Instructions 95-8546: UVIR Flame Detector X5200

Download as pdf or txt
Download as pdf or txt
You are on page 1of 34

Instructions

95-8546
UVIR Flame Detector
X5200

9.2 Rev: 5/11 95-8546


Table of Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 15
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Optical Integrity (oi) . . . . . . . . . . . . . . . . . . . . . . 2 Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . 16
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3 oi Plate Removal and Replacement . . . . . . . . 16
Data Logging / Event Monitoring . . . . . . . . . . . . . 3 Periodic Checkout Procedure . . . . . . . . . . . . . . 17
Integral Wiring Compartment . . . . . . . . . . . . . . . 3 Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Signal Processing Options . . . . . . . . . . . . . . 3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17


IR Detector Options . . . . . . . . . . . . . . . . . . . . . . 3
UV Detector Options . . . . . . . . . . . . . . . . . . . . . . 4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 18

General Application Information . . . . . . . . 4 Replacement Parts . . . . . . . . . . . . . . . . . . . . . 20


Response Characteristics . . . . . . . . . . . . . . . . . . 4
Welding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Device Repair And Return . . . . . . . . . . . . . . 20
Artificial Lighting . . . . . . . . . . . . . . . . . . . . . . . . . 4
EMI / RFI Interference . . . . . . . . . . . . . . . . . . . . . 4
Ordering Information . . . . . . . . . . . . . . . . . . 20
Non-Carbon Fires . . . . . . . . . . . . . . . . . . . . . . . . 4
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
False Alarm Sources . . . . . . . . . . . . . . . . . . . . . . 5
Factors Inhibiting Detector Response . . . . . . . . . 5
Appendix A – FM Approval AND
PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . . . 22
Important safety notes . . . . . . . . . . . . . . . . . 6
Appendix B – csa Approval . . . . . . . . . . . . . . . . 27

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Appendix C – ATEX / CE Approval . . . . . . . . . . 28


Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 7
Appendix D – iecex Approval . . . . . . . . . . . . . . 30
Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 7
Protection Against Moisture Damage . . . . . . . . . 7 Appendix E – vdS Approval . . . . . . . . . . . . . . . . 31
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . 8
EOL Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Setting Device Network Addresses
(EQ and EQP Models Only) . . . . . . . . . . . . . 14

Startup Procedure . . . . . . . . . . . . . . . . . . . . 15
Fire Alarm Test . . . . . . . . . . . . . . . . . . . . . . . . . 15
INSTRUCTIONS

UVIR Flame Detector


X5200

Important
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.

ATTENTION
The X5200 includes the Automatic Optical Integrity
(oi ) feature — a calibrated performance test that
®

is automatically performed once per minute to


verify complete detector operation capabilities. No
testing with an external test lamp is required.

DESCRIPTION
The evolution continues with the new X5200 UVIR
A tricolor LED on the detector faceplate indicates
Flame Detector. The X5200 meets the most stringent
normal condition and notifies personnel of fire alarm or
requirements worldwide with advanced detection
fault conditions.
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
Microprocessor controlled heated optics increase
mounting arrangement allows the UV and IR sensors to
resistance to moisture and ice.
monitor the same hazardous location with a 90 degree
cone of vision. When both sensors simultaneously detect
The X5200 housing is available in copper-free aluminum
the presence of a flame, an alarm signal is generated.
or stainless steel, both with NEMA 4X and IP66 rating.
The detector has Division and Zone explosion-proof
ratings and is suitable for use in indoor and outdoor
Outputs
applications.
Relays
The standard output configuration includes fire, fault and The standard detector is furnished with fire, fault and
auxiliary relays. Output options include: auxiliary relays. All three relays are rated 5 amperes at
–– 0 to 20 mA output (in addition to the three relays) 30 Vdc.

–– Pulse output for compatibility with existing controller The Fire Alarm relay has redundant terminals and
based systems (with fire and fault relays) normally open / normally closed contacts, normally
–– Eagle Quantum Premier ® (EQP) compatible model de-energized operation, and latching or non-latching
(no analog or relay outputs) operation.
–– HART Communication
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.

9.2 ©Detector Electronics Corporation 2011 Rev: 5/11 95-8546


The Auxiliary relay has normally open / normally Table 2—Detector Status Indicator
closed contacts, and is configurable for energized or
de-energized operation, and latching or non-latching Detector Status LED Indicator
operation. Power On/Normal Auto oi Green
(no fault or fire alarm)
0 to 20 mA Output
Green, flashing on for 0.5 sec.
A 0 to 20 mA output is available as an option (in addition Power On/Normal Man oi every 5 sec.
to the three relays). This option provides a 0 to 20 mA dc
Fault Yellow
current output for transmitting detector status information
to other devices. The circuit can be wired in either an UV Alarm only
Red, flashing on for
isolated or non-isolated configuration and can drive 500 ms. and off for 500 ms.
a maximum loop resistance of 500 ohms from 18 to IR Alarm only
Red, flashing on for
19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table 1 250 ms. and off for 250 ms.
indicates the detector status conditions represented by Pre-Alarm
Red, flashing on for
the various current levels. The output is calibrated at the 1 sec. and off for 1 sec.
factory, with no need for field calibration. A model with Fire (Alarm) Steady Red
relays and 0-20 mA with HART is also available. Refer to
Addendum number 95-8636 for complete details. On Power-Up, The LED Flashes in Sequence as Follows,
Indicating Sensitivity and Signal Processing Status
NOTE
Low UV Sensitivity One Red Flash
The output of the 0 to 20 mA current loop is not
Medium UV Sensitivity Two Red Flashes
monitored by the fault detection circuitry of the
High UV Sensitivity Three Red Flashes
X5200. Therefore, an open circuit on the loop will Very High UV Sensitivity Four Red Flashes
not cause the fault relay to change state or the
detector status LED to indicate a fault. The status of Stand. UV Signal Process. One Yellow Flash
the LED always follows the status of the relays. Arc Rej. UV Signal Process. Two Yellow Flashes
Low IR Sensitivity One Green Flash
An alarm condition will normally over-ride a fault condition, Medium IR Sensitivity Two Green Flashes
unless the nature of the fault condition impairs the ability High IR Sensitivity Three Green Flashes
of the detector to generate or maintain an alarm output, Very High IR Sensitivity Four Green Flashes
i.e. loss of operating power. Quick Fire/TDSA IR Signal One Yellow Flash
TDSA only IR Signal Two Yellow Flashes
Table 1—Detector Status Conditions Indicated by Current Level

Current Level (±0.3 mA) Detector Status


LED
0 mA Power Fault
1 mA General Fault A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
2 mA oi Fault
or fault conditions. Table 2 indicates the condition of the
4 mA Normal Operation LED for each status.
8 mA IR Pre-Alarm only
12 mA UV Alarm only OPTICAL INTEGRITY (oi)
14 mA IR Alarm only Automatic oi
16 mA Pre-Alarm
The X5200 includes the Automatic Optical Integrity
20 mA Fire Alarm (oi) feature — a calibrated performance test that is
automatically performed once per minute to verify
LON/SLC Output complete detector operation capabilities. No testing
with an external test lamp is required. The detector
The EQP model is designed for use exclusively with automatically performs the same test that a maintenance
the Det-Tronics Eagle Quantum Premier system. The person with a test lamp would perform — once every
detector communicates with the system controller over minute, 60 times per hour. However, a successful
a digital communication network or LON/SLC (Local automatic oi test does not produce an alarm condition.
Operating Network / Signaling Line Circuit). The LON/
SLC is a fault tolerant, two wire digital communication
network arranged in a loop configuration. Analog and
relay outputs are not available on this model.

