Interface C Connectors
Interface C Connectors
Catalogue 2011
Nexans Network Solutions
Div. Euromold
COMPANY PRESENTATION
1
SEPARABLE CONNECTORS
AND BUSHINGS
INTERFACE C
90±0.2
11
min
01/2011
Dia. 70±0.2
2
Connecting possibilities
Equipment dead-ending
interface of equipment (K)(M)400DR-B
Dead-end receptacle
(K)(M)400AR-3
Equipment bushing
(K)(M)400AR-4
Equipment bushing
(K)400LB/G
Elbow connector
cable to
(K)(M)400AR-5 equipment
Equipment bushing
(K)(M)400AR-6
Equipment bushing
(K)(M)430TB/G (K)(M)300PBM/G
Tee connector Coupling connector
(K)(M)400SFR-B
Equipment bushing
400A-24B
In-air bushing
(K)(M)434TB/G
Tee connector
cable 300SA
isolation Surge arrester
(K)(M)400SOP-B
Stand-off plug
cable
400GP-B earthing
Earthing plug
in-line
junction
(K)(M)400CP-SC
Connecting plug
in-line (K)(M)(P)440TB/G
junction Tee connector
(K)(M)440CP 400PB-XSA
Connecting plug Surge arrester
01/2011
3
400LB
INTERFACE C
ELBOW CONNECTOR
Design 205 mm
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket. 9
4. Type C - 630 A interface 6
as described by CENELEC 4
EN 50180 and 50181. 5
5. Conductor connector (not
included in the standard kit). 1
6. Insulating plug.
7. Cable reducer.
8. Earthing lead. 2
9. Transition contact M10/M16. 330 mm
8
The screen break design 3
enables cable outer sheath
testing without removing or
dismantling the connector.
Specifications and
standards 7
The 400LB separable connector
meets the requirements of
CENELEC HD 629.1.
4
Kit contents
The complete (K)400LB/G The kit also comprises silicone grease, field
elbow connector kit comprises control mastic and installation instructions.
3 x (K)400LB/G-W(-X)
connector kit
Transition
contact + Insulating
Connector housing screw assembly plug Cable reducer
(K)400BLB 400LTS 400LBP 411CA-W
For use with For use with Alupe or For use with fabric tape Can be supplied For applications Components can be
copper tape C 33-226 cables. (graphite) screened cables. with cable lugs. outdoors and in ordered individually.
screened cables. Please contact our Order additional humid climate.
Order: Kit MT. representative. semi-conductive tape Order: +MWS.
(type TSC).
5
430TB
INTERFACE C
TEE CONNECTOR
Design 185 mm
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type C interface as
described by CENELEC
4 9
EN 50180 and 50181. 8
5. Conductor connector.
6. Basic insulating plug (with 5
VD point).
6
7. Cable reducer. 1
8. Conductive rubber cap.
290 mm
9. Clamping screw.
10. Earthing lead. 2
(350 mm
The screen break design for 36 kV)
3
enables cable outer sheath
testing without removing or
dismantling the connector.
10
Specifications and
standards
The 430TB separable connector 7
meets the requirements of
CENELEC HD 629.1.
6
Kit contents
The complete (K)(M)430TB/G The kit also comprises silicone grease, field
control mastic, installation rod, installation
tee connector kit comprises 3 x instructions and crimp chart.
the following components:
Conductor
contact TMBC-X
3 x (K)(M)430TB/G-W-X
connector kit
Cable reducer
Basic insulating
430CA-W
Clamping plug
Connector housing screw Conductor (K)(M)300BIPA + (411CA-W
(K)(M)430BT/G 430TCS contact TBC-X rubber cap for 36 kV)
16.95-14-5
50.150-14-5
50 50(K)M-10-2 50(K)M-10-1 50(K)M-11-2
50.150-14-5
95.240-14-5
120.300-12-5
For use with For use with Alupe or For use with For use with For applications When installed on an
copper tape C 33-226 cables. easy strip semi-conductive other cable types. outdoors and in appropriate equipment
screened cables. Please contact our screened cables. Order: Please contact our humid climate. bushing:
Order: Kit MT. representative. Field control mastic representative. Order: +MWS. 800 A continuously
(type MFC).
7
400TB
INTERFACE C
TEE CONNECTOR
255 mm
Design 220 mm
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer.
