DIgSILENT PowerFactory

Relay model description

Siemens 7SJ63

Version 002
DIgSILENT GmbH

Heinrich-Hertz-Str. 9
72810 - Gomaringen
Germany

T: +49 7072 9168 00


F: +49 7072 9168 88

http://www.digsilent.de
[email protected]

Format rev. 1, Copyright ©2012, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT
GmbH. No part of this document may be reproduced, copied, or transmitted in any form, by any means
electronic or mechanical, without the prior written permission of DIgSILENT GmbH.

Siemens 7SJ63 Version: 002 1


DIgSILENT PowerFactory
Relay model description

Siemens 7SJ63

Version 002
DIgSILENT GmbH

Heinrich-Hertz-Str. 9
72810 - Gomaringen
Germany

T: +49 7072 9168 00


F: +49 7072 9168 88

http://www.digsilent.de
[email protected]

Format rev. 1, Copyright ©2012, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT
GmbH. No part of this document may be reproduced, copied, or transmitted in any form, by any means
electronic or mechanical, without the prior written permission of DIgSILENT GmbH.

Siemens 7SJ63 Version: 002 1


Contents

Contents

1 Model information 3

2 General description 3

3 Supported features 3

3.1 Measurement and acquisition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3.1.1 Available Units and input signals . . . . . . . . . . . . . . . . . . . . . . . 4

3.1.2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3.1.3 Data input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3.2 Protective elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3.2.1 Available Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3.2.2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3.2.3 Data input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

3.3 Output logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.3.1 Available Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.3.2 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3.3.3 Data input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4 Features not supported 9

5 Scheme 10

6 References 11

7 Change Log 12

Siemens 7SJ63 Version: 002 2


3 Supported features

1 Model information

Manufacturer Siemens

Model 7SJ63

Variants These models can be used to simulate the features present in the Siemens SIPROTEC
7SJ63 protective relays up to firmware version V4.6.

Minimum requirements PowerFactory V 14.1

2 General description

The numerical, multi-functional SIPROTEC 4 7SJ63 is a versatile device designed for many ap-
plications. The 7SJ63 can be used as a protective, control, and monitoring device for distribution
feeders and transmission lines of any voltage in networks that are grounded, low-resistance
grounded, ungrounded, or of a compensated neutral point structure. The device is suited for
networks that are radial or looped, and for lines with single or multi-terminal feeds. The 7SJ63 is
equipped with motor protection applicable for asynchronous machines of all sizes.

The Siemens 7SJ63 relay has been modeled using two PowerFactory relay models:

• 7SJ63_1A (phase and ground rated current equal to 1 A).


• 7SJ63_5A (phase and ground rated current equal to 5 A).

They include the phase, ground directional and non directional overcurrent protective elements,
the thermal image element, the negative sequence elements, the overvoltage and the undervolt-
age elements available in the relay.

The model implementation has been based on the information available in the relay manual [1]
[2].

3 Supported features

3.1 Measurement and acquisition

It represents the interface between the power system and the relay protective elements. The
currents flowing in the power system are converted by an element which simulates a 3 phase CT
(”Ct-3p” block) ; the voltages are converted by an element which simulates a 3 phase VT (”Vt-3P”
block); the secondary currents and voltages are then measured by one element which models
the digital filter of the relay.

Siemens 7SJ63 Version: 002 3


3 Supported features

3.1.1 Available Units and input signals

• One 3 phase current transformer (”Ct-3p” block).

• One 3 phase voltage transformer (”Vt-3P” block).


• One 3 phase measurement element (”MeasPhase” block).
• One voltage sequence measurement element (”MeasSeq” block).

The following relay input signals can be used to block the protective elements:

• I >51 iblock controlling the Ip 51 element.


• I >67 TOC iblock controlling Ip 67 TOC element.

• I > >50_1 iblock controlling the I >50_1 element.


• I > >67_1 iblock controlling I >67_1 element.
• I > >50_2 iblock controlling the I > >50_2 element.

• I > >67_2 iblock controlling I > >67_2 element.


• Ie >51N iblock controlling the Iep 51N element.
• Ie >67N TOC iblock controlling Iep 67N TOC element.
• Ie > >50N_1 iblock controlling the Ie >50N_1 element.

• Ie > >67N_1 iblock controlling Ie >67N_1 element.


• Ie > >50N_2 iblock controlling the Ie > >50N_2 element.
• Ie > >67N_2 iblock controlling Ie > >67N_2 element.

