MWPA404 Cathodic Protection Guideline Rev 0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

 

 
 

MID WEST PORTS 
TECHNICAL GUIDELINE 
MWPA404 – CATHODIC PROTECTION GUIDELINE 
 

UNCONTROLLED WHEN PRINTED 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Version  Revision dated  Details  Prepared by  Authorised by 
Draft  28/08/2015  Draft  SMEC   
Rev 0  05/09/2017  Document approved for use  SMEC  P. Blundell 
 

UNCONTROLLED WHEN PRINTED 
MWPA404 – Cathodic Protection Guideline 

 
 
 
CONTENTS 
1.  PREFACE ...................................................................................................................................... 1 
2.  SCOPE .......................................................................................................................................... 2 
2.1.  GENERAL ................................................................................................................................. 2 
2.2.  EXCLUSIONS ............................................................................................................................ 2 
3.  GLOSSARY .................................................................................................................................... 3 
4.  RELEVANT DOCUMENTATION ..................................................................................................... 7 
4.1.  GUIDELINE SERIES ................................................................................................................... 7 
4.2.  MID WEST PORTS POLICIES AND PROCEDURES ...................................................................... 7 
4.3.  LOCAL, STATE AND FEDERAL STATUTORY REQUIREMENTS ................................................... 7 
4.4.  AUSTRALIAN STANDARDS AND DESIGN CODES ...................................................................... 8 
4.4.1.  AUSTRALIAN STANDARDS AND DESIGN CODES .............................................................. 8 
4.5.  INTERNATIONAL STANDARDS ................................................................................................. 8 
4.5.1.  INTERNATIONAL STANDARDS AND DESIGN CODES ........................................................ 8 
4.6.  ADDITIONAL REFERENCES ....................................................................................................... 9 
4.7.  PRECEDENCE ......................................................................................................................... 10 
5.  ASSETS REQUIRING CATHODIC PROTECTION ........................................................................... 11 
5.1.  GENERAL ............................................................................................................................... 11 
5.2.  DESIGN PHILOSOPHY ............................................................................................................ 11 
6.  COMPETENCE OF PERSONNEL .................................................................................................. 13 
6.1.  GENERAL ............................................................................................................................... 13 
6.2.  IMPRESSED CURRENT SYSTEM SPECIFIC REQUIREMENTS .................................................... 13 
7.  DESIGN OBJECTIVES .................................................................................................................. 14 
7.1.  GENERAL ............................................................................................................................... 14 
7.2.  DESIGN PARAMETERS ........................................................................................................... 14 
7.3.  CATHODIC PROTECTION CRITERIA ........................................................................................ 14 
7.4.  ELECTRICAL CURRENT DEMANDS ......................................................................................... 15 
7.5.  COATING BREAK DOWN FACTORS ........................................................................................ 17 
7.6.  CONSIDERATIONS WHEN CHOOSING CATHODIC PROTECTION SYSTEMS ............................ 18 
7.7.  ELECTRICAL CONTINUITY ...................................................................................................... 19 
7.8.  STRAY CURRENT AND OTHER INTERACTIONS ....................................................................... 19 
8.  GALVANIC ANODE SYSTEMS ..................................................................................................... 20 
8.1.  GENERAL ............................................................................................................................... 20 
8.1.1.  SUBMERGED ‐ STEEL ASSETS ......................................................................................... 20 
8.1.2.  ATMOSPHERIC EXPOSED – CONCRETE ASSETS ............................................................. 20 
8.2.  SYSTEM DESIGN .................................................................................................................... 20 
8.3.  GENERAL COMPONENTS ....................................................................................................... 21 
9.  IMPRESSED CURRENT SYSTEMS ................................................................................................ 22 
9.1.  GENERAL ............................................................................................................................... 22 

UNCONTROLLED WHEN PRINTED 
MWPA404 – Cathodic Protection Guideline 

 
 
 
9.1.1.  SUBMERGED ‐ STEEL ASSETS ......................................................................................... 22 
9.1.2.  ATMOSPHERIC EXPOSED – CONCRETE ASSETS ............................................................. 23 
9.2.  SYSTEM DESIGN .................................................................................................................... 24 
9.3.  GENERAL COMPONENTS ....................................................................................................... 25 
10.  HYBRID ANODE SYSTEMS .......................................................................................................... 26 
10.1.  GENERAL ........................................................................................................................... 26 
11.  GUIDANCE TO DESIGNERS ........................................................................................................ 27 
11.1.  SAFETY IN DESIGN ............................................................................................................. 27 
11.2.  DESIGN TO ACHIEVE CATHODIC PROTECTION .................................................................. 27 
11.3.  SERVICE LIFE REQUIREMENTS ........................................................................................... 27 
11.4.  MONITORING AND MAINTENANCE .................................................................................. 28 
12.  GUIDANCE TO CONTRACTORS .................................................................................................. 29 
12.1.  PRE‐CONTRACT MEETING ................................................................................................. 29 
12.2.  SYSTEM INSTALLATION PRACTICE ..................................................................................... 29 
12.3.  SYSTEM COMMISSIONING ................................................................................................ 29 
12.4.  ONGOING SYSTEM PERFORMANCE MONITORING ........................................................... 29 
13.  QUALITY CONTROL AND QUALITY ASSURANCE – GUIDANCE TO INSPECTORS ........................ 32 
13.1.  GENERAL REQUIREMENTS ................................................................................................ 32 
13.2.  INSPECTION AND TESTING PLAN ...................................................................................... 32 
13.3.  IDENTIFICATION AND TRACEABILITY................................................................................. 32 
13.4.  COMPLIANCE INSPECTIONS AND TESTING ....................................................................... 32 
14.  DOCUMENTS TO BE SUBMITTED .............................................................................................. 34 
14.1.  GENERAL ........................................................................................................................... 34 
14.1.1.  SYSTEM DESIGN DOCUMENTATION ............................................................................. 34 
14.1.2.  COMMISSIONING DOCUMENTATION ........................................................................... 34 
 
APPENDICES 
APPENDIX A – EXAMPLE CATHODIC PROTECTION SYSTEM INFORMATION 
APPENDIX B – EXAMPLE TEST INSPECTION RECORD 
 

UNCONTROLLED WHEN PRINTED 
MWPA404 – Cathodic Protection Guideline 

 
 
 

1. PREFACE  
This document has been compiled for the Mid West Ports (MWPA) to provide developers, designers, 
contractors and inspectors guidance on the corrosion protection by cathodic protection of MWPA’s 
berth  and  wharf  assets.    It  does  not  replace  bespoke  project  basis  of  design,  design  criteria  or 
specifications but it is intended to provide designers, contractors and inspectors with a benchmark for 
the  minimum  technical  requirements  for  designing,  installing,  commissioning  and  maintaining 
cathodic protection systems.  

The  chapters  of  this  guide  include  methods  and  guidance  on  the  statutory  requirements;  MWPA 
health;  safety,  environment,  quality  and  operational  policies  and  procedures;  cathodic  protection 
materials:  protection  criteria;  installation,  commissioning,  inspection  and  testing  information  to 
undertake a project with MWPA assets. 

This document will be used as a basis for identifying any shortcomings in the technical content and 
ultimately accepting or rejecting proposed, underway or completed projects. 

UNCONTROLLED WHEN PRINTED  1 
MWPA404 – Cathodic Protection Guideline 

 
 
 

2. SCOPE  
2.1. GENERAL  
This document provides information and guidance on the design, installation, commissioning and on‐
going  monitoring  and  maintenance  of  Cathodic  Protection  (CP)  systems  with  a  particular  focus  on 
Galvanic  (Sacrificial)  Anode  Cathodic  Protection  systems  and  forms  part  of  the  MWPA  Technical 
Guidelines Series. 

It includes guidance on the technical requirements for the design, installation, commissioning and on‐
going monitoring and maintenance of the various types of CP systems, including: 
 specific system design criteria  
 description of the various system components  
 Installation testing procedures 
 commissioning 
 on‐going operation, and monitoring of existing and future cathodic protection systems 
within the port area.  

2.2. EXCLUSIONS 
This guideline focuses solely on the cathodic protection of marine assets including atmospherically 
exposed, immersed and buried steel and reinforced concrete structures specifically relating to Port 
berths and wharves.  It does not account for the design or recommendations of cathodic protection 
systems for other structures or assets such as tanks, tank bottoms, pipelines and the like which often 
require  unique  and  detailed  system  designs  to  meet  safety  and  other  statutory  regulatory 
requirements.  If cathodic protection of such assets is required, then future revisions of this document 
shall be created.  

