The document contains settings for a power system protection relay. It includes settings for the rated voltage and current levels, auto-reclosing parameters, and fault thresholds. Measurement and annunciation settings are also provided, with the last section showing a spontaneous annunciation record indicating internal auto-reclosing tripped the line after a fault was detected.

Uploaded by

karthik kanchi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views7 pages

Sip5 Bcu Settings

The document contains settings for a power system protection relay. It includes settings for the rated voltage and current levels, auto-reclosing parameters, and fault thresholds. Measurement and annunciation settings are also provided, with the last section showing a spontaneous annunciation record indicating internal auto-reclosing tripped the line after a fault was detected.

Uploaded by

karthik kanchi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

426_TIE_6MD664 V4_8_prn_00_26_42

Power System Data 1


PGCIL RANCHI250613 / 400kV / 4K9 /
SIMATIC 426_TIE_6MD664 V4.8/6MD664 29.06.19 00:26:45

1 Power System Data 1

1.1 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0203 Rated Primary Voltage 400.0 kV All


0204 Rated Secondary Voltage (Ph-Ph) 110 V All
0205 CT Rated Primary Current 3000 A All
0206 CT Rated Secondary Current 1A All
0214 Rated Frequency 50 Hz All
0276 Unit of temperature measurement Degree Celsius All

1.2 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0240 Minimum TRIP Command Duration 0.10 sec All


0241 Maximum Close Command Duration 0.10 sec All

Page 1 of 7
426_TIE_6MD664 V4_8_prn_00_26_42
Settings groups
PGCIL RANCHI250613 / 400kV / 4K9 /
SIMATIC 426_TIE_6MD664 V4.8/6MD664 29.06.19 00:26:45

2 Settings groups

2.1 Group Power System Data 2

Group Power System Data 2


No. Settings Value Group

1130A Pole Open Current Threshold 0.10 A A


1135 RESET of Trip Command with Pole Open Current Threshold only A
1150A Seal-in Time after MANUAL closures 0.30 sec A

2.2 Group Auto Reclose; Group General

Group Auto Reclose; Group General


No. Settings Value Group

3401 Auto-Reclose Function ON A


3402 CB ready interrogation at 1st trip NO A
3403 Auto Reclosing reset time 3.00 sec A
3404 AR blocking duration after manual close 1.00 sec A
3406 Evolving fault recognition with Trip A
3407 Evolving fault (during the dead time) blocks AR A
3408 AR start-signal monitoring time 0.20 sec A
3409 Circuit Breaker (CB) Supervision Time 3.00 sec A
3410 Send delay for remote close command 1.60 sec A
3411A Maximum dead time extension 10.00 sec A
3413 Close command via control device <none> A
3414 Internal synchronisation <none> A

2.3 Group Auto Reclose; Group 1st AR-cyle

Group Auto Reclose; Group 1st AR-cyle


No. Settings Value Group

3450 Start of AR allowed in this cycle YES A


3451 Action Time 0.20 sec A
3456 Dead time after 1pole trip 1.20 sec A
3457 Dead time after 3pole trip 0.50 sec A

Page 2 of 7
426_TIE_6MD664 V4_8_prn_00_26_42

PGCIL RANCHI250613 / 400kV / 4K9 /


SIMATIC 426_TIE_6MD664 V4.8/6MD664 29.06.19 00:26:45

Group Auto Reclose; Group 1st AR-cyle(2)


No. Settings Value Group

3458 Dead time after evolving fault 1.20 sec A


3459 CB ready interrogation before reclosing NO A
3460 Request for synchro-check after 3pole AR NO A

2.4 Group Auto Reclose; Group 3pTRIP/DLC/RDT

Group Auto Reclose; Group 3pTRIP/DLC/RDT


No. Settings Value Group

3430 3pole TRIP by AR YES A


3431 Dead Line Check / Reduced Dead Time Without A
3438 Supervision time for dead/live voltage 0.10 sec A
3440 Voltage threshold for live line or bus 48 V A
3441 Voltage threshold for dead line or bus 30 V A