4. Type C - 630 A interface
as described by CENELEC
EN 50180 and 50181. 4 9
5. Conductor connector.
5
6. Basic insulating plug (with 6 8
VD point).
7. Cable reducer. 1
8. Conductive rubber cap.
9. Clamping screw. 2
10. Earthing lead.
350 mm
3
The screen break design
enables cable outer sheath
testing without removing or 10
dismantling the connector.
Specifications and
standards
The 400TB separable connector
meets the requirements of 7
CENELEC HD 629.1 S1.
8
Kit contents
The complete (K)(M)(P)400TB/G The kit also comprises silicone grease, field
tee connector kit comprises the control mastic, installation instructions and
crimp chart.
following components:
Conductor
contact TMBC-X
(K)(M)(P)400TB/G-W-X
connector kit
Basic insulating
Clamping plug
Connector housing screw Conductor (K)(M)(P)400BIPA Cable reducer
(K)(M)(P)400BT/G 400TCS contact TBC-X + rubber cap 411CA-W
16.95-14-5
The copper wire screened cable 50.150-14-5
50 50(K)M-10-2 50(K)M-10-1 50(K)M-11-2
is 36 kV, 150 mm2 stranded
50.150-14-5
95.240-14-5
120.300-12-5
For use with For use with For applications For use in potentially Components can be When installed on an
copper tape other cable types. outdoors and in explosive atmospheres ordered individually. appropriate equipment
screened cables. Please contact our humid climate. (for 12 kV max). bushing:
Order: Kit MT. representative. Order: +MWS. Add -/ATEX to part number. 800 A continuously
9
434TB
INTERFACE C
TEE CONNECTOR
Design 185 mm
Separable connector
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type C interface as
4 9
described by CENELEC
EN 50180 and 50181. 8
5
5. Conductor connector.
6. Basic insulating plug (with 6
1
VD point).
7. Cable reducer.
2
8. Conductive rubber cap.
9. Clamping screw.
355 mm 3
10. Earthing lead.
The screen break design
enables cable outer sheath
testing without removing or 10
dismantling the connector.
Specifications and
standards
The 434TB separable connector
meets the test requirements of 7
CENELEC HD 629.1.
10
Kit contents
The complete (K)(M)434TB/G The kit also comprises silicone grease, field
tee connector kit comprises the control mastic, installation instructions and
crimp chart.
following components:
Conductor
contact TMBC-X
(K)(M)434TB/G-W-X
connector kit
Basic insulating
Clamping plug
Connector housing screw Conductor (K)(M)300BIPA + Cable reducer
(K)(M)434BT/G 430TCS contact TBC-X rubber cap 611CA-W
For use with For use with For use with Alupe or For applications Components can be When installed on an
copper tape other cable types. C 33-226 cables. outdoors and in ordered individually. appropriate equipment
screened cables. Please contact our Please contact our humid climate. bushing:
Order: Kit MT. representative. representative. Order: +MWS. 1250 A continuously
11
440TB
INTERFACE C
TEE CONNECTOR
Design 255 mm
Separable connector 220 mm
comprising:
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer
moulded between the insert
and the jacket.
4. Type C - 630 A interface
4 9
as described by CENELEC
EN 50180 and 50181.
5. Conductor connector. 5 6 8
6. Basic insulating plug (with
VD point). 1
7. Cable reducer.
8. Conductive rubber cap. 2
9. Clamping screw.
10. Earthing lead. 355 mm 3
Specifications and
standards
The 440TB separable connector 7
meets the requirements of
CENELEC HD 629.1.
12
Kit contents
The complete (K)(M)(P)440TB/G The kit also comprises silicone grease, field
tee connector kit comprises the control mastic, installation instructions and
crimp chart.
following components:
Conductor
contact TMBC-X
(K)(M)(P)440TB/G-W-X
connector kit
Basic insulating
Clamping plug
Connector housing screw Conductor (K)(M)(P)400BIPA Cable reducer
(K)(M)(P)440BT/G 430TCS contact TBC-X + rubber cap 611CA-W
For use with For use with For applications For use in potentially Components can be When installed on an
copper tape other cable types. outdoors and in explosive atmospheres ordered individually. appropriate equipment
screened cables. Please contact our humid climate. (for 12 kV max). bushing:
Order: Kit MT. representative. Order: +MWS. Add -/ATEX to part number. 1250 A continuously
13
300PBM
COUPLING CONNECTOR
FOR 430TB/G
290 mm
Design
1. Interface designed to fit
430TB connector.