UNCONTROLLED WHEN PRINTED  2 
MWPA404 – Cathodic Protection Guideline 

 
 
 

3. GLOSSARY 
For the purposes of this Guideline the following particular definitions apply: 

Table 1:  Glossary of Terms 
Term*  Definition 
AC  Alternating Current 
ASS / Reactive soils  Acid sulphate / reactive soils are soils which contain metal sulphide 
minerals in high concentrations.  On exposure to the atmosphere or 
when these soils are disturbed during excavation or construction, 
these sulphide rich minerals can oxidise liberating large amounts of 
sulphuric acids.  Steel exposed to such aggressive conditions will 
generally require high current densities to achieve cathodic 
protection criteria.  
Acceptable  Shall mean acceptable to MWPA (the Owner) or the owner’s Engineer  
Anaerobic  Lack of free oxygen  
Anode   An electrode, placed in soil, concrete or aqueous medium to apply 
cathodic protection to a metallic structure. It is the positive side of 
the cathodic protection circuit.  
Anode Current Density  Current flowing from the anode divided by the surface area. 
Anode Screen  A safety barrier surrounding a submerged anode to protect from 
electric shock or shorting. 
Anode Shield   A protective covering of insulating material applied to a structure to 
reduce local cathodic density. Also referred to as a dielectric shield. 
Usually made from rigid polyethylene, polypropylene or Teflon.  
Anode Backfill  Backfill used to surround buried anodes in ground bed to provide 
even current output and extend life of anode. Material is most 
usually calcined petroleum coke.  
Bond   An electrical metallic connection between points on the same or 
different structures. 
Buried Zone  Zone located under the mud line or in soil or fill. 
Cathode   The metal asset or  structure that is requiring corrosion protection 
and forms the negative side of the CP circuit. 
Cathodic Protection  Electrochemical protection by decreasing the corrosion potential to a 
level at which the corrosion rate of the metal is significantly reduced 
(ISO8044) or a technique to reduce the corrosion of a metal surface 
by making that surface a cathode of an electrochemical cell. (NACE 
RP0176). 
Cathodic Protection Unit   DC power supply for an impressed current cathodic protection 
system. The DC output can either be manually or automatically 
controlled depending on system requirements. 

UNCONTROLLED WHEN PRINTED  3 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Term*  Definition 
Corrosion   The deterioration of a metal caused by its electrochemical reaction 
with the environment it is exposed to. 
DC  Direct Current 
Cathode Current Density  Current flowing onto the cathode (structure) divided by the cathode 
surface area. 
Design Life  Period of time the component must perform its intended function 
before first major maintenance.  
Exceptional Exposure   Special Cases, such as exposure that substantially intensifies the 
corrosive exposure and/or places increased demands on the 
corrosion protection system. 
Ground Bed   Groups of anodes buried in a land based location in a backfill 
materials is referred to as an anode ground bed. 
Hybrid Anode  An anode which is capable of operating both in galvanic and 
impressed current modes. 
Immersed Zone   Level continually submerged by water. 
Incipient anode effect  Corrosion of reinforcement steel in unrepaired concrete adjacent to 
recent concrete patch repair areas which ultimately leads to spalling 
and delamination of further areas of concrete.  
Passivity is restored to the reinforcement steel within the patch 
repair due to the removal of chloride contaminated concrete and 
replacement with highly alkaline repair material. The adjacent 
existing concrete may still contain chloride contamination and as a 
result is more anodic than the steel in the repair area. The potential 
difference between the cathodic (patch repair) and anodic (existing 
concrete) areas on the structure drives the corrosion cell which in 
time leads to the corrosion of the steel, delamination and spalling of 
the cover concrete in the anodic unrepaired concrete.  
Life to first maintenance  The time interval that can elapse after a component has been 
installed and deteriorates to the point when maintenance is 
necessary to restore it to operational service. 
Manufacturer  The supplier or manufacturer of the coating system or materials. 
MMO  Mixed Metal Oxide coating applied to the surface of a noble metal 
e.g. titanium to activate it produce reliable high performance 
impressed current anodes.  
Owner  Means the owner of the project or asset. 
Over Protection  Occurs when excess current is applied to a structure and the current 
is at a level that may cause detrimental effects to the structure e.g. 
coating damage, hydrogen embrittlement of high strength steel and 
other susceptible metals.  Risk of overprotection generally greater 
with impressed current systems given higher outputs compared to 
galvanic systems.  Can be mitigated with self‐adjusting control 
systems in TR electronics.  

UNCONTROLLED WHEN PRINTED  4 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Term*  Definition 
Reference Electrode  An electrode that has a stable potential in one or more electrolytes 
which can be used as a reference for measuring structure potentials 
to confirm satisfactory operation of the CP system. Common 
reference electrodes include Silver / Silver Chloride Reference 
Electrode (Ag/AgCl2), Copper / Copper Sulphate Reference Electrode 
(Cu/CuSO4). 
Splash Zone  Region above and below max/min tide levels subject to repetitive 
wetting and drying cycles from splashing.  Results in elevated 
localised corrosion rates of bare steel at this location.   
Stray Current   Current flowing through unintended paths which has the potential to 
cause damage. 
Structure Potential   The electrical potential of a structure relative to that of a specific 
reference electrode. 
Sulphate Reducing  Sulphate Reducing Bacteria (SRB) feed on metallic iron in a marine or 
Bacteria  soil environment and excrete large amounts of sulphuric acid 
resulting in pitting corrosion and rapid penetration / loss of localised 
wall thickness.  Often form within or under a biofilm which makes 
detection difficult.   
Transformer Rectifier  Transformer Rectifier units provide a DC power supply in impressed 
Unit   current cathodic protection systems.  They typically contain a step 
down transformer which converts a mains AC power input to a ripple 
free DC power output.  
*Note:  A full list of Cathodic Protection Terminology and definitions are available in AS 2832.1‐2004 Section 1.3. 

   

UNCONTROLLED WHEN PRINTED  5 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Table 2:  Abbreviations 
Abbreviation  Meaning 
ACA  Australasian Corrosion Association 
AINDT  Australian Institute for Non‐Destructive Testing 
ANSI  American National Standards Institute 
ALWC  Accelerated Low Water Corrosion  
AS  Australian Standard 
AS/NZS  Australian‐New Zealand Standard 
ASTM  American Standard of Testing and Materials 
BS  British Standards 
CP   Cathodic Protection  
CPU  Cathodic Protection Unit 
EPA  Environment Protection Authority 
HACP  Hybrid Anode Cathodic Protection System 
HAT  Highest astronomical tide  
HSEC  Health, Safety, Environment and Community 
ICCP  Impressed Current Cathodic Protection System 
ISO  International Standards Organization 
ITP  Inspection and Testing Plan 
LAT  Lowest astronomical tide 
MIC  Microbial Influenced Corrosion  
MMO  Mixed Metal Oxide  
MWL   Mean Water Level  
MRWA  Main Roads Western Australia 
MWPA  Mid West Ports Authority 
NACE  National Association of Corrosion Engineers 
SRB  Sulphate Reducing Bacteria 
QA / QC  Quality Assurance / Quality Control  
TRU  Transformer Rectifier Unit 
 

UNCONTROLLED WHEN PRINTED  6 
MWPA404 – Cathodic Protection Guideline 

 
 
 

4. RELEVANT DOCUMENTATION 
4.1. GUIDELINE SERIES 
This guideline should be read in conjunction with other parts of the MWPA Technical Guideline series, 
where relevant, and these are listed below: 
 MWPA 000 Series – Port Development Guidelines; 
 MWPA 100 Series – Technical Guidelines – General; 
 MWPA 200 Series – Drafting Guidelines and AutoCAD Standards; 
 MWPA 300 Series – Mechanical Guidelines; 
 MWPA 400 Series – Guidelines for Maritime Structures; 
 MWPA 500 Series – Civil Engineering Guidelines; 
 MWPA 600 Series – Buildings and Structures Guidelines; 
 MWPA 700 Series – Electrical and Instrumentation; 
 MWPA 800 Series – T.B.A; and 
 MWPA 900 Series – T.B.A. 

4.2. MID WEST PORTS POLICIES AND PROCEDURES 
All parties developing, designing, specifying, preparing, applying and inspecting any aspect of a MWPA 
coating project should be aware and abide with MWPA policies and procedures.  A full list of MWPA’s 
policies  and  procedures  can  be  found  in  MWPA 100 and  obtained  either  from the  MWPA website 
(https://www.midwestports.com.au) or requested from the MWPA Project Coordinator or Owner’s 
Engineer. 

