Choice 12345
Choice 12345
Choice 12345
95
Time Domain
Reflectometers -
Applications
WWW.MEGGER.COM
As shown in Figure 2, the reflections are translated by the TDR to traces which can
be interpreted to indicate that certain “events” such as opens, shorts, splices, etc.
are in the cable. But all traces follow these two basic rules stated above and are
displayed on a TDR as shown in Figures 2 and 3.
VOP=0.670 519.1 ft
Cursor
LESS MORE
CABLE CABLE ZOOM SETUP
VOP=0.670 519.1 ft
Cursor
LESS MORE
CABLE CABLE ZOOM SETUP
Knowing that these events are in the cable is beneficial but to be really helpful, we
need to know WHERE they are in the cable. Above, we discussed that a TDR sends
pulses along the cable that are reflected back when they hit a change in impedance.
The TDR times how long it takes for the reflections to get back to the unit. It knows
how long the pulse has been gone and how long it has been travelling. TDRs are
like an arithmetic word problem that asks “if you leave Chicago and travel for two
and a half hours at 50 miles an hour, how far have you gone?” Because the TDR
knows how long the pulse has been gone, if we could tell it how fast these pulses
and their reflections travel along the cable, it would be able to calculate the distance
from the TDR to the impedance change. We are able to do this. But to complicate it,
the TDR’s pulse travels at different speeds in different types of cables.
n Twisted pair
n 22 gauge filled – 0.66
n 22 gauge air-core – 0.67
n 24 gauge filled – 0.62
n 24 gauge air-core – 0.67
If we can see the length markings or measure it to get the length of a section of
cable, we can work backwards with a TDR and calculate the VoP. (This gets a bit
tricky with twisted pair because the conductors are longer than the cable.)
The TDR now has enough information to calculate where the “event” is. Like our
trip from Chicago, it knows how long the pulse and its reflection travelled and it
knows how fast that pulse was going. The TDR merely has to do the arithmetic, a
LOT of arithmetic.
Does it matter if the event that we are trying to find is very close to the TDR, or far
away? It sure does. We can “look” along the entire distance of a very long cable
by varying the power, the “width”, of the pulses that the TDR sends out. This is the
amount of time that the transmitter is turned on.
We “set” the pulse width. TDRs have varying pulse width settings and modern
units, while allowing the operator to vary the pulse width, will automatically set the
proper pulse width to best display the first event. The larger the pulse width, the
more energy and, therefore, the further the signal will travel on a given cable. A
TDR’s distance range is determined by how far the transmitted pulse will travel while
still having a detectable reflection returned.
<1 ns 1 foot
One billionth
2 ns 3 feet
10 ns 14 feet
100 ns 55 feet
1 µs 430 feet
One millionth
2 µs 810 feet
4 µs 1,600 feet
We not only have to worry about blind spots at launch (right next to the TDR) but
the reflections of events also have blind spots, the size of which are related to the
pulse width. The second of two closely-spaced reflections may become masked by
the dead zone of the first one.
We’ll consider later what the shape of a trace tells us about an event but for now
accept that the signatures displayed in Figure 5 show a twisted pair cable of 3,000
foot length with a splice at 2,000 feet. Signature 1 used a pulse width of 160 ns.
Signature 2 used a pulse width of 500 ns and signature 3 used a pulse width of
2 µs. Notice the lengths of the launch dead zones. Also consider the dead zones
following the splice. If the splice were a short bridged tap, we wouldn’t see the end
of the lateral if we used the 500 ns pulse width.
500 ns
2 µs
Gain is another variable that we can set that needs consideration. Gain has nothing
to do with the physics of what the TDR is doing. Rather, it is a way for us to adjust
the trace that the TDR is showing us. It is the degree to which the trace deviates
from the horizontal. Remember that a TDR shows us events in a cable that cause the
impedance to change at that spot. Consider also that elements that are placed in
the cable are meant to exactly match the impedance of that cable so as to minimize
the very reflection that the TDR depends on. So, elements such as well-made splices
and terminations are, by design, hard for a TDR to see. Modern TDRs adjust the
display such that they try to show the trace of the most prominent element. To do
this they automatically adjust the gain of the display to nicely show, for example, a
major event such as an open. This is all well and good if what we want to see is the
open. But, what if we really wanted to see a well-made splice that was somewhere
before the open? The impedance mismatch at the open is much more than that at
In the real world, when water causes a problem in the cable, it takes place
over a long period of time. Also, the water by itself is not the problem. It is the
contamination (for example, salt from the ground and air) that the water is carrying
that causes the problem. To simulate the water-in-the-cable problem, make a hole
in the cable and immerse the cable in water. To simulate the salts in the ground or
air and to speed up the cable deterioration process, simply add some common table
salt to the water. Now, using the TDR, it is possible to see what water in the cable
really looks like.
Another example of modeling a field problem in the shop is to test across the pair
with an ohmmeter. A reading of less than 100 K Ohms indicates a bad pair. A TDR
connected to this pair will usually find the problem. However, if you try to simulate
this problem in the shop by simply connecting a 100 K Ohm resistor across a pair,
the TDR will not find the 100 K Ohm resistor. Why not?