9.2 2 95-8546
The X5200 signals a fault condition when less than half data logging / event monitoring
of the detection range remains. This is indicated by the Data logging for event monitoring capability is also
Fault relay and is evident by the yellow color of the LED provided. The detector can log up to 1500 events
on the face of the detector. See the "Troubleshooting" (up to 1000 general and 500 alarm events). Status
section for further information. conditions such as normal, power down, general and
oi faults, pre-alarm, fire alarm, time and temperature
Magnetic oi / Manual oi are recorded. Each event is time and date stamped,
The detector also incorporates both magnetic oi and along with the temperature and input voltage. Event
manual oi features that provide the same calibrated test data is stored in non-volatile memory when the event
as the automatic oi, and in addition actuates the Alarm becomes active, and again when the status changes.
relay to verify output operation for preventive maintenance Data is accessible using the RS-485 port or the EQP
requirements. These features can be performed at controller.
any time and eliminate the need for testing with a non-
calibrated external test lamp. integral wiring compartment
All external wiring to the device is connected within
CAUTION the integral junction box. The screw terminals accept
These tests require disabling of all extinguishing wiring from 14 to 24 AWG. The detector is furnished with
devices to avoid release resulting from a four conduit entries, with either 3/4 inch NPT or 25 mm
successful test. threads.
The magnetic oi test is performed by placing a magnet by
the marked location (mag oi) on the outside of the detector.
The manual oi test is accomplished by connecting the oi
Signal Processing options
lead (terminal 22) to power supply minus via an external The X5200 features signal processing options for both the
switch. The magnet or switch must be held in place for a UV and IR sensor. These options determine the type of
minimum of 6 seconds to complete the test. Either of these logic that the detector will use for processing fire signals
test methods activates the calibrated UV and IR emitters. to customize the X5200 to the application.
If the resulting signal meets the test criteria, indicating
that greater than half of the detection range remains, the IR Detector Options
Alarm relay changes state, the indicating LED changes
to red, and the 0-20 mA current output goes to 20 mA. The IR detector in the X5200 can be programmed for:
This condition remains until the magnet is removed or the –– TDSA enabled
switch is released, regardless of whether the relays are set
–– Both TDSA and Quick Fire enabled (either initiates
for latching or non-latching operation.
fire alarm).
If less than half of the detection range remains, no alarm
Time Domain Signal Analysis (TDSA)
is produced and a fault is generated. The fault indication
can be reset by momentarily applying the magnet or The TDSA signal processing technique analyzes the
manual oi switch. input signal in real time, requiring the IR signal to flicker
randomly in order to recognize it as a fire condition.
NOTE
Refer to the Appendix A for FM verification of Using TDSA signal processing, the X5200 ignores
Det-Tronics’ Optical Integrity oi function. regularly chopped blackbody sources (occurring in areas
where moving conveyors and hot objects in proximity
communication to one another result in a regularly chopped IR signal),
because it looks for a less uniform signal. However, in
The X5200 is furnished with an RS-485 interface for
the presence of a regularly chopped signal, the unit is
communicating status and other information with external
more susceptible to false alarms due to sporadic IR that
devices. The RS-485 supports MODBUS protocol, with
functions as a trigger when occurring in conjunction with
the detector configured as a slave device.
the regularly chopped signal.
NOTE
The EQP model uses LON/SLC communication.
RS-485 communication is not available on the
EQP model.

9.2 3 95-8546
Quick Fire (High Speed) General APPLICATION
The Quick Fire (High Speed) feature can be used in INformation
conjunction with the TDSA signal processing method.
Response Characteristics
This method overrides TDSA requirements in the event
of an intense signal. When Quick Fire is activated, the Response is dependent on distance, type of fuel,
detector is capable of responding to an intense fire signal temperature of the fuel, and time required for the fire to
in less than 30 milliseconds (0.030 seconds). Using come to equilibrium. As with all fire tests, results must be
the Quick Fire feature in conjunction with TDSA signal interpreted according to an individual application.
processing allows the detector to provide a high speed
response to a large, non-flickering fire (such as in high See Appendix A for fire test results.
pressure gas applications) while maintaining an ability to
respond to smaller fires. Welding
Electric arc welding is a source of intense ultraviolet
UV Detector Options radiation. UV radiation from arc welding readily scatters
The UV detector output (measured in counts per second) and can deflect across significant distances, even when
is compared to the fire threshold (the “sensitivity” setting). direct obstructions exist. Any open door or window can
If the radiant energy level from the fire exceeds the allow nuisance UV radiation from arc welding to enter an
selected alarm threshold level, the fire alarm output is enclosed area.
activated. In every application, it is crucial to ensure that
the radiant ultraviolet energy level from the expected fire It is recommended that the system be bypassed during
at the required distance from the detector will exceed the welding operations in situations where the possibility of a
selected sensitivity level. false alarm cannot be tolerated. Gas welding mandates
system bypass, since the gas torch is an actual fire. Arc
The UV detector in the X5200 can be programmed for: welding rods can contain organic binder materials in
the flux that burn during the welding operation and are
–– Arc Rejection
detectable by the X5200. Welding rods with clay binders
–– Standard Signal Processing. do not burn and will not be detected by the X5200.
However, system bypass is always recommended, since
Arc Rejection (Recommended Factory Setting) the material being welded may be contaminated with
organic substances (paint, oil, etc.) that will burn and
The Arc Rejection mode enables the detector to prevent
possibly trigger the X5200.
nuisance fire alarms caused by UV from short-duration
electrical arcs or electrostatic discharge, while maintaining
Artificial Lighting
the ability to reliably detect the UV given off by a flame.
Typical applications that benefit from arc rejection logic The X5200 should not be located within 3 feet of artificial
include electrostatic coating processes and uncontrolled lights. Excess heating of the detector could occur due to
environments where transient UV sources can be present, heat radiating from the lights.
such as many typical outdoor applications. Most false
alarm sources have short transient UV signatures, while EMI/RFI Interference
fire creates a long UV signature over many seconds. The X5200 is resistant to interference by EMI and RFI,
Most fires are detected in a few seconds (see response and is EMC Directive compliant and CE marked. It will
times in Appendix A). not respond to a 5 watt walkie-talkie at distances greater
than 1 foot.
Standard Signal Processing
Standard signal processing is recommended for high- Non-Carbon Fires
speed suppression systems only. To allow for high- The response of the X5200 is limited to carbonaceous
speed operation, the standard processing mode does not fuels. It should not be used to detect fires from fuels
incorporate the arc rejection programming. This mode that do not contain carbon, such as hydrogen, sulfur and
should only be used in a controlled, indoor environment. burning metals.

9.2 4 95-8546
FALSE ALARM SOURCES FACTORS INHIBITING DETECTOR RESPONSE
Windows
UV: The UV sensor is solar blind to the ultraviolet
component of solar radiation. However, it will Glass and Plexiglas windows significantly attenuate
respond to sources of UV besides fire, such as radiation and must not be located between the detector
electric arc welding, lightning, high voltage corona, and a potential flame source. If the window cannot be
x-rays and gamma radiation. eliminated or the detector location changed, contact
Detector Electronics Corporation's (Det-Tronics®) for
IR: The detector has been designed to ignore steady recommendations regarding window materials that will
state infrared sources that do not have a flicker not attenuate radiation.
frequency characteristic of a fire, however, it should
be noted that if these steady state infrared sources Obstructions
are hot enough to emit adequate amounts of infrared Radiation must be able to reach the detector in order
radiation in the response range of the IR sensor and for it to respond. Care must be taken to keep physical
if this radiation becomes interrupted from the view of obstructions out of the line of view of the detector. In
the detector in a pattern characteristic of a flickering addition, UV or IR absorbing gases or vapors must not
flame, the IR sensor can respond. be allowed to accumulate between the detector and
the protected hazard. See Table 3 for a list of these
Any object having a temperature greater than substances.
0° Kelvin (–273°C) emits infrared radiation. The
hotter the object, the greater the intensity of the Smoke
emitted radiation. The closer the infrared source is
Smoke will absorb radiation. If accumulations of dense
to the detector, the greater the potential for a false
smoke can be expected to precede the presence of a
alarm. The IR sensor can respond to IR radiation
flame, then detectors that are used in enclosed areas
sources that can meet the amplitude and flicker
should be mounted on the wall approximately 3 feet
requirements of the detector such as vibrating hot
(1 meter) from the ceiling where the accumulation of
objects.
smoke is reduced.
Although the detector is designed to reduce
Detector Viewing Windows
false actuations, certain combinations of ambient
radiation must be avoided. For example, if IR It is important to keep the detector viewing windows as
radiation with an intensity that exceeds the fire free of contaminants as possible in order to maintain
threshold of the IR sensor should reach the detector maximum sensitivity. Commonly encountered substances
as a flickering signal, and if at the same time that can significantly attenuate UV and/or IR radiation
an electric arc welding signal also reaches the include, but are certainly not limited to, the following:
detector, an alarm output will be generated. Silicones
Oils and greases
NOTE Dust and dirt buildup
Radiation generated by false alarm sources such Paint overspray
as periodic lightning or sparks in the area can be Water and ice.
effectively ignored by the detector using the arc
rejection feature or time delay.