4.3. LOCAL, STATE AND FEDERAL STATUTORY REQUIREMENTS 
In addition to the requirements of this part of the MWPA Technical Guidelines, all protective coating 
works  shall  meet  the  requirements  of  Local,  State  and  Federal  statutory,  health,  safety  and 
environmental requirements and regulations and include, but not be limited to the following: 
 Western Australian Environmental Protection  
 Western Australian Occupational Safety and Health Act (1984) and Regulations (1996)  
 Western Australian Occupational Safety and Health Legislation Amendment Act (1984) 
 Western Australian (Certificates of Competency and Safety Manning) Regulations (1983) 
 Transport Operation (Marine Safety) Act  
 Western Australian Mines Safety and Inspection Act 2005 and Regulations (2005) 
 Dangerous Goods Safety Act (2004) 
 Port Authorities Act (1999) 
 Maritime Transport and Offshore Facilities Security Act (MTOFSA) (2003) 
 Environmental Protection Act and Regulations (1986) 
 

   

UNCONTROLLED WHEN PRINTED  7 
MWPA404 – Cathodic Protection Guideline 

 
 
 
4.4. AUSTRALIAN STANDARDS AND DESIGN CODES 
The latest version of the following standards and documents shall be adopted for Works covered by 
this Guideline: 

4.4.1. AUSTRALIAN STANDARDS AND DESIGN CODES 
Table 3:  Australian Standards and Codes 
No.  Title 
AS 2832.1‐2004  Cathodic protection of metals – Pipes and cables 
AS 2832.2‐2003  Cathodic protection of metals – Compact buried structures 
AS 2832.3‐2005   Cathodic protection of metals – Fixed immersed structures 
AS 2832.4‐2006  Cathodic protection of metals – Internal surfaces 
AS 2832.5‐2008  Cathodic protection of metals – Steel in concrete structures 
AS 2239‐2003  Galvanic (sacrificial) anodes for cathodic protection 
AS 4832‐2007  Cathodic protection – Installation of galvanic sacrificial anodes in soil 
AS 2159  Piling – Design and Installation 
AS 3000‐2007  Electrical Installations (Australian and New Zealand Wiring Rules) 
AS/NZS 3100‐2009  Approval and test specification – General requirements for electrical 
equipment 
AS 4312  Atmospheric Corrosivity Zones in Australia 
AS/NZS ISO 9001  Quality Management Systems 
AS/NZS ISO 14001  Environmental Management Systems 
 

4.5. INTERNATIONAL STANDARDS 
In the absence of suitable Australian Standards and where items are to be sourced from overseas, the 
latest version of the following International Standards may be referenced.  

4.5.1. INTERNATIONAL STANDARDS AND DESIGN CODES 
Table 4:  International Standards and Codes 
No.  Title 
ISO 8044  Corrosion of Metals and Alloys – Basic Terms and Definitions  
ISO 9001  Quality Management System 
ISO 9223  Corrosion of Metals and Alloys, Corrosivity of Atmospheric Classifications 
ISO 9224  Corrosion of Metals and Alloys, Corrosivity of Atmospheres – Guiding 
values for the Corrosivity Categories 
ISO 12473  General Principles of Cathodic Protection in Sea Water  
BS EN 12474  Cathodic Protection for Submarine Pipelines  
BS EN 13509‐2003  Cathodic Protection Measurement Techniques  
EN 12496  Galvanic Anodes for Cathodic Protection in Seawater and Saline Mud  

UNCONTROLLED WHEN PRINTED  8 
MWPA404 – Cathodic Protection Guideline 

 
 
 
No.  Title 
ISO 12696  Cathodic Protection of Steel in Concrete  
EN 12954  Cathodic Protection of Buried or Immersed Metallic Structures – General 
Principles and Application for Pipelines  
EN 13509  Cathodic Protection against Stray Current from Direct Current Systems  
ISO 13173  Cathodic Protection for Steel Offshore Floating Structures  
BS EN ISO 13174  Cathodic Protection of Harbour Installations  
ISO 8044‐1999  Corrosion of Metals and Alloys ‐‐ Basic Terms and Definitions 
DNV‐RP‐B401  Recommended Practice for Cathodic Protection Design (Det Norske 
Veritas) 
NACE SP0176‐2007  Corrosion Control of Submerged Areas of Permanently Installed Steel 
Offshore Structures Associated With Petroleum Production 
NACE SP0572‐2007  Design, Installation, Operation and Maintenance of Impressed Current 
Deep Ground beds 
NACE SP0290‐2007  Impressed Current Cathodic Protection of Reinforcing Steel in 
Atmospherically Exposed Concrete Structures  
NACE SP0408‐2008  Cathodic Protection of Reinforcing Steel in Buried or Submerged Concrete 
Structures 
NACE TMO0294‐ Testing of Embeddable Impressed Current Anodes for use in Cathodic 
2007  Protection of Atmospherically exposed Steel‐reinforced Concrete 
 

4.6. ADDITIONAL REFERENCES 
The following references have been used in the production of this guideline: 
Table 5:  Additional References 
References 
  i.  www.midwestports.com.au 
 ii.  Contractor and Worker Requirements (Contractor Handbook) – A summary of the OSH, 
Environmental and Security Requirements at Geraldton Port (May 2013) 
iii.  Australian Corrosion Association Advanced Cathodic Protection Course Notes. 
 iv.  Installation of Sacrificial Cathodic Protection System at Mid‐West Ports’ Berths 4 & 6, 
Project No. 2015‐545, Project Report July 2015 
   

UNCONTROLLED WHEN PRINTED  9 
MWPA404 – Cathodic Protection Guideline 

 
 
 
4.7. PRECEDENCE 
As a general guide, where particular aspects are not covered in the MWPA Technical Guidelines or 
where conflict between documents exists, the following precedence for standards applies:  
1. Statutory Regulations  
2. Design Codes and Standards  
3. Project Specific Specification 
4. MWPA Technical Guidelines; and 
5. Other References (e.g. Recognised Industry Best Practice) 
Regardless of the general order of precedence, if there is a conflict between documents, the clause 
presenting the more conservative and pragmatic guidance will govern. If in doubt, or in all cases where 
noncompliance is anticipated, clarification shall be sought from the MWPA. 

UNCONTROLLED WHEN PRINTED  10 
MWPA404 – Cathodic Protection Guideline 

 
 
 

5. ASSETS REQUIRING CATHODIC PROTECTION  
5.1. GENERAL  
New galvanic cathodic protection systems have been recently installed on a number of Berths at the 
Port.  These galvanic systems have replaced or upgraded previous impressed current systems.   

MWPA undertook a review of the performance of existing cathodic protection systems to determine 
their suitability, safety and efficacy of their operation.  Considerations were also given to the design 
and installation of new or additional systems through incorporating recommendations made within 
this guideline.  

Galvanic systems were found to be preferential for installation on berth structures due to their relative 
ease of operation and maintenance as compared to impressed current systems.   

Currently the systems installed have not been designed to protect sheet piling or I beams, but this will 
be part of further investigations at the Port as current drain to the sheet pile wall is a concern and 
ultimately will effect anode output, cathodic protection of circular piles and result in reduced anode 
life expectancy.   

5.2. DESIGN PHILOSOPHY  
For Port Assets requiring cathodic protection, the systems will be designed, installed and maintained 
according to the criteria described in AS 2832.1 to AS 2832.5 standards series.  Table 6 below is an 
excerpt  from  “Table  17  in  MWP100  General  Guidelines  Document”  and  prescribes  design  life 
requirements for various Port Assets.   

Table 6:  Design Life Criteria 
Structure Type  Design Life (Years) 
Berths, wharfs, jetties , pens and similar structures  50 
Piles and sheetpiles (onshore/sheltered)  50 
Piles (offshore/exposed)  100 
Retaining walls (including sheetpiled)  50 
Structural Steel Access Structures  50 
 

Depending on environmental conditions, a galvanic cathodic protection systems’ design life will be in 
the order of 15 to 25 years depending on sacrificial anode consumption rate.  Therefore as part of the 
asset management plan, to achieve the desired structure design life, galvanic anodes may need to be 
replaced and other components of the system such as cabling, structure connections and reference 
electrodes will need to be maintained at regular intervals.  

During the initial period after installation, regular potential testing should be undertaken at 3 monthly 
intervals for the first 6 to 12 months to establish baseline potential readings during initial structure 
polarisation.  After stable potentials have been achieved, it is agreed that annual inspections of the 
anodes, anode connections and potential measurements should be undertaken.  

   

UNCONTROLLED WHEN PRINTED  11 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Whilst  the  use  of  smaller  anodes  will  greatly  assist  in  ease  of  inspection,  future  designers  should 
ensure that the design of the anode suspension system will: 
 be of sufficient length to ensure the anode remains fully submerged even at Lowest 
Astronomical Tide (LAT); 
 suspension system is strong enough to support anodes in strong currents;  
 anodes are installed in a location that minimises disturbance from prop‐wash effects. 
Thus ensuring cathodic protection is maintained as intended.  

UNCONTROLLED WHEN PRINTED  12 
MWPA404 – Cathodic Protection Guideline 

 
 
 

6. COMPETENCE OF PERSONNEL  
6.1. GENERAL  
As outlined in Section 1.4 AS 2832.1, persons responsible for the design, survey, inspection, testing 
and maintenance of cathodic protection systems shall have the requisite minimum experience and 
qualifications  in  cathodic  protection.    The  Australasian  Corrosion  Association  provides  training  and 
accreditation for personnel in the corrosion prevention industry.  

6.2. IMPRESSED CURRENT SYSTEM SPECIFIC REQUIREMENTS 
Due to potentially dangerous operating currents and voltages output by impressed current systems, 
all installation and commissioning work on impressed current cathodic protection systems should be 
overseen by certified licenced electricians and/or electrical engineers.  

