M210543EN F User S
M210543EN F User S
M210543EN F User S
M210543EN-F
PUBLISHED BY
Vaisala Oyj
Street address: Vanha Nurmijärventie 21, FI-01670 Vantaa, Finland
Mailing address: P.O. Box 26, FI-00421 Helsinki, Finland
Phone: +358 9 8949 1
Fax: +358 9 8949 2227
© Vaisala 2015
No part of this manual may be reproduced, published or publicly displayed in any form
or by any means, electronic or mechanical (including photocopying), nor may its
contents be modified, translated, adapted, sold or disclosed to a third party without prior
written permission of the copyright holder. Translated manuals and translated portions
of multilingual documents are based on the original English versions. In ambiguous
cases, the English versions are applicable, not the translations.
The contents of this manual are subject to change without prior notice.
Local rules and regulations may vary and they shall take precedence over the
information contained in this manual. Vaisala makes no representations on this
manual’s compliance with the local rules and regulations applicable at any given time,
and hereby disclaims any and all responsibilities related thereto.
This manual does not create any legally binding obligations for Vaisala towards
customers or end users. All legally binding obligations and agreements are included
exclusively in the applicable supply contract or the General Conditions of Sale and
General Conditions of Service of Vaisala.
.
________________________________________________________________________________
Table of Contents
CHAPTER 1
GENERAL INFORMATION ............................................................................ 9
About This Manual ................................................................... 9
Version Information ............................................................... 9
Related Manuals ................................................................... 9
Documentation Conventions ............................................... 10
Safety ....................................................................................... 11
ESD Protection .................................................................... 13
Recycling ................................................................................ 13
Regulatory Compliances ....................................................... 14
Trademarks ............................................................................. 14
License Agreement ................................................................ 14
Warranty .................................................................................. 14
CHAPTER 2
PRODUCT OVERVIEW ................................................................................ 15
Introduction to Vaisala Present Weather Detector
PWD22/52 ................................................................................ 15
Hardware Structure ................................................................ 16
PWD22/52 Output ................................................................... 17
Product Nomenclature ........................................................... 18
Spare Parts ............................................................................. 18
CHAPTER 3
FUNCTIONAL DESCRIPTION ..................................................................... 19
Optical Measurements ........................................................... 21
Optical Arrangement ........................................................... 21
Transmitter Unit PWT11...................................................... 21
Light Receiver ..................................................................... 22
Additional Measurements ..................................................... 23
Vaisala RAINCAP® Rain Sensor ......................................... 23
Temperature Sensor ........................................................... 24
Background Luminance Sensor PWL111 (optional) ........... 24
BLSC Command ............................................................ 25
Continuous Mode ...................................................... 25
Day/night Switch Mode ............................................. 25
Disabling PWL111 .................................................... 25
BLCAL Command .......................................................... 26
Internal Monitoring ................................................................. 27
Built-in Tests........................................................................ 27
Memory Tests...................................................................... 28
Signal Monitoring ................................................................ 28
Hardware Monitoring ........................................................... 28
Monitoring Contamination ................................................... 29
Data Message Formats .......................................................... 29
VAISALA ________________________________________________________________________ 1
USER'S GUIDE ____________________________________________________________________
CHAPTER 4
INSTALLATION ............................................................................................ 31
Selecting Location .................................................................. 31
Grounding and Lightning Protection ................................... 33
Equipment Grounding ......................................................... 33
Internal Grounding ............................................................... 33
Grounding the Remote Units and the Communication
Cable ................................................................................... 33
Installation Procedure ............................................................ 34
Unpacking PWD22/52 ......................................................... 34
Storage ........................................................................... 34
Mounting .............................................................................. 35
Connections ............................................................................ 36
Connecting Cables .............................................................. 36
Basic Wiring ................................................................... 37
Power Supply ...................................................................... 39
Internal Heaters and Heaters for PWL111 ..................... 39
PWH111 Hood Heaters .................................................. 39
Communication Options ...................................................... 40
Serial Communication Settings ...................................... 40
Serial Transmission RS-232........................................... 40
Serial Multipoint Transmission RS-485 .......................... 41
Connection of the Maintenance Terminal ...................... 41
Relay Controls ..................................................................... 42
RELAY Command .......................................................... 44
Initial Settings ...................................................................... 45
Weather Parameters ...................................................... 45
Verifying the Installation ...................................................... 46
CHAPTER 5
OPERATION ................................................................................................. 49
Getting Started ........................................................................ 49
Operating Instructions ........................................................... 50
Entering and Exiting Command Mode................................. 51
OPEN ............................................................................. 51
CLOSE ........................................................................... 51
Message Types ................................................................... 52
Message 0 ...................................................................... 53
Message 1 ...................................................................... 53
Message 2 ...................................................................... 54
Message 3 ...................................................................... 54
Message 4 ...................................................................... 54
Messages 5 and 6 .......................................................... 55
Message 7 ...................................................................... 55
Automatic Message Sending............................................... 56
Message Polling ............................................................. 57
Precipitation Sums ................................................................. 58
Commands .............................................................................. 59
PWD22/52 Commands ........................................................ 59
HELP .............................................................................. 59
MES ................................................................................ 60
AMES ............................................................................. 60
Weather Related Commands .............................................. 60
WPAR ............................................................................. 61
WSET ............................................................................. 61
2 ___________________________________________________________________ M210543EN-F
________________________________________________________________________________
CLRS .............................................................................. 64
System Configuration Commands ...................................... 64
PAR ................................................................................ 64
CONF ............................................................................. 65
Hood Heaters ................................................................. 69
BAUD ............................................................................. 69
Analog Output ..................................................................... 69
Analog Output Modes .................................................... 71
Mode 0 ...................................................................... 71
Mode 1 ...................................................................... 72
Mode 2 ...................................................................... 72
Mode 3 ...................................................................... 73
Mode 4 ...................................................................... 73
Analog Output Calibration .............................................. 73
Maintenance Commands .................................................... 75
STA ................................................................................ 75
CAL ................................................................................ 76
CLEAN ........................................................................... 77
ZERO ............................................................................. 77
CHEC ............................................................................. 78
DRY ON and WET ......................................................... 78
DRY ON .................................................................... 78
WET .......................................................................... 78
TCAL .............................................................................. 79
HEAT .............................................................................. 79
Other Commands ................................................................ 80
TIME ............................................................................... 80
DATE .............................................................................. 80
RESET ........................................................................... 81
VER ................................................................................ 81
CHAPTER 6
MAINTENANCE ........................................................................................... 83
Periodic Maintenance ............................................................ 83
Cleaning .............................................................................. 84