9.2 5 95-8546
Table 3 IMportant safety notes
UV and IR Absorbing Gases and Vapors

The following is a partial list of compounds that exhibit Warning


significant UV absorption characteristics. These are Do not open the detector assembly in a hazardous
also usually hazardous vapors. While generally of little area when power is applied. The detector contains
consequence in small amounts, these gases can restrict limited serviceable components and should never
UV detection if they are in the atmosphere in heavy be opened. Doing so could disturb critical optical
concentrations. It should also be determined whether or alignment and calibration parameters, possibly
not large amounts of these gases may be released as a causing serious damage. This type of damage
result of a fire-causing occurrence. could be undetected and could result in failure to
see a fire and/or false alarm.
Acetaldehyde Methyl Methacrylate
Acetone Alpha-Methylstyrene
Caution
Acrylonitrile Naphthalene
The wiring procedures in this manual are intended
Ethyl Acrylate Nitroethane
to ensure proper functioning of the device under
Methyl Acrylate Nitrobenzene
Ethanol Nitromethane
normal conditions. However, because of the
Ammonia 1-Nitropropane many variations in wiring codes and regulations,
Aniline 2-Nitropropane total compliance to these ordinances cannot be
Benzene 2-Pentanone guaranteed. Be certain that all wiring complies
1,3 Butadiene Phenol with the NEC as well as all local ordinances. If
2—Butanone Pyridine in doubt, consult the authority having jurisdiction
Butylamine Hydrogen Sulfide before wiring the system. Installation must be
Chlorobenzene Styrene done by a properly trained person.
1-Chloro-1-Nitropropane Tetrachloroethylene
Chloroprene Toluene Caution
Cumene Trichloroethylene To prevent unwanted actuation or alarm,
Cyclopentadiene Vinyl Toluene extinguishing devices must be disabled prior to
O-Dichlorobenzene Xylene performing detection system tests or maintenance.
P-Dichlorobenzene
If UV-absorbing gases may be a factor in a given application, Caution
precautionary measures should be taken. Detectors can The UVIR flame detectors are to be installed in
be placed closer to the potential hazard area, and/or places where the risk of mechanical damages is low.
the sensitivity of the detection system can be increased.
Contact the factory for further details. Attention
Remove the protective cap from the front of the
Substances such as methane, propane, butane, hexane,
detector before activating the system.
camphor and octane are not UV absorbing.
Absorption of infrared radiation in the range of 4.2 to 4.7 Attention
microns is not a significant problem with most organic Observe precautions for handling electrostatic
vapors, with the exception of those compounds that sensitive devices.
have triple bonds such as acetylene, nitriles, silane, or
isocyanates. Carbon dioxide concentrations higher than
normally present in the atmosphere can also cause
substantial loss of fire detection sensitivity.

9.2 6 95-8546
INSTALLATION

note CENTER AXIS


OF DETECTOR
The recommended lubricant for threads and FIELD OF VIEW

O-rings is a silicone free grease (part number


005003-001) available from Detector Electronics.
Under no circumstances should a lubricant
containing silicone be used. INCORRECT

Detector Positioning
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The following
factors should also be taken into consideration:
CENTER AXIS
• Identify all high risk fire ignition sources. OF DETECTOR
FIELD OF VIEW

• Be sure that enough detectors are used to adequately


cover the hazardous area. B1974
CORRECT
• Be sure that the unit is easily accessible for cleaning
and other periodic servicing. NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.

• Locate and position the detector so that the fire


hazard(s) are within both the field of view and Figure 1—Detector Orientation Relative to Horizon
detection range of the device. Refer to Appendix A
for specific information.
• The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain. See IMPORTANT
Figure 1. The detector should be positioned so The oi plate must be securely tightened to ensure
that its field of view does not cover areas outside proper operation of the oi system (40 oz./inches
the hazardous area. This will minimize the possibility recommended).
of false alarms caused by activities outside the area
requiring protection.
Protection Against Moisture Damage
• For best performance, the detector should be
mounted on a rigid surface in a low vibration area. It is important to take proper precautions during installation
to ensure that moisture will not come in contact with
• Dense fog, rain as well as certain gases and vapors the electrical connections of the system. The integrity
(see Table 3) can absorb UV and IR radiation and of the system regarding moisture protection must be
reduce the sensitivity of the detector. maintained for proper operation and is the responsibility
• Verify that all detectors in the system are properly of the installer.
aimed at the area to be protected. (The Det-Tronics
Q1201C Laser Aimer is recommended for this
purpose.)
oi PLATE
• If possible, fire tests should be conducted to verify
correct detector positioning and coverage. PLACE MAGNET
HERE TO INITIATE
• For ATEX installations, the X5200 detector housing MAGNETIC oi

must be electrically connected to earth ground.


IR VIEWING WINDOW

UV VIEWING WINDOW
detector Orientation
oi MAGNET
Refer to Figure 2 and ensure that the oi plate will
be oriented as shown when the X5200 is mounted A2134 DETECTOR STATUS INDICATOR
and sighted. This will ensure proper operation of the
oi system and will also minimize the accumulation of Figure 2—Front View of the X5200
moisture and contaminants between the oi plate and the
viewing windows.

9.2 7 95-8546
If conduit is used, we recommend installing drains, note
according to local codes, at water collection points Refer to“Power Consumption”in the“Specifications”
to automatically drain accumulated moisture. It is section of this manual.
also recommended to install at least one breather,
according to local codes, at upper locations to provide The use of shielded cable is required to protect against
ventilation and allow water vapor to escape. interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures
Conduit raceways should be inclined so that water will 7 through 12, and Figure 14. Consult the factory if not
flow to low points for drainage and will not collect inside using shielded cable.
enclosures or on conduit seals. If this is not possible, install
conduit drains above the seals to prevent the collection In applications where the wiring cable is installed in
of water or install a drain loop below the detector with a conduit, the conduit must not be used for wiring to other
conduit drain at the lowest point of the loop. electrical equipment.

Conduit seals are not required for compliance with If disconnection of power is required, separate disconnect
explosion-proof installation requirements, but are highly capability must be provided.
recommended to prevent water ingress in outdoor
applications. Units with M25 thread must use an IP66 CAUTION
washer or an O-ring sealed adapter/gland to prevent Installation of the detector and wiring should be
water ingress. performed only by qualified personnel.

Wiring Procedure Detector Mounting


Wire Size and Type Install the swivel mounting bracket assembly on the wall.
The installation surface should be free of vibration and
The system should be wired according to local codes.
suitable to receive 1/4 inch (M6) screws with a length of
The wire size selected should be based on the number
at least 1 inch (25 mm), and have sufficient capacity to
of detectors connected, the supply voltage and the
hold the detector and bracket weight. Refer to Figure 3
cable length. Typically 14 AWG (2.08 mm 2) or 16 AWG
for dimensions.
(1.31 mm2) shielded cable is recommended. Wires
should be stripped 3/8 inch (9 mm). A minimum input
voltage of 18 Vdc must be present at the X5200.

4.0
(10.2)
4X ø0.42 3.0 13.1
(1.1) (7.6) (33.4)

NOTE: THIS ILLUSTRATION SHOWS THE


DETECTOR MOUNTED AT THE 10° MINIMUM.
3.0 THESE DIMENSIONS WILL CHANGE BASED
(7.6) ON THE DETECTOR’S MOUNTING ANGLE.

4.0
(10.2)

10.6
(27.0)

E2069

Figure 3—Q9033 Mounting Bracket Dimensions in Inches (cm)


(See Figure 1 for Correct Detector Orientation.)

