4207.50 4207.50
15336.72 15336.72 15336.72 15336.72 15336.72

Total 99761.9 109096.6 116441.3 122590.6 124780.1


TOR 8.3 9.1 9.7 10.2 10.4 217.1394
Latent 17661.7 17661.7 17661.7 17661.7 17661.7
Sensible 82100.2 91434.9 98779.6 104928.9 107118.4
COOLING LOAD CALCULATION

Floor Third Design condition DBT(F) WBT(F)


Room Leisure Room Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 150.00 8.35 8.85 10.35 11.35 13.35
WNW 0.36 117.25 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 84.22 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 98.02 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 234.23
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 84.22 0.78 0.84 0.80 0.66 0.46
WNW 211.45 98.02 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 278.00
q n CLF
People Qs 245.00 4.00 1.00
Ql 155.00 4.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 4.00 1.00 17.00 15.00
Ql 0.68 4.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
448.41 475.26 555.81 609.51 716.91
650.64 629.66 650.64 671.63 734.60
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1148.32 1233.38 1318.44 1318.44 1233.38
1336.56 1435.56 1534.57 1534.57 1435.56
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 1177.69 1177.69 1177.69 1177.69 1177.69


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1909.10 2055.95 1958.05 1615.39 1125.88
0.44 2006.39 3921.58 5927.97 7295.97 7660.76
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
945.20 945.20 945.20 945.20 945.20
Qs=q*n*LCF , Ql=q*n
980.00 980.00 980.00 980.00 980.00
620.00 620.00 620.00 620.00 620.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1122.00 1122.00 1122.00 1122.00 1122.00
4089.79 4089.79 4089.79 4089.79 4089.79

Total 16434.1 18686.1 20880.2 21980.2 21841.8


TOR 1.4 1.6 1.7 1.8 1.8 159.7688
Latent 4709.8 4709.8 4709.8 4709.8 4709.8
Sensible 11724.3 13976.3 16170.4 17270.4 17132.0
COOLING LOAD CALCULATION

Floor Third Design condition DBT(F) WBT(F)


Room Maker Space Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 246.41 16.15 16.65 17.15 18.15 18.65
ESE 0.36 676.10 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 346.50 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 337.28 12.65 12.65 12.65 13.65 14.65
NNE 1.01 184.15 13.50 14.50 15.50 15.50 14.50
ESE 1.01 236.68 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 313.98 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 44.23 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 473.66
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 23.63
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 184.15 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 236.68 0.27 0.24 0.21 0.19 0.15
SSW 66.05 313.98 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 44.23 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 2884.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment 597.00
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1424.65 1468.76 1512.87 1601.08 1645.19
4459.67 4822.74 5185.81 5548.87 5790.92
1035.78 1097.80 1283.87 1407.92 1656.01
0.00 0.00 0.00 0.00 0.00
1527.44 1527.44 1527.44 1648.19 1768.94
2510.87 2696.86 2882.85 2882.85 2696.86
3227.09 3466.13 3705.18 3705.18 3466.13
4281.06 4598.17 4915.29 4915.29 4598.17
0.00 0.00 0.00 0.00 0.00
603.10 647.78 692.45 692.45 647.78

Qs=U*A*dT

12.00 2381.59 2381.59 2381.59 2381.59 2381.59


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 107.74 107.74 107.74 107.74 107.74
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 3654.90 3553.38 3248.80 2842.70 2335.08
0.44 5152.48 4579.98 4007.48 3625.82 2862.49
0.44 7117.31 7664.80 7299.80 6022.34 4197.39
0.44 0.00 0.00 0.00 0.00 0.00
0.44 893.78 863.65 823.48 753.18 783.31
Qs=3.4*W*BF*CLF
9805.60 9805.60 9805.60 9805.60 9805.60
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
597.00 597.00 597.00 597.00 597.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 91353.8 92453.1 92551.0 91111.5 87913.9


TOR 7.6 7.7 7.7 7.6 7.3 373.9345
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 61917.6 63016.9 63114.8 61675.3 58477.7
COOLING LOAD CALCULATION

Floor Fourth Design condition DBT(F) WBT(F)