3.1.2 Functionality

The ”Ct-3p” block represents an ideal CTs. Using the CT default configuration the current at the
primary side are converted to the secondary side using the CT ratio. The CT saturation and/or
its magnetizing characteristic are not considered. Please set the ”Detailed Model” check box in
the ”Detailed Data” tab page of the CT dialog and insert the data regarding the CT burden, the
CT secondary resistance and the CT excitation parameter if more accurate simulation results
are required.

The input current values are sampled by the ”MeasPhase” block at 16 samples/cycle. The values
are processed by a digital filter, integrating the samples over a cycle, which then calculates the
voltage and current RMS values used by the protective elements.

3.1.3 Data input

No manual data input is required. Please use the relay model which supports the setting ranges
for the connected 3 phase Ct rated current.

Siemens 7SJ63 Version: 002 4


3 Supported features

3.2 Protective elements

A set of inverse time and definite time overcurrent elements is modeling the relay protective
functions. The inverse characteristics available in the relay are available as well in the inverse
time model blocks.

3.2.1 Available Units

• One 3 phase inverse time overcurrent element (”Ip 51” block).


• Two 3 phase definite time overcurrent elements (”I >50_1”, and ”I > >50_2” block).
• One ground current inverse time overcurrent element (”Iep 51N” block).
• Two ground current definite time overcurrent elements (”Ie >50N_1”, and ”Ie > >50N_2”
block).
• One directional 3 phase inverse time overcurrent element (”Ip 67 TOC” block).
• Two directional 3 phase definite time overcurrent elements (”I >67_1”, and ”I > >67_2” block).
• One phase directional element (”Dir OC” block).
• One directional ground current inverse time overcurrent element (”Iep 67N TOC” block).
• Two directional ground current definite time overcurrent elements (”Ie>67N_1”, and ”Ie> >67N_2”
block).
• One ground directional element (”Dir EF” block).
• One negative sequence current inverse time overcurrent element (”I2p 46 TOC” block).
• Two negative sequence current definite time overcurrent elements (”Ie >46_1”, and ”Ie > >46_2”
block).
• One thermal image element (”Overload 49” block).
• Two phase-phase overvoltage elements (”U >59_1” and ”U > >59_1” block).
• Two positive sequence undervoltage elements (”U <27_1” and ”U < <27_1” block).

3.2.2 Functionality

The phase and the ground inverse time overcurrent elements (”Ip 51”, ”Ip 67 TOC”, ”Iep 51N”,
and ”Iep 67N TOC” block) support the following trip characteristics:

• IEC Normal Inverse (”IEC 255-3 inverse” item).


• IEC Very Inverse (”IEC 255-3 very inverse” item).
• IEC Extremelyl Inverse (”IEC 255-3 extremely inverse” item).
• IEC Long Time Inverse (”IEC 255-3 long inverse” item).
• ANSI/IEEE Inverse (”ANSI/IEEE inverse” item).
• ANSI/IEEE Short inverse (”ANSI/IEEE short inverse” item).
• ANSI/IEEE Long inverse (”ANSI/IEEE long inverse” item).

Siemens 7SJ63 Version: 002 5


3 Supported features

• ANSI/IEEE Moderately inverse (”ANSI/IEEE moderately inverse” item).


• ANSI/IEEE Very inverse (”ANSI/IEEE very inverse” item).
• ANSI/IEEE Extremely inverse (”ANSI/IEEE extremely inverse” item).
• ANSI/IEEE Definite inverse (”ANSI/IEEE definite inverse” item).

• Definite time.
• User Defined 1.
• User Defined 2.

• User Defined 3.
• User Defined 4.
• User Defined 5.

The User defined x with x = from 1 to 5 trip characteristics are defined by up to 23 current and
time value couples which can be set by the user. The trip characteristic definitions are unique
for any instance of the Siemens 7SJ63 relay model and be found in the TCCs folder contained
inside the 7SJ63 relay model object.

The negative sequence inverse time overcurrent element (”I2p 46 TOC” block) supports the
following trip characteristics:

• ANSI/IEEE Inverse (”ANSI/IEEE inverse” item).

• ANSI/IEEE Moderately inverse (”ANSI/IEEE moderately inverse” item).


• ANSI/IEEE Very inverse (”ANSI/IEEE very inverse” item).
• ANSI/IEEE Extremely inverse (”ANSI/IEEE extremely inverse” item).

• IEC Normal Inverse (”IEC 255-3 inverse” item).


• IEC Very Inverse (”IEC 255-3 very inverse” item).
• IEC Extremely Inverse (”IEC 255-3 extremely inverse” item).
• Definite time.