2.5 Group Measurement Supervision

Group Measurement Supervision


No. Settings Value Group

2915 Voltage Failure Supervision with current supervision A


2916A Delay Voltage Failure Supervision 3.00 sec A
2917 Maximum Voltage Threshold U< (3phase) 5V A

Page 3 of 7
426_TIE_6MD664 V4_8_prn_00_26_42
Annunciation
PGCIL RANCHI250613 / 400kV / 4K9 /
SIMATIC 426_TIE_6MD664 V4.8/6MD664 29.06.19 00:26:45

3 Annunciation

3.1 Spontaneous Annunciation - 28-06-19 7:27:56.715 PM (SIGNALS\SP000001.SFP)

Spontaneous Annunciation - 28-06-19 7:27:56.715 PM (SIGNALS\SP000001.SFP)


Number Indication Value Date and time Cause State

02712 >AR: Ext. Trip L1 for internal AR ON 28.06.2019 19:24:35.527 Spontaneous


Com.Issued=AutoLocal
02713 >AR: Ext. Trip L2 for internal AR ON 28.06.2019 19:24:35.527 Spontaneous
Com.Issued=AutoLocal
Reset LED OFF 28.06.2019 19:24:35.527 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 6 - ON 28.06.2019 19:24:35.527 Spontaneous
Com.Issued=AutoLocal
00302 Fault Event 6 - ON 28.06.2019 19:24:35.527 Spontaneous
Com.Issued=AutoLocal
00501 Relay PICKUP ON 0 ms Spontaneous
Com.Issued=AutoLocal
00503 Relay PICKUP Phase L1 ON 0 ms Spontaneous
Com.Issued=AutoLocal
00504 Relay PICKUP Phase L2 ON 0 ms Spontaneous
Com.Issued=AutoLocal
00505 Relay PICKUP Phase L3 ON 0 ms Spontaneous
Com.Issued=AutoLocal
00515 Relay TRIP command Phases L123 ON 0 ms Spontaneous
Com.Issued=AutoLocal
00507 Relay TRIP command Phase L1 ON 0 ms Spontaneous
Com.Issued=AutoLocal
00508 Relay TRIP command Phase L2 ON 0 ms Spontaneous
Com.Issued=AutoLocal
00509 Relay TRIP command Phase L3 ON 0 ms Spontaneous
Com.Issued=AutoLocal
00511 Relay GENERAL TRIP command ON 0 ms Spontaneous
Com.Issued=AutoLocal
01001 Number of breaker TRIP commands L1 4 0 ms Spontaneous
Com.Issued=AutoLocal
01002 Number of breaker TRIP commands L2 4 0 ms Spontaneous
Com.Issued=AutoLocal
01003 Number of breaker TRIP commands L3 4 0 ms Spontaneous
Com.Issued=AutoLocal
00536 Final Trip ON 0 ms Spontaneous
Com.Issued=AutoLocal
02871 AR: TRIP command 3pole ON 0 ms Spontaneous
Com.Issued=AutoLocal
30053 Fault recording is running ON 3 ms Spontaneous
Com.Issued=AutoLocal
AR-R-INITI ON 0 ms Spontaneous
AR-Y-INITI ON 0 ms Spontaneous
AR-HOLD ON 6 ms Spontaneous

Page 4 of 7
426_TIE_6MD664 V4_8_prn_00_26_42

PGCIL RANCHI250613 / 400kV / 4K9 /


SIMATIC 426_TIE_6MD664 V4.8/6MD664 29.06.19 00:26:45

Spontaneous Annunciation - 28-06-19 7:27:56.715 PM (SIGNALS\SP000001.SFP)(2)