2. Bus for 300PBM.
3. Conductive EPDM insert.
4. Insulating EPDM layer
moulded between the
insert and the jacket.
5. Conductive EPDM jacket. 2
6. Conductive EPDM cap. 6
7. Basic insulating plug (with 1
8 7
VD point).
8. Conductor connector 3
(hexagonal crimping, deep
indent crimping or bolted). 290 mm
9. Cable reducer. (350 mm
10. Earthing lead. for 36 kV) 4
300PBM
The screen break design 430TB coupling
5
enables cable outer sheath connector connector
testing without removing or
dismantling the connector.
10
9
Specifications and
standards
The 300PBM coupling
connector meets the
requirements of CENELEC
HD 629.1. 105 mm
14
Kit contents
The complete (K)(M)300PBM/G The kit also comprises silicone grease, field
coupling connector kit control mastic, installation rod, installation
instructions and crimp chart.
comprises 3 x the following
components:
Conductor
contact TMBC-X
3 x (K)(M)300PBM/G-W-X
coupling connector kit
Cable reducer
430CA-W
Connector housing Contact rod Conductor (411CA-W
(K)(M)300BP/G 300PB-CR contact TBC-X for 36 kV)
16.95-14-5
50.150-14-5
50 50(K)M-10-2 50(K)M-10-1 50(K)M-11-2
50.150-14-5
95.240-14-5
120.300-12-5
For use with For use with fabric tape For use with For use with copper For use with For outdoor
copper tape (graphite) screened cables. easy strip semi-conductive wire screened cables. other cable types. applications.
screened cables. Order additional screened cables. Order: No earthing Please contact our Order: +MWS.
Order: Kit MT. semi-conductive tape Field control mastic device is representative.
(type TSC). (type MFC). necessary.
15
430TBM-P2/P3
DUAL/TRIPLE CABLE ARRANGEMENT
FOR 430TB CONNECTOR
Application Technical characteristics Up to 36 kV
Separable connectors (bolted
630 A (1250 A)
type) for dual (P2) and triple jacket provides a total safe to
(P3) cable arrangements. touch screen.
6/10 (12) kV
tested for AC withstand and 6.35/11 (12) kV
partial discharge prior to 8.7/15 (17.5) kV
leaving the factory. 12/20 (24) kV
12.7/22 (24) kV
18/30 (36) kV
19/33 (36) kV
Design 290 mm
1. Type C interface as
described by CENELEC
EN 50180 and 50181.
2. Bus for 300PBM.
3. Conductive EPDM insert.
4. Insulating EPDM layer
moulded between the
insert and the jacket. 2
1
5. Conductive EPDM jacket. 6
6. Conductive EPDM cap. 8
7. Basic insulating plug (with Non-size 7
sensitive: 3
VD point).
290 mm
8. Conductor connector.
9. Cable reducer. Size
10. Earthing lead. sensitive:
350 mm 4
The screen break design 300PBM
430TBM coupling
enables cable outer sheath connector 5 connector
testing without removing or
dismantling the connector.
10
Specifications and
standards 9
The 430TBM-P2/P3 connectors
meet the requirements of
CENELEC HD 629.1.
105 mm
16
Kit contents
The complete (K)(M)430TBM-P2 The complete (K)(M)430TBM-P3
connector kit comprises 3 x the connector kit comprises 3 x the
following components: following components:
290
300BIPA
300BIPA basic
basic insulating
insulating plug
plug
300PBM
300PBM
coupling
coupling
connectors
connector
430TB tee
connector 430TB tee
connector
110 105
In mm.
16.95-14-5
3 x M430TBM-P3-W-X. 50.150-14-5
50 50(K)M-10-2 50(K)M-10-1 50(K)M-11-2
50.150-14-5
95.240-14-5
120.300-12-5
For use with For use with Alupe or For use with For use with For applications When installed on an
copper tape C 33-226 cables. other cable types. easy strip semi-conductive outdoors and in appropriate equipment
screened cables. Please contact our Please contact our screened cables. Order: humid climate. bushing:
Order: Kit MT. representative. representative. Field control mastic Order: +MWS. 1250 A continuously
(type MFC).
