Current Transformer Burden Chart
SUPPORT CONTACT
If 2.5 VA total is available then 2.5 - 0.75 = 1.75 VA is available for the wire. Assuming the maximum 5 amp
secondary current, on Nomogram No. 1, align a straightedge on 5 amps (left hand column) and 1.75 VA
(center column). Read the impedance in ohms (right hand column). This should read 0.07 ohms.
Now go to Nomogram No. 2. Place a straightedge on 0.07 ohms (center column) and 30 ft. cable length one
way (right hand column). Read the cable size (left hand column), which should read #10 AWG copper cable
or larger.
With the above conditions, #10 wire or larger will keep the current transformer within its best accuracy
limit.
This website uses cookies to provide you with the best browsing experience.
Find out more or adjust your settings.
Accept
ADDITIONALThis website usesMFG.CROSS
cookies to provide you with the best
CUSTOM browsing experience.CUSTOM
PRODUCT
OFFERINGSFind out more or adjust your settings.
REFERENCE REQUEST APPLICATION
AVAILABLE REQUEST SUPPORT
Accept
PRODUCTS CATALOG SUPPORT CONTACT
FLEX-CORE®
Current Download Our Request Technical
Transformers Product Catalog Support Div. Morlan &
Potential Send Me a Printed Purchase Order
Associates, Inc.
P.O.Box 6047
Transformers Catalog Form 4970 Scioto-Darby
Current Credit Application Rd.
LATEST NEWS Hilliard, OH 43026
Transformer/Transducers Form
Transducers Press Releases Flex-Core® Return
Phone: (614) 889-
Meters Policy 6152
Accessories Flex-Core® Fax: (614) 876-
View All Warranty 8538
Email: sales@ ex-
Flex-Core® Privacy
core.com
Policy Support:
support@ ex-
core.com
This website uses cookies to provide you with the best browsing experience.
Find out more or adjust your settings.
Accept