Number Indication Value Date and time Cause State

CB-R-CLS OFF 12 ms Spontaneous


ARL/O-OPTD ON 20 ms Spontaneous
CB-R-OPN ON 24 ms Spontaneous
CB-Y-CLS OFF 34 ms Spontaneous
CB-B-CLS OFF 36 ms Spontaneous
CB-Y-OPN ON 45 ms Spontaneous
CB-B-OPN ON 45 ms Spontaneous
02712 >AR: Ext. Trip L1 for internal AR OFF 96 ms Spontaneous
Com.Issued=AutoLocal
02713 >AR: Ext. Trip L2 for internal AR OFF 96 ms Spontaneous
Com.Issued=AutoLocal
00501 Relay PICKUP OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00503 Relay PICKUP Phase L1 OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00504 Relay PICKUP Phase L2 OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00505 Relay PICKUP Phase L3 OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00515 Relay TRIP command Phases L123 OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00511 Relay GENERAL TRIP command OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00507 Relay TRIP command Phase L1 OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00508 Relay TRIP command Phase L2 OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00509 Relay TRIP command Phase L3 OFF 97 ms Spontaneous
Com.Issued=AutoLocal
02871 AR: TRIP command 3pole OFF 97 ms Spontaneous
Com.Issued=AutoLocal
00302 Fault Event 6 - OFF 28.06.2019 19:24:35.624 Spontaneous
Com.Issued=AutoLocal
00301 Power System fault 6 - OFF 28.06.2019 19:24:35.624 Spontaneous
Com.Issued=AutoLocal
AR-R-INITI OFF 28.06.2019 19:24:35.623 Spontaneous
AR-Y-INITI OFF 28.06.2019 19:24:35.623 Spontaneous
30053 Fault recording is running OFF 28.06.2019 19:24:35.752 Spontaneous
Com.Issued=AutoLocal
52-CB-OPN ON 28.06.2019 19:24:35.844 Spontaneous
Com.Issued=AutoLocal
52-CB OPEN 28.06.2019 19:24:35.844 Spontaneous
Com.Issued=AutoLocal
31000 Q0 operationcounter= 9 28.06.2019 19:24:35.845 Spontaneous
Com.Issued=AutoLocal

Page 5 of 7
426_TIE_6MD664 V4_8_prn_00_26_42

PGCIL RANCHI250613 / 400kV / 4K9 /


SIMATIC 426_TIE_6MD664 V4.8/6MD664 29.06.19 00:26:45

Spontaneous Annunciation - 28-06-19 7:27:56.715 PM (SIGNALS\SP000001.SFP)(3)