Room Leisure Room Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 150.00 8.35 8.85 10.35 11.35 13.35
WNW 0.36 117.25 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 84.22 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 98.02 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 234.23
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 84.22 0.78 0.84 0.80 0.66 0.46
WNW 211.45 98.02 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 278.00
q n CLF
People Qs 245.00 4.00 1.00
Ql 155.00 4.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 4.00 1.00 17.00 15.00
Ql 0.68 4.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
448.41 475.26 555.81 609.51 716.91
650.64 629.66 650.64 671.63 734.60
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1148.32 1233.38 1318.44 1318.44 1233.38
1336.56 1435.56 1534.57 1534.57 1435.56
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 1177.69 1177.69 1177.69 1177.69 1177.69


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1909.10 2055.95 1958.05 1615.39 1125.88
0.44 2006.39 3921.58 5927.97 7295.97 7660.76
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
945.20 945.20 945.20 945.20 945.20
Qs=q*n*LCF , Ql=q*n
980.00 980.00 980.00 980.00 980.00
620.00 620.00 620.00 620.00 620.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1122.00 1122.00 1122.00 1122.00 1122.00
4089.79 4089.79 4089.79 4089.79 4089.79

Total 16434.1 18686.1 20880.2 21980.2 21841.8


TOR 1.4 1.6 1.7 1.8 1.8 159.7688
Latent 4709.8 4709.8 4709.8 4709.8 4709.8
Sensible 11724.3 13976.3 16170.4 17270.4 17132.0
COOLING LOAD CALCULATION

Floor Fourth Design condition DBT(F) WBT(F)


Room Maker Space Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 246.41 16.15 16.65 17.15 18.15 18.65
ESE 0.36 676.10 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 346.50 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 337.28 12.65 12.65 12.65 13.65 14.65
NNE 1.01 184.15 13.50 14.50 15.50 15.50 14.50
ESE 1.01 236.68 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 313.98 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 44.23 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 473.66
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 23.63
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 184.15 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 236.68 0.27 0.24 0.21 0.19 0.15
SSW 66.05 313.98 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 44.23 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 2884.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment 597.00
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1424.65 1468.76 1512.87 1601.08 1645.19
4459.67 4822.74 5185.81 5548.87 5790.92
1035.78 1097.80 1283.87 1407.92 1656.01
0.00 0.00 0.00 0.00 0.00
1527.44 1527.44 1527.44 1648.19 1768.94
2510.87 2696.86 2882.85 2882.85 2696.86
3227.09 3466.13 3705.18 3705.18 3466.13
4281.06 4598.17 4915.29 4915.29 4598.17
0.00 0.00 0.00 0.00 0.00
603.10 647.78 692.45 692.45 647.78

Qs=U*A*dT

12.00 2381.59 2381.59 2381.59 2381.59 2381.59


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 107.74 107.74 107.74 107.74 107.74
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 3654.90 3553.38 3248.80 2842.70 2335.08
0.44 5152.48 4579.98 4007.48 3625.82 2862.49
0.44 7117.31 7664.80 7299.80 6022.34 4197.39
0.44 0.00 0.00 0.00 0.00 0.00
0.44 893.78 863.65 823.48 753.18 783.31
Qs=3.4*W*BF*CLF
9805.60 9805.60 9805.60 9805.60 9805.60
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
597.00 597.00 597.00 597.00 597.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 91353.8 92453.1 92551.0 91111.5 87913.9


TOR 7.6 7.7 7.7 7.6 7.3 373.9345
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 61917.6 63016.9 63114.8 61675.3 58477.7
COOLING LOAD CALCULATION

Floor Fifth Design condition DBT(F) WBT(F)