17
440PBM
COUPLING CONNECTOR
FOR 440TB
Design
1. Interface designed to fit
440TB connector. 410 mm
2. Bus for 440PBM.
3. Conductive EPDM insert.
4. Insulating EPDM layer
moulded between the
insert and the jacket.
5. Conductive EPDM jacket. 2
6. Conductive EPDM cap. 6
1 8
7. Basic insulating plug. 7
8. Conductor connector 3
440TB 440PBM
(hexagonal crimping, deep connector coupling
4
indent crimping or bolted). connector
400 mm
9. Cable reducer. 5
10. Earthing lead.
Specifications and
standards
The 440PBM coupling 155 mm
connector meets the
requirements of CENELEC
HD 629.1.
18
Kit contents
The complete The kit also comprises silicone grease, field
(K)(M)440PBM/G coupling control mastic, installation rod, installation
instructions and crimp chart.
connector kit comprises 3 x the
following components:
Conductor
contact TMBC-X
3 x (K)(M)440PBM/G-W-X
coupling connector kit
Contact rod
Connector housing 440PB-CR Conductor Cable reducer
(K)(M)440BP/G + M16 stud contact TBC-X 611CA-W
For use with For use with fabric tape For use with For use with copper For use with For outdoor
copper tape (graphite) screened cables. easy strip semi-conductive wire screened cables. other cable types. applications.
screened cables. Order additional screened cables. Order: No earthing Please contact our Order: +MWS.
Order: Kit MT. semi-conductive tape Field control mastic device is representative.
(type TSC). (type MFC). necessary.
19
434TBM-P2
DUAL CABLE ARRANGEMENT FOR
434TB CONNECTOR
Design 345 mm
1. Type C interface as
described by CENELEC
EN 50180 and 50181.
2. Bus for 440PB.
3. Conductive EPDM insert.
4. Insulating EPDM layer 11 2
moulded between the
1 6
insert and the jacket. 8
5. Conductive EPDM jacket.
6. Conductive EPDM cap. 3 7
440PB
7. Basic insulating plug (with coupling
VD point). connector 4
8. Conductor connector. 434TB
5 connector
9. Cable reducer.
10. Earthing lead.
11. Threaded M16 stud for the
equipment bushing.
10
The screen break design
enables cable outer sheath
testing without removing or
dismantling the connector. 9
Specifications and
standards 155 mm
The 434TBM-P2 connectors
meet the requirements of
CENELEC HD 629.1.
20
Kit contents
The complete (K)(M)434TBM-P2
connector kit comprises 3 x the
following components:
345
300BIPA
basic
insulating
plug
434TB
tee
connector
440PB
coupling
connector
110 155
In mm.
For use with For use with Alupe or For use with For use with For applications When installed on an
copper tape C 33-226 cables. other cable types. easy strip semi-conductive outdoors and in appropriate equipment
screened cables. Please contact our Please contact our screened cables. Order: humid climate. bushing:
Order: Kit MT. representative. representative. Field control mastic Order: +MWS. 1250 A continuously
(type MFC).
21
400AR-3
INTERFACE C
EQUIPMENT BUSHING
Specifications and
standards
The bolted type equipment
bushings 400AR-3 are moulded
epoxy insulated parts and meet
the requirements of CENELEC
EN 50180 and IEC 60137. 133
Ordering instructions 30
To order the equipment
10
bushing, specify the type.
The bushings can be supplied 330
with an earth jumper (/J).
E.g. M400AR-3/J.
For use in potentially explosive 144
atmospheres (for 12 kV max),
Minimum oil level:
order: 400AR-3/ATEX. -12 kV: 40 mm
Dia.
25
-24 kV: 50 mm
-36 kV: 70 mm
40
M16
Dia. 70
Dia. 88
Dia. 128
In mm.
K400AR-3 24 630
M400AR-3 36 630
22
FIXINGS FOR
EQUIPMENT BUSHINGS
fixing flange
B DIN 42 538
E DIN 42 538
stud clamp
equipment
M10
connection
55
25
6 fixing
Dia. 90
studs
Dia. 140
earth jumper
In mm.