UNCONTROLLED WHEN PRINTED  13 
MWPA404 – Cathodic Protection Guideline 

 
 
 

7. DESIGN OBJECTIVES  
7.1. GENERAL  
The purpose of this section is to provide information specific to the design and operation of cathodic 
protection systems. 

7.2. DESIGN PARAMETERS 
There are two common types of cathodic protection systems available: 
1. Galvanic systems, which rely on buried or submerged metallic anodes which sacrificially 
corrode to provide a source of direct current for the corrosion protection of a structure.   
2. Impressed current systems, which use an external electrical power supply to apply direct 
current for the corrosion protection of the structure.   

7.3. CATHODIC PROTECTION CRITERIA  
Given  the  majority  of  MWPA  assets  are  steel  or  ferrous  structures,  this  specification  will  focus  on 
corrosion prevention through the application of cathodic protection to these elements.  Should the 
specific potential criteria for other alloys or metals be required refer to Section 2.2.2 Potential Criteria 
in  AS 2832.1  and  AS 2832.3.  Table  7  provides  a  summary of  electrical  potential  criteria  in  order to 
achieve cathodic protection.   

Table 7:  Cathodic Protection Potentials for Steel Elements Exposed to Various Environments 
Overprotection 
Location Of Steel  Protection Potential  Reference Electrode 
Potential 
Immersed in  ‐800mV  Ag/AgCl2  ‐1200mV 
seawater* 
Immersed in other  ‐850mV  Cu/CuSO4  ‐1200mV 
waters* 
Buried in ground  ‐850mV  Cu/CuSO4  ‐1200mV 
In concrete  ‐720mV  Ag/AgCl2  ‐1100mV# 
‐900mV 
*Note:  In cases where sulphate reducing bacteria (SRB’s) are active a more negative protection 
potential maybe required.   
# over protection potential depends on type of reinforcement present in the concrete i.e. ‐
1100mV for conventional steel and ‐900mV for pre‐stressed or post‐tensioned steel – to 
reduce the risk of failure due to hydrogen embrittlement.  

It is very important that over‐protection potentials are not exceeded in order to prevent deleterious 
surface effects  from  occurring  such  as  coating  disbondment  or  hydrogen embrittlement  leading to 
potential failure of stressed reinforcing elements.   

To confirm that a structure is receiving adequate cathodic protection and indeed meets the required 
design  criteria,  instantaneous  ‐OFF  potential  (IR  Free)  measurements  are  taken  at  all  permanently 
installed reference electrodes and at other locations.   

   

UNCONTROLLED WHEN PRINTED  14 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Potential measurements are taken a short period of time after switching off DC power supplies for 
impressed  current  systems  or  disconnecting  galvanic  anode  systems.    This  measurement  gives  an 
indication as to how well a structure is maintaining the desired protection potential which will protect 
the structure from corrosion.   

Each standard will cover system or structure specific potential requirements depending on whether 
or not the steel is coated, in concrete, immersed or buried.  Further detailed information can be found 
in Section 3.2 of AS 2832.2, Section 2.2 of AS 2832.3 and Section 7.6 of AS 2832.5.  

7.4. ELECTRICAL CURRENT DEMANDS   
Cathode current density is defined simply as the amount of current applied per square meter of steel 
structure being protected.  Generally, there are three critical electrical design current densities (as 
defined by BS EN ISO 13174) which need to be considered for the successful operation of any cathodic 
protection system.  They are as follows: 
 Initial Current Density – used to verify that the output current capacity of the new anodes, is 
capable of obtaining complete initial polarisation of the structure; 
 Maintenance Current Density – used to determine the approximate mass of the galvanic 
anodes material required.  This is the cathode current density considered necessary to 
maintain the desired polarisation criteria of the structure during the cathodic protection 
systems design life.  Seasonal variations in current requirements between summer and 
winter months can be negated by using a conservative current density during the design 
process; 
 Repolarisation Current Density – is used to verify that the output current capacity of the 
anodes when they are consumed to their utilization factor, i.e. at their final usable (end of 
life) dimensions, allows to repolarise the structure after severe storms or marine growth 
cleaning operations. 
Tables 8 to 10 provide examples of recommended current densities for various scenarios and is by no 
means to be considered an exhaustive list.  The discretion, expertise and past practical experience of 
the cathodic protection systems’ designer is also fundamental to determining an appropriate cathode 
current density for a specific application.  This will be dependent on specific variables, including but 
not limited to: 
 The local micro environment 
 Electrolyte type i.e. water, soil, concrete 
 Electrolyte resistivity 
 Electrolyte aeration 
   

UNCONTROLLED WHEN PRINTED  15 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Table 8:  Typical Design Current Densities for Bare Steel Immersed in Seawater 
Current Densities (mA/m2) 
Initial Value  Maintenance Value  Repolarisation Value 
Water Condition/ 
Description*  Poorly  Well  Poorly  Well  Poorly  Well 
Aerated  Aerated  Aerated  Aerated  Aerated  Aerated 
Waters  Waters  Waters  Waters  Waters  Waters 
Tidal Flow <0.5m/s  80 – 120  120 – 150  50 – 65  65 – 80  60 – 80  80 – 100 
Tidal Flow >0.5m/s  120 – 150  170 – 200  60 – 80  80 – 100  80 – 100  100 – 130 
ALWC or Active MIC1   170 – 200  60 – 100  80 – 130       
*Table  7  excerpt  from  BS  EN  ISO13174  Annex  A.2,  1.Table  A1)  ALWC  –  Accelerated  Low  Water 
Corrosion, MIC – Microbial Influenced Corrosion 

Table 9:  Typical Design in Current Densities for Bare Steel Buried in Saline Mud 
Current Densities 
(mA/m2) 
Description 
Maintenance  Repolarisation 
Initial Value 
Value  Value 
All types of structures in  25  20  20 
normal saline muds  
Conditions with  30 – 50  25 – 30  25 – 30 
established microbial 
corrosion  
*Values obtained from BS EN ISO13174 Table A.2 – 
 

Table 10:  Typical Design Current Densities for Steel in Other Specific Conditions 
Description*    Current Densities 
(mA/m2) 
Reinforcing steel in concrete   5 ‐ 20 
Poorly coated steel in ground or water   1 
Well coated steel in earth or water  0.03 
Very well coated steel  <0.01 
*Values obtained from Section A4 – AS 2832.5‐2008 

   

UNCONTROLLED WHEN PRINTED  16 
MWPA404 – Cathodic Protection Guideline 

 
 
 
7.5. COATING BREAK DOWN FACTORS 
Additional protection for steel assets can be afforded by the combined use of a suitable coating and 
cathodic protection.  This can significantly reduce the current density demand and improve current 
distribution and corrosion protection across the structures surface.  As with all coatings however, as 
the coating deteriorates over time, the current density required for protection will increase.   

For  marine  assets,  cathodic  protection  of  bare  steel  maybe  more  cost  effective  than  the  cathodic 
protection of coated steel over the life of the asset.  However, corrosion protection at and above the 
mid tide level is not possible by cathodic protection and therefore coatings may be necessary to satisfy 
durability or aesthetic requirements.   

Coating breakdown factors are used to account for the increased current demands required to protect 
a  structure  where  mechanical  damage  or  degradation  to  a  coating  has  occurred.  Initial  coating 
breakdown factors are often applied to account for coating loss during fabrication and installation of 
the structure.  

Coating breakdown factors are strongly influenced by the following: 
 Actual coating type  
 Surface preparation and how the coating is applied 
 Construction and operational conditions 
 Severity of the exposure environment  
 Interactions between the coating and cathodic protection systems (coating disbondment 
possible if the structure is suffering from overprotection or if incompatible coatings are 
used).  
Guidelines  for  the  values  of  coating  breakdown  factors  (fc)  are  presented  in  Annexure  A  of 
BS EN ISO13174.  The formula for calculating the resulting current density required for the protection 
of coated steel is as follows: 
Jc = Jb x fc …………………………………………………………………………………..Equation 1 

where: 
Jc is the protection current density for coated steel (mA/m2); 

Jb is the protection current density for bare steel (mA/m2); 

fc is the coating breakdown factor which varies with time due to ageing and or extent of 
mechanical damage to the coating. 

Generally, fc = 0 for a perfectly insulating coating, fc = 1 for a bare structure.  This formula should be 
applied to each individual component or zone as defined in Section 5.3 of BS EN ISO 13174 where the 
coating, or the current density for bare steel can differ significantly. 

Table 11 offers guidance values to be used when calculating coating breakdown factors for a particular 
structure.   

   

UNCONTROLLED WHEN PRINTED  17 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Table 11:  Guidance values for the calculation of coating breakdown factors for the design of 
cathodic protection systems 
Initial Coating Breakdown Factor*    Estimated Deterioration Rates Of Coatings  
1 % to 2 % (immersed areas)  3 % per year low durability coatings 
25 % to 50 % in driven piled (buried) areas;  1.5 % per year for medium durability coatings 
5 % to 25 % in backfilled (buried) areas  0.5 % to 1 % per year for high durability 
coatings 

*Note:  Very dependent on soil conditions or backfill material, construction methodology and coating 
selection.    Estimated  coating  deterioration  rates  are  based  on  exposure  classification  and 
durabilities as defined in ISO 12944‐1 and ISO 12944‐2.  Coating Breakdown Factor Calculation 
is described in further detail in BS EN ISO 13174. 