3.2.3 Data input

The relationships between the relay settings and the model parameters can be found in the
following table:

Address Relay Setting Model block Model setting Note


112 Charac. Phase Ip 51 Out of Service (outserv) When Disabled in the
model put the block out of
service
Ip 51 Characteristic (pcharac)
113 Charac. Ground Iep 51N Out of Service (outserv) When Disabled in the
model put the block out of
service
Iep 51N Characteristic (pcharac)
115 67/67TOC Ip 67 TOC Out of Service (outserv) When Disabled in the
model put the block out of
service

Siemens 7SJ63 Version: 002 6


3 Supported features

Address Relay Setting Model block Model setting Note


116 67N/67N TOC I2p 67N TOC Out of Service (outserv) When Disabled in the
model put the block out of
service
131 Sens. Gnd Fault Ieep 51Ns Characteristic (pcharac)
140 46 I2p 46 TOC Out of Service (outserv) When Disabled in the
model put the block out of
service
I2p 46 TOC Characteristic (pcharac)
142 49 Overload 49 Out of Service (outserv)
150 2759 U >59_1 Out of Service (outserv)
U > >59_2 Out of Service (outserv)
U <27_1 Out of Service (outserv)
U < <27_2 Out of Service (outserv)
1201 FCT 5051 Ip 51 Out of Service (outserv)
I >50_1 Out of Service (outserv)
I > >50_2 Out of Service (outserv)
1202 50-2 PICKUP I > >50_2 Current Pickup (Ipsetr)
1203 50-2 DELAY I > >50_2 Time Setting (Tset)
1204 50-1 PICKUP I >50_1 Current Pickup (Ipsetr)
1205 50-1 DELAY I >50_1 Time Setting (Tset)
1207 51 PICKUP Ip 51 Current Setting (Ipsetr)
1208 51 TIME DIAL Ip 51 Time Dial (Tpset)
1209 51 TIME DIAL Ip 51 Time Dial (Tpset)
1211 51 IEC CURVE Ip 51 Characteristic (pcharac)
1212 51 ANSI CURVE Ip 51 Characteristic (pcharac)
1301 FCT 50N/51N Iep 51N Out of Service (outserv)
Ie >50N_1 Out of Service (outserv)
Ie > >50N_2 Out of Service (outserv)
1302 50N-2 PICKUP Ie > >50N_2 Current Pickup (Ipsetr)
1303 50N-2 DELAY Ie > >50N_2 Time Setting (Tset)
1304 50N-1 PICKUP Ie >50N_1 Current Pickup (Ipsetr)
1305 50N-1 DELAY Ie >50N_1 Time Setting (Tset)
1307 51N PICKUP Iep 51N Current Setting (Ipsetr)
1308 51N TIME DIAL Iep 51N Time Dial (Tpset)
1309 51N TIME DIAL Iep 51N Time Dial (Tpset)
1311 51N IEC CURVE Iep 51N Characteristic (pcharac)
1312 51N ANSI CURVE Iep 51N Characteristic (pcharac)
1501 FCT 6767 Ip 67 TOC Out of Service (outserv)
I >67_1 Out of Service (outserv)
I > >67_2 Out of Service (outserv)
1502 67-2 PICKUP I > >67_2 Current Pickup (Ipsetr)
1503 67-2 DELAY I > >67_2 Time Setting (Tset)
1504 67-1 PICKUP I >67_1 Current Pickup (Ipsetr)
1505 67-1 DELAY I >67_1 Time Setting (Tset)
1507 67 PICKUP Ip 67 TOC Current Setting (Ipsetr)
1508 67 TIME DIAL Ip 67 TOC Time Dial (Tpset)
1509 67 TIME DIAL Ip 67 TOC Time Dial (Tpset)
1511 67 IEC CURVE Ip 67 TOC Characteristic (pcharac)
1512 67 ANSI CURVE Ip 67 TOC Characteristic (pcharac)
1515 Normal Load Dir OC Max. Torque Angle In the Voltage Polarizing tab
(mtau) page
1516 67 Direction Dir OC Tripping Direction (idir)
1601 FCT 67N/67N Iep 67N TOC Out of Service (outserv)
I >67N_1 Out of Service (outserv)
I > >67N_2 Out of Service (outserv)
1602 67N-2 PICKUP I > >67N_2 Current Pickup (Ipsetr)
1603 67N-2 DELAY I > >67N_2 Time Setting (Tset)
1604 67N-1 PICKUP I >67N_1 Current Pickup (Ipsetr)
1605 67N-1 DELAY I >67N_1 Time Setting (Tset)
1607 67N PICKUP Ip 67N TOC Current Setting (Ipsetr)
1608 67N TIME DIAL Ip 67N TOC Time Dial (Tpset)
1609 67N TIME DIAL Ip 67N TOC Time Dial (Tpset)
1611 67N IEC CURVE Ip 67N TOC Characteristic (pcharac)
1612 67N ANSI CURVE Ip 67N TOC Characteristic (pcharac)
1615 Normal Load Dir EF Max. Torque Angle In the Voltage Polarizing tab
(mtau) page
1616 67N Direction Tripping Direction (idir)
4001 FCT 46 I2p 46 TOC Out of Service (outserv)
4002 46-2 PICKUP I2 > >46_2 Current Pickup (Ipsetr)
4003 46-2 DELAY I2 > >46_2 Time Setting (Tset)