Cleaning Lenses and Hoods .......................................... 84
Cleaning RAINCAP® ...................................................... 85
Calibration ............................................................................... 85
Visibility Calibration ............................................................. 85
Calibration Check ........................................................... 86
Calibration Procedure .................................................... 87
Repair ...................................................................................... 88
Removing and Replacing Optical Units .............................. 88
Removing PWT11 .......................................................... 89
Removing PWC22/52 .................................................... 90
Replacing RAINCAP® .................................................... 92
Cleaning and Maintaining Painted Surfaces ....................... 93
Preparing for Painting ......................................................... 93
Painting ............................................................................... 93
Commonly Used Vaisala Colors ......................................... 94
CHAPTER 7
TROUBLESHOOTING ................................................................................. 95
Common Problems ................................................................ 95
Message Indicating Warning or Alarm ................................ 95
VAISALA ________________________________________________________________________ 3
USER'S GUIDE ____________________________________________________________________
CHAPTER 8
TECHNICAL DATA .................................................................................... 101
Mechanical Specifications ................................................... 101
Electrical Specifications ...................................................... 101
Optical Specifications .......................................................... 102
Visibility Measurement Specifications ............................... 102
Weather Sensing Specifications ......................................... 103
Environmental Specifications ............................................. 103
APPENDIX A
INTERNAL MONITORING VALUES .......................................................... 105
APPENDIX B
PWC22/52 CONNECTORS AND JUMPER SETTINGS ............................ 109
APPENDIX C
NWS AND WMO CODE TABLES .............................................................. 113
APPENDIX D
CALIBRATING THE TS SENSOR ............................................................. 115
Checking TS Sensor Temperature ...................................... 116
Calibrating and Adjusting the TS Sensor .......................... 119
4 ___________________________________________________________________ M210543EN-F
________________________________________________________________________________
List of Figures
Figure 1 PWD22/52 Present Weather Detector ..................................... 16
Figure 2 PWD22/52 Block Diagram........................................................ 20
Figure 3 PWD22/52 Optical System ....................................................... 21
Figure 4 RAINCAP Block Diagram ......................................................... 23
Figure 5 PWL111 Block Diagram ........................................................... 26
Figure 6 LED Indicators on the PWC22/52 Board.................................. 27
Figure 7 Recommended Location of PWD22/52 Sensor. ...................... 32
Figure 8 Installing PWD22/52 on the Support Arm ................................ 35
Figure 9 Installing the Sensor on the Mast with Optional Mounting
Clamp ....................................................................................... 35
Figure 10 Testing the Connector .............................................................. 36
Figure 11 Cabling Principle ...................................................................... 38
Figure 12 Maintenance Cable .................................................................. 38
Figure 13 PWL111 Jumper Settings......................................................... 39
Figure 14 Relay Connection: PWD22/52 Supplies................................... 43
Figure 15 Relay Connection: External Relay Supply ............................... 44
Figure 16 Contents of Messages 0, 1, and 2 ........................................... 52
Figure 17 Analog Current Output Connection .......................................... 70
Figure 18 Analog Current Output Connection (External Current Source) 71
Figure 19 Assembling the Opaque Glass Plates...................................... 87
Figure 20 Removing PWT11 .................................................................... 89
Figure 21 Opening Box Screws ................................................................ 90
Figure 22 Removing the PWC15PB Protection Board ............................. 91
Figure 23 Removing the PWC22/52 Board .............................................. 91
Figure 24 Removing the Rain Sensor ...................................................... 92
Figure 25 Jumpers and Connectors on the PWC22/52 Processor/
Receiver Board ....................................................................... 111
Figure 26 Removing Internal Temperature Sensor for Calibration ........ 116
Figure 27 Removing External Temperature Sensor for Calibration ....... 117
VAISALA ________________________________________________________________________ 5
USER'S GUIDE ____________________________________________________________________
6 ___________________________________________________________________ M210543EN-F
________________________________________________________________________________
List of Tables
Table 1 Manual Revisions ....................................................................... 9
Table 2 Related Manuals ........................................................................ 9
Table 3 PWD Sensor Series Model and Performance .......................... 15
Table 4 Vaisala Present Weather Detector PWD22/52 Nomenclature . 18
Table 5 Optional Vaisala Present Weather Detector PWD Family
Nomenclature ........................................................................... 18
Table 6 Receptable Connector Default Wiring ...................................... 37
Table 7 Control Logic of Relay Controls 1 and 2 .................................. 42
Table 8 Control Logic of Relay Controls 1, 2, and 3 ............................. 42
Table 9 Default Communication Settings .............................................. 45
Table 10 Default Settings Commands .................................................... 45
Table 11 Display and Change Parameters Commands .......................... 46
Table 12 Settings and Corresponding Commands ................................. 50
Table 13 Routine Maintenance Commands ............................................ 50
Table 14 Command Set .......................................................................... 59
Table 15 Hardware Error Texts ............................................................... 76
Table 16 Warnings .................................................................................. 76
Table 17 PWD22/52 Mechanical Specifications ................................... 101
Table 18 PWD22/52 Electrical Specifications ....................................... 101
Table 19 Light Transmitter Optical Specifications ................................. 102
Table 20 Light Receiver Optical Specifications ..................................... 102
Table 21 Visibility Measurement Specifications .................................... 102
Table 22 Weather Sensing Specifications ............................................ 103
Table 23 Environmental Specifications ................................................. 103
Table 24 STA Message Values ............................................................. 105
Table 25 Internal Weather Types and Supported NWS Codes ............ 113
Table 26 WMO SYNOP Codes (Table 4680, WaWa) Used by
PWD22/52 .............................................................................. 113
Table 27 WMO METAR Codes (Table 4678) Used by PWD22/52 ....... 114
VAISALA ________________________________________________________________________ 7
USER'S GUIDE ____________________________________________________________________
8 ___________________________________________________________________ M210543EN-F
Chapter 1 ________________________________________________________ General Information
CHAPTER 1
GENERAL INFORMATION
Version Information
Table 1 Manual Revisions
Manual Code Description
M210543EN-F September 2015. This manual. Added information on the
two heating options. Added Appendix D describing how to
calibrate the TS sensor. Added cleaning and painting
instructions.
M210543EN-E Previous version.
Related Manuals
Table 2 Related Manuals
Manual Code Manual Name
M210542EN Vaisala Present Weather Detector PWD12, User's Guide
M210541EN Vaisala Visibility Sensor PWD10/20/50, User's Guide
VAISALA ________________________________________________________________________ 9
USER'S GUIDE ____________________________________________________________________
Documentation Conventions
Throughout the manual, important safety considerations are highlighted
as follows:
WARNING!
Warning alerts you to a serious hazard. If you do not read and follow
instructions very carefully at this point, there is a risk of injury or even
death.
CAUTION!
Caution warns you of a potential hazard. If you do not read and follow
instructions carefully at this point, the product could be damaged or
important data could be lost.
10 __________________________________________________________________ M210543EN-F
Chapter 1 ________________________________________________________ General Information
Safety
Vaisala Present Weather Detector PWD22/52 delivered to you has been
tested for safety and approved as shipped from the factory. Note the
following precautions:
WARNING!
WARNING!
Do not touch the surface of the RAINCAP® Rain sensor plate. When you
need to touch the sensors plate, for example during cleaning, touch first a
metallic part of PWD22/52 to discharge your body’s electrostatic load.
The measuring principle does not allow for proper ESD protection.
WARNING!
WARNING!
CAUTION!
CAUTION!
Tighten the connector properly. The cable connector must not swing in
relation to the fixed connector.
VAISALA _______________________________________________________________________ 11
USER'S GUIDE ____________________________________________________________________
CAUTION!
CAUTION!
This equipment generates and uses radio frequency energy and if not
installed and used properly, that is in strict accordance with the
manufacturer's instructions, may cause interference to radio and
television reception. The Present Weather Detector is designed to
provide reasonable protection against such interference in an airport
installation. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment causes interference to
radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
12 __________________________________________________________________ M210543EN-F
Chapter 1 ________________________________________________________ General Information
ESD Protection
Electrostatic Discharge (ESD) can cause immediate or latent damage to
electronic circuits. Vaisala products are adequately protected against
ESD for their intended use. However, it is possible to damage the product
by delivering electrostatic discharges when touching, removing, or
inserting any objects inside the equipment housing.
To make sure you are not delivering high static voltages yourself:
Recycling
Recycle all applicable material.
VAISALA _______________________________________________________________________ 13
USER'S GUIDE ____________________________________________________________________
Regulatory Compliances
The PWD series visibility sensors and present weather detectors are in
conformity with the provisions of the following EU directive(s):
Trademarks
RAINCAP is a registered trademark of Vaisala. Microsoft and
Windows are registered trademarks of Microsoft Corporation in the
United States and/or other countries.