9.2 8 95-8546
Relay and 0-20 mA Output Models EOL Resistors (Not Used with EQP Model)
Follow the instructions below to install the X5200. To ensure that the insulating material of the wiring terminal
block will not be affected by the heat generated by EOL
1. Make field connections following local ordinances resistors, observe the following guidelines when installing
and guidelines in this manual. Refer to Figures 4 the resistors.
through 12.
1. Required EOL resistor power rating must be 5 watts
2. Check all field wiring to be sure that the proper
minimum.
connections have been made.

note
Important
EOL resistors must be ceramic, wirewound
Do not test any wiring connected to the detector
type, rated 5 watts minimum, with actual power
with a meg-ohmmeter. Disconnect wiring at
dissipation not to exceed 2.5 watts. This applies
the detector before checking system wiring for
to ATEX/IEC installations only.
continuity.
2. Resistor leads should be cut to a length of
3. Make the final sighting adjustments and ensure that
approximately 1 1/2 inches (40 mm).
the mounting bracket hardware is tight.
3. Bend the leads and install the EOL resistor as shown
in Figure 6.
4. Maintain a 3/8 inch (10 mm) minimum gap between
the resistor body and the terminal block or any other
neighboring parts.

NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused
apertures shall be closed with suitable blanking
elements.

Figure 4—X5200 Terminal Block

3/8 INCH (10 MM) GAP MINIMUM


9 4-20 mA + 19 4-20 mA – SPARE 29

8 4-20 mA + REF 18 4-20 mA – REF SPARE 28

7 COM FIRE 17 COM FIRE COM AUX 27

6 N.O. FIRE 16 N.O. FIRE N.O. AUX 26

5 N.C. FIRE 15 N.C. FIRE N.C. AUX 25


19 18 17 16 15 14 13 12 11
4 COM FAULT 14 COM FAULT RS-485 A 24

3 N.O. FAULT 13 N.O. FAULT RS-485 B 23 BULKHEAD


2 24 VDC + 12 24 VDC + MAN Oi 22

1 24 VDC – 11 24 VDC – 24 VDC – 21 A2126

B2061

Figure 5—Wiring Terminal Identification Figure 6—EOL Resistor Installation

9.2 9 95-8546
X5200 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29

8 4-20 mA + REF 18 4-20 mA – REF SPARE 28

7 COM FIRE2 COM FIRE 17 COM AUX 27

6 N.O. FIRE2 N.O. FIRE 16 N.O. AUX 26


E.O.L.
DEVICE4
5 N.C. FIRE2 N.C. FIRE 15 N.C. AUX 25
ALARM
4 COM FAULT1 COM FAULT 14 RS-485 A 24

3 N.O. FAULT1 N.O. FAULT 13 RS-485 B 23


+
2 24 VDC + 12 24 VDC + MAN Oi 22
24 VDC

1 24 VDC – 11 24 VDC – 24 VDC – 21

oi TEST 3

B2136 WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.

Figure 7—Ex d Wiring Option

X5200 DETECTOR
FIRE ALARM PANEL
9 4-20 mA + 19 4-20 mA – SPARE 29

8 4-20 mA + REF 18 4-20 mA – REF SPARE 28

EOL ALARM 7 COM FIRE2 COM FIRE 17 COM AUX 27


DEVICE 4

ALARM 6 N.O. FIRE2 N.O. FIRE 16 N.O. AUX 26

5 N.C. FIRE2 N.C. FIRE 15 N.C. AUX 25

4 COM FAULT1 COM FAULT 14 RS-485 A 24

3 N.O. FAULT1 13 N.O. FAULT RS-485 B 23


+
2 24 VDC + 12 24 VDC + MAN Oi 22
24 VDC

1 24 VDC – 11 24 VDC – 24 VDC – 21

oi TEST 3

B2137 WIRING NOTES:

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.

2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.

4 EOL RESISTOR SUPPLIED BY PANEL.

Figure 8—Ex e Wiring Option

9.2 10 95-8546
X5200 DETECTOR
X5200 DETECTOR
PLC PLC

600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29 600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29


AT 24 VDC AT 24 VDC
+ 8 4-20 mA + REF 18 28 + 8 18 4-20 mA – REF 28

– 7 17 27 – 7 17 27

4 TO 20 mA 6 16 26 4 TO 20 mA 6 16 26

5 15 25 5 15 25
+ +
24 VDC 24 VDC
4 14 24 4 14 24
– –
3 13 23 3 13 23

2 24 VDC + 12 MAN Oi 22 2 24 VDC + 12 MAN Oi 22


C2138 C2139
1 24 VDC – 11 24 VDC – 21 1 24 VDC – 11 24 VDC – 21

Oi TEST1 Oi TEST1

Figure 9—X5200 Detector Wired for Non-Isolated 0 to 20 mA Current Figure 10—X5200 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sourcing) Output (Sinking)

24 VDC 24 VDC
X5200 DETECTOR
– + + – X5200 DETECTOR
PLC PLC

600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29 600 Ω MAX 9 4-20 mA + 19 4-20 mA – 29


AT 24 VDC AT 24 VDC
+ 8 18 28 + 8 18 28

– 7 17 27 – 7 17 27

4 TO 20 mA 6 16 26 4 TO 20 mA 6 16 26

5 15 25 5 15 25
+ +
24 VDC 24 VDC
4 14 24 4 14 24
– –
3 13 23 3 13 23

2 24 VDC + 12 MAN Oi 22 2 24 VDC + 12 MAN Oi 22


C2140 C2141
1 24 VDC – 11 24 VDC – 21 1 24 VDC – 11 24 VDC – 21

Oi TEST1 Oi TEST1

Figure 11—X5200 Detector Wired for Isolated 0 to 20 mA Figure 12—X5200 Detector Wired for Isolated 0 to 20 mA
Current Output (Sourcing) Current Output (Sinking)

NOTES: 1. INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE


INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.

9.2 11 95-8546
EQP Model 5. Check all field wiring to be sure that the proper
1. Connect external wires to the appropriate terminals connections have been made.
inside the device junction box. (See Figure 13 for 6. Replace the device cover.
terminal identification.) 7. Make the final sighting adjustments and ensure that
2. Connect the shield of the power cable to “earth the mounting bracket hardware is tight.
ground” at the power source.
3. Connect shields for the LON cable as indicated. See NOTE
Figure 14. Refer to the Eagle Quantum Premier system
manual 95-8533 for information regarding power
NOTE and network communication cable requirements.
DO NOT ground any shields at the detector
housing.

4. Set the device network address. (See “Setting


Device Network Addresses” section of this manual
for switch setting procedure.)

COM SHIELD 6 16 COM SHIELD

COM 1 A 5 15 COM 2 A

COM 1 B 4 14 COM 2 B

POWER SHIELD 3 13 POWER SHIELD

24 VDC + 2 12 24 VDC +

24 VDC – 1 11 24 VDC –
A2089

Figure 13—Wiring Terminal Identification for X5200 EQP Model

9.2 12 95-8546
9.2
+ +
– –
– POWER –
+ DISTRIBUTION +
+

+ – + –
CONTROLLER EQP3700DCIO EQP2100PSM EQPX5200 EQPX5200 EQPX5200 EQPX5200
P1 P1
6 SHIELD 3 4 SHIELD 9 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3 13 SHIELD 3

4 24 VDC – 2 5 24 VDC – 2 6 24 VDC – 7 11 24 VDC – 1 11 24 VDC – 1 11 24 VDC – 1 11 24 VDC – 1

3 24 VDC + 1 4 24 VDC + 1 5 24 VDC + 8 12 24 VDC + 2 12 24 VDC + 2 12 24 VDC + 2 12 24 VDC + 2


P7 P2
COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1 COM2 COM1

51 SHIELD 48 6 SHIELD 3 12 SHIELD 1 16 SHIELD 6 16 SHIELD 6 16 SHIELD 6 16 SHIELD 6

52 B 49 5 B 2 11 B 3 14 B 4 14 B 4 14 B 4 14 B 4

53 A 50 4 A 1 10 A 2 15 A 5 15 A 5 15 A 5 15 A 5
P6
BUS BAR P3
C 45 A2208
C 1 N
FAULT NO 46 P4 P3
B 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3
B IN–/OUT+ B + –