Room Leisure Room Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 16.15 16.65 17.15 18.15 18.65
ESE 0.36 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 150.00 8.35 8.85 10.35 11.35 13.35
WNW 0.36 117.25 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 12.65 12.65 12.65 13.65 14.65
NNE 1.01 13.50 14.50 15.50 15.50 14.50
ESE 1.01 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 84.22 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 98.02 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 234.23
Partition
glass 1.01
Glass 1.01
Door
wood 0.38
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 0.00 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 0.00 0.27 0.24 0.21 0.19 0.15
SSW 66.05 84.22 0.78 0.84 0.80 0.66 0.46
WNW 211.45 98.02 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 0.00 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 278.00
q n CLF
People Qs 245.00 4.00 1.00
Ql 155.00 4.00
Equipment
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 4.00 1.00 17.00 15.00
Ql 0.68 4.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
448.41 475.26 555.81 609.51 716.91
650.64 629.66 650.64 671.63 734.60
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
1148.32 1233.38 1318.44 1318.44 1233.38
1336.56 1435.56 1534.57 1534.57 1435.56
0.00 0.00 0.00 0.00 0.00

Qs=U*A*dT

12.00 1177.69 1177.69 1177.69 1177.69 1177.69


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 0.00 0.00 0.00 0.00 0.00
0.44 0.00 0.00 0.00 0.00 0.00
0.44 1909.10 2055.95 1958.05 1615.39 1125.88
0.44 2006.39 3921.58 5927.97 7295.97 7660.76
0.44 0.00 0.00 0.00 0.00 0.00
Qs=3.4*W*BF*CLF
945.20 945.20 945.20 945.20 945.20
Qs=q*n*LCF , Ql=q*n
980.00 980.00 980.00 980.00 980.00
620.00 620.00 620.00 620.00 620.00
0.00 0.00 0.00 0.00 0.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
1122.00 1122.00 1122.00 1122.00 1122.00
4089.79 4089.79 4089.79 4089.79 4089.79

Total 16434.1 18686.1 20880.2 21980.2 21841.8


TOR 1.4 1.6 1.7 1.8 1.8 159.7688
Latent 4709.8 4709.8 4709.8 4709.8 4709.8
Sensible 11724.3 13976.3 16170.4 17270.4 17132.0
COOLING LOAD CALCULATION

Floor Fifth Design condition DBT(F) WBT(F)


Room Maker Space Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 246.41 16.15 16.65 17.15 18.15 18.65
ESE 0.36 676.10 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 346.50 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 337.28 12.65 12.65 12.65 13.65 14.65
NNE 1.01 184.15 13.50 14.50 15.50 15.50 14.50
ESE 1.01 236.68 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 313.98 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 44.23 13.50 14.50 15.50 15.50 14.50
Roof 0.46 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 473.66
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 23.63
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 184.15 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 236.68 0.27 0.24 0.21 0.19 0.15
SSW 66.05 313.98 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 44.23 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 2884.00
q n CLF
People Qs 245.00 25.00 1.00
Ql 155.00 25.00
Equipment 597.00
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 25.00 1.00 17.00 15.00
Ql 0.68 25.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1424.65 1468.76 1512.87 1601.08 1645.19
4459.67 4822.74 5185.81 5548.87 5790.92
1035.78 1097.80 1283.87 1407.92 1656.01
0.00 0.00 0.00 0.00 0.00
1527.44 1527.44 1527.44 1648.19 1768.94
2510.87 2696.86 2882.85 2882.85 2696.86
3227.09 3466.13 3705.18 3705.18 3466.13
4281.06 4598.17 4915.29 4915.29 4598.17
0.00 0.00 0.00 0.00 0.00
603.10 647.78 692.45 692.45 647.78

Qs=U*A*dT

12.00 2381.59 2381.59 2381.59 2381.59 2381.59


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 107.74 107.74 107.74 107.74 107.74
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 3654.90 3553.38 3248.80 2842.70 2335.08
0.44 5152.48 4579.98 4007.48 3625.82 2862.49
0.44 7117.31 7664.80 7299.80 6022.34 4197.39
0.44 0.00 0.00 0.00 0.00 0.00
0.44 893.78 863.65 823.48 753.18 783.31
Qs=3.4*W*BF*CLF
9805.60 9805.60 9805.60 9805.60 9805.60
Qs=q*n*LCF , Ql=q*n
6125.00 6125.00 6125.00 6125.00 6125.00
3875.00 3875.00 3875.00 3875.00 3875.00
597.00 597.00 597.00 597.00 597.00
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
7012.50 7012.50 7012.50 7012.50 7012.50
25561.20 25561.20 25561.20 25561.20 25561.20