License Agreement
All rights to any software are held by Vaisala or third parties. The
customer is allowed to use the software only to the extent that is provided
by the applicable supply contract or Software License Agreement.
Warranty
Visit our Internet pages for standard warranty terms and conditions:
www.vaisala.com/warranty.
Please observe that any such warranty may not be valid in case of
damage due to normal wear and tear, exceptional operating conditions,
negligent handling or installation, or unauthorized modifications. Please
see the applicable supply contract or Conditions of Sale for details of the
warranty for each product.
14 __________________________________________________________________ M210543EN-F
Chapter 2 __________________________________________________________ Product Overview
CHAPTER 2
PRODUCT OVERVIEW
VAISALA _______________________________________________________________________ 15
USER'S GUIDE ____________________________________________________________________
Hardware Structure
PWD22/52 is a self-contained instrument fastened to the side of a mast
and into a cross arm using mounting clamps.
1502-007
1 = Transmitter
2A = Pt100 temperature sensor in the tube (Option A)
2B = Pt100 temperature sensor in the radiation shield (Option B)
3 = Mounting clamp
4 = Place for Vaisala Luminance Sensor PWL111 (optional)
5 = PWR211 Vaisala RAINCAP® Rain Sensor
(PWR111 in PWD22M)
6 = Controller/Receiver
7 = Hood heaters (optional)
16 __________________________________________________________________ M210543EN-F
Chapter 2 __________________________________________________________ Product Overview
PWD22/52 Output
The PWD22/52 output is either:
VAISALA _______________________________________________________________________ 17
USER'S GUIDE ____________________________________________________________________
Product Nomenclature
Table 4 Vaisala Present Weather Detector PWD22/52
Nomenclature
Code Common Name Description
PWT11 Transmitter LED Transmitter circuit board
PWC22 Controller/Receiver Controller and photo diode circuit
board for PWD22
PWC52 Controller/Receiver Controller and photo diode circuit
board for PWD52
PWR211 RAINCAP® Double- A capacitive detector to sense
Plate Rain Sensor water droplets and/or moisture.
Two plate in a 90-degree angle
towards each other.
Spare Parts
For a list of spare parts, contact Vaisala Technical Support at
[email protected].
18 __________________________________________________________________ M210543EN-F
Chapter 3 ______________________________________________________ Functional Description
CHAPTER 3
FUNCTIONAL DESCRIPTION
Larger particles behave as reflectors and refractors and their effect on the
MOR must be handled separately. Usually these particles are
precipitation droplets. The optical arrangement of PWD22/52 allows
individual droplets to be detected from rapid signal changes. The
PWD22/52 software calculates the precipitation intensity by analyzing
the amplitudes of these changes. The intensity estimate is proportional to
the volume of the precipitation droplets.
VAISALA _______________________________________________________________________ 19
USER'S GUIDE ____________________________________________________________________
PWT11 Transmitter
(R)
RAINCAP
Rain Detector Optical Filter
Power
Serial line
20 __________________________________________________________________ M210543EN-F
Chapter 3 ______________________________________________________ Functional Description
Optical Measurements
Optical Arrangement
Transmitter Receiver
3 cm
4 cm
Sample volume
0403-103
PWD22/52 has a small sample volume of about 0.1 liters (see Figure 3).
This allows for independent particles to be measured at relatively heavy
precipitation intensities. The signal levels from the smallest precipitation
droplets can also be detected.
The feedback loop compensates for the LED temperature and aging
effects of the LED. On the other hand, the active compensation slightly
accelerates the LED aging. The initial LED current is set to a value that
ensures several years of operation without maintenance.
VAISALA _______________________________________________________________________ 21
USER'S GUIDE ____________________________________________________________________
Light Receiver
The Light Receiver consists of a PIN photodiode, preamplifier, voltage to
frequency converter, backscatter measurement light source LED, and
control and timing electronics.
22 __________________________________________________________________ M210543EN-F
Chapter 3 ______________________________________________________ Functional Description
Additional Measurements
PWD22/52 includes RAINCAP for estimating the water content of
precipitation, and a temperature sensor in the sensor cross arm or in an
external radiation shield (TS). Both additional sensors are measured and
interfaced by the PWC22/52 board. The RAINCAP temperature TDRD
is measured for the RAINCAP heating (drying) control, and the box
(PWC22/52) temperature TB is measured for the monitoring box heating.
0008-012
The heating element built into the surface heats the RAINCAP. The
heating power is controlled by software.
When the sensor element heating is switched off, they become highly
sensitive to ambient moisture. If the relative humidity of the air is more
than about 70 %, the surfaces produce a measurable signal even with no
precipitation. In PWD22/52 this is used as an estimated humidity
measurement. The estimated humidity is used to differentiate between
dust and mist.
VAISALA _______________________________________________________________________ 23
USER'S GUIDE ____________________________________________________________________
Temperature Sensor
The primary temperature sensor of PWD22/52 is a Pt100 thermistor. The
temperature is measured once a minute using a high resolution A/D
converter. The sensor temperature (TS) is used to select an initial default
precipitation type for the algorithm.
The sensor heaters are controlled in the same way as the other
PWD22/52 heaters.
24 __________________________________________________________________ M210543EN-F
Chapter 3 ______________________________________________________ Functional Description
BLSC Command
The background luminance sensor can be used in continuous or day/night
switch modes. When you give 1.0 as the BLSC value, the background
luminance measurement mode is continuous. When you give a zero as
the value, the measurement uses day/night switch mode.
Continuous Mode
The following command activates the sensor and gives a positive scaling
factor to the luminance value.
>BLSC 1.0
Disabling PWL111
The negative scale directs PWD22/52 to skip the background luminance
action. See the example below:
>BLSC -1
VAISALA _______________________________________________________________________ 25
USER'S GUIDE ____________________________________________________________________
BLCAL Command
PWD22/52 calculates the new BL scale if the current background
luminance in cd/m2 is known. The PWL111 sensor must be activated by
the BLSC command and the BLSC must be 1.0. where 12300 is the
current background luminance in cd/m2. Do not enter this command
repeatedly with less than one minute intervals. Use the command only in
stable weather with clear skies.
0310-001
26 __________________________________________________________________ M210543EN-F
Chapter 3 ______________________________________________________ Functional Description
Internal Monitoring
Built-in Tests
Built-in tests are included in the PWD22/52 operation to measure various
voltages and check the corresponding alarm and warning limits. Optical
contamination of both the transmitter and the receiver is continuously
monitored by measuring the backscattered light. An additional
transmitting LED is installed in the receiver for this purpose.
1206-026
The RxD and TxD LEDs are directly controlled by the serial line
hardware indicating all action in the serial line.
VAISALA _______________________________________________________________________ 27
USER'S GUIDE ____________________________________________________________________
Memory Tests
After resetting, PWD22/52 tests and clears its SRAM data memory. It
indicates an error by the Signal/Offset LED blinking. After 50 blinks
PWD22/52 tries to start the program anyway. Usually this causes a
watchdog reset, if the SRAM is really faulty.
Signal Monitoring
PWD22/52 measures the optical signal, receiver backscatter, and offset
as frequencies in about eight millisecond samples. As the measuring
times are 10 s, 1 s, and 4 s correspondingly, they must have different
numbers of samples in a batch. PWD22/52 checks that the frequencies
are not zero and signal sample count is bigger than the offset sample
count.
The user can follow the progress of the measurement sequence as the
Signal/Offset LED sequence of 10 seconds on, and 5 seconds off.