CH 1

CH 5
GND 5 57 GND GND 54 24 VDC 4 H
C COMMON C SUPPLY
RXD 2 58 RxD B 55
TXD 3

13
59 TxD A 56 A + SUPPLY A
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE

CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY
B IN–/OUT+ B

CH 3

CH 7
9 3+ 7+ 17
10 3– 7– 18 C COMMON C
11 4+

DIGITAL INPUTS
8+ 19
A + SUPPLY A
12 4– 8– 20
B IN–/OUT+ B

CH 4

CH 8
P4 P5
21 C C 33 C COMMON C
22 NO NO 34

RELAY 5
RELAY 1
23 NC NC 35

24 C C 36
25 NO NO 37

RELAY 6
RELAY 2
26 NC NC 38

27 C C 39
28 NO NO 40

RELAY 7
RELAY 3
29 NC NC 41

30 C C 42
31 NO NO 43

RELAY 4

RELAY 8
32 NC NC 44

Figure 14—A Typical EQP System

95-8546
ADDRESS SWITCHES SENSOR MODULE
REMOVED FROM HOUSING

A2191

Figure 15—Location of Address Switches

Setting Device network addresses The address number is binary encoded with
(EQ and EQP Models Only) each switch having a specific binary value with
Overview of Network Addresses switch 1 being the LSB (Least Significant Bit).
(See Figure 16) The device’s LON address is
Each device on the LON must be assigned a unique equal to the added value of all closed rocker
address. Addresses 1 to 4 are reserved for the switches. All “Open” switches are ignored.
controller. Valid addresses for field devices are from
5 to 250. Example: for node No. 5, close rocker switches 1 and
3 (binary values 1 + 4); for node No. 25, close rocker
IMPORTANT switches 1, 4 and 5 (binary values 1 + 8 + 16).
If the address is set to zero or an address above
250, the switch setting will be ignored. Note
The field device sets the LON address only when
Duplicated addresses are not automatically detected. power is applied to the device. Therefore, it is
Modules given the same address will use the number important to set the switches before applying
given and report to the controller using that address. power. If an address is ever changed, system
The status word will show the latest update, which power must be cycled before the new address will
could be from any of the reporting modules using that take effect.
address.
After setting address switches, record the address
Setting Field Device Addresses number and device type.
Selection of the node address is done by setting rocker
switches on an 8 switch “DIP Switch Assembly” within
the detector’s housing. Refer to Figure 15 for switch ON
location.
1 2 3 4 5 6 7 8
WARNING BINARY
VALUE 1 2 4 8 16 32 64 128
The network address switches are located within
the detector housing. Disassembly of the detector
NODE ADDRESS EQUALS THE ADDED VALUE OPEN = OFF
head that contains powered electrical circuits is OF ALL CLOSED ROCKER SWITCHES CLOSED = ON
required to gain access to the network address A2190

switches. For hazardous areas, the area must be Figure 16—Address Switches for X5200
de-classified before attempting disassembly of the
device. Always observe precautions for handling
electrostatic sensitive devices.

9.2 14 95-8546
STARTUP PROCEDURE Table 4—Current Level Output Troubleshooting Guide

Current Level
When installation of the equipment is complete, perform Status Action
(±0.3 mA)
the “Fire Alarm Test” below.
0 mA Power Fault Check system wiring.
Fire Alarm Test 1 mA General Fault Cycle power.1
2 mA oi Fault Clean windows.2
1. Disable any extinguishing equipment that is
connected to the system. 4 mA Normal Operation
2. Apply input power to the system. Remove IR source or
Hi Background IR
8 mA aim detector away
3. Initiate an oi test. (See “Magnetic oi / Manual oi” (IR pre-alarm)
from IR source.
under Optical Integrity in the Description section of Remove UV source
this manual. Hi Background UV
12 mA or aim detector away
(UV alarm)
from UV source.
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting” Remove IR source or
Hi Background IR
section. 14 mA aim detector away
(IR alarm)
from IR source.
5. Verify that all detectors in the system are properly UV and IR sensors If no fire exists, remove
aimed at the area to be protected. (The Det-Tronics in pre-alarm, or one UV and IR sources
16 mA
Q1201C Laser Aimer is recommended for this in alarm and the or aim detector away
purpose.) other in pre-alarm. from sources.

6. Enable extinguishing equipment when the test is 20 mA Fire Alarm


complete.
1If fault continues, return device to factory for repair.
2See “Maintenance” section for cleaning procedure.

TROUBLESHOOTING

Warning 6. If all wiring checks out and cleaning of the oi plate/


The sensor module (“front” half of the detector) window did not correct the fault condition, check
contains no user serviceable components for high levels of background UV or IR radiation by
and should never be opened. The terminal covering the detector with the factory supplied cover
compartment is the only part of the enclosure that or aluminum foil. If the fault condition clears, extreme
should be opened by the user in the field. background UV or IR radiation is present. Re-adjust
the view of the detector away from the UV or IR
1. Disable any extinguishing equipment that is source or relocate the detector.
connected to the unit.
If none of these actions corrects the problem, return the
2. Inspect the viewing windows for contamination and detector to the factory for repair.
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning NOTE
of the detector viewing windows.) It is highly recommended that a complete spare
3. Check input power to the unit. be kept on hand for field replacement to ensure
continuous protection.
4. If the fire system has a logging function, check the
fire panel log for output status information. See Table
4 for information regarding 0 to 20 mA output.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.

9.2 15 95-8546
MAINTENANCE LOOSEN TWO CAPTIVE SCREWS

IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.

Warning GRASP VISOR AND


REMOVE oi PLATE
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that C2135

should be opened by the user in the field.


Figure 17—oi Plate Removal
NOTE
Refer to the X5200 Safety Manual 95-8672 for
specific requirements and recommendations 2. Clean the viewing windows and reflective surfaces
applicable to the proper installation, operation, of the oi plate using a clean cloth, cotton swab or
and maintenance of all SIL-Certified X5200 flame tissue, and Det-Tronics window cleaning solution.
detectors. Use Isopropyl alcohol for contaminations that the
Det-Tronics window cleaning solution can not
To maintain maximum sensitivity and false alarm remove. If a fault condition is still indicated after
resistance, the viewing windows of the X5200 must be cleaning, remove and clean the oi plate using the oi
kept relatively clean. Refer to the following procedure for Plate Removal and Replacement procedure.
cleaning instructions.
Important
When used in extreme environments, the reflective
Cleaning PROCEDURE
surface of the detector oi plate may eventually
deteriorate, resulting in reoccurring oi faults and
CAUTION
the need for oi plate replacement.
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
oi plate Removal and replacement
1. Disable any extinguishing equipment that is
To clean the windows and oi plate, use Det-Tronics connected to the unit.
window cleaner (part number 001680-001) and a soft
cloth, cotton swab or tissue and refer to the following 2. Loosen the two captive screws, then grasp the oi
procedure: plate by the visor and remove it from the detector.
See Figure 17.
1. Disable any extinguishing equipment that is 3. Install the new (or cleaned) oi plate.
connected to the unit.
4. Re-calibrate the detector's oi system.
NOTE
Remove input power when cleaning the detector Caution
windows. The rubbing motion on the surface of Do not replace the oi reflector plate without also
the windows during cleaning can create static recalibrating the oi system.
electricity that could result in unwanted output
activation. Recalibration of the oi system requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.

Refer to the Inspector Monitor manual, 95-8581, for


instructions regarding oi plate replacement and oi
system recalibration.

9.2 16 95-8546
PERIODIC CHECKOUT PROCEDURE FEATURES
A checkout of the system using the manual or magnetic
• Responds to a fire in the presence of modulated
oi feature should be performed on a regularly scheduled
blackbody radiation (i.e. heaters, ovens, turbines)
basis to ensure that the system is operating properly.
without false alarm.
To test the system, perform the “Fire Alarm Test” as
described in the “Startup Procedure” section of this • High speed capability.
manual. • Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms).
Clock Battery
• Microprocessor controlled heated optics for
The real time clock has a backup battery that will operate increased resistance to moisture and ice.
the clock with no external power for nominally 10 years.
It is recommended that the battery be replaced every • Automatic, manual or magnetic optical integrity (oi)
7 years. Return the device to the factory for battery testing.
replacement. • Easily replaceable oi plate.