23
400AR-4
INTERFACE C
EQUIPMENT BUSHING
Specifications and
standards
The bolted type equipment
bushings 400AR-4 are moulded
epoxy insulated parts and meet
the requirements of CENELEC
EN 50180 and IEC 60137. 139
Ordering instructions 36
40
M16
Dia. 70
Dia. 100
Dia. 150
In mm.
K400AR-4 24 1250
M400AR-4 36 1250
24
FIXINGS FOR
EQUIPMENT BUSHINGS
400AR-4/GS Bushing 400AR-4/J Bushing
bushing interface
fixing studs
fixing flange
NF C 52-053
claw clamp F DIN 42 538
stud clamp
equipment
sealing gasket
equipment
connection
earth plate
earth jumper
M10 or
M10
M12
50 to
60
70 25 30
4 fixing 6 fixing
studs Dia. 105 studs Dia. 105
Dia. 171 Dia. 171
In mm.
25
400AR-5
INTERFACE C
EQUIPMENT BUSHING
Specifications and
standards
The bolted type equipment
bushings 400AR-5 are moulded
epoxy insulated parts and meet
the requirements of CENELEC
EN 50180 and IEC 60137.
139
Ordering instructions
To order the equipment 36
245
bushing, specify the type.
The bushings can be supplied
with an earth jumper (/J) or an Minimum oil level:
-12 kV: 40 mm Dia. 32 72
earth plate (/GS). This earth -24 kV: 50 mm
connection must be specified -36 kV: 70 mm
when ordering.
E.g. M400AR-5/GS. 32
M16
Dia. 76
Dia. 150
In mm.
K400AR-5 24 1250
M400AR-5 36 1250
26
FIXINGS FOR
EQUIPMENT BUSHINGS
400AR-5/GS Bushing 400AR-5/J Bushing
bushing interface
fixing studs
fixing flange
NF C 52-053
claw clamp F DIN 42 538
stud clamp
equipment
sealing gasket
equipment
connection
earth plate
earth jumper
M10 or
M10
M12
50 to
60
70 25 30
4 fixing 6 fixing
studs Dia. 105 studs Dia. 105
Dia. 171 Dia. 171
In mm.
27
400AR-6
INTERFACE C
EQUIPMENT BUSHING
Specifications and
standards
The bolted type equipment
bushings 400AR-6 are moulded
epoxy insulated parts and meet 133
the requirements of CENELEC
EN 50180 and IEC 60137.
30
10
Ordering instructions
To order the equipment
bushing, specify the type.
The bushings can be supplied 398
with an earth jumper (/J).
This earth connection must be
specified when ordering. 213
E.g. M400AR-6/J.
40
M16
Dia. 70
Dia. 74
Dia. 128 In mm.
K400AR-6 24 630
M400AR-6 36 630
28
FIXINGS FOR
EQUIPMENT BUSHINGS
fixing flange
B DIN 42 538
E DIN 42 538
stud clamp
equipment
Fixing dimensions
standards DIN 42 538
sealing gasket German standards.
M10
55
25
equipment
connection
6 fixing
Dia. 80
studs
Dia. 140
earth jumper
In mm.
29
400SFR-B
INTERFACE C
EQUIPMENT BUSHING
Dia. 70
Design
The equipment bushing is a
moulded epoxy insulated part
with a connector interface in
accordance with CENELEC EN
50180.
The 400SFR-B bushing has a
shank outside this standard, 219.5
adapted to use in SF6 gas.
Specifications and 33
standards
The bolted type equipment
bushing 400SFR-B meets the
requirements of CENELEC EN
50180 and IEC 60137.
95
Ordering instructions
To order the equipment
bushing, simply specify the
type.
M12
Dia. D
Dia. 70
Dia. 109 In mm.
30
FIXINGS FOR
EQUIPMENT BUSHINGS
UNMOUNTED
60°
60° 60°
M4
83
M6
Dia. 91.5
Dia. 103.1
equipment
MOUNTED
equipment
connection
earth
bushing
connection
interface 6 fixing M4
screws sealing
M6 O-ring
gasket
In mm.
31
400A-24B
INTERFACE C
IN-AIR BUSHING
6/10 (12) kV
6.35/11 (12) kV
8.7/15 (17.5) kV
12/20 (24) kV
12.7/22 (24) kV
Specifications and
standards
The bolted type equipment
bushings 400A-24B are
moulded epoxy insulated parts
and meet the requirements
of CENELEC EN 50180, IEC
30
60071 and IEC 60137.