Hardware Monitoring
An eight-channel analog-to-digital converter is used to measure hardware
signals and voltages. The STA command displays the internal monitoring
values (See section STA on page 75).
28 __________________________________________________________________ M210543EN-F
Chapter 3 ______________________________________________________ Functional Description
Monitoring Contamination
PWD22/52 monitors both transmitter and receiver contamination by
measuring the backscattered signal.
The CLEAN command sets the clean reference values of the backscatter
signals. Deviation of the backscatter signal from the clean values is
proportional to the contamination on the lenses.
The alarm and warning limits are given in the configuration session. If
the alarm limit is exceeded, data is set to ///// and an alarm is generated.
The measured values are used only for warnings and alarms. No
compensation for the visibility signal is calculated.
PWD22/52 has seven standard message formats for data message output.
VAISALA _______________________________________________________________________ 29
USER'S GUIDE ____________________________________________________________________
30 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
CHAPTER 4
INSTALLATION
Selecting Location
Finding a suitable site for Vaisala Present Weather Detector PWD22/52
is important for getting representative ambient measurements.
VAISALA _______________________________________________________________________ 31
USER'S GUIDE ____________________________________________________________________
0308-003
32 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
Internal Grounding
The electronics enclosure of PWD22/52 is grounded by the power/data
cable jacket. The other parts of the sensor are in galvanic contact with
each other.
WARNING!
VAISALA _______________________________________________________________________ 33
USER'S GUIDE ____________________________________________________________________
Installation Procedure
This section describes only one installation alternative using a sensor
support arm and Vaisala weather station as the host computer.
Unpacking PWD22/52
The delivery contents are specified in the packing list included with the
delivery documents. The PWD22/52 equipment is usually delivered in
one case.
To unpack PWD22/52:
Storage
Store PWD22/52 in its package in dry conditions, not in the open air. The
storage conditions are as follows:
- Temperature -40 °C to 70 °C
- Relative humidity up to 95 %
34 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
Mounting
To mount PWD22/52, do one of the following:
0308-005
- Install the sensor on the mast with Vaisala Clamp Assembly. Note that
you need an optional Mounting Clamp for Pole Mast for the mast
assembly.
0308-004
VAISALA _______________________________________________________________________ 35
USER'S GUIDE ____________________________________________________________________
Connections
Connecting Cables
The PWD22/52 enclosure is equipped with a connector for connecting
the signal and power cable. The connector enables easy installation and
maintenance. The cable shield and connector is grounded to the
PWD22/52 enclosure to keep EMI levels within the specifications.
1502-006
CAUTION!
Tighten the connector so that the cable connector does not swing when
tightened.
Insulate the unused wires of the PWD22/52 mast cable from each other,
for example, by connecting them to void screw terminals in the junction
box.
36 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
Basic Wiring
The PWD22/52 cable has 16 connection wires.
VAISALA _______________________________________________________________________ 37
USER'S GUIDE ____________________________________________________________________
0104-002
0309-044
38 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
Power Supply
Power supply can be connected separately for the measurement
electronics and heating. This allows for the battery backup to be limited
to the measurement power supply.
Measurement electronics require 12 VDC ... 50 VDC. All the heaters can
take AC, DC, or rectified AC. The heater voltage dimensions are
specified below.
1206-035
VAISALA _______________________________________________________________________ 39
USER'S GUIDE ____________________________________________________________________
Communication Options
PWD22/52 has one serial line with two interfaces. The two-wire RS-485
is the standard interface. The PWD22/52 software is designed to allow
the RS-232 interface to be used as a service line, when the RS-485
interface is connected to the host computer.
Usually, PWD22/52 waits for input from both the RS-232 and RS-485
interfaces. Any character from the RS-232 interface disables the RS-485
communication for 10 seconds or until the line is closed by the operator.
Automatic messages are sent to both interfaces along with the messages
polled from the RS-485 interface.
- 9600 baud
- Even parity
- 7 data bits
- 1 stop bit
40 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
The wiring and wire colors are identical in PWD11 and PWD22/52.
VAISALA _______________________________________________________________________ 41
USER'S GUIDE ____________________________________________________________________
Relay Controls
PWD22/52 has three open collector relay controls that are controlled by
software using the alarms limits set in the CONF command.
The three PWD22/52 relay controls can be driven by the visibility limits.
The third relay control can also be driven by the hardware status.
- ALARM LIMIT 1
- ALARM LIMIT 2
- ALARM LIMIT 3
- RELAY ON DELAY
- RELAY OFF DELAY
The table below shows a control logic example of relay controls 1 and 2
and 3 when all the relay controls are driven by visibility limits.
42 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
When the third relay control output is set to be driven by the hardware
status, it pulls whenever a hardware alarm is detected. For details, see
section System Configuration Commands on page 64.
Relay 1
VB12V X3-9
(X4-5)
Control 1
X4-6
Relay 2
X4-7
X4-5
DGND X4-8
1008-015
Figure 14 illustrates the external relay connections when relay coils are
powered by PWD22/52. Voltage pin VB 12 V and relay controls 1, 2,
and 3 are wired by default.
The 100R series resistors limit the current of the relay ports. A typical
relay recommendation for the minimum operating or pick-up voltage
over the relay is around 0.8 *12 V. Thus the relay’s pick-up current must
be not more than 24 mA which means the coil resistance is 400 or more.
VAISALA _______________________________________________________________________ 43
USER'S GUIDE ____________________________________________________________________
+5...12V supply
Relay 1
Control 1
X4-6
X4-7
Relay 2
X4-5
DGND
X4-8
GND (12V)
1008-016
You can also use Ext Vb voltage, nominally 12V, to supply the relays.
Then PWD limits the corresponding current to < 200 mA.
RELAY Command
Set/display the relay control states.
Relay control 1 can be set on until ESC is pressed. See the example
below:
>RELAY 1 ON
44 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
Initial Settings
PWD22/52 typically interfaces with a host computer or data logger in an
automatic weather observing system. After the physical connection has
been made, the details of the communication can be configured in the
software. Suitable communication settings depend on the system
implementation.
By default the sensor is on a polled mode. That is, a data message is only
sent when the host computer requests one with a command.
Table 10 lists the commands for changing the default settings. For details
on the commands, see Chapter 5, Operation on page 49.
Weather Parameters
PWD22/52 has several changeable parameters, which control the
operation of the present weather algorithm and precipitation
measurement. The parameter values set at the factory have been tested
and found appropriate. They usually do not need to be changed. There
VAISALA _______________________________________________________________________ 45
USER'S GUIDE ____________________________________________________________________
Table 11 below lists the commands for displaying and changing the
parameters.
The low visibility alarm limits (3) are zero by default. That is, no alarms
are generated and no relays are activated.
If the output is not as in the above example, check the cabling and
baud rate of the service terminal (program). If wrong characters are
shown, try other baud rates, such as, 300, 1200, 2400, and 4800.
46 __________________________________________________________________ M210543EN-F
Chapter 4 _______________________________________________________________ Installation
VAISALA _______________________________________________________________________ 47
USER'S GUIDE ____________________________________________________________________
48 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
CHAPTER 5
OPERATION
Getting Started
Vaisala Present Weather Detector PWD22/52 is a fully automatic
instrument for continuous weather measurement. Usually, PWD22/52 is
set either to send a data message automatically or it is polled by a host
computer. In addition, a set of user commands is provided for
configuring and monitoring the system performance. These commands
can be given in the command mode (see Entering and Exiting Command
Mode on page 51).
VAISALA _______________________________________________________________________ 49
USER'S GUIDE ____________________________________________________________________
Operating Instructions
Normal operation of PWD22/52 does not require user intervention.
Operator commands are used during the initial setup, routine
maintenance, and troubleshooting.