NOTE • Fire, fault and auxiliary relays standard.


If the backup battery is depleted, there is no effect • 0 to 20 mA isolated output (optional).
on the operation of the flame detector, but the time
• Eagle Quantum Premier LON/SLC output (optional).
stamping of the data log may be affected.
• A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions.
• Operates under adverse weather conditions.
• Mounting swivel allows easy sighting.
• Integral wiring compartment for ease of installation.
• Explosion-proof/flame-proof detector housing. Meets
FM, CSA, ATEX and CE certification requirements.
• Class A wiring per NFPA-72.
• Meets NFPA-33 response requirement for under
0.5 second (available when model selected).
• 3 year warranty.
• Advanced signal processing (ARC/TDSA).
• RFI and EMC Directive compliant.

Associated MANUALS
List of X5200 related manuals:
TITLE FORM NUMBER
Pulse 95-8547
EQP 95-8533
SIL 2 (Safety) 95-8672
HART Addendum 95-8636

9.2 17 95-8546
SPECIFICATIONS 100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.

OPERATING VOLTAGE— VIEWING ANGLE

24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum). 0∞


15∞ 15∞
Maximum ripple is 2 volts peak-to-peak. 100

30∞ 90 30∞
POWER CONSUMPTION—
80
Without heater: 2.8 watts at 24 Vdc nominal; 45∞ 45∞
4.8 watts at 24 Vdc in alarm. 70

3.1 watts at 30 Vdc nominal; 60

5.4 watts at 30 Vdc in alarm. DETECTION 50


Heater only: 8 watts maximum. DISTANCE
(PERCENT) 40
Total power: 17.5 watts at 30 Vdc with EOL resistor
installed and heater on maximum. 30

EOL resistor must be ceramic, wirewound type, rated 20

5 watts minimum, with actual power dissipation not to 10


exceed 2.5 watts.
A1288
For HART models, refer to Addendum number 95-8636.
Figure 18—Detector Cone of Vision
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds. CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
OUTPUT RELAYS—
maximum loop resistance of 500 ohms from 18 to
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts, LON Output—
normally de-energized operation, and latching or Digital communication, transformer isolated (78.5 kbps).
non-latching operation.
TEMPERATURE RANGE—
Fault relay, Form A, 5 amperes at 30 Vdc: Operating: –40°F to +167°F (–40°C to +75°C).
The Fault relay has redundant terminals and Storage: –67°F to +185°F (–55°C to +85°C).
normally open contacts, normally energized Hazardous location ratings from –55°C to +75°C available
operation, and latching or non-latching operation. on flameproof model.
Auxiliary relay, Form C, 5 amperes at 30 Vdc: HUMIDITY RANGE—
The auxiliary relay has normally open / normally 0 to 95% relative humidity, can withstand 100%
closed contacts, normally energized or condensing humidity for short periods of time.
de-energized operation, and latching or non-
latching operation.

4.7
(11.9)

10.2 4.8
B2223
(25.9) (12.2)

Figure 19—Dimensions in Inches (cm)

9.2 18 95-8546
CONE OF VISION— Thread SIZE—
The detector has a 90° cone of vision (horizontal) with Conduit connection: Four entries, 3/4 inch NPT or M25.
the highest sensitivity lying along the central axis. Conduit seal not required.
See Figure 18.
SHIPPING WEIGHT (Approximate)—
RESPONSE TIME— Aluminum: 6 pounds (2.75 kilograms).
32 inch methane plume: < 10 seconds. Stainless Steel: 10 pounds (4.5 kilograms).
1 foot x 1 foot n-Heptane: < 15 seconds. Swivel Mount (AL): 6 pounds (2.75 kilograms).
(See Appendix A for details.) Swivel Mount (SS): 14 pounds (6.4 kilograms).

ENCLOSURE MATERIAL— WARRANTY PERIOD—


Copper-free aluminum (painted) or 316 stainless steel. 3 years.

Vibration— Certification—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
FM ® VdS
DIMENSIONS—
APPROVED

See Figure 19.


For complete approval details, refer to the appropriate
WIRING— Appendix:
Field wiring screw terminals are UL/CSA rated for up to Appendix A - FM
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire. Appendix B - CSA
Screw terminal required torque range is 3.5–4.4 in.-lbs. Appendix C - ATEX/CE
(0.4-0.5 N·m). Appendix D - IECEx
14 AWG (2.08 mm2) or 16 AWG (1.31 mm2) shielded Appendix E - VdS.
cable is recommended.
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C and
above +60°C use field wiring suitable for both minimum
and maximum ambient temperature.

9.2 19 95-8546
replacement parts ORDERING INFORMATION
The detector is not designed to be repaired in the field. When ordering, please specify:
If a problem should develop, refer to the Troubleshooting X5200 UVIR Flame Detector
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the Refer to the X5200 Model Matrix below for details
factory for repair. Q9033 mount is required:

Q9033A for aluminum detectors only.


DEVICE REPAIR AND RETURN Q9033B for aluminum and stainless steel detectors.

Prior to returning devices, contact the nearest local X-Series Flame Detector Accessories
Detector Electronics office so that a Return Material
Part Number Description
Identification (RMI) number can be assigned. A 000511-029 Converter RS485 to RS232
written statement describing the malfunction must W6300B1002 Serial Inspector Connector
007819-001
accompany the returned device or component to (Inspector Monitor software included)
assist and expedite finding the root cause of the 007819-002
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
failure. 009207-001 Flame Inspector Monitor CD
103922-001 Model 475 HART Communicator
Pack the unit properly. Always use sufficient packing 102740-002 Magnet
material. Where applicable, use an antistatic bag as 007739-001 Magnet and Extension Pole
oi Replacement kit for X3301 (5 Black reflector plates)
protection from electrostatic discharge. 009208-001
with Inspector Connector and Monitor
oi Replacement kit for X3301 (5 Stainless Steel reflector plates)
010831-001
note with Inspector Connector and Monitor

Det-Tronics reserves the right to apply a service oi Replacement kit for X3302 (5 Black reflector plates)
009208-003
with Inspector Connector and Monitor
charge for repairing returned product damaged as oi Replacement kit for X3302 (5 Stainless Steel reflector plates)
010831-002
a result of improper packaging. with Inspector Connector and Monitor
oi Replacement kit for X52/X22/X98 (5 reflector plates)
009208-002
with Inspector Connector and Monitor
Return all equipment transportation prepaid to the factory Replacement oi reflector plate for X3301 with Black plate
007307-001
in Minneapolis. (requires inspector connector to calibrate)
Replacement oi reflector plate for X3301 with Stainless Steel
010830-001
plate (requires inspector connector to calibrate)
NOTE Replacement oi reflector plate for X3302 with Black plate
007307-003
It is highly recommended that a complete spare (requires inspector connector to calibrate)
be kept on hand for field replacement to ensure 010830-002
Replacement oi reflector plate for X3302 with Stainless Steel
plate (requires inspector connector to calibrate)
continuous protection. Replacement oi reflector plate for X52/X22/X98
007307-002
(requires inspector connector to calibrate)
007240-001 Q1116A1001, Air Shield (AL)
007818-001 Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
007818-002 Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
009177-001 Q1120A1001 Paint shield mounting ring (AL)
009199-001 Q1198A1001 Dual Air Shield/Flange Mount (X9800 only)/(AL)
006097-001 Q1201 Laser
102871-001 Laser Battery, 3V Lithium (laser)
007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic)
007338-001 Q2000A1001 X-Series Weather Shield (AL)
007338-010 Q2033A10R X3301/X3302 FOV Limiter 10° (AL)
007338-020 Q2033A20R X3301/X3302 FOV Limiter 20° (AL)
007338-030 Q2033A30R X3301/X3302 FOV Limiter 30° (AL)
007912-010 Spare Restrictor Plate 10° (AL)
007912-020 Spare Restrictor Plate 20° (AL)
007912-030 Spare Restrictor Plate 30° (AL)
Q9033B Stainless Steel Swivel Mount Assembly is for
007290-001
aluminum and stainless steel detectors
Q9033A Aluminum Swivel Mount Assembly is for aluminum
007290-002
detectors only
101197-003 Stop Plug, SS, IP66, Ex d e, M25 (SS)
103517-001 Stop Plug, AL, IP66, Ex d e, M25 (AL)
103363-001 14 mm Hex Wrench (Steel)
103406-001 Screwdriver
107427-040 O-ring - Rear Cover (Viton)
005003-001 1 oz grease for detectors (non-silicon)
001680-001 Window cleaner (6 pack)

