GE Gas Turbine Accessory and Load Gear Compartments Temperature Running High
GE Gas Turbine Accessory and Load Gear Compartments Temperature Running High
GE Gas Turbine Accessory and Load Gear Compartments Temperature Running High
high
GT's Turbine accessory and load gear compartments temperature are running
very high close to trip value of 450F.
we have GE frame5 Model R gas turbine at our plant. We use to run this GT
by keeping its turbine, accessory, and load gear compartment doors open. A
month ago we closed the doors and afterwards operator observed that
compartment temperature had been raised near to trip value of 450F. so,we
again opened the door to normalize the temperature in the compartments.
Kindly suggest is it in GE design to operate this GT by keeping doors
closed or open?
Also please share the design flow and pressure of pressurizing fan
(ventilation fan) which it maintains in turbine and load gear compartments
for this model of GE gas turbine. In our case ventilation fan is not working
properly.
Abdur Rehman,
Running with compartment doors open means if a real fire is detected and
extinguishing agent is discharged, the extinguishing agent will not be
effective because it will not remain in the compartment.
Also, air will be allowed to enter the compartment through the open doors,
and since air contains oxygen which is required for combustion the fire
will not be starved for oxygen as it should be if the compartment doors are
closed and the ventilation louvers (gravity-operated and/or latched) are
working correctly.
If you have a Frame 5 heavy duty gas turbine packaged by GE (not one of
its licensed turbine packagers) then you should be able to find a P&ID
called 'Heating & Vent Flow' or something similar. If the unit is older,
many of these diagrams listed heat loads and sometimes air flows, though
not always.
As for fan flow ratings, every GE-design heavy duty gas turbine package
was different, and depending on the ambient and customer requirements so
were the ventilation fans and schemes.
Finally, if you are still having problems, then it would be wise to get
someone knowledgeable to site to help with the problem. Because running
with compartment doors open is asking for BIG trouble if a real fire ever
does occur!
Please write back to let us know how you fare in resolving your problems.
Lastly, exhaust leaks are another common cause of high load compartment
temperatures.
Best of luck!
3-You right in saying that ventilation fan is not working properly and we
are also suspecting this. Fan and dampers checkup is on its way.
8-Could you please also suggest the normal pressure in the GE frame5
Model R gas turbine compartments if we have pressurizing fan operating
normally with Gt doors closed.
By otised on 15 June, 2013 - 11:32 am
please provide more help in this regard. The issue of high temperature
is still persisting.
Dear CSA
Abdur Rehman,
The Mark V can accept most all types of T/Cs; check the Mark V
Maintenance Manual, GEH-6195, for more information.
So, what's changed since the time the unit was run with the doors
closed, to the time it was started being run with the doors open?
T/C installation will be just to monitor the temp after sorting out the
true cause of temp rise and solving it.
Abdur Rehman,
These both assume that either the air being pushed into the
compartment by a pressurizing fan can get out through the
compartment's exit dampers and louvers (quite often they get stuck),
or the air being drawn out of the compartment can be "replenished"
by air being drawn into the compartment through the entrance
dampers and louvers. In either case, air needs to get out of the
compartment (in the case of pressurization by the fan) or into the
compartment (in the case of the fan drawing a suction on the
compartment) for cooling to work properly.
If the exit dampers or louvers are not working properly, the positive
pressure will be higher than it should be and the doors will really
"fly" open when unlatched. If the entrance dampers or louvers are not
working properly the negative pressure will be higher than it should
be and it will take a great deal of force to open the compartment
doors.
Some fans have dampers or louvers on the suction side of the fan, and
some on the discharge side of the fan, which must also be working
properly.
In essence, what you need to solve is: Why is the air flowing into (or
out of) the compartment not sufficient to cool the compartment
properly?
If you resolve the air flow problem (fan; dampers; louvers) you can
use an infrared heat gun (always aimed at the same location/device in
the compartment) to measure changes in temperature. You could do
that whilst troubleshooting, also.
Of course, this requires a human to get up out of his chair, and go out
of the air-conditioned control room or office and take a measurement;
not as easy as an operator pointing to a value on a display....
Thanks
WillyBlackson,
You should know that it's quite common for some compartment to be
pressurized and others to be under a slight vacuum--on the SAME
turbine. The common thought is that all compartment should be under
pressure by the vent fan, or all compartment should be under a slight
vacuum by the vent fan--but, unfortunately, that's not always the case,
and frequently compartments of the same unit are under pressure and
vacuum when proper ventilation is being provided.
But, the 'Heating and Ventilation Flow Diagram' provided with every
GE-design heavy duty gas turbine package will definitely show air
flows through the compartment. There is usually a tab in the
Operation, Maintenance and Parts manuals provided with GE-design
heavy duty gas turbines with all of the P&IDs (Piping Schematics, or
Schematic Piping Diagrams as GE calls them), and the 'Heating &
Ventilation Flow Diagram' will be included with them. Or, some
manuals have individual tabs/sections with descriptions of every
system, and you should be able to locate the 'Heating & Ventilation'
tab/section and find information there.
One thing to know about some of the vent fans provided with many
GE-design heavy duty gas turbines is that they frequently supply
what are called 'reverse-tangential' centrifugal fans. This means that
the fans rotate OPPOSITE to the direction one would generally think
a centrifugal blower (fan) would rotate based on the angle of the fan
blades. Reverse-tangential fans can move more air than their "non-
reverse" counterparts for the same energy input (from the AC motor
driving the fan).
So, the "easy" way to determine if the fan is rotating in the proper
direction is to measure the current drawn by the motor and compare it
to the motor nameplate rating. If the current is equal to or slightly less
than the motor nameplate rating (presuming all the dampers and
doors are in their proper operating positions!!!) then the motor/fan is
likely rotating in the proper direction. If the current is more than the
motor nameplate rating, then the motor is likely rotating in the wrong
direction.
>You should know that it's quite common for some compartment
>to be pressurized and others to be under a slight vacuum--on
>the SAME turbine. The common thought is that all compartment
>should be under pressure by the vent fan, or all compartment
>should be under a slight vacuum by the vent fan--but,
>unfortunately, that's not always the case, and frequently
>compartments of the same unit are under pressure and vacuum
>when proper ventilation is being provided.
By CSA on 16 April, 2018 - 11:03 pm
In general, if there is poor airflow and/or hot air leaks, then yes. The
direction of airflow (into or out of the vent fans) doesn't matter.
Your use of this site is subject to the terms and conditions set forth under
Legal Notices and the Privacy Policy. Please read those terms and conditions
carefully. Subject to the rights expressly reserved to others under Legal
Notices, the content of this site and the compilation thereof is © 1999-2019
Nerds in Control, LLC. All rights reserved.