When the sensor is installed, the user may need to change some default
settings. Initial Settings on page 45 describes the initial setup. Table 12
describes the settings and corresponding commands.
50 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
OPEN
If no device identifier (ID) is defined, type:
OPEN
CLOSE
Use the CLOSE command to release the line to automatic data messages
or polling commands.
VAISALA _______________________________________________________________________ 51
USER'S GUIDE ____________________________________________________________________
Message Types
Message 2 is the standard present weather message. The length of the
STA Message 3 depends on the possible alarm and warning states.
PWD22/52 adds frame strings to the polled and automatic messages. The
content of the frame strings is presented in the following:
S
H PW idSXmessage bodyEXCRLF
where
S
H = Start of heading (ASCII 1, non-printable character)
PW = PWD sensor identifier
= Space character
id = Unit identifier, 2 characters. If the ID is not defined, characters
space and 1 are shown.
S
X = Start of text (ASCII 2, non-printable character)
message body
E
X = End of text (ASCII 3, non-printable character)
C L
R F = CR + LF (ASCII 13 + ASCII 10)
S
H PW 1 S X 00 680 1230 E X C R L F
1234567890123456789012345
52 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
Message 0
Message 0 displays the one-minute average visibility and ten-minute
average visibility.
00 680 1230
------ 10 minute average visibility
------- one minute average visibility
- 1=hardware error, 2= hardware warning,
3= backscatter alarm, 4= backscatter warning
- 1= visibility alarm 1, 2= visibility alarm 2,
3=visibility alarm 3
Message 1
Message 1 displays the one-minute average visibility, instant
precipitation type, and the one-minute average water intensity.
00 1839 61 0.3
------ water intensity 1min ave, mm/h
--- instant precipitation type, 0 ... 99
------- visibility one minute average
- 1=hardware error, 2= hardware warning,
3= backscatter alarm, 4= backscatter warning
- 1= visibility alarm 1, 2= visibility alarm 2,
3= visibility alarm 3
VAISALA _______________________________________________________________________ 53
USER'S GUIDE ____________________________________________________________________
Message 2
Message 2 is the standard present weather message used in data loggers
or display units and set as a default at the factory.
Message 3
Message 3 is the same as the status message obtained by the STA
command. See status message description in section Maintenance
Commands on page 75.
Message 4
Message 4 is for replacing Fumosens E visibility sensors.
54 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
Messages 5 and 6
Messages 5 and 6 are for message emulation of MITRAS
Transmissometer.
Message 7
Message 7 is for aviation-specific purposes. The message format is same
as in FD12P message 7.
VAISALA _______________________________________________________________________ 55
USER'S GUIDE ____________________________________________________________________
where
Message_number = Valid range 0 ... 7. Selects the corresponding
message. Negative message numbers are
converted to 0. If only the message number is
given, the previous message interval setting is
used.
Message_interval = Given in multiples of 15 s (= measuring
interval). Therefore, intervals 15, 30, 45... are
valid. Other intervals are converted to
multiples of 15 s. The maximum sending
interval is 255 s (4 min 15 s).
Messages can also be displayed in the command mode with the MES
command, as described in section MES on page 60.
56 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
Message Polling
In the polled (CLOSE) mode, PWD22/52 sends a data message when the
host computer transmits a polling command. The message polling mode
is selected with the following command:
AMES Message_number 0
where
Message_number = Valid range 0 ... 7. Selects the corresponding
message as the default polled message.
Negative message numbers are converted to 0.
Message_interval = Use the negative or zero interval to disable
automatic sending when messages are polled.
For example:
AMES 0 0
The above command selects message 0 for default answer for the polling
and cancels the automatic sending.
where
C
R = ASCII character 13 hex (Carriage Return)
E
Q = ASCII character 05 hex (CTRL-E).
id = Selected in the configuration.
message number = This is optional.
C
R = ASCII character 13 hex (Carriage Return)
When the PWD22/52 unit number one (ID=1) is polled for message
number 3 (status), the command format is the following:
C E C
R Q PW 1 3 R
Use character 1 as the ID if the ID has not been set but a specific
message type is polled. This allows the PWD22/52 software to
distinguish the ID from the message number.
Use the CREQPWCR command only if one PWD22/52 unit is on the line (no
ID is set) and the default message is wanted.
VAISALA _______________________________________________________________________ 57
USER'S GUIDE ____________________________________________________________________
Precipitation Sums
PWD22/52 has no internal clock for automatic resetting of the sum data
at certain times. This can be done by the host with the following
command:
E
C PW 0 CCR
where
E
C = ESC (ASCII character 1B hex).
C
R = Carriage Return (13 hex.)
The host computer can also maintain its own sum calculated from the
continuous PWD22/52 data. This may be safer, if the PWD22/52 power
breaks often and resets the sums before the scheduled time. The water
sum automatically resets when it reaches 99.99 mm and the snow sum at
999 mm.
58 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
Commands
PWD22/52 Commands
HELP
Use HELP to get information about available commands.
VAISALA _______________________________________________________________________ 59
USER'S GUIDE ____________________________________________________________________
MES
After opening the line for operator commands (see section Entering and
Exiting Command Mode on page 51), use the MES command to display
a data message. See section Message Types on page 52 for message type
descriptions.
MES Message_number
For example, to choose the data message number 0, type the following:
>MES 0
AMES
The AMES command defines the message, which PWD22/52 transmits
as the automatic message or as the default polled message. See section
Automatic Message Sending on page 56.
60 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
WPAR
The WPAR command displays the present weather analysis parameters.
WEATHER PARAMETERS
PRECIPITATION LIMIT 40
WEATHER UPDATE DELAY 6
RAIN INTENSITY SCALE 1.00
HEAVY RAIN LIMIT 8.0
LIGHT RAIN LIMIT 2.0
SNOW LIMIT 5.0
HEAVY SNOW LIMIT 600
LIGHT SNOW LIMIT 1200
DRD SCALE 1.0
DRD DRY OFFSET 809.5
DRD WET SCALE 0.0017
WSET
Use the WSET command to modify present weather analysis parameters.
The WSET command asks for one parameter at a time, showing the
parameter name and the current setting. Accept the current value by
pressing ENTER. Add a new value by typing the value before pressing
ENTER.
VAISALA _______________________________________________________________________ 61
USER'S GUIDE ____________________________________________________________________
where
Precipitation limit = The threshold of accumulated particle
magnitudes (in PWD22/52 internal units) to
report the precipitation state 'on'. A typical
parameter value is 20 to 60 (max. 255). A
smaller value is more sensitive operation
and faster response at the beginning of an
event. It is also more sensitive to false rain
and snow reports.
Weather update delay = A time as multiple of 15 seconds, during
which the instant precipitation type is not
changed. The intensity may change faster.
Synop haze limit = Maximum visibility when mist or haze is
reported.
Metar haze limit = Maximum visibility when mist or haze is
reported.
Rain intensity scale = It is multiplied by the measured raw
intensity gives the reported precipitation
intensity (optical). The rain amount is scaled
with the same coefficient because the
amount is a direct integral of 15-second
intensities.
A typical value for the Rain intensity scale is
1.0. Since the optimal value depends on the
optical, optoelectronic, and electronic
parameters in a very complex way, no
applicable factory calibration method has
been developed yet.
Heavy rain limit = The minimum rain intensity (mm/h), when
the intensity is reported as heavy.
62 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
where
Light rain limit = The maximum rain intensity (mm/h), when
the intensity is reported as light. If rain
intensity is between the above heavy and
light limits, it is reported as moderate.
Snow limit = The minimum ratio of optical precipitation
intensity to surface sensor (RAINCAP®)
precipitation intensity, when precipitation is
snow.