20
40
B M16
Dia. 80
In mm.
32
FIXINGS FOR
400A-24B In-air bushing
EQUIPMENT BUSHINGS
bushing interface
earth jumper
equipment
gasket
equipment
connection
fixing flange
BCA-B or fixing flange
BCA-D BCA-F
Dia.12 Dia.12
Dia. 94.5 Dia. 94.5
4 4
10 10
Dia. 111 Dia. 111
120°
126
120°
BS 2562 stand.: 120
DIN 42 538 stand.: 123 Dia. 150
Dia. 150
Type BCA-B : BS 2562 British standards Type BCA-F : NFC 52-053 French standards
Type BCA-D : DIN 42 538 German standards
M10 M10
55 52
20 20
4 fixing 3 fixing
studs studs
Dia. 82 Dia. 82 In mm
Dia. 123 Dia. 126
33
300SA
SURGE ARRESTER
FOR 430TB AND 434TB CONNECTOR
Design 170 mm
Surge arrester comprising: 105 mm
1. Interface designed to fit the
430TB/G or 434TB/G tee
connector.
2. Conductive EPDM insert. Dia.
75 mm
3. Conductive EPDM jacket.
4. Insulating EPDM layer
moulded between the insert 1
and the jacket.
5. Receptacle for contact rod. 5
6. Metal oxide valve elements. 2
7. Steel cap.
8. Earth connection. 3 9
L2
9. Earth lead.
L1
4
Specifications and 6
standards
The 300SA surge arresters meet
the test requirements of IEC Dia.
60099-4. 65 mm
7
8
34
Typical application and Ordering instructions
dimensions To order the surge arrester,
specify the surge arrester type,
as described on previous page.
290 mm
Example:
180 mm 107 mm
For a maximum continuous
operating voltage (r.m.s.) of
24 kV and a nominal discharge
current of 10 kA.
Order a 300SA-10-30N surge
arrester.
Type 300SA
surge arrester
Type
430TB or
434TB
tee connector
Technical data
35
400PB-XSA
INTERFACE C
SURGE ARRESTER
Design 252 mm
Surge arrester comprising: 150 mm
1. Conductive EPDM insert.
2. Conductive EPDM jacket.
3. Insulating EPDM layer Dia.
moulded between the insert 80 mm
and the jacket.
4. Contact rod. 4
5. Earthing lead.
6. Earth connection. 1 9
7. Steel cap.
2
8. Metal oxide valve elements.
5
9. Type C - 630 A interface 3
L2
as described by CENELEC
L1
EN 50180 and 50181.
8
Specifications and
standards Dia.
70 mm
The 400PB-XSA surge arresters
meet the test requirements of 7
IEC 60099-4.
6
36
Typical applications and Ordering instructions
dimensions To order the surge arrester,
specify the surge arrester type,
as described on previous page.
410 mm
Example:
220 mm 185 mm For a maximum continuous
operating voltage (r.m.s.) of
24 kV and a nominal discharge
current of 10 kA.
Order a 400PB-10SA-30N
surge arrester.
Type
400TB
Type 400PB-5SA
or 440TB
or 400PB-10SA
tee connector
surge arrester
Technical data
37
400TR and 400TR-LB
INTERFACE C
TEST RODS
Application Technical characteristics
* <==>
- cable fault location be used with 400TE,
- cable testing 430TB, 400TB and 440TB
- phasing checks, etc. connectors.
% !;!
<==>?@Q
with a cable lug, a 4 mm the 400LB connector.
plug or spring clips.
400TR 400TR-LB
Design
1. Insulating shroud.
2. Threaded rod for test
connection. 1
3. Two nuts M12.
4. Insulation.
M10
5. Copper test rod stem.
6. Wing nut. 1
2
An insulating shroud is M12 60
provided to allow the 2 6
application of test voltages
3 40
when bushings are closely
spaced.
480
465
Installation
The test rod is mounted on
4
to the clamping screw in
the type C interface tee and
coupling connectors. The 310
4 288
test cable is connected to Dia.
25
the threaded stem and the
insulating shroud moved to its 5
final position over the end of
the test rod.
5
Ordering instructions
Simply specify:
400TR or 400TR-LB test rod.
In mm.