Total 91353.8 92453.1 92551.0 91111.5 87913.9


TOR 7.6 7.7 7.7 7.6 7.3 373.9345
Latent 29436.2 29436.2 29436.2 29436.2 29436.2
Sensible 61917.6 63016.9 63114.8 61675.3 58477.7
COOLING LOAD CALCULATION

Floor Sixth Design condition DBT(F) WBT(F)


Room Researchers Library Indoor 75.0 62.6
Outdoor 92.0 83.7

CLTDc
Direction U Net area A 1pm 2pm 3pm 4pm 5pm
NNE 0.36 226.57 16.15 16.65 17.15 18.15 18.65
ESE 0.36 321.00 18.43 19.93 21.43 22.93 23.93
Wall SSW 0.36 353.84 8.35 8.85 10.35 11.35 13.35
WNW 0.36 15.50 15.00 15.50 16.00 17.50
Shaded 0.36 382.08 12.65 12.65 12.65 13.65 14.65
NNE 1.01 214.75 13.50 14.50 15.50 15.50 14.50
ESE 1.01 593.50 13.50 14.50 15.50 15.50 14.50
Glass
SSW 1.01 88.49 13.50 14.50 15.50 15.50 14.50
(Conduction)
WNW 1.01 13.50 14.50 15.50 15.50 14.50
Shaded 1.01 44.18 13.50 14.50 15.50 15.50 14.50
Roof 0.46 2563.32 35.93 45.93 53.93 60.93 64.93

Floor
brick 0.42 935.78
Partition
glass 1.01
Glass 1.01
Door
wood 0.38 22.20
CLF
Direction SHGF A 1pm 2pm 3pm 4pm 5pm
NNE 125.30 214.75 0.36 0.35 0.32 0.28 0.23
Solar glass ESE 183.25 593.50 0.27 0.24 0.21 0.19 0.15
SSW 66.05 88.49 0.78 0.84 0.80 0.66 0.46
WNW 211.45 0.00 0.22 0.43 0.65 0.80 0.84
Shaded 51.60 44.18 0.89 0.86 0.82 0.75 0.78
BF CLF Installed Wattage
Light
1.00 1.00 2563.00
q n CLF
People Qs 245.00 45.00 1.00
Ql 155.00 45.00
Equipment 2268.95
factor n CLF dT dw CFM
Ventilation
Ventilation Qs 1.10 45.00 1.00 17.00 15.00
Ql 0.68 45.00 100.24 15.00

Total
TOR
Latent
Sensible
ALCULATION

RH(%) w(gr/lb)
50.0 65.1
72.0 165.3

RSHG Qs=U*A*CLTDc (Btu/hr),Qs=U*A*dT


dT 1pm 2pm 3pm 4pm 5pm
1309.94 1350.50 1391.06 1472.17 1512.72
2117.39 2289.77 2462.14 2634.52 2749.44
1057.73 1121.06 1311.07 1437.75 1691.10
0.00 0.00 0.00 0.00 0.00
1730.31 1730.31 1730.31 1867.09 2003.87
2928.14 3145.04 3361.94 3361.94 3145.04
8092.35 8691.78 9291.22 9291.22 8691.78
1206.52 1295.90 1385.27 1385.27 1295.90
0.00 0.00 0.00 0.00 0.00
602.33 646.94 691.56 691.56 646.94
42360.14 54151.42 63584.43 71838.32 76554.83
Qs=U*A*dT

12.00 4705.12 4705.12 4705.12 4705.12 4705.12


12.00 0.00 0.00 0.00 0.00 0.00
12.00 0.00 0.00 0.00 0.00 0.00
12.00 101.25 101.25 101.25 101.25 101.25
RSHG Qs=A*SC*SHGF*CLF
SC 1pm 2pm 3pm 4pm 5pm
0.44 4262.29 4143.90 3788.71 3315.12 2723.13
0.44 12920.52 11484.90 10049.29 9092.22 7178.07
0.44 2005.86 2160.16 2057.29 1697.27 1182.94
0.44 0.00 0.00 0.00 0.00 0.00
0.44 892.62 862.54 822.42 752.21 782.30
Qs=3.4*W*BF*CLF
8714.20 8714.20 8714.20 8714.20 8714.20
Qs=q*n*LCF , Ql=q*n
11025.00 11025.00 11025.00 11025.00 11025.00
6975.00 6975.00 6975.00 6975.00 6975.00
2268.95 2268.95 2268.95 2268.95 2268.95
Qs=f*n*CLF*CFM*dT,Ql=f*n*CLF*CFM*dw
12622.50 12622.50 12622.50 12622.50 12622.50
46010.16 46010.16 46010.16 46010.16 46010.16