Number Indication Value Date and time Cause State

00536 Final Trip OFF 28.06.2019 19:24:36.029 Spontaneous


Com.Issued=AutoLocal
AR-HOLD OFF 28.06.2019 19:24:36.530 Spontaneous
AR-HOLD ON 28.06.2019 19:24:42.785 Spontaneous
AR-HOLD OFF 28.06.2019 19:24:43.780 Spontaneous
ARL/O-OPTD OFF 28.06.2019 19:26:00.753 Spontaneous
CB-Y-OPN OFF 28.06.2019 19:26:05.119 Spontaneous
CB-R-OPN OFF 28.06.2019 19:26:05.120 Spontaneous
CB-B-OPN OFF 28.06.2019 19:26:05.120 Spontaneous
00371 >Circuit Breaker 1 READY for reclosing OFF 28.06.2019 19:26:05.134 Spontaneous
Com.Issued=AutoLocal
AR-CB-HLTY OFF 28.06.2019 19:26:05.134 Spontaneous
SPR-CHRG OFF 28.06.2019 19:26:05.135 Spontaneous
CB-Y-CLS ON 28.06.2019 19:26:05.143 Spontaneous
CB-R-CLS ON 28.06.2019 19:26:05.147 Spontaneous
CB-B-CLS ON 28.06.2019 19:26:05.147 Spontaneous
52-CB-OPN OFF 28.06.2019 19:26:05.217 Spontaneous
Com.Issued=AutoLocal
52-CB CLOSE 28.06.2019 19:26:05.217 Spontaneous
Com.Issued=AutoLocal
31000 Q0 operationcounter= 10 28.06.2019 19:26:05.225 Spontaneous
Com.Issued=AutoLocal
00371 >Circuit Breaker 1 READY for reclosing ON 28.06.2019 19:26:09.503 Spontaneous
Com.Issued=AutoLocal
AR-CB-HLTY ON 28.06.2019 19:26:09.503 Spontaneous
SPR-CHRG ON 28.06.2019 19:26:09.504 Spontaneous
Reset LED ON 28.06.2019 19:26:20.356 Spontaneous
Command Issued=Local
Reset LED OFF 28.06.2019 19:26:21.420 Spontaneous
Com.Issued=AutoLocal
CB-R-CLS OFF 28.06.2019 19:26:49.946 Spontaneous
CB-Y-CLS OFF 28.06.2019 19:26:49.947 Spontaneous
CB-B-CLS OFF 28.06.2019 19:26:49.949 Spontaneous
CB-R-OPN ON 28.06.2019 19:26:49.958 Spontaneous
CB-Y-OPN ON 28.06.2019 19:26:49.958 Spontaneous
CB-B-OPN ON 28.06.2019 19:26:49.959 Spontaneous
52-CB-OPN ON 28.06.2019 19:26:50.259 Spontaneous
Com.Issued=AutoLocal
52-CB OPEN 28.06.2019 19:26:50.259 Spontaneous
Com.Issued=AutoLocal
31000 Q0 operationcounter= 11 28.06.2019 19:26:50.265 Spontaneous
Com.Issued=AutoLocal
MCB OPEN ON 28.06.2019 19:26:50.403 Spontaneous
Com.Issued=AutoLocal

Page 6 of 7
426_TIE_6MD664 V4_8_prn_00_26_42

PGCIL RANCHI250613 / 400kV / 4K9 /


SIMATIC 426_TIE_6MD664 V4.8/6MD664 29.06.19 00:26:45

Spontaneous Annunciation - 28-06-19 7:27:56.715 PM (SIGNALS\SP000001.SFP)(4)


Number Indication Value Date and time Cause State

Reset LED ON 28.06.2019 19:27:12.070 Spontaneous


Command Issued=Local
Reset LED OFF 28.06.2019 19:27:13.134 Spontaneous
Com.Issued=AutoLocal
Reset LED ON 28.06.2019 19:27:13.570 Spontaneous
Command Issued=Local
Reset LED OFF 28.06.2019 19:27:14.635 Spontaneous
Com.Issued=AutoLocal
CB-Y-OPN OFF 28.06.2019 19:27:24.349 Spontaneous
CB-B-OPN OFF 28.06.2019 19:27:24.349 Spontaneous
CB-R-OPN OFF 28.06.2019 19:27:24.350 Spontaneous
00371 >Circuit Breaker 1 READY for reclosing OFF 28.06.2019 19:27:24.365 Spontaneous
Com.Issued=AutoLocal
SPR-CHRG OFF 28.06.2019 19:27:24.365 Spontaneous
AR-CB-HLTY OFF 28.06.2019 19:27:24.365 Spontaneous
CB-Y-CLS ON 28.06.2019 19:27:24.374 Spontaneous
CB-R-CLS ON 28.06.2019 19:27:24.377 Spontaneous
CB-B-CLS ON 28.06.2019 19:27:24.377 Spontaneous
52-CB-OPN OFF 28.06.2019 19:27:24.500 Spontaneous
Com.Issued=AutoLocal
52-CB CLOSE 28.06.2019 19:27:24.500 Spontaneous
Com.Issued=AutoLocal
31000 Q0 operationcounter= 12 28.06.2019 19:27:24.505 Spontaneous
Com.Issued=AutoLocal
00371 >Circuit Breaker 1 READY for reclosing ON 28.06.2019 19:27:28.749 Spontaneous
Com.Issued=AutoLocal
AR-CB-HLTY ON 28.06.2019 19:27:28.749 Spontaneous
SPR-CHRG ON 28.06.2019 19:27:28.750 Spontaneous

Page 7 of 7