9.2 20 95-8546
X5200 MODEL MATRIX
MODEL DESCRIPTION
X5200 UV/IR Flame Detector
X5200M UV/IR Flame Detector with Molybdenum Tube
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
4M 4 PORT, METRIC M25
4N 4 PORT, 3/4" NPT
TYPE OUTPUTS
11 Relay
13 Relay and 4-20 mA
14 Eagle Quantum Premier (EQP)
15 Relay and Pulse
16 Addressable Module Only (Third Party Type)*
23 HART, Relay and 4-20 mA
24 Eagle Quantum
TYPE APPROVAL AGENCY
W FM/CSA/ATEX/CE/IECEx
TYPE CLASSIFICATION**
1 Division/Zone Ex d e
2 Division/Zone Ex d
*The Addressable Module Only (Type 16) is not FM approved.
**Detectors are always Class I, Div. 1.

9.2 21 95-8546
APPENDIX A
FM Approval and Performance Report

THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:

• Explosion-proof for Class I, Div. 1, Groups B, C and D (T5) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T5) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).

The following performance criteria were verified:

AUTOMATIC OPTICAL INTEGRITY TEST:


The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic Optical Integrity (oi) test for each sensor. Upon removal of the contamination, the detector fault was cleared
and the detector was verified to detect a fire.

MANUAL OPTICAL INTEGRITY TEST:


The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.

The Optical Integrity test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual,
is the approved external optical test method for this detector to verify end-to-end detector function. This test replaces
the function and need of a traditional external test lamp.

RESPONSE CHARACTERISTICS
High Sensitivity UV & IR, Hi Arc, TDSA On, Quick Fire Off
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
n-Heptane 1 x 1 foot 50 (15.2) 7
Methane 32 inch plume 35 (10.7) 3.5

High Sensitivity UV & IR, Very Hi Arc, TDSA On, Quick Fire Off
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
n-Heptane 1 x 1 foot 50 (15.2) 8

9.2 22 95-8546
FM Approval and Performance Report – Continued

High Sensitivity UV & IR, Very Hi Arc, TDSA On, Quick Fire On
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
n-Heptane 1 x 1 foot 50 (15.2) 8

High Sensitivity UV, Low Sens. IR, Hi Arc, TDSA On, Quick Fire Off
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
n-Heptane 1 x 1 foot 15 (4.6) 9

High Sensitivity UV, Very High Sens. IR, Arc Off, TDSA On, Quick Fire On
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
Methane 32 inch plume 15 (4.6) 0.12

High Sensitivity UV, Very High Sens. IR, Hi Arc, TDSA On, Quick Fire On
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
Methane 32 inch plume 15 (4.6) 0.3

Very High Sensitivity UV & IR, Low Arc, TDSA On, Quick Fire On
Distance Typical Response Time
Fuel Size feet (m) (seconds)*
n-Heptane 1 x 1 foot 85 (25.9) 14
Methane 32 inch plume 65 (19.8) 5

High Sensitivity UV, Very High Sensitivity IR, Hi Arc, TDSA On, Quick Fire Off
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
n-Heptane 1 x 1 foot 60 (18.3) 6
Methane 32 inch plume 65 (19.8) 9

Medium Sensitivity UV, High Sensitivity IR, Hi Arc, TDSA On, Quick Fire On
Distance Typical Response Time
Fuel Size
feet (m) (seconds)*
n-Heptane 1 x 1 foot 50 (15.2) 5
Methane 32 inch plume 60 (18.3) 5
*Add 2 seconds for EQP Model.

9.2 23 95-8546
FM Approval and Performance Report – Continued

RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES


High Sensitivity, Hi Arc, TDSA On, Quick Fire Off
Distance Distance Average Response Time
False Alarm Source Fire Source
feet (m) feet (m) (seconds)*
Sunlight, direct, modulated/unmodulated — 2 inch dia Heptane 10 (3) < 30
Sunlight, reflected, modulated/unmodulated — 2 inch dia Heptane 10 (3) < 30
70 w sodium vapor lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3
70 w sodium vapor lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3
250 w mercury vapor lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 2
250 w mercury vapor lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3
300 w incandescent lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 4
300 w incandescent lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 3
500 w shielded quartz halogen lamp, unmodulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 2
500 w shielded quartz halogen lamp, modulated 5 (1.5) 2 inch dia Heptane 5 (1.5) 2
1500 w electric quartz heater, unmodulated 10 (3) 2 inch dia Heptane 5 (1.5) 3
1500 w electric quartz heater, modulated 10 (3) 2 inch dia Heptane 3 (0.9) 11
Two 34 w fluorescent lamps, unmodulated 3 (0.9) 2 inch dia Heptane 10 (3) 3
Two 34 w fluorescent lamps, modulated 3 (0.9) 2 inch dia Heptane 10 (3) 5
Arc welding 15 (4.6) 2 inch dia Heptane 5 (1.5) N/A
*Add 2 seconds for EQP Model.

FALSE ALARM IMMUNITY


High Sensitivity, Hi Arc, TDSA On, Quick Fire Off
Distance
False Alarm Source Modulated Response Unmodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Vibration N/A No alarm No alarm
Arc welding 15 (4.6) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w mercury vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w shielded quartz halogen lamp 3 (0.9) No alarm No alarm
1500 w electric quartz heater 10 (3) No alarm No alarm
Two 34 w fluorescent lamps 3 (0.9) No alarm No alarm

9.2 24 95-8546
FM Approval and Performance Report – Continued

FIELD of view
High Sensitivity UV & IR, Hi Arc, TDSA On, Quick Fire Off
Distance Horizontal Typical Horz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds)* (degrees) Time (seconds)*
25 +45 5 +45 4
n-Heptane 1 x 1 foot
(7.6) –45 8 –30 8
17.5 +45 3 +45 4
Methane 32 inch plume
(5.3) –45 4 –30 4

High Sensitivity UV & IR, Very Hi Arc, TDSA On, Quick Fire On
Distance Horizontal Typical Horz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds)* (degrees) Time (seconds)*
25 +45 12 +45 13
n-Heptane 1 x 1 foot
(7.6) –45 9 –30 6

High Sensitivity UV, Low Sensitivity IR, Hi Arc, TDSA On, Quick Fire Off
Distance Horizontal Typical Horz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds)* (degrees) Time (seconds)*
7.5 +45 6 +45 9
n-Heptane 1 x 1 foot
(2.2) –45 6 –30 6

High Sensitivity UV, Very High Sensitivity IR, Arc Off, TDSA On, Quick Fire On
Distance Horizontal Typical Horz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds)* (degrees) Time (seconds)*
7.5 +45 0.9 +45 0.1
Methane 32 inch plume
(2.2) –45 0.2 –30 0.1

Very High Sensitivity UV & IR, Low Arc, TDSA On, Quick Fire On
Distance Horizontal Typical Horz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds)* (degrees) Time (seconds)*
42.5 +45 12 +45 11
n-Heptane 1 x 1 foot
(13) –45 14 –30 13
32.5 +45 5 +45 6
Methane 32 inch plume
(9.9) –45 7 –30 6

High Sensitivity UV, Very High Sensitivity IR, Hi Arc, TDSA On, Quick Fire Off
Distance Horizontal Typical Horz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds)* (degrees) Time (seconds)*
30 +45 8 +45 10
n-Heptane 1 x 1 foot
(9.1) –45 8 –30 7
32.5 +45 4 +45 5
Methane 32 inch plume
(9.9) –45 5 –30 5

Medium Sensitivity UV, High Sensitivity IR, Hi Arc, TDSA On, Quick Fire On
Distance Horizontal Typical Horz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds)* (degrees) Time (seconds)*
25 +45 15 +45 7
n-Heptane 1 x 1 foot
(7.6) –45 7 –30 9
30 +45 8 +45 8
Methane 32 inch plume
(9.1) –45 6 –30 12
*Add 2 seconds for EQP Model.