Total 173908.3 185496.4 194348.9 201258.8 202580.3


TOR 14.5 15.5 16.2 16.8 16.9 158.2515
Latent 52985.2 52985.2 52985.2 52985.2 52985.2
Sensible 120923.2 132511.2 141363.7 148273.7 149595.1
Floor Area No. of
Floor Room Equipments
(sq.ft) People
General Enquiry 327.9 4 2 Computers
1 Data Projector , 2
Conference hall 1349.7 105
Speakers
Control room 209.3 2
1 Data Projector , 2
Seminar hall 1024.4 30
Speakers
Ground Office (Wood Workshop) 142.8 5 1 Desktop ,1 idle printer
2 Desktop ,
Account 157.5 6
2 continuous printer
Staff room 543.6 19
Cafeteria Dining Space 1357.4 20
Office( Metal Workshop) 249.0 7 2 Desktop ,2 idle printer
Total 5361.5

Training Hall 629.3 17 10 desktop


Office 133.3 5 1 desktop
Director's Room 277.9 5 1 desktop
Deputy Director's Room 217.6 6 1 desktop
Cafeteria Dining Space 1935.8 25
Leisure Room N 277.6 4
Maker Space N 2883.5 25 4 laptops
Lecture Room1 409.9 25
Lecture Room 2 409.9 25
First
Lecture Room 3 489.4 38
Lecture Room 4 432.2 25
Lecture Room 5 432.2 25
Maker Space S 1102.1 13 3 laptops
Leisure Room S 304.0 4
1 Data Projector,
Auditorium Room 5025.1 250 1 interactive white board,
5 speakers
Total 14959.8

Cafeteria Dining Space 1536.7 25


Maker Room N 2883.5 25 5 Laptops
Leisure Room N 277.6 4
Second
Maker Room S 2106.9 15 3 Laptops
Leisure Room S 300.9 3
Second

Total 7105.6

Leisure Room 277.6 4


Third Maker Space 2883.5 25
Total 3161.1

Leisure Room 277.6 4


Fourth Maker Space 2883.5 25 5 laptops
Total 3161.1

Leisure Room 277.6 4


Fifth Maker space 2883.5 25 5 laptops
Total 3161.1

Sixth Researcher's Library 2563.3 45 4 laptops, 8 Desktops

Grand Total 39473.6


Load Calculation(TR)
1pm 2pm 3pm 4pm 5pm
1.56 1.76 1.97 2.11 2.15
15.85 15.85 15.86 15.87 15.89
0.58 0.58 0.58 0.58 0.58
5.00 5.00 5.00 5.01 5.02
1.27 1.30 1.30 1.28 1.24
1.26 1.26 1.26 1.27 1.28
4.03 4.20 4.36 4.44 4.40
5.15 5.38 5.59 5.71 5.67
2.22 2.21 2.19 2.15 2.06
36.94 37.54 38.11 38.41 38.28

4.66 5.41 6.20 6.72 6.83


1.15 1.15 1.15 1.15 1.16
1.68 1.90 2.12 2.26 2.26
1.26 1.26 1.26 1.24 1.22
6.73 6.91 7.07 7.11 7.03
1.27 1.28 1.28 1.27 1.27
7.97 7.94 7.89 7.82 7.62
4.08 4.08 4.08 4.08 4.08
4.18 4.18 4.18 4.17 4.15
6.06 6.05 6.03 6.02 5.98
4.08 4.08 4.08 4.08 4.09
4.13 4.14 4.14 4.14 4.13
4.61 4.65 4.63 4.50 4.24
1.31 1.35 1.35 1.30 1.23