A typical value for Snow limit is 5. Smaller
value directs PWD22/52 to report more wet
precipitation as snow.
Make the comparison after a few rain events with 5 mm or more of total
accumulated rain. Calculate a new scaling factor using the following
formula:
where
OLDSCALE = The old value of rain intensity scale.
REF_AMOUNT = The amount measured with the reference rain
gauge.
PWD_AMOUNT = The corresponding amount measured by
PWD22/52.
VAISALA _______________________________________________________________________ 63
USER'S GUIDE ____________________________________________________________________
CLRS
The CLRS command resets (to 0.00) the precipitation cumulative sums.
where
E
C = ESC (ASCII character 1B hex.
< AK = ASCII character (06 hex).
C
R = ASCII character (13 hex.)
id = Identification number of PWD, for example, id = 0
PAR
Use the PAR system parameters command to display the current system
parameters.
64 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
CONF
Use the CONF configuration command to set or update system
parameters and adjust calibrations, reference values, and limits. Use
password protection to limit the use of this command. New parameter
values are saved in non-volatile memory (EEPROM).
CONF
CONF password
If the previous password is known, the password can be changed with the
CONF password N command, where the N character stands for new.
VAISALA _______________________________________________________________________ 65
USER'S GUIDE ____________________________________________________________________
END OF CONFIGURATION
The output illustrates the response to the command when using PWD22.
With PWD52 the maximum visibility is 35000 meters. The system
responses are otherwise identical for PWD22 and PWD52.
66 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
VAISALA _______________________________________________________________________ 67
USER'S GUIDE ____________________________________________________________________
The alarm limits are also used to control the two (pull
down) alarm controls. Control 1 sets when alarm 1 is on.
Control 2 sets when alarm 2 is on. Control 3 sets when
alarm 3 is on. The controls are usually used to for external
relays. For details on relay logic, see section Relay
Controls on page 42.
68 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
Hood Heaters
By default 0, no hood heaters are used. The hood heater option is factory
installed and may be used or disabled in the CONF session. All the
PWD22/52 heaters are switched ON below 2 °C and off at 5 °C. When
using hood heaters, a separate 24 V heating power must be supplied.
Hood heating power is 30 W for each hood.
BAUD
Use the following command to change the baud rate and communication
type:
The new value is saved in EEPROM and it is used also after reset or
power up. The default baud rate set at the factory is 9600 bps (7E1). The
communication type definition is optional. It does not change if the baud
rate is changed.
The BAUD command displays the current baud rate and communication
type.
BAUD RATE: 9600 E71
Analog Output
Analog output is wired in the default configuration.
The analog output connection is set at the factory as shown in Figure 17.
You must do the differential measurement connection at the user's end,
which is also shown in Figure 17.
VAISALA _______________________________________________________________________ 69
USER'S GUIDE ____________________________________________________________________
1206-027
- VIO
- GRY/PNK
- RED/BLU
- PNK
- GRY
70 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
1206-028
MIN VISIBILITY defines the visibility value where the analog output
has its lowest value. In most cases this is 10, but other values can also be
used depending on the application.
MAX VISIBILITY defines the visibility value where the analog output
has its highest value. In most cases this is the visibility measurement
range of the sensor (20000 for PWD22 and 35000 for PWD52), but other
values can also be used.
Mode 0
Mode 0 indicates standard linear visibility to the current mode. The
maximum visibility must be higher than the minimum visibility as well
as the corresponding currents.
VAISALA _______________________________________________________________________ 71
USER'S GUIDE ____________________________________________________________________
Mode 1
Mode 1 is the logarithmic mode and it uses ln (visibility) values for the
output. The calculation is the following:
I out
= I min + (I range ⋅ X coeff ),
where
Iout = Current that flows to analog output current sink.
Imin = Specified lowest output current value (for example 4 mA)
Irange = Current range specified
(for example Irange = 20 mA - 4 mA =16 mA)
VIS i
ln
ln(VIS i ) − ln(VIS min ) VIS min
X coeff = = ,
ln(VIS max ) − ln(VIS min ) VIS max
ln
VIS min
where
VISi = Initial visibility value in meters
VISmin = Lowest visibility value specified in configuration
(for example 10 m or 100 m).
VISmax = Corresponding maximum visibility value (for example
2000 m or 20000 m).
Mode 2
Mode 2 is the extinction mode, which gives lower output for higher
visibility. The maximum visibility must be higher than the minimum.
The corresponding currents are automatically handled so that the lower
current corresponds to the maximum visibility. The calculation is the
following:
I out
= I max − (I range ⋅ X coeff ),
where
Iout = Current that flows to analog output current sink.
Imax = Specified highest output current value (for example 20 mA).
Irange = Current range specified
(for example Irange = 20 mA - 4 mA =16 mA)
72 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
VIS i
ln
ln(VIS i ) − ln(VIS min ) VIS min
X coeff = = ,
ln(VIS max ) − ln(VIS min ) VIS max
ln
VIS min
where
VISi = Initial visibility value in meters.
VISmin = Lowest visibility value specified in configuration
(for example 10 m or 100 m).
VISmax = Corresponding maximum visibility value (for example
2000 m or 20000 m).
Mode 3
Mode 3 is the non-linear Videograph mode . The visibility range from
100 m to 10000 m corresponds to the current range of 1 ... 0 mA.
Mode 4
Mode 4 is the non-linear Videograph mode . The visibility range from
180 m to 20000 m corresponds to the current range of 1 ... 0.1 mA.
PWD22/52 set two-bit patterns to the DAC circuit and asks for the
corresponding measured currents. If the higher current is less than
2 mA, PWD22/52 calculates the current range of 0 ... 1 mA. Otherwise, it
calculates the current range of 0 ... 20 mA.
VAISALA _______________________________________________________________________ 73
USER'S GUIDE ____________________________________________________________________
DAC scale 1
DAC scale 0
DAC scale 21
DAC scale 20
74 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
Maintenance Commands
The maintenance commands are used in installation, maintenance, and
troubleshooting. They are as follows:
STA
The STA command (or MES 3 command) displays the results from the
built-in test system as a status message.
VAISALA _______________________________________________________________________ 75
USER'S GUIDE ____________________________________________________________________
Table 16 Warnings
Warning Description
Backscatter Increased Receiver or transmitter contamination signal has
increased above the WARNING limit selected in the
configuration.
Transmitter Intensity LEDI signal less than -6 V.
Low
Receiver Saturated AMBL signal is less than -9 V.
Offset Drifted Offset Drifted
Visibility Not Calibrated Visibility calibration coefficient has not been
changed from the default value (see section CAL
below).
CAL
Use the CAL command to calibrate the visibility measurement. The
calibration is done using opaque glass plates with known scatter
properties. The plates belong to the PWA12 calibrator kit.
CAL Calibrator_signal_value
For example:
>CAL 485
76 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
The calibrator signal value is printed on the labels of the glass plates.
Typically the signal is close to 500 Hz. PWD22/52 calculates a new
scaling factor and stores it in the non-volatile memory (EEPROM).
If the PWC22/52 board has been changed and the status message shows
the VISIBILITY NOT CALIBRATED error, use FCAL instead of CAL
to make a factory-like calibration.
CLEAN
Use the CLEAN command to set the clean references for contamination
control . Give this command during maintenance procedures after
cleaning the lenses or after replacing the transmitter or receiver
electronics. This command has no parameters.
UPDATED
>
ZERO
Use the ZERO command when calibrating visibility to display the zero
signal status. This command has no parameters.
When the signal blocker of the PWA12 calibrator kit is installed to the
lens hood of the receiver (box), the PWD22/52 software checks for the
very low signal and low noise. If the signal or noise is out of the internal
check limits, an error message appears.
