1) The document discusses power factor in AC circuits, which is the ratio of true power to apparent power and indicates how efficiently power is delivered through the circuit. 2) A circuit's power factor is 1 if it is purely resistive, 0 if it is purely inductive or capacitive, and between 0 and 1 otherwise. Poor power factor means power is delivered less efficiently. 3) Power factor can be corrected by adding a capacitor to an inductive circuit to produce equal and opposite reactive power, bringing the total impedance closer to the total resistance to make power factor closer to 1.

Uploaded by

Fahrul Muhamad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views6 pages

Calculating Power Factor

1) The document discusses power factor in AC circuits, which is the ratio of true power to apparent power and indicates how efficiently power is delivered through the circuit. 2) A circuit's power factor is 1 if it is purely resistive, 0 if it is purely inductive or capacitive, and between 0 and 1 otherwise. Poor power factor means power is delivered less efficiently. 3) Power factor can be corrected by adding a capacitor to an inductive circuit to produce equal and opposite reactive power, bringing the total impedance closer to the total resistance to make power factor closer to 1.

Uploaded by

Fahrul Muhamad
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

CALCULATING POWER FACTOR

As was mentioned before, the angle of this “power triangle” graphically indicates
the ratio between the amount of dissipated (or consumed) power and the amount
of absorbed/returned power. It also happens to be the same angle as that of the
circuit’s impedance in polar form. When expressed as a fraction, this ratio between
true power and apparent power is called the power factor for this circuit. Because
true power and apparent power form the adjacent and hypotenuse sides of a right
triangle, respectively, the power factor ratio is also equal to the cosine of that
phase angle. Using values from the last example circuit:

It should be noted that power factor, like all ratio measurements, is


a unitless quantity.
For the purely resistive circuit, the power factor is 1 (perfect), because the reactive
power equals zero. Here, the power triangle would look like a horizontal line,
because the opposite (reactive power) side would have zero length.
For the purely inductive circuit, the power factor is zero, because true power
equals zero. Here, the power triangle would look like a vertical line, because the
adjacent (true power) side would have zero length.
The same could be said for a purely capacitive circuit. If there are no dissipative
(resistive) components in the circuit, then the true power must be equal to zero,
making any power in the circuit purely reactive. The power triangle for a purely
capacitive circuit would again be a vertical line (pointing down instead of up as it
was for the purely inductive circuit).
Power factor can be an important aspect to consider in an AC circuit, because any
power factor less than 1 means that the circuit’s wiring has to carry more current
than what would be necessary with zero reactance in the circuit to deliver the
same amount of (true) power to the resistive load. If our last example circuit had
been purely resistive, we would have been able to deliver a full 169.256 watts to
the load with the same 1.410 amps of current, rather than the mere 119.365 watts
that it is presently dissipating with that same current quantity. The poor power
factor makes for an inefficient power delivery system.
Poor power factor can be corrected, paradoxically, by adding another load to the
circuit drawing an equal and opposite amount of reactive power, to cancel out the
effects of the load’s inductive reactance. Inductive reactance can only be canceled
by capacitive reactance, so we have to add a capacitor in parallel to our example
circuit as the additional load. The effect of these two opposing reactances in
parallel is to bring the circuit’s total impedance equal to its total resistance (to
make the impedance phase angle equal, or at least closer, to zero).
Since we know that the (uncorrected) reactive power is 119.998 VAR (inductive),
we need to calculate the correct capacitor size to produce the same quantity of
(capacitive) reactive power. Since this capacitor will be directly in parallel with the
source (of known voltage), we’ll use the power formula which starts from voltage
and reactance:

Let’s use a rounded capacitor value of 22 µF and see what happens to our circuit:
(Figure below)
Parallel capacitor corrects lagging power factor of inductive load. V2 and node
numbers: 0, 1, 2, and 3 are SPICE related, and may be ignored for the moment.

The power factor for the circuit, overall, has been substantially improved. The main
current has been decreased from 1.41 amps to 994.7 milliamps, while the power
dissipated at the load resistor remains unchanged at 119.365 watts. The power
factor is much closer to being 1:
Since the impedance angle is still a positive number, we know that the circuit,
overall, is still more inductive than it is capacitive. If our power factor correction
efforts had been perfectly on-target, we would have arrived at an impedance angle
of exactly zero, or purely resistive. If we had added too large of a capacitor in
parallel, we would have ended up with an impedance angle that was negative,
indicating that the circuit was more capacitive than inductive.
A SPICE simulation of the circuit of (Figure above) shows total voltage and total
current are nearly in phase. The SPICE circuit file has a zero volt voltage-source
(V2) in series with the capacitor so that the capacitor current may be measured.
The start time of 200 msec ( instead of 0) in the transient analysis statement
allows the DC conditions to stabilize before collecting data. See SPICE listing
“pf.cir power factor”.

pf.cir power factor


V1 1 0 sin(0 170 60)
C1 1 3 22uF
v2 3 0 0
L1 1 2 160mH
R1 2 0 60
# resolution stop start
.tran 1m 200m 160m
.end

The Nutmeg plot of the various currents with respect to the applied voltage V total is
shown in (Figure below). The reference is Vtotal, to which all other measurements
are compared. This is because the applied voltage, Vtotal, appears across the
parallel branches of the circuit. There is no single current common to all
components. We can compare those currents to Vtotal.
Zero phase angle due to in-phase Vtotal and Itotal . The lagging IL with respect to
Vtotal is corrected by a leading IC .
Note that the total current (Itotal) is in phase with the applied voltage (Vtotal), indicating
a phase angle of near zero. This is no coincidence. Note that the lagging current,
IL of the inductor would have caused the total current to have a lagging phase
somewhere between (Itotal) and IL. However, the leading capacitor current, IC,
compensates for the lagging inductor current. The result is a total current phase-
angle somewhere between the inductor and capacitor currents. Moreover, that
total current (Itotal) was forced to be in-phase with the total applied voltage (Vtotal), by
the calculation of an appropriate capacitor value.
Since the total voltage and current are in phase, the product of these two
waveforms, power, will always be positive throughout a 60 Hz cycle, real power as
in Figure above.

Had the phase-angle not been corrected to zero (PF=1), the product would have
been negative where positive portions of one waveform overlapped negative
portions of the other as in Figure above. Negative power is fed back to the
generator. It cannont be sold; though, it does waste power in the resistance of
electric lines between load and generator. The parallel capacitor corrects this
problem.
Note that reduction of line losses applies to the lines from the generator to the
point where the power factor correction capacitor is applied. In other words, there
is still circulating current between the capacitor and the inductive load. This is not
normally a problem because the power factor correction is applied close to the
offending load, like an induction motor.
It should be noted that too much capacitance in an AC circuit will result in a low
power factor just as well as too much inductance. You must be careful not to over-
correct when adding capacitance to an AC circuit. You must also be very careful to
use the proper capacitors for the job (rated adequately for power system voltages
and the occasional voltage spike from lightning strikes, for continuous AC service,
and capable of handling the expected levels of current).
If a circuit is predominantly inductive, we say that its power factor
is lagging (because the current wave for the circuit lags behind the applied voltage
wave). Conversely, if a circuit is predominantly capacitive, we say that its power
factor is leading. Thus, our example circuit started out with a power factor of 0.705
lagging, and was corrected to a power factor of 0.999 lagging.