45.74 47.68 49.28 50.66 51.51

98.89 102.06 104.74 106.54 106.79

8.03 8.64 9.11 9.49 9.66


7.11 7.13 7.13 7.13 7.05
1.27 1.28 1.28 1.27 1.27
8.30 9.08 9.69 10.21 10.39
1.55 1.66 1.74 1.81 1.81
26.27 27.79 28.95 29.90 30.19

1.37 1.55 1.74 1.83 1.82


7.60 7.69 7.70 7.58 7.32
8.97 9.25 9.44 9.41 9.13

1.37 1.55 1.74 1.83 1.82


7.60 7.69 7.70 7.58 7.32
8.97 9.25 9.44 9.41 9.13

1.37 1.55 1.74 1.83 1.82


7.60 7.69 7.70 7.58 7.32
8.97 9.25 9.44 9.41 9.13

14.48 15.45 16.18 16.76 16.87

203.49 210.59 216.31 219.85 219.53


Floor Area No. of
Floor Room Equipments
(ft) People
Cafeteria Dining Space 1536.66 25
Maker Room N 2883.54 25 5 Laptops
Leisure Room N 277.60 4
Second
Maker Room S 2106.93 15 3 Laptops
Leisure Room S 300.85 3
Total

Leisure Room 277.60 4


Third Maker Space 2883.54 25
Total

Leisure Room 277.60 4


Fourth Maker Space 2883.54 25 5 laptops
Total

Leisure Room 277.60 4


Fifth Maker space 2883.54 25 5 laptops
Total

Sixth Researcher's Library 2563.32 45 4 laptops, 8 Desktop

Grand
204
Total
Load Calculation
1pm 2pm 3pm 4pm 5pm
8.03 8.65 9.12 9.49 9.66
7.12 7.14 7.13 7.13 7.06
1.27 1.28 1.28 1.27 1.27
8.31 9.09 9.70 10.22 10.40
1.55 1.66 1.74 1.81 1.82
26.29 27.81 28.98 29.92 30.21

1.37 1.56 1.74 1.83 1.82


7.61 7.70 7.71 7.59 7.33
8.98 9.26 9.45 9.42 9.15

1.37 1.56 1.74 1.83 1.82


7.61 7.70 7.71 7.59 7.33
8.98 9.26 9.45 9.42 9.15

1.37 1.56 1.74 1.83 1.82


7.61 7.70 7.71 7.59 7.33
8.98 9.26 9.45 9.42 9.15

14.49 15.46 16.20 16.77 16.88

203.56 210.66 216.38 219.92 219.60


Floor 1pm 2pm 3pm 4pm 5pm
Ground 36.9 37.5 38.1 38.4 38.3
First 98.9 102.1 104.7 106.5 106.8
Second 26.3 27.8 29.0 29.9 30.2
Third 9.0 9.3 9.5 9.4 9.1 Duration/Floor
Fourth 9.0 9.3 9.5 9.4 9.1 full
Fifth 9.0 9.3 9.5 9.4 9.1 partial
Sixth 14.5 15.5 16.2 16.8 16.9 Total
Total 203.6 210.7 216.4 219.9 219.6
GF 1F 2F 3F 4F 5F 6F Total
17.53 49.16 29.92 9.42 9.42 9.42 16.77 141.65
20.88 57.38 0 0 0 0 0 78.26
38.41 106.54 29.92 9.42 9.42 9.42 16.77 219.92

219.92
Cooling Load Fluctuation
225.00

220.00

Cooling Load (TOR)


215.00

210.00

205.00

200.00

195.00
1pm 2pm 3pm
Time 4pm 5
d Fluctuation

3pm
Time 4pm 5pm
Cooling load at 4pm
Floor Area No. of Latent
Floor Room
(sq.ft) People Load
General Enquiry 327.9 4 0.39
Conference hall 1349.7 105 10.30
Control room 209.3 2 0.20
Seminar hall 1024.4 30 2.94
Office Wood 142.8 5 0.49
Ground
Account 157.5 6 0.59
Staff room 543.6 19 1.86
Cafeteria Dining Space 1357.4 20 1.96
Office Metal 249.0 7 0.69
Total 5361.5 198 19.43