>
VAISALA _______________________________________________________________________ 77
USER'S GUIDE ____________________________________________________________________
CHEC
Use the CHEC command when calibrating visibility to display the one-
minute average signal frequency in hertz (Hz). This command has no
parameters.
Press ESC to terminate the display. If you press any other key, the
display pauses. In the beginning, the four-location buffer, which is used
to calculate the average, is filled with the first value.
DRY ON
Use the DRY ON command to set the reference level of the dry signal
for the RAINCAP® signal normalization calculation. When giving the
DRY ON command, the sensor surface and weather conditions must be
dry.
The DRY OFFSET value must be between 700 and 900, when the
RAINCAP® hardware operates normally. The DRY command without a
parameter just shows this parameter.
WET
The WET command without a parameter shows the scaling factor that
normalizes the RAINCAP® signal change from the dry state to the wet
state to be 1.00. A typical value is close to 0.0015.
78 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
The wet scale normalizes the measured signal range (DRY - WET) to
1.00.
TCAL
Use the TCAL command to set the ambient temperature.
>TCAL ↵
PWD responds
HEAT
Use this test command to test the heater control relays and the heating
elements and power. For example:
HEAT ON
Press ESC to stop the heater test and quit the test mode.
In warm conditions, do not leave the heater testing on for long periods of
time.
VAISALA _______________________________________________________________________ 79
USER'S GUIDE ____________________________________________________________________
Other Commands
TIME
Use the TIME command during maintenance to display the current
system time:
TIME
TIME hh mm ss
where
hh = hours
mm = minutes
ss = seconds
The time and date has to be reset after a power break. There is no battery
backup.
DATE
Use the DATE command to display the current date.
where
yyyy = year
mm = month
dd = day
80 __________________________________________________________________ M210543EN-F
Chapter 5 ________________________________________________________________ Operation
RESET
The RESET command makes the hardware reset by the watchdog
circuitry.
VER
The VER command shows the version of the software.
VAISALA _______________________________________________________________________ 81
USER'S GUIDE ____________________________________________________________________
82 __________________________________________________________________ M210543EN-F
Chapter 6 ______________________________________________________________ Maintenance
CHAPTER 6
MAINTENANCE
Periodic Maintenance
PWD22/52 is calibrated at the factory and no initial calibration is
required.
To release the line to automatic messages, use the CLOSE command. For
details, see Chapter 5, Operation on page 49.
VAISALA _______________________________________________________________________ 83
USER'S GUIDE ____________________________________________________________________
Cleaning
It is important to clean PWD22/52. No specific operations are necessary
before cleaning the sensor and it is possible to use the service terminal
while cleaning. Some erroneous data may, however, be generated. To
minimize this problem, restart PWD22/52 after cleaning by pressing
power OFF/ON.
The hardware alarm field of the data message (2nd character on the
message) indicates when cleaning is needed. See section Message Types
on page 52.
1. Moisten a soft, lint-free cloth with isopropyl alcohol and wipe the
lenses. Be careful not to scratch the lens surfaces.
Confirm that the lens heating works by checking that the lenses dry
after wiping.
2. Check that the hoods and lenses are free of condensed water, or ice
and snow deposits.
3. Wipe the dust from the inner and outer surfaces of the hoods.
4. After the optical surfaces are properly cleaned, give the CLEAN
command.
Alternatively, give the STA command and check that the Backscatter
CHANGE value of both the receiver and the transmitter is close to zero
(set to zero by the previous CLEAN command).
84 __________________________________________________________________ M210543EN-F
Chapter 6 ______________________________________________________________ Maintenance
Cleaning RAINCAP®
Clean Vaisala RAINCAPRain Sensor at least every six months, more
often if local conditions require it.
The measuring principle does not allow for proper ESD protection of the
RAINCAP® electronics, so you must follow the following instructions:
Calibration
PWD22/52 is calibrated at the factory. Normally, PWD22/52 needs no
recalibration as long as the circuit boards are not changed and there are
no warnings or alarms.
Visibility Calibration
The calibration is checked and adjusted with the PWA12 calibration kit.
The kit consists of a blocking plate and two opaque glass plates with
known scatter properties. The ZERO, CHEC, and CAL commands are
used in the procedure. The calibration procedure checks two points; zero
scatter signal and a very high scatter signal. The zero signal is obtained
using a blocking plate and the high signal using opaque glass plates.
VAISALA _______________________________________________________________________ 85
USER'S GUIDE ____________________________________________________________________
Calibration Check
The calibration check procedure determines whether or not the unit needs
calibrating. Before performing the calibration check:
1. Block the light path by placing the blocking plate in the receiver
hood and wait 30 seconds.
2. Give the ZERO command.
PWD22/52 responds as follows:
ZERO SIGNAL: OK
3. Move the blocking plate.
4. Install the calibrator plates on the lens hoods. See Figure 19 on
page 87.
5. Fasten the opaque glass plates to the hoods.
Note the signal value printed on the plates, you will need it during
the following steps.
6. Move away from the optical path and wait 30 seconds.
7. Give the CHEC command.
8. After one minute, read the displayed signal.
9. The signal value must be close to the one printed on the plates. If
the difference is less than 5 %, calibration is correct. If not,
continue with the calibration procedure.
10. Press the ESC key to terminate the CHEC command.
86 __________________________________________________________________ M210543EN-F
Chapter 6 ______________________________________________________________ Maintenance
0308-006
Calibration Procedure
If calibrating is needed according to the calibration check (see section
Calibration Check on page 86), calibrate the unit:
VAISALA _______________________________________________________________________ 87
USER'S GUIDE ____________________________________________________________________
Repair
This section describes how to remove and replace the optical units
PWT11, Transmitter, and PWC22/52 Controller/Receiver.
After replacing the optical units you need factory calibration. (See
section Calibration Procedure on page 87).
88 __________________________________________________________________ M210543EN-F
Chapter 6 ______________________________________________________________ Maintenance
Removing PWT11
To remove the transmitter:
1. Open the four countersunk screws and remove the transmitter cover
and the gasket.
2. Disconnect the control cable connector (2).
3. Loosen the set screw (3) to release the transmitter module (5).
4. Pull the module out of the transmitter head by prying it from the
back by a screwdriver.
5. Loosen the nylon screw (6) and slide the transmitter board (4) off
the module (5).
0308-007
VAISALA _______________________________________________________________________ 89
USER'S GUIDE ____________________________________________________________________
1. Slide the transmitter board (4) to the module (5) and tighten the
nylon screw (6).
2. Lightly grease the O-ring (5) surface on the optics module with
silicon grease.
3. Press the optics assembly into the transmitter. Be careful not to
touch the lens. Make sure that the module seats properly. If not,
lead it to the sink by pointed pliers.
4. Lock the module with an M4x4 set screw.
5. Connect control cable (1) and make sure the cable gasket seats tight
into its groove.
6. Check that all the optical surfaces, LED and lens, are clean.
7. Close the transmitter cover with the gasket by four counter sunk
screws.
Removing PWC22/52
1. Open the four box screws in the corners of the controller box. See
(1) in Figure 21.
.
0308-008
90 __________________________________________________________________ M210543EN-F
Chapter 6 ______________________________________________________________ Maintenance
1502-004
1 = PWC15PB
2 = Screws
1206-029
VAISALA _______________________________________________________________________ 91
USER'S GUIDE ____________________________________________________________________
Replacing RAINCAP®
1. Open the control box (see section Removing PWC22 on page 90).
2. Remove the two screws of the PWC15PB protection board, see
Figure 22 on page 91.