400TR 36 kV 96 kV 95 kV
400TR-LB 36 kV 96 kV 95 kV
38
400TK & 400SW
INSTALLATION TOOL
400SW
400TK
Ordering instructions
Simply specify:
- 400TK box spanner
01/2011
39
ACCESSORIES
INTERFACE C
40
400BIPA Ordering instructions
Basic insulating plug Order
Acts as a tightening nut for 400BIPA for 12 kV,
the 400TB and 440TB tee K400BIPA for 24 kV
connector kits. M400BIPA for 36 kV or
The plug contains a voltage P400BIPA for 41.5 kV
detection point. applications.
The conductive rubber
protection cap is included.
41
POSSIBLE ARRANGEMENTS
INTERFACE C
430TB 430TBM-P2
Single cable arrangement. Dual cable arrangement.
Order 430TB for 12 kV, Order 430TBM-P2 for 12 kV,
K430TB for 24 kV or M430TB K430TBM-P2 for 24 kV or
for 36 kV applications. M430TBM-P2 for 36 kV
applications.
185 290
300BIPA
300BIPA
basic
basic
insulating
insulating
plug
plug
300PBM
430TB tee coupling
connector connector
430TB tee
connector
110 105
430TBM-P3 430TBM-L3
Triple cable arrangement. 3-way connection.
Order 430TBM-P3 for 12 kV, Order 430TBM-L3 for 12 kV,
K430TBM-P3 for 24 kV or K430TBM-L3 for 24 kV or
M430TBM-P3 for 36 kV M430TBM-L3 for 36 kV
applications. applications.
425
300BIPA 300BIPA
basic basic
insulating insulating
plug plug
400BIPA
basic
300PBM 300PBM
insulating
coupling coupling
plug
connectors connectors
430TB tee
430TB tee connector
connector
01/2011
In mm.
42
434TB 434TBM-P2
Single cable arrangement. Dual cable arrangement.
Order 434TB for 12 kV, Order 434TBM-P2 for 12 kV,
K434TB for 24 kV or M434TB K434TBM-P2 for 24 kV or
for 36 kV applications. M434TBM-P2 for 36 kV
applications.
185 345
300BIPA 300BIPA
basic basic
insulating insulating
plug plug
434TB
434TB tee tee
connector connector
440PB
coupling
connector
450 410
300BIPA
400BIPA
basic
basic
insulating
insulating
plug
plug
300SA
surge arrester 400PB-XSA
surge arrester
434TB
tee connector 440TB
tee connector
440PB
coupling
110 155 connector
110
43
400TB/G 400TB/G-P2
Single cable arrangement. Dual cable arrangement.
Order 400TB/G for 12 kV, Order 400TB/G-P2 for 12 kV,
K400TB/G for 24 kV, K400TB/G-P2 for 24 kV or
M400TB/G for 36 kV or M400TB/G-P2 for 36 kV
P400TB/G for 41.5 kV applications.
applications.
250 500
basic
insulating
plug
tee
connecting basic
connector
plug insulating
plug
400TB/G-L2
2-way connection.
Order 400TB/G-L2 for 12 kV,
K400TB/G-L2 for 24 kV or
M400TB/G-L2 for 36 kV
applications.
400TB/G-L3
3-way connection.
Order 400TB/G-L3 for 12 kV,
K400TB/G-L3 for 24 kV or
M400TB/G-L3 for 36 kV
applications.
In mm.
44
400TB/G-L4
Disconnectable tap-off.
Order 400TB/G-L4 for 12 kV,
K400TB/G-L4 for 24 kV or
M400TB/G-L4 for 36 kV
applications.
400TB/G-L5 505
2-way connection with tap-off.
Order 400TB/G-L5 for 12 kV
or K400TB/G-L5 for 24 kV
applications.
Connector on stand-off
plug
Order 400SOP-B for 12 kV,
K400SOP-B for 24 kV or
M400SOP-B for 36 kV
applications.
300BIPA 400BIPA
basic basic
insulating insulating
plug plug
400TB/G tee
stand-off 430TB tee stand-off connector
plug connector plug
In mm.
45
Earthing plug on Connector on earthing
connector plug
Order 300GP-B for 12 kV, Order 400GP-B for 12 kV,
24 kV and 36 kV applications. 24 kV and 36 kV applications.
In mm.
46
Additional catalogue information on power cable accessories