Training Hall 629.3 17 1.67


Office 133.3 5 0.49
Director's Room 277.9 5 0.49
Deputy Director's Room 217.6 6 0.59
Cafeteria Dining Space 1935.8 25 2.45
Leisure Room N 277.6 4 0.39
Maker Space N 2883.5 25 2.45
Lecture Room1 409.9 25 2.45
First
Lecture Room 2 409.9 25 2.45
Lecture Room 3 489.4 38 3.73
Lecture Room 4 432.2 25 2.45
Lecture Room 5 432.2 25 2.45
Maker Space S 1102.1 13 1.28
Leisure Room S 304.0 4 0.39
Auditorium Room 5025.1 250 24.53
Total 14959.8 492 48.28

Cafeteria Dining Space 1536.7 25 2.45


Maker Sapce N 2883.5 25 2.45
Leisure Room N 277.6 4 0.39
Second
Maker Space S 2106.9 15 1.47
Leisure Room S 300.9 3 0.29
Total 7105.6 72 7.06

Leisure Room 277.6 4 0.39


Third Maker Space 2883.5 25 2.45
Total 3161.1 29 2.85
Leisure Room 277.6 4 0.39
Fourth Maker Space 2883.5 25 2.45
Total 3161.1 29 2.85

Leisure Room 277.6 4 0.39


Maker space 2883.5 25 2.45
Fifth Total 3161.1 29 2.85

Sixth Researcher's Library 2563.3 45 4.42

Total 39473.6 87.72


Cooling load at 4pm
Sensible Total Cooling No of Latent Sensible
Floor Area
Load Load people Load Load
1.72 2.11 Ground 5361.5 198.0 19.4 19.0
5.57 15.87 First 14959.8 492.0 48.3 58.3
0.38 0.58 Second 7105.6 72.0 7.1 22.8
2.07 5.01 Third 3161.1 29.0 2.8 6.6
0.79 1.28 Fourth 3161.1 29.0 2.8 6.6
0.68 1.27 Fifth 3161.1 29.0 2.8 6.6
2.57 4.44 Sixth 2563.3 45.0 4.4 12.3
3.74 5.71
1.46 2.15
18.98 38.41

5.05 6.72
0.66 1.15
1.77 2.26
0.66 1.24
4.66 7.11
0.88 1.27
5.37 7.82
1.62 4.08
1.72 4.17
2.29 6.02
1.63 4.08
1.69 4.14
3.22 4.50
0.91 1.30
26.13 50.66
58.27 106.54

7.03 9.49
4.67 7.13
0.87 1.27
8.74 10.21
1.51 1.81
22.83 29.90

1.44 1.83
5.13 7.58
6.57 9.41
1.44 1.83
5.13 7.58
6.57 9.41

1.44 1.83
5.13 7.58
6.57 9.41

12.34 16.76

132.13 219.85
Total
38.4
106.5
29.9
9.4
9.4
9.4
16.8
No. of
Floor Room Latent Sensible
People
Cafeteria Dining Space 25 2.45 7.04
Maker Sapce N 25 2.45 4.68
Leisure Room N 4 0.39 0.88
Second
Maker Space S 15 1.47 8.74
Leisure Room S 3 0.29 1.52
Total 7.06 22.86

Leisure Room 4 0.39 1.44


Third Maker Space 25 2.45 5.14
Total 2.85 6.58

Leisure Room 4 0.39 1.44


Fourth Maker Space 25 2.45 5.14
Total 2.85 6.58

Leisure Room 4 0.39 1.44


Fifth Maker space 25 2.45 5.14
Total 2.85 6.58

Sixth Researcher's Library 45 4.42 12.36

Grand
204 87.72 132.20
Total
Total
9.49
7.13
1.27
10.22
1.81
29.92

1.83
7.59
9.42

1.83
7.59
9.42

1.83
7.59
9.42

16.77

219.92
Floor Latent Sensible Total Percentage
Ground 19.4 19.0 38.4 17.47
First 48.3 58.3 106.5 48.45
Second 7.1 22.9 29.9 13.61
Third 2.8 6.6 9.4 4.29
Fourth 2.8 6.6 9.4 4.29
Fifth 2.8 6.6 9.4 4.29
Sixth 4.4 12.4 16.8 7.63
Total 87.7 132.2 219.9 100.00