7.6. CONSIDERATIONS WHEN CHOOSING CATHODIC PROTECTION SYSTEMS    
During the conceptual design stage when considering if a cathodic protection system is required the 
following should be considered.  
 Decide if the structure should be coated.  If the structure is to be coated, ensure the coating 
is compatible with cathodic protection systems.  It should also be noted that the use of an 
appropriate coating system in conjunction with cathodic protection will significantly reduce 
the current demand on the cathodic protection system and therefore the coast of the anode 
system.  It is recommended that if coating systems are required they are designed in 
conjunction with the cathodic protection system and installed at the same time.   
 For new structures, design the structure accordingly so that cathodic protection can be 
installed immediately or in the future when desired without the need for major 
modifications e.g. continuity bonds. 
 For existing structures, identify what measures are required for the effective application of 
cathodic protection, this may require minor modifications to the structure such as the 
installation of anode or cable connection points.   
 During the design, consider the need for the cathodic protection system to be able to 
mitigate the effects of stray currents from other cathodic protection systems or current 
sources such: 
– Berthed ships CP systems 

– CP systems of adjacent or near‐by structure 

– DC traction systems associated with railways.  

 During the design, consideration should also be given as to the effect or interaction of a new 
cathodic protection system on foreign structures not necessarily requiring cathodic 
protection.  In some cases interference may only be resolved by field testing after 
installation. 
 Environmental and structural variables need to be carefully considered as these will 
determine which type of cathodic protection system is most suitable for a particular 
structure.   
 A number of assumptions and estimations will need to be made during the design process 
for design parameters to achieve adequate cathodic protection of the structure.   

UNCONTROLLED WHEN PRINTED  18 
MWPA404 – Cathodic Protection Guideline 

 
 
 
 Before installation of a cathodic protection system can occur, as part of the due diligence 
process and in some states, a legislative requirement in some Australian states, assets 
owners require a permit to be issued by relevant bodies such as electrolysis committees 
before a system can be commissioned.  The contact details for the Western Australia – 
Electrolysis Subcommittee (ACA)  as supplied as follows :  Water Corporation Western 
Australia, 629 Newcastle Street, Leederville WA 6007) – for further details refer Appendix K 
AS 2832.1)   
 Commissioning the new system will require site measurements to determine that sufficient 
protection is being provided to the structure and the overprotection and stray currents are 
mitigated accordingly.   
 Monitoring cathodic protection systems at regular predetermined intervals by qualified 
persons is key to the successful maintenance and operation of any system. 
 Sufficient easy access to all parts of the asset will be required to enable the completion of 
the commissioning and on‐going monitoring in an efficient manner and to enable 
confirmation that the CP system is providing satisfactory corrosion protection to all parts. 

7.7. ELECTRICAL CONTINUITY  
To ensure the effectiveness and efficiency of cathodic protection systems, it is necessary to ensure 
that the structure or sections of the structure are electrically connected or continuous.  Bonds may be 
necessary  to  connect  isolated  parts  of  the  structure  together  to  ensure  electrical  continuity.  For 
example across bolted connections or where adequate contact is uncertain such as between individual 
sheet,  tubular  or  fender  piling.    The  bond  shall  be  designed  for  ease  of  installation  and  access  for 
maintenance purposes.  

The continuity bond shall be of low resistance so as not to adversely interfere with the performance 
and operation of the cathodic protection system.  

Continuity  bonds,  where  possible,  shall  utilise solid metal  conductors welded to  each  asset,  rather 
than cables and crimped connections, as they provide a more durable maintenance free connection 
with less likelihood of failure which can lead to loss of adequate corrosion protection and the risk of 
stray current corrosion on electrically discontinuous structures.   

7.8. STRAY CURRENT AND OTHER INTERACTIONS 
Cathodic  Protection  systems  shall  be  designed  as  to  minimise  the  risk  of  corrosion  caused  by 
interference currents to other structures.  Section 6.2 and Section 8 of AS 2832.3 discuss at length the 
general and regulatory requirements for the minimisation of stray current and other interactions.  

UNCONTROLLED WHEN PRINTED  19 
MWPA404 – Cathodic Protection Guideline 

 
 
 

8. GALVANIC ANODE SYSTEMS  
8.1. GENERAL  
Galvanic (Sacrificial) anode cathodic protection (GACP) systems are generally easier to install, operate 
and maintain than the more complex impressed current cathodic protection (ICCP) systems.  However, 
in high resistivity environments, the output current of the anode is limited by the driving voltage of 
the anode material (potential difference between the anode and cathode); hence the variable driving 
voltage provided by ICCP systems is required to provide sufficient polarisation of the asset to achieve 
satisfactory corrosion protection.  Galvanic systems are generally self‐regulating cathodic protection 
systems only applying a corrosion current when corrosion on the structure is active.   

8.1.1. SUBMERGED ‐ STEEL ASSETS  
Generally the  types of  steel  assets  requiring  impressed  current  cathodic  protection  are  steel  piles, 
steel sheet pile walls and other retaining wall structures around berths, wharfs, jetties and pens.   

The general protection criteria for steel structures submerged in seawater is obtained from AS 832.3.  
A structure is considered protected when a potential equivalent to or more negative than ‐800 mV 
with respect to a silver/silver chloride reference electrode.  For structures submerged in other waters 
(including drinking water) the potential required is ‐850 mV with respect to a copper / copper sulphate 
reference electrode.   

In  some  cases  the  potential  required  may  be  more  negative  to  mitigate  the  effects  of  sulphate 
reducing bacteria.   

Generally  galvanic  cathodic  protection  systems  function  best  when  used  in  conjunction  with 
protective coatings and or pile wraps etc.  If the environment is particularly aggressive or there are 
large surfaces of bare steel requiring protection, impressed current systems may prove to be more 
cost effective due to their higher output levels.   

8.1.2. ATMOSPHERIC EXPOSED – CONCRETE ASSETS  
Port assets which may require galvanic cathodic protection would generally be concrete decks, beams 
/  soffits of  berths  and  wharfs  where  reinforcement corrosion may  be occurring  or  where  localised 
concrete repairs have been undertaken and small anodes are installed around the repair to prevent 
incipient anode effects.   

The  general  protection  criteria  for  galvanic  concrete  cathodic  protection  systems  according  to 
AS 2832.5, is that no instantaneous off steel / concrete potential shall be more negative than ‐1100 
mV for plain reinforcing steel or no more negative than ‐900 mV for prestressing steel with respect to 
a saturated silver/silver chloride reference electrode.  Further detailed protection criteria for concrete 
cathodic protection is provided in Section 9.1.2 of this guideline.   

8.2. SYSTEM DESIGN   
When commencing the design of a GACP system, the following process should be considered:  
 Divide the structure into various zones requiring protection in order to simplify the design 
process; 
 Calculate surface area of steel to be protected in each zone 
 Determine design protection criteria and appropriate current densities based on exposure 
environment, expected corrosion rates and coating status (as discussed in Section 7);  

UNCONTROLLED WHEN PRINTED  20 
MWPA404 – Cathodic Protection Guideline 

 
 
 
 Record assumed anode performance data based on theoretical efficiency and output 
potential for the entire design life of the anode; 
 Calculate and record the number of anodes required, their mass, specification, alloy 
composition, effective consumption rate.  Ensure the anodes are installed in such a way that 
they remain fully submerged at all times but are also retrievable for inspection to avoid 
having to involve a diver in the routine system assessment;  
 Record the proposed manufacturer / suppliers details and ensure anodes are properly 
QA/QC inspected and certified before installation.  Galvanic anodes shall be supplied and 
installed in accordance with AS 2399.  Provide copies of anode certification to MWPA; 
 Agree on and record proposed location of any switching, control or monitoring devices 
including reference electrodes.  Ensure monitoring devices and reference electrodes are 
certified by their manufacturers and test certificates are supplied;  
 Provide MWPA a detailed Operation and Maintenance Manual which shall address the 
operation of the as‐built system, commissioning, monitoring, inspection and testing intervals 
and procedures;  
 Record commissioning results including potential survey data to MWPA;  
 Record periodic maintenance inspection survey data including current and protection 
potential measurements, equipment and the measuring technique to follow the changes of 
the protection potential status of the structure. 