Siemens 7SJ63 Version: 002 7


3 Supported features

Address Relay Setting Model block Model setting Note


4004 46-1 PICKUP I2 >46_1 Current Pickup (Ipsetr)
4005 46-1 DELAY I2 >46_1 Time Setting (Tset)
4006 46 IEC CURVE I2p 46 TOC Characteristic (pcharac)
4007 46 ANSI CURVE I2p 46 TOC Characteristic (pcharac)
4008 46 PICKUP I2p 46 TOC Current Setting (Ipsetr)
4009 46 TIME DIAL I2p 46 TOC Time Dial (Tpset)
4010 46 TIME DIAL I2p 46 TOC Time Dial (Tpset)
4201 FCT 49 Overload 49 Out of Service (outserv)
4202 49 K-FACTOR Overload 49 Current Setting (Ipsetr)
4203 TIME CONSTANT Overload 49 Time Dial (Tpset)
4207 Kt-FACTOR Overload 49 Reset Delay (ResetT)
5001 FCT 59 U >59_1 Out of Service (outserv)
U > >59_2 Out of Service (outserv)
5002 59-1 PICKUP U >59_1 Pickup Voltage (Usetr)
5003 59-1 PICKUP U >59_1 Pickup Voltage (Usetr)
5004 59-1 DELAY U >59_1 Time Delay (Tdel)
5005 59-2 PICKUP U > >59_2 Pickup Voltage (Usetr)
5006 59-2 PICKUP U > >59_2 Pickup Voltage (Usetr)
5007 59-2 DELAY U > >59_2 Time Delay (Tdel)
5101 FCT 27 U <27_1 Out of Service (outserv)
U < <27_2 Out of Service (outserv)
5102 27-1 PICKUP U <27_1 Pickup Voltage (Usetr)
5103 27-1 PICKUP U <27_1 Pickup Voltage (Usetr)
5106 27-1 DELAY U <27_1 Time Delay (Tdel)
5110 27-2 PICKUP U < <27_2 Pickup Voltage (Usetr)
5111 27-2 PICKUP U < <27_2 Pickup Voltage (Usetr)
5112 27-2 DELAY U < <27_2 Time Delay (Tdel)

3.3 Output logic

It represents the output stage of the relay; it’s the interface between the relay and the power
breaker.

3.3.1 Available Units

• one output element (”Logic” block)

3.3.2 Functionality

The ”Logic” block collects the trip signals coming from the protective elements and operates the
relay output contact. The only available output contact is Trip.

3.3.3 Data input

To disable the relay model ability to open the power circuit breaker simply disable the ”Logic”
block.

Siemens 7SJ63 Version: 002 8


4 Features not supported

4 Features not supported

The following features are not supported:

• 50 1Ph-1 and 50 1Ph-2 element.


• Sensitive earth fault elements.
• Frequency elements (81).

• Disk emulation reset.


• Dynamic cold load pickup.
• 2nd harmonic blocking.
• Start inhibit for motors (66/68).

• Motor starting protection(48).


• Automatic reclosing (79).
• Breaker failure protection (50BF).

Siemens 7SJ63 Version: 002 9


5 Scheme

5 Scheme

Figure 5.1: Siemens 7SJ63 Relay model connection scheme

Siemens 7SJ63 Version: 002 10


6 References

6 References
[1] Siemens AG, Wittelsbacherplatz 2, 80333 Munich, Germany. SIPROTEC Multi-Functional
Protective Relay with Local Control 7SJ63 V4.2 Instruction Manual C53000-G1140-C120-2,
1999.
[2] Siemens AG, Wittelsbacherplatz 2, 80333 Munich, Germany. SIPROTEC Multi-Functional
Protective Relay with Local Control 7SJ62/63/64 V4.6 Manual C53000-G1140-C147-6, 2004.

Siemens 7SJ63 Version: 002 11