186.9296

Total Coolin

9.4; 4.29%
9.4; 4.29%
16.8; 7.63%
9.4; 4.29%

29.9; 13.61%

Ground Fi rst Second Thi rd


Comparison of latent and sensible load
70.0
Latent
Sens i bl e
60.0

50.0

40.0
Load (TOR)

30.0

20.0

10.0

0.0
Ground Fi rst Second Thi rd Fourth Fi fth Si xth

Floor

Total Cooling Load

9.4; 4.29% 38.4; 17.47%


9.4; 4.29%
16.8; 7.63%
9.4; 4.29%

; 13.61%

106.5; 48.45%

Ground Fi rst Second Thi rd Fourth Fi fth Si xth


tent
ns i bl e

Si xth
Floor Area No. of
Floor Room Total(at 4pm)
(sq.ft) People
General Enquiry 327.87 4 2.11

Conference hall 1349.69 105 15.87

Control room 209.25 2 0.58


Seminar hall 1024.40 30 5.01
Ground
Office (Wood Workshop) 142.84 5 1.28
Account 157.48 6 1.27
Staff room 543.58 19 4.44
Cafeteria Dining Space 1357.44 20 5.71
Office( Metal Workshop) 248.97 7 2.15
Total 5361.50 198.00 38.41

Training Hall 629.26 17 6.72


Office 133.26 5 1.15
Director's Room 277.92 5 2.26
Deputy Director's Room 217.65 6 1.24
Cafeteria Dining Space 1935.78 25 7.11
Leisure Room(north) 277.60 4 1.27
Maker Space (north) 2883.54 25 7.82
Lecture Room1 409.89 25 4.08
First
Lecture Room 2 409.89 25 4.17
Lecture Room 3 489.44 38 6.02
Lecture Room 4 432.17 25 4.08
Lecture Room 5 432.17 25 4.14
Maker Space South 1102.12 13 4.50
Leisure Room (south) 303.97 4 1.30
Auditorium Room 5025.14 250 50.66
Total 25682.8083 888 106.54
A Cooling Load (TR)
Floor Single Glazed Double Glazed
Window Window
B
C Ground 38.4 36.6
D First 106.5 101.6
Second 29.9 28.0
Third 9.4 8.3
Fourth 9.4 8.3
Fifth 9.4 8.3
Sixth 16.8 15.8
Total 219.9 206.8
Floor Area No. of
Floor Room Total(at 4pm)
(ft) People
Cafeteria Dining Space 1536.66 25 9.49
Maker Room North 2883.54 25 7.13
Leisure Room(north) 277.60 4 1.27
Second
Maker Room South 2106.93 15 10.22
Leisure Room (south) 300.85 3 1.81
Total 29.92

Leisure Room 277.60 4 1.83


Third Maker Space 2883.54 25 7.59
Total 9.42

Leisure Room 277.60 4 1.83


Fourth Maker Space 2883.54 25 7.59
Total 9.42

Leisure Room 277.60 4 1.83


Fifth Maker space 2883.54 25 7.59
Total 9.42

Sixth Researcher's Library 2563.32 45 16.77

Grand
204 219.92
Total
A B C D A+B C+D A+D

GF 0 13.53 21.46 3.43 13.53 24.88 3.43


1F 9.09 18.49 50.66 28.29 27.58 78.96 37.39
2F 8.40 9.49 0 12.03 17.89 12.03 20.43
3F 9.42 0 0 0 9.42 0.00 9.42
4F 9.42 0 0 0 9.42 0.00 9.42
5F 9.42 0 0 0 9.42 0.00 9.42
6F 16.77 0 0 0 16.77 0.00 16.77
TOTAL 62.54 41.51 72.12 43.75 104.05 115.87 106.29
B+C

34.99
69.15
9.49
0.00
0.00
0.00
0.00
113.63

You might also like