8.3. GENERAL COMPONENTS   
Common components of a GACP system are as follows:  
 Anodes  
 Anode to structure connections e.g. fixing brackets, bracelets, sleds etc. 
 Test Points 
 Junction Boxes   
 Reference Electrodes 
 Structure bonding (continuity connections) 
 

UNCONTROLLED WHEN PRINTED  21 
MWPA404 – Cathodic Protection Guideline 

 
 
 

9. IMPRESSED CURRENT SYSTEMS  
9.1. GENERAL  
Impressed current cathodic protection (ICCP) systems are generally more complex than GACP systems, 
as  they  have more  components  and  also  require  increased on‐going monitoring  and  maintenance.  
ICCP systems are generally chosen to operate in places where the current output of GACP systems 
cannot meet protection criteria.  This can be due to a number of reasons, including but not limited to 
some or all of the following: 
 Presence of high resistivity electrolytes; 
 Requirement for high cathode current densities due to the aggressive nature of the exposure 
environment or higher current demand for large surface area assets; 
 Limitations to the size, weight and number of galvanic anodes that can be accommodated on 
the asset requiring protection; 
 Accommodation of current drainage to adjacent structures. 
Unlike  GACP  systems  where  the  anodes  are  consumed  over  a  period  of  time,  impressed  current 
anodes have extremely low consumption rates and rely on an external DC current source to provide 
the cathodic protection current from the anode. This is often in the form of a Transformer Rectifier 
Unit (TRU).  The TRU utilises an external power supply (often Mains AC) and steps down the voltage 
and converts the AC input current to ripple free DC to power to the anodes.   

TRU unit(s) are often manually controlled with the end user adjusting the output voltage and current 
in order to achieve the desired protection criteria.  Auto‐potential control and remote controlled TRU 
systems are also available which use proprietary computer hardware and software to autonomously 
monitor structure potentials via permanent reference electrodes then adjust the ICCP systems output 
current  and/or  voltage  within  user  defined  parameters  to  maintain  adequate  levels  of  protection 
during  variations  in  the  operational  environment  e.g.  tide  level,  electrolyte  resistivity  etc.  Such 
systems have a variable reliability track record. The TRU manufacturers QA/QC and ongoing support 
and maintenance of their products should be evaluated closely during the procurement phase of the 
project.   

9.1.1. SUBMERGED ‐ STEEL ASSETS  
Generally the  types of  steel  assets  requiring  impressed  current  cathodic  protection  are  steel  piles, 
steel sheet pile walls and other retaining wall structures around berths, wharfs, jetties and pens.   

The general protection criteria for steel structures submerged in seawater is obtained from AS 2832.3.  
A structure is considered to be protected when it is maintaining a structure potential equivalent to or 
more negative than ‐800 mV with respect to a silver/silver chloride reference electrode.  For structures 
submerged in other waters (including drinking water) the potential required is ‐850 mV with respect 
to a copper/copper sulphate reference electrode.   

In  some  cases  the  potential  required  may  be  more  negative  to  mitigate  the  effects  of  sulphate 
reducing bacteria.   

   

UNCONTROLLED WHEN PRINTED  22 
MWPA404 – Cathodic Protection Guideline 

 
 
 
9.1.2. ATMOSPHERIC EXPOSED – CONCRETE ASSETS  
Port  assets  requiring  impressed  current  cathodic  protection  would  generally  be  concrete  decks, 
beams/soffits of berths and wharfs where reinforcement corrosion may be occurring.   

The  impressed  current  cathodic  protection  criteria  for  concrete  is  taken  from  AS 2832.5  Cathodic 
Protection of Metals – Part 5 Steel in Concrete Structures.  In general the criteria is as follows: 
 No instantaneous off steel/concrete potential shall be more negative than ‐1100 mV for 
black reinforcing steel and ‐900 mV for prestressing steel with respect to Ag/AgCl reference 
electrode.  
 Potential decay criterion: shall not fall further than a maximum of 100 mV from the 
instantaneous off potential over a 24 hour period; 
 Extended potential decay criterion: A potential decay over a maximum of 72 hours of at least 
100mV from the instantaneous off potential subject to a continuing decay and the use 
reference electrodes.  
 Absolute potential criterion: An instantaneous off potential (measured between 0.1s and 1s 
after switching the DC circuit open. More negative than ‐720 mV with respect to Ag/AgCl 
reference electrode. 
 Absolute passive criterion: A fully depolarised potential, or a potential which is continuing to 
depolarize over a maximum of 72 hours after the cathodic protection system has been 
switched off, which is consistently less negative than ‐150 mV with respect to Ag/AgCl 
reference electrode.   
Compliance with at least one of the above criteria shall be generally be achieved within 6 months or 
alternatively, within a longer period subject to agreement with MWPA.  .  A careful monitoring plan 
shall be developed to specifically determine when a specific system would be expected to meet the 
protection criteria detailed above.   

At this point it should be noted if any structure receiving impressed current from an ICCP system has 
pre‐stressed or post‐tensioned steel reinforcement, great care must be taken to avoid over protection.  
Overprotection will result in the generation of excessive amounts of hydrogen gas on the surface of 
the steel.  High tensile steel is extremely sensitive to hydrogen embrittlement leading to cracking and 
catastrophic failure of highly stressed elements.   

For a concrete element requiring cathodic protection, firstly the continuity of the reinforcement needs 
to be confirmed by site testing as per AS 2832.5 Section 3.2.8.  If the reinforcement is found to be 
discontinuous  then  the  reinforcement  will  need  to  be  made  electrically  continuous  to  achieve  full 
protection and prevent stray current corrosion of any discontinuous reinforcement steel or embedded 
metallic fixtures and fittings.   

An assessment should also be undertaken to determine the risk of alkali aggregate reactions in the 
concrete  as  the  cathodic  protection  system  can  exacerbate  the  condition.    Potential  mapping  and 
concrete electrical resistivity measurements shall be undertaken as per AS 2832.5, Section 3.2.9 and 
3.2.10.      

   

UNCONTROLLED WHEN PRINTED  23 
MWPA404 – Cathodic Protection Guideline 

 
 
 
9.2. SYSTEM DESIGN   
When  commencing  the  design  of  an  impressed  current  cathodic  protection  system,  the  following 
process should be considered:  
 Divide the structure into various zones requiring protection in order to simplify the design 
process.  Often various areas of large structures will have different current demands or will 
require multiple TRU units to power the system;  
 Determine: 
– design protection criteria 

– appropriate current densities  

– anode current densities and output currents based on exposure environment 

– expected corrosion rates  

– coating status and break down factors (as discussed in Chapter 7); 

 Undertake detailed design calculations including the calculations of:  
– surface areas to be protected 

– current demands 

– distribution of anodes and zoning 

– cable requirements 

– power supply requirements; 

 Other data including: 
– number of anodes including size, current output  

– specification  

– description of anodic equipment i.e. cables, connection details, jointing systems   

– effective anode output current densities  

– acceptable anode operating voltage ranges  

– cable volt  

– Manufacturer/supplier data and documentation.   

(Note:  AS 2832  has  specific  requirements  regarding  the  safe  design  and  operation  of 
impressed  current  systems  and  these  include  maximum  allowable  voltage 
gradients  around  immersed  anodes  as  well  as  maximum  circuit  voltages  in 
cabling.)   

 Provide a description for method of attachment of anodes, the composition and location of 
any dielectric shield (if applicable), as well as the specification, characteristics and 
attachment method of the connecting cables and cable management system e.g. location of 
junction boxes and cable runs; 

UNCONTROLLED WHEN PRINTED  24 
MWPA404 – Cathodic Protection Guideline 

 
 
 
 Record the location of each anode as checked during construction, all deviations from the 
design location being highlighted and the date of installation; this data should be updated 
during the life of the structure; 
 Record the location, detailed specification, drawings, and output characteristics of each TRU 
with their factory test reports and provide copies to MWPA; 
 Record location, description and specification of any protection, potential control or 
monitoring device, including reference electrodes, measuring equipment and connecting 
cables; 
 Provide a detailed report on the commissioning results including potential survey data, 
current and voltage output values of each TRU, individual anode current and any adjustment 
made for non‐automatic devices to MWPA; 
 Provide a report detailing the results of any interaction testing of adjacent structures to 
MWPA; 
 Provide any data recorded during periodic maintenance inspection including protection 
potential values, DC output values, maintenance data on DC power sources and downtime 
periods to follow the changes of the protection potential level status of the structure to 
MWPA; 
 Provide a detailed Operation and Maintenance Manual to MWPA which shall detail the as‐
built system, inspection and testing procedures, inspection and testing intervals and a fault 
finding guide. The data detailed above may in addition be incorporated into this document. 