The field pair with the low resistance will also have a change in impedance caused
by moisture in the cable. The ohmmeter is looking only at the resistance; the TDR
is looking at the total cable impedance. The total cable impedance includes the
resistance, the capacitance, and the inductance. The whole cable and the whole
Basic tests are once again conducted on the pairs and the original pair now appears
quieter. This is a common problem experienced when water gets into a cable; noisy
pairs going quiet and quiet pairs becoming noisy.
A TDR will find water in the cable. It shows up as a lowering of the cable
impedance. Most times though, it is not possible to accurately tell how wide the
water problem is. In filled cable, moisture cannot migrate inside the cable so it is
always a point problem. In air-core or pulp cable, moisture can migrate anywhere
along the cable.
When testing through water, measurements up to the water are very accurate. After
the water, distance readings may be erroneous due to a change in the VF (velocity
factor) caused by the water. Even though the moisture may be 20 or 30 feet wide,
each pair usually becomes impregnated at different points. The range of these
points will indicate the length of the problem.
Water can seep into the conductors through pin holes in the plastic insulator around
the conductors. Water in a multi-paired, air-core cable may be several feet wide.
When testing each pair, the footage to the problem may read different for each
pair. This is because the water has penetrated through the conductor insulation at
different points and shorted out the conductors at different footages.
After performing TDR tests on the pairs, the location and how wide the water
damage ranges are now known. But it is still necessary to locate where the water
actually entered the cable. The break in the sheath will not necessarily be within the
span of where the water is found and will not necessarily show up in the testing. If
the break in the sheath of the cable is not fixed, the problem will show up again in
the future.
If the hole in the sheath happens to be at a high point in the cable, the water will
enter through the hole then migrate to a lower point. If the water entry point is not
found, it may be necessary to visually inspect the cable. It is also necessary to check
the integrity of the sheath.
The definition of a bridged tap itself can often cause confusion. Some people refer
to a bridged tap as the lateral which extends off of a main cable circuit. However,
the true definition of a bridged tap is the point on the cable where a lateral
connects to the main cable.
A B C D
Figure 7: Bridged Tap (example)
Referring to Figure 7, a person reviewing the waveform might assume the following:
Point B: (downward reflection) The point of a bridged tap on the main cable.
However, Figure 7 could also be the result of a somewhat different cable layout as
explained below. A common mistake that is made when testing through bridged
taps is to incorrectly identify the end of the lateral for the end of the main cable
circuit.
Figures 8a and 8b show two slightly different cable plant layouts. However, notice
that the resulting waveforms are identical.
A B D A B C
A B C D A B C D
In Figure 8a, the length of the lateral is shorter than the end of the main cable circuit.
In Figure 8b, the length of the lateral is longer than the main cable circuit.
NOTE: Do not assume the first upward reflection after a bridged tap is
always the end of the lateral; it may be the end of the cable.
It is always a good idea to refer to plant maps whenever possible to help minimize
confusion or errors when testing cable plant, especially when testing through
bridged taps.
A B A B
Using the Model CFL535F in the XTALK mode greatly enhances the reflection and
makes finding splits that are far away much easier.
A B
A B
A bridged tap on a TDR will look similar to a short or downward reflection. Keep
in mind that the TDR does not distinguish between the lateral and the continuing
length of cable. After finding and removing a lateral, make sure you retest the cable
for any laterals that may have been missed.
There are two basic rules in identifying a load coil from an open. First, a load coil
generally displays a more rounded appearance than an open. Second, load coil
spacing is very particular; at 3,000 feet (914 m) or 6,000 feet (1829 m) intervals,
depending on the location in the section. While not all load coils look the same, if
you see an open-like reflection on the waveform at approximately 6,000 feet (1829
m) from the TDR, suspect a load coil. Remember that because the TDR’s signal
cannot pass through a load coil, the first load coil is all that you will see. Once you
have found the first, remove it and retest the cable.
One of the more frustrating troubles found in outside plant today is noisy static.
Many times, the customer calls with complaints of sizzling on the line. However,
by the time the trouble ticket is received, there is no trouble found. This is because
many times, these types of troubles come and go as do the loop current on line.
When there is no loop current, the fault heals itself. As soon as you leave the
trouble, and the customer uses the line again, they report the same type of trouble
again.
To locate noisy static troubles quickly and easily with the CFL535F, do the following:
2. Confirm the trouble. Connect a butt set, turn the speaker on and listen to the
line. Confirm that the trouble you hear (if any) is what the customer reported,
and not a separate case of trouble.
3. Turn the butt set to mute, and dial the silent termination. This is done to prevent
any noise picked up by the microphone of the butt set being put on the line. It
may affect the TDR waveform.
4. Connect the CFL535F. Connect the test probe leads to the pair under test.
Continue to keep the butt set connected to the pair with the silent termination.
7. Wait for the fault to occur. With the loop current on line, the trouble will normally
appear within 5 to 10 minutes.