9.2 25 95-8546
FM Approval and Performance Report – Continued

MODEL X5200M
The X5200M uses a sensor that has a broader spectrum than the standard sensor. It is designed to detect fires with
unusual chemistry such as black powder and sulphur fires. Consult factory for usage recommendations.

X5200M RESPONSE CHARACTERISTICS


High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Distance Typical Response Time
Fuel Size
feet (m) (seconds)
Black Powder 40 grams 10 (3) 0.12

X5200M RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARMS


High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Distance Distance Typical Response Time
False Alarm Source Fire Source
feet (m) feet (m) (seconds)
Sunlight, direct, reflected, modulated & unmodulated — 2 inch dia Heptane 10 (3) < 15
70 w sodium vapor lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 5
70 w sodium vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) <1
250 w vapor lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 11
250 w vapor lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) <1
300 w incandescent lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 7
300 w incandescent lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 6
500 w halogen lamp, unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) <1
500 w halogen lamp, modulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 11
1500 w electric radiant heater, unmodulated 10 (3) 1 x 1 foot n-Heptane 40 (12) <1
1500 w electric radiant heater, modulated 10 (3) 1 x 1 foot n-Heptane 40 (12) <1
2-34 w fluorescent lamps , unmodulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) 15
2-34 w fluorescent lamps , modulated 3 (0.9) 1 x 1 foot n-Heptane 40 (12) <1

X5200M FALSE ALARM IMMUNITY


High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Distance
False Alarm Source Modulated Response Unodulated Response
feet (m)
Sunlight, direct, reflected — No alarm No alarm
Arc welding 15 (4.6) No alarm No alarm
70 w sodium vapor lamp 3 (0.9) No alarm No alarm
250 w vapor lamp 3 (0.9) No alarm No alarm
300 w incandescent lamp 3 (0.9) No alarm No alarm
500 w halogen lamp 3 (0.9) No alarm No alarm
1500 w electric radiant heater 3 (0.9) No alarm No alarm
2-34 w fluorescent lamps 3 (0.9) No alarm No alarm

X5200M FIELD of view


High Sensitivity UV & IR, Arc Off, TDSA On, Quick Fire On
Distance Horizontal Typical Horz. Response Vertical Typical Horz. Response
Fuel Size
feet (m) (degrees) Time (seconds) (degrees) Time (seconds)
5 +45 0.1 +45 0.1
Black Powder 40 grams
(1.5) –45 0.1 –30 0.1

9.2 26 95-8546
APPENDIX B
CSA Approval

PRODUCTS
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T5); Class II, Division 1, Groups E, F, and G (T5);
Class I, Division 2, Groups A, B, C, and D (T3); Class II, Division 2, Groups F and G (T3);
Class III; Enclosure Type 4X;

Ultraviolet Infrared Flame Detector/Controller X5200 series, rated 18-30 Vdc, 2.8 Watts to 17.5 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.

9.2 27 95-8546
APPENDIX C
ATEX / CE Approval

EC-TYPE EXAMINATION CERTIFICATE


DEMKO 02 ATEX 132195X
Increased Safety Model Flameproof Model
0539 II 2 G 0539 II 2 G
II 2 D II 2 D
FM ® FM ®
APPROVED APPROVED

Ex d e IIC T5–T6 Gb Ex d IIC T5–T6 Gb


Ex tb IIIC T80°C Ex tb IIIC T80°C
T6 (Tamb –50°C to +60°C) T6 (Tamb –55°C to +60°C)
T5 (Tamb –50°C to +75°C) T5 (Tamb –55°C to +75°C)
IP66/IP67. IP66/IP67.

Compliance with:
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-31: 2009
EN / IEC 60529: 2001.

Installation instructions
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring diameter from 14 AWG
(2.08 mm2) to 22 AWG (0.33 mm2).

The flame detector model X5200UVIR shall be installed according to the instructions given by the manufacturer.

The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They
shall be IP66 rated, suitable for the conditions of use and correctly installed.

Unused entries shall be closed with suitable certified blanking elements.

The metal housing for the Ultraviolet Infrared (UVIR) flame detector type X5200 must be electrically connected to
earth ground.

For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.

Special conditions for safe use:


The EOL resistor can only be used within the flameproof terminal compartment.

EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed
2.5 watts.

The Ultraviolet Infrared (UVIR) flame detector type X5200 is to be installed in places where there is a low risk of
mechanical damage.

9.2 28 95-8546
NOTE
Operational performance verified from –40°C to +75°C.

note
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.

NOTE
Refer to “EOL Resistors” section for installation details. All cable entry devices and blanking elements shall be
certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or flameproof
enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66 for the apparatus. Unused apertures shall be closed with suitable blanking
elements.

Note
For ATEX installations, the X5200 detector housing must be electrically connected to earth ground.

9.2 29 95-8546
APPENDIX D
IECEx Approval

IECEx Certificate of Conformity


DEMKO
IECEx ULD 06.0018X
Ex d e IIC T5-T6 Gb Ex d IIC T4-T6 Gb
T6 (Tamb =–50°C to +60°C) or T6 (Tamb =–55°C to +60°C)
T5 (Tamb =–50°C to +75°C) T5 (Tamb =–55°C to +75°C)
IP66. IP66.

Compliance with:
IEC 60079-0: 2007
IEC 60079-1: 2007
IEC 60079-7: 2006
EN / IEC 60529: 2001.

Installation instructions
The field wiring connections in the terminal compartment are suitably certified and accepts wiring diameter from 14
AWG (2.08 mm2) to 22 AWG (0.33 mm2).

The flame detector model X5200UVIR shall be installed according to the instructions given by the manufacturer.

The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They
shall be IP66 rated, suitable for the conditions of use and correctly installed.

Unused entries shall be closed with suitable certified blanking elements.

The metal housing for the Ultraviolet Infrared (UVIR) flame detector type X5200 must be electrically connected to
earth ground.

For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.

Special conditions for safe use:


The EOL resistor can only be used within the flameproof terminal compartment.

EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed
2.5 watts.

The Ultraviolet Infrared (UVIR) flame detector type X5200 is to be installed in places where there is a low risk of
mechanical damage.

9.2 30 95-8546
APPENDIX E
VdS Schadenverhütung GmbH Approval

VdS
Performance per EN54-10,
Certificate of Approval G-203085.

EC-Certificate of Conformity
09 0786 – CPD – 20778
EN54-10 Flame detectors - Point detectors.

SUBJECT MATTER OF THE APPROVAL


UVIR Flame Detector Type X5200 for use in Automatic Fire Detection and Fire Alarm Systems.

BASIS OF APPROVAL
DIN EN 54, Part 10 (05/02) - Flame Detectors.

Instructions for the application of the approval component/system


The installation shall take into account, that the orientation arrow on the flame detector is directed upwards, as the view
angle in this direction is <90°.

The UVIR-flame detector corresponds to class 1.

9.2 31 95-8546
95-8546

­Detector Electronics Corporation


6901 West 110th Street
Minneapolis, MN 55438 USA

T: 952.941.5665 or 800.765.3473
F: 952.829.8750
W: http://www.det-tronics.com
X3301 Multispectrum PointWatch Eclipse® FlexVu® Universal Display Eagle Quantum Premier®
IR Flame Detector IR Combustible Gas Detector w/ GT3000 Toxic Gas Detector Safety System E: det-tronics@det-tronics.com

Det-Tronics, the DET-TRONICS logo, Protect•IR, and Automatic Optical Integrity (oi) are registered trademarks or trademarks of Detector Electronics
Corporation in the United States, other countries, or both. Other company, product, or service names may be trademarks or service marks of others.

© Copyright Detector Electronics Corporation 2011. All rights reserved

You might also like