9.3. GENERAL COMPONENTS   
Common components of an impressed current cathodic protection system are as follows:  

 Mixed Metal Oxide (MMO) Coated Titanium Anodes  
 Anode Feeder Cables  
 Anode Header Cables 
 Structure Negative Return Cables 
 Junction Boxes 
 Test Points  
 Reference Electrodes 
 Power Supply  
 Transformer Rectifier Unit(s) or Cathodic Protection Unit(s)  
 Structure bonding (continuity connections) 
 

UNCONTROLLED WHEN PRINTED  25 
MWPA404 – Cathodic Protection Guideline 

 
 
 

10. HYBRID ANODE SYSTEMS  
10.1. GENERAL  
Hybrid  anode  cathodic  protection  (HACP)  systems  are  a  relatively  new  concept  in  the  Australian 
industry; hence they are not explicitly discussed in any of the relevant cathodic protection standards 
listed in Section 4.4.  To date the technology is only available from a single source technology supplier.  
The  following  points  should  be  considered  in  detail  before  deciding  to  use  a  Hybrid  Cathodic 
Protection System:    
 The hybrid concept currently has only been applied to corroding reinforcing steel in concrete 
which is also often heavily contaminated with chlorides.   
 The system is designed to initially “rapidly re‐passivate” the surface of the steel to “arrest 
corrosion” whilst operating under an accelerated impressed current regime. 
 The power supply is the switched off and removed allowing the system to operate as a 
galvanic system with the intent to provide continued corrosion protection.  
 Cathodic protection of steel reinforcement in concrete is difficult with galvanic anodes due 
to the limited driving voltage of the anodes and relatively high resistivity of the concrete, 
which is often why impressed current cathodic protection of steel reinforcement is preferred 
 Hybrid systems require a large number of closely spaced anodes to be installed in the 
concrete structure to achieve sufficient protection.   
 Steel reinforcement in concrete requiring cathodic protection still requires appropriate 
zoning (i.e. exposure zone dependent on current demands). 
It should be noted that there is significant debate across the corrosion prevention industry as to the 
long term efficacy or applicability of the technology so caution is urged when considering the use of 
this technology for corrosion prevention.  Generally a well‐designed galvanic anode system should be 
capable  of  meeting  required  potential  criteria  for  most  reinforced  concrete  structures  in  most 
circumstances. 

UNCONTROLLED WHEN PRINTED  26 
MWPA404 – Cathodic Protection Guideline 

 
 
 

11. GUIDANCE TO DESIGNERS 
11.1. SAFETY IN DESIGN  
It is the responsibility of the cathodic protection system designer to ensure the following:  
 The system has sufficient current capacity to meet the required protection criteria;  
 The risk of over protection or current drain to surrounding structures is mitigated 
accordingly through design;    
 Standard specific requirements such as maximum allowable voltage drops/gradients are met 
and maintained for the safety of personal and the asset structure (Section 5.2 AS 2382.1); 
 General compliance to electrical standards and electrolysis committee guidelines 
requirements are met.    

11.2. DESIGN TO ACHIEVE CATHODIC PROTECTION   
Guidelines  for  achieving  system  and  asset  specific  cathodic  protection  criteria  for  each  type  of 
cathodic protection system/asset are detailed in Section 2 of AS 2832 Parts 1‐5.   

11.3. SERVICE LIFE REQUIREMENTS 
As per Table 6 in Section 5.1 of this guideline and according to the full table in MWPA100 ‐ General 
Guidelines  document,  asset  life  requirements  for  individual  structures  and  components  have  been 
defined.  For new structures, the cathodic protection systems shall be designed accordingly so that 
they also have equivalent service design lives.  If cathodic protection systems are not required initially 
for new structures, it is recommended that provisions are made during design and constructions such 
that cathodic protection can be “retrofit” at a later stage.   

For existing structures, the design and installation of cathodic protection systems will be used as a 
method  of  extending  service  life  of  the  asset  and  thus  the  required  service  life  of  the  cathodic 
protection system in this case will need to be specified by MWPA.  

GACP  systems  generally  have  a  service  design  life  10  to  20  years  for  anodes  depending  on  anode 
current demand, size and consumption rates and 25 years for all other system components including 
wiring, test points and junction boxes etc.  Appropriate anode sizing should be undertaken during the 
design process to suit alignment with design life in maritime structures guidelines.  As part of the asset 
management and maintenance plans, anode replacement or system upgrades should also be allowed 
for so that the cathodic protection system continues to provide suitable protection from corrosion.   

ICCP systems are generally design to have service lives of up to 50 years for the anode system with all 
electrical system components having a minimum durability requirement of 25 years.  In the case of 
cable insulation for example, which may be subject to years of ultraviolet light degradation from sun 
exposure, secondary encasement in ultraviolet resistant PVC conduits would be recommended.     

Table  12  provides  a  summary  of  anticipated  cathodic  protection  system  service  lives  for  various 
system  components  and  anodes.    This  is  an  indicative  guide  only  as  environmental  conditions  will 
heavily influence the service life of the system, particularly with respect to galvanic anodes.  Regular 
routine  system  performance  monitoring  is  key  to  ensuring  the  systems  are  providing  continued 
protection to the specific port asset. 

UNCONTROLLED WHEN PRINTED  27 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Table 12:  Typical Design Current Densities for Bare Steel Buried in Saline Mud 
Cathodic Protection System Typical Service Life 
Galvanic Systems  Impressed Current Systems 
Asset Type And Location 
(Years)  (Years) 
Description 
System  System 
Anodes  Anodes 
Components  Components 
Metallic (Submerged)  10 ‐ 15  25  25 – 50  25 ‐ 30 
e.g. Berth Piles  
Metallic (Buried)  10 ‐ 15  25  25 ‐ 50  25 ‐ 30 
e.g. Structure Piles, Pipelines, 
Tank bottoms etc.  
Concrete (Atmospheric)   10 ‐ 20  15 – 20  25  25 ‐ 30 
 

11.4. MONITORING AND MAINTENANCE   
The CP system design shall give thorough consideration as to the ease of future inspection, difficulty 
in changing galvanic anodes, location of reference electrodes and test points as this will greatly affect 
the cost of on‐going monitoring and maintaining the system.  For example, large galvanic anodes in 
the marine environment are often difficult to inspect or replace in confined spaces particularly under 
berth structures.  In such cases the design for multiple smaller anodes strategically placed around the 
structure according to protection criteria and design calculations would be a preferred option.      

UNCONTROLLED WHEN PRINTED  28 
MWPA404 – Cathodic Protection Guideline 

 
 
 

12. GUIDANCE TO CONTRACTORS 
12.1. PRE‐CONTRACT MEETING  
Contractors should refer to Section 7 Installation of Cathodic Protection Systems in AS 2832.1.  Prior 
to system installation, contractors must obtain approval to install a cathodic protection system not 
only  from  the  asset  owner  requiring  cathodic  protection  but  also  from  neighbouring  asset  owners 
who’s  structures/assets  may  be  subject  to  unwanted  effects  of  cathodic  protection  and  other 
regulatory bodies as defined by state statutes.  Unwanted effects of cathodic protection systems may 
include potential current drain in galvanic systems resulting in decreased protection performance and 
increased anode consumption rates or detrimental stray current effects from higher output impressed 
current systems.  

12.2. SYSTEM INSTALLATION PRACTICE  
The  installer  shall  be  familiar  with  the  specifications outlined  in  this  document and  covered  in  the 
relevant Australian Standards.  Works shall be completed in accordance with good industry practice 
and to the satisfaction of MWPA.  Additional requirements are as follows:  
 Any deviations from original design shall be first approved by MWPA and permanently 
recorded for future reference; 
 Installation of all electrical work shall be in accordance with local regulations and relevant 
standards;  
 Cable connections shall be clean, dry and free of damage at the time of connection; 
 Test point, anode and structure connections shall be mechanically secure and electrically 
conductive for the entire design life of the system; 
 All cable attachments shall be coated with an electrically insulating material that prevents 
ingress of moisture and shall be compatible with various structure coatings and have good 
adhesion to all surfaces; 
 All ground surfaces that are disturbed during the installation of reference electrodes or 
anode ground beds etc. shall be suitably reinstated. 

12.3. SYSTEM COMMISSIONING  
Contractors are to advise MWPA of all stages of the commissioning process including recording the 
performance  and  system  parameter  data  in  accordance  with  AS 2832.    An  example  format  of  the 
system record is provided in Appendix A.   

12.4. ONGOING SYSTEM PERFORMANCE MONITORING 
Table  13  provides  an  indicative  guide  to  monitoring  intervals  based  on  requirements  detailed  in 
AS 2382.1 to AS 2382.5.  This table is a guide only as monitoring intervals are ultimately determined 
by specific system performance.   