Cellular
The TDR can be a very useful tool when turning-up a new cell site. Within a single
cell there may be as many as six antenna cables with multiple transmit antenna
cables and multiple receive antenna cables.
During installation, it is possible that the cables can become mixed up. Installers are
usually more intent on safely making all the right mechanical connections, rather
than making sure the cables are connected to the proper antennas. On the other
hand, the site operator is very interested in the accuracy of matching cables to
antennas.
If it is necessary to see the actual waveform of the cable under test, even with the
antenna connected, simply turn the instrument on and activate the TDR’s noise
filter. It will remove most of the RF signal even in a relatively high RF energy level
environment.
Electric
Track Down Illegal Electrical Taps
Illegal taps are a huge problem for many electric companies throughout the world
because millions of dollars are lost due to theft of service. An illegal tap occurs
when an individual connects to the power cable before it reaches the meter. When
a customer connects before the meter, they bypass the meter that measures power
consumption. In the United States, and other similar networks, power is distributed
using high voltage lines to the neighborhood. The high voltage is reduced by a step
down transformer near the customer’s home. The smaller low voltage is the 110
Volts that runs most of our appliances. In most cases homes receive two phases
of 110 Volts in order to power larger appliances that run on 220 Volts. These two
phases are run with a neutral. Normally, the drop line will run directly from the
transformer to the house. However, the power company may run a feeder cable
of 110 Volts to connect a strip of houses or businesses. Either way, the cable runs
to a meter box that registers power usage for the billing process. After the meter,
the cable runs to a breaker box and then is distributed throughout the subscriber’s
home or office.
When looking for an illegal tap, focus should be placed on the drop line from the
meter to the transformer. In the case of aerial cables, focus only on the section of
cable that is not visible. This may be the cable inside the conduit, which can be
4-12 feet (1-4 meters) of cable. In the case of buried cable, lengths are often much
longer; however, the focus is still on the cable running between the meter and
To apply the TDR to the low voltage network, the user must be aware of the
network they are testing. The tee joints on this type of power network increase the
complexity of the waveform trace. The service connection tee joints reflect and split
the TDR pulse. The net effect is a complex TDR waveform trace and attenuation that
reduces the testable length. The TDR can be useful on the low voltage network, but
the user must be wary.
Isolating a fault to a section or particular run of cable will prove valuable by allowing
the operator to get closer to the fault. Although the TDR traces produced by the
low voltage network are complex, a short or open circuit can be easily visible if
the TDR is connected close to the fault. Be aware of how the fault manifests itself
and make logical conclusions based on this information. If a group of customers
The best methods for fault locating on a complex network involve a “before and
after” or “good vs. bad” comparison. A healthy TDR trace produced by the complex
network shows many reflections caused by the service connection taps and the ends
of these cables. Even a gross fault down the network will be masked by the other
features of the network. In many cases, comparison and differential techniques are
the only option.
Although not quite as definitive as a before and after trace in which the fault has
changed because of an action, comparison to a good phase can also indicate a fault
location. Again, the process is to store a good trace of another phase in the cable as
a reference in order to compare the faulty trace.
Figure 12 shows an example of where an open circuit fault is located on the yellow
phase. The blue phase is chosen arbitrarily as common. A TDR trace is stored
between the red and blue phases (good) and compared to a TDR trace between
the blue and yellow phase (bad). A point of significant difference is most likely the
fault location. With this procedure, keep in mind the two traces will not necessarily
be identical as will be the case with a before and after test of the same cable.
Differences in service connection joint locations and lengths may add minor different
features on the TDR trace which are not the fault.
Outside Broadcasting
Outside broadcast vehicles carry an enormous amount of cables depending on
the situation; e.g., sporting events can use ten or more different camera locations.
Due to the temporary nature of the installation, cables get damaged and TDRs are
extensively used to quickly find the faults as they can work on all different types of
cable without re-calibration; i.e., from power cables to coax to twisted pair, all of
which are in use in an outside broadcast. In outside broadcasting, the camera cables
in particular, usually triax construction, are vulnerable. On large sites, e.g. race tracks
and golf courses, many drums of cable will be linked together to reach some of the
cameras.
Megger CFL510G
This hand-held TDR is designed to test virtually all types of
cable and provide the user with the ability to perform fault
diagnosis. The unit offers multiple ranges from 0-30 ft to
15,000 ft.
Megger TDR500/3
The Megger TDR500/3 breaks new ground as a cost-effective,
high specification hand-held time domain reflectometer
for locating faults on metallic cables. Designed for the field
engineer requiring a low cost solution to field testing, the
TDR500/3 offers all the benefits of Megger quality and reliability
in an affordable package.
Megger TDR900
The Megger TDR900 is an advanced instrument capable of
measuring cable lengths and finding distance to an open or
a short using time domain reflectometry. It offers exceptional
features and a range capability normally associated with far
more expensive instruments. The measurement range spans
from 15 feet (5 m) to 10,000 feet (3 km) with a minimum
resolution of 20 inches (50 cm).
TDR_AG_en_V01