   

UNCONTROLLED WHEN PRINTED  29 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Table 13:  Recommended Monitoring Intervals 
Cathodic Protection System Monitoring Intervals 
Monitoring Intervals  Monitoring Intervals Impressed  
Year  Galvanic Systems  Current Systems 
New  Established  New  Established 
1  Undertake  N/A  Undertake  N/A 
Functional checks  Functional checks 
monthly to establish  monthly to establish 
satisfactory  satisfactory 
performance   performance 
2  Routine  6 to 12 monthly  Routine  6 to 12 monthly 
performance  depending on  performance  depending on 
monitoring 3  previous  monitoring 3  previous 
monthly intervals  performance  monthly intervals,  performance, adjust 
adjust system  system outputs 
outputs accordingly   accordingly 
3+  6 to 12 monthly  6 to 12 monthly  6 to 12 monthly  6 to 12 monthly 
depending on  depending on  depending on  depending on 
previous  previous  previous  previous 
performance  performance  performance, adjust  performance, adjust 
system outputs  system outputs 
accordingly if  accordingly 
required   
10   More frequent  More frequent  Check performance  Check performance 
monitoring maybe  monitoring maybe  of reference  of reference 
required if  required if  electrodes, replace  electrodes, replace 
decreased  decreased  if required.  More  if required.  More 
performance in  performance in  frequent monitoring  frequent monitoring 
noticed as anodes  noticed as anodes  intervals maybe  intervals maybe 
are consumed.   are consumed.   required if  required if 
Check performance  Check performance  reference  reference 
of reference  of reference  electrodes are  electrodes are 
electrodes, replace  electrodes, replace  replaced   replaced 
if required  if required 
10 to 15  Anodes may require  Anodes may require  6 to 12 monthly  6 to 12 monthly 
replacement, if  replacement, if  performance  performance 
anodes are replaced  anodes are replaced  monitoring  monitoring 
suggest monthly  suggest monthly  sufficient depending  sufficient depending 
monitoring until  monitoring until  on system  on system 
system returns to  system returns to  performance  performance 
steady state   steady state 

UNCONTROLLED WHEN PRINTED  30 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Cathodic Protection System Monitoring Intervals 
Monitoring Intervals  Monitoring Intervals Impressed  
Year  Galvanic Systems  Current Systems 
New  Established  New  Established 
20 to 25  Major system    6 to 12 monthly  6 to 12 monthly 
overhaul required,  performance  performance 
replace wiring  monitoring  monitoring 
junction boxes etc.,  sufficient depending  sufficient depending 
monthly system  on system  on system 
monitoring required  performance.  Will  performance.  Will 
until system returns  become more  become more 
to steady state    frequent if system  frequent if system 
components are  components are 
upgraded or  upgraded or 
replaced    replaced   
 

UNCONTROLLED WHEN PRINTED  31 
MWPA404 – Cathodic Protection Guideline 

 
 
 

13. QUALITY CONTROL AND QUALITY ASSURANCE 
– GUIDANCE TO INSPECTORS  
13.1. GENERAL REQUIREMENTS  
This section aims to list the minimum requirements for quality control and quality assurance to ensure 
the  cathodic  protection  systems  operate  with  minimum  maintenance  and  as  the  detailed  design 
intended.    

13.2. INSPECTION AND TESTING PLAN 
Section 10.3 AS 2831.1 and Appendix L provides detailed information on the required inspection and 
testing of Cathodic Protection systems.  As a minimum to ensure the correct operation of a cathodic 
protection system the following items should be verified regularly:  
 All cathodic protection system equipment is sound and operating as intended 
 Condition of continuity bonds where accessible 
 Earthing systems installed to control induced voltages and operating correctly  
 Foreign Structure bonds and stray current drainage bonds  
 All electrical equipment, including rectifiers, transformers and switchgear is kept clean to 
ensure adequate ventilation for cooling 
 Where a structure has been exposed for any purpose it shall be examined for corrosion and 
if coated, the condition of the coating should be assessed and repaired as required.  
 Periodic Potential Surveys should be undertaken as determined by the system designer as it 
is structure dependent refer Section 10.4 AS 2832.1, Section 10.3 AS 2832.3 and Section 7 
AS 2382.5 for maximum time intervals between cathodic protection potential surveys.   
An example test record form has been provided in Appendix B of this document.   

13.3. IDENTIFICATION AND TRACEABILITY 
The following certification and accreditation should be used to confirm the quality of the anodes and 
other system components before installation: 

The Anode manufacturer shall supply MWPA with the following items: 
 A copy of the anode certification (including mass, dimensions, core material data and 
chemical analysis of anode purity).    
 ISO 9001 accreditation of any company providing cathodic protection system components is 
recommended.  

13.4. COMPLIANCE INSPECTIONS AND TESTING 
The  purpose  of  an  independent  review  is  to  confirm  that  the  system  meets  the  intended  design 
requirements and protection criteria.  This shall include but not be limited to the following: 
 Current densities and current requirements are appropriate for all cathodic protection 
zones; 
 Anode materials and anode operational parameters are suitable for the intended purpose;   
 Confirm that the reference electrodes, cables, conduits, connections, DC power supplies 
(where impressed current system is used) and all other equipment are suitably rated; 

UNCONTROLLED WHEN PRINTED  32 
MWPA404 – Cathodic Protection Guideline 

 
 
 
 Ensure all drawings adequately reflect the proposed system and contain sufficient detail to 
enable correct installation of the system; 
 Ensure all installation procedures are adequate; 
 Ensure that the inspection and testing methods are appropriate to ensure the system will be 
installed and perform as designed; 
 Ensure all aspects of the design, specification, drawings, installation, commissioning, records, 
documentation and operation conform to the requirements of AS 2832 and this guideline.   

UNCONTROLLED WHEN PRINTED  33 
MWPA404 – Cathodic Protection Guideline 

 
 
 

14. DOCUMENTS TO BE SUBMITTED  
14.1. GENERAL 
14.1.1. SYSTEM DESIGN DOCUMENTATION  
Example system information, design documentation system operating provided in Appendix A.  Prior 
to the installation, the design documentation must be submitted to the relevant state authority such 
as the local electrolysis committee for review and accepted.  

14.1.2. COMMISSIONING DOCUMENTATION 
Commissioning documentation must be submitted to the relevant state authority once a system is 
commissioned.    Commission  reports  and  documentation  will  also  be  submitted  to  MWPA  and  any 
deviations from original design or intended operating parameters must be brought to the attention of 
the project engineer.   

UNCONTROLLED WHEN PRINTED  34 
MWPA404 – Cathodic Protection Guideline 

 
 
 

APPENDIX A 
EXAMPLE CATHODIC PROTECTION SYSTEM INFORMATION  
 

UNCONTROLLED WHEN PRINTED  35 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Example of Cathodic Protection System Design General Documentation for Immersed Structures – 
Part 1 
Structure Details 
Name of Structure:   
Materials of Construction:   
Structure Dimensions   
Diameter (mm):   
Wall Thickness (mm):    
Length (m):   
Field Joint Type (e.g. Fully welded, spigot and   
socket etc.): 
Design Life:   
Coating    
Surface Preparation:    
Application Method:   
Joint Coating:   
Temperature    
Design:   
Operational:    
Unintended Isolations:    
Structure Continuity:    
Cathodic Protection Design Details:    
Protection Criterion:   
Design Life:    
Coating Breakdown / Holiday Factor:   
Initial CD (mA/m2):    Mean CD:    Final CD:   
Initial CD (mA/m2):    
Initial Surface Area to be protected:    
Total Current Demand (A):   
 

   

UNCONTROLLED WHEN PRINTED  36 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Example of Cathodic Protection System Design Documentation for Immersed Structures –  
Part 2 – Site Details – Impressed Current Systems 
Location:   
Resistivity:   

Cables (core size, length, insulation) 
Ground bed Feeder:   
Structure Negative:   
Anode Header:   
Anode:   
Material:   
Design Life:   

Backfill  
Type:   
Resistivity:   

Layout 
Anode Orientation:   
Anode Spacing:   
Length:   
Design Resistance:   
Actual Resistance:   

T/R Unit Capacity 
Size:   
Power Source:   
Surge Protection:   
 

   

UNCONTROLLED WHEN PRINTED  37 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Example of Cathodic Protection System Design Documentation for Immersed Structures –  
Part 2 – Site Details – Galvanic Anode Systems 
Sacrificial Anodes Individual Site Details 
Location:   
Resistivity:   

Anode Details   
Material:   
Size:   
Installation Details:   
Connection Details:   
Backfill Type:   
Design Current:   
Design Life:   
 

UNCONTROLLED WHEN PRINTED  38 
MWPA404 – Cathodic Protection Guideline 

 
 
 

APPENDIX B 
EXAMPLE TEST INSPECTION RECORD 
 

UNCONTROLLED WHEN PRINTED  39 
MWPA404 – Cathodic Protection Guideline 

 
 
 
Example Test Record/Inspection Form 
Cathodic Protection System Name  
Date Inspected:   
Location:   
Overall Inspection Summary:   

Test Points 
Date Inspected:     
Location:   
Details of tests points operating,  need of   
upgrade or additional added to the 
structure:  

Anodes 
Date Inspected:    
Location:   
Details of repairs needed, replacement or   
additional cathodic protection equipment: 

Earthing Systems 
Date Inspected:   
Location:   
Details of any repairs, replacements or   
additional earthing systems: 

Structure Alterations 
Details of any modifications made to the   
structure which may affect the operation of 
the cathodic protection system: 

Structure Observations 
Evidence of corrosion, including the possible   
cause of corrosion: 

Structure Damage 
Any damage to the structure including the   
nature and extent of repairs carried out:  

Coating Survey 
Condition of any coatings at the time of   
inspection including the results of any defect 
surveys carried out: 
 

UNCONTROLLED WHEN PRINTED  40 

You might also like