3. Unplug the rain sensor cables (X6 and X7).
4. Remove the two screws below RAINCAP®.
5. Remove RAINCAP® by pulling it out of the control box.
6. Reassemble in the reverse order. Note that the flat cable marked
with a stripe is connected to X6.
7. Calibrate the new RAINCAP® by giving the DRY ON command
as described in section DRY ON on page 78.
8. Re-install the PWC15PB protection board.
0312-112
92 __________________________________________________________________ M210543EN-F
Chapter 6 ______________________________________________________________ Maintenance
Vaisala recommends that you wash all the painted surfaces at least once a
year. Use only warm water or warm, mildly soapy water. Wipe with soft
cloth or sponge and rinse with clean water.
1. Clean the surface and remove any loose coating with a scraper and
a steel brush.
2. Use sandpaper on damaged areas and around the damaged area’s
edges.
3. Remove impurities, such as dirt and grease, with warm soapy
water.
4. Rinse with warm water.
The surface must be completely dry before starting maintenance painting.
Protect the surfaces that will not be painted with tape or paper.
Make sure the air temperature, the paint, and the painted surface are at
least +10 °C and the relative humidity below 80% during painting and
drying. Do not paint in rain or in direct sunlight.
Painting
After preparing the surface, coat the surface as soon as possible. Follow
your paint manufacturer’s instructions carefully.
VAISALA _______________________________________________________________________ 93
USER'S GUIDE ____________________________________________________________________
If you use other paints, make sure the paint is compatible with the
polyester powder coating.
94 __________________________________________________________________ M210543EN-F
Chapter 7 ___________________________________________________________ Troubleshooting
CHAPTER 7
TROUBLESHOOTING
Common Problems
CAUTION!
Servicing the equipment must be performed by qualified personnel.
Message Missing
1. Does your terminal have the right settings?
- Change the baud rate, for example, to 9600 bps.
- Check that you have 7 data bits, even parity, 1 stop bits.
2. Give the OPEN command (see section OPEN on page 51).
3. Give other commands to see if PWD22/52 is already in the
command mode.
4. Go to the site.
- Take the maintenance PC (terminal), tools, and the calibrator set
with you.
VAISALA _______________________________________________________________________ 95
USER'S GUIDE ____________________________________________________________________
96 __________________________________________________________________ M210543EN-F
Chapter 7 ___________________________________________________________ Troubleshooting
1. Check the condition of the hoods. If the hoods are twisted, consult
Vaisala.
2. Try to find a better direction for the receiver/transmitter optics. See
section Selecting Location on page 31.
3. Electrical fault. See items in section Message Exists but Visibility
Value Does Not on page 96.
VAISALA _______________________________________________________________________ 97
USER'S GUIDE ____________________________________________________________________
98 __________________________________________________________________ M210543EN-F
Chapter 7 ___________________________________________________________ Troubleshooting
VAISALA _______________________________________________________________________ 99
USER'S GUIDE ____________________________________________________________________
6. If the LEDs are not lit, check the internal connector connections of
PWD22/52. The following measurement can be done:
- Measure the input voltage:
X1-5 = power GND, X1-4 = power + V
7. If the LEDs are lit but the sequence starts again and again, try the
following:
- Check the cable end for short-circuit with neighboring leads.
Unused wires of the PWD22/52 mast cable must be insulated
from each other, for example, by connecting them to void screw
terminals in the junction box.
- Try with a power with a higher current supply capability (the
power supply may go to current limiting state for a short while).
- Try with a higher supply voltage (max. 55 VDC.) This helps the
starting current need.
Technical Support
For technical questions, contact the Vaisala technical support by e-mail at
[email protected].
CHAPTER 8
TECHNICAL DATA
Mechanical Specifications
Table 17 PWD22/52 Mechanical Specifications
Property Description / Value
Dimensions 199 mm (h) × 695 mm (w) × 404 mm (d)1)
Weight 3 kg
Mounting To a metal rod or directly to the mast.
Material Aluminum
1) Height × width × depth (with maximum options)
Electrical Specifications
Table 18 PWD22/52 Electrical Specifications
Property Description / Value
Maximum power 6 W, 12-50 VDC
consumption Optional luminance sensor: 2 W, 24 V
Optional hood heaters: 65 W, 24 V
Sensor electronics Lock-in amplifier.
LED power stabilizer.
Contamination monitor.
Lens heater.
Temperature sensor.
Outputs Serial data line may be used either as RS-232 or RS-
485 (2-wire) level signals.
Three relay controls (open collector).
Analog output
8-m power/data cable standard. The PWD22/52 end is
equipped with connector.
Output data Automatic or polled data messages.
Visibility, present weather, precipitation, and status
data.
Automatic message type and interval is selectable at
15 s ... n x 15 s (n < 18) intervals.
Auxiliary data Low visibility alarms in the data messages. Three
adjustable alarm limits to set the three relay controls.
Hardware status (fail/warning) in the data messages.
Third relay output can also be driven by hardware
status.
Optical Specifications
The operating principle of the device is to measure forward scatter at an
angle of 45°.
Environmental Specifications
Table 23 Environmental Specifications
Property Description / Value
Operating temperature -40 ... +60 °C
range
Operating humidity range Up to 100 % RH
Wind speed Up to 60 m/s
Sun orientation Sunlight into the light receiver must be avoided
APPENDIX A
INTERNAL MONITORING VALUES
Typical values come from factory testing and may change within the
given Min/Max limits. Fault limits give hints for troubleshooting.
VBB
Raw, unregulated 12V... 12 V / 15 V <12 V Switched-mode 1) Reset.
voltage in the 13V >15 V power supply is 2) Check
internal overloaded or connectors
transformer working wrong. and cable.
output VBB 3) Change the
measurement control unit
may also fail due PWC22/52.
to heavy
electrostatic
discharge to
RAINCAP® plate.
APPENDIX B
PWC22/52 CONNECTORS AND
JUMPER SETTINGS
X9 Reset
X10-1 2) +5 VA
X10-2 2) AUX: CPU ADC input (internally connected to X3-2)
X10-3 2) AGND
1504-013
APPENDIX C
NWS AND WMO CODE TABLES
NWS codes are used with intensity indicator '+' (plus) for heavy
intensity, '-' (minus) for light, and none (space) for moderate. For
example, 'R+' means heavy rain.
APPENDIX D
CALIBRATING THE TS SENSOR
The checking and calibration is carried out with the TS sensor removed
from the cross arm to avoid the possible heating effects by electronics or
hood heaters.
1502-009
1502-010
3. Let the TS sensor and the reference sensor stabilize for at least five
minutes.
4. Use the TCAL command without a parameter to check the TS
sensor temperature:
Enter
>TCAL
PWD responds with
>TS 1 1.0000 TS 0 0.00 TS -0.5
Where
TS 1 = always 1.0000
TS 0 = offset correction
TS = measured and corrected temperature
5. Compare the values. If the TS value differs more than 2.5 °C from
the reference sensor reading, proceed to Calibrating and Adjusting
the TS Sensor on page 119. If the TS value differs less than 2.5 °C
from the reference sensor reading, you do not need to calibrate the
sensor. Continue with step 6.
6. Insert the TS sensor back to its original place. Note that right after
the TS sensor is inserted back it may show a slightly higher
temperature than the reference.
Prepare an ice bath in a large enough (>1 liter) thermos container (glass
or polystyrene). Vaisala recommends preparing the container in a
laboratory before going out to the field.
1. Use a sturdy ramp or ladders where you can place the reference
sensor and the ice bath container and have your hands free.
3. Insert the reference probe in the ice bath. Let it stabilize and
compare the sensor reading with the value that was measured in the
laboratory.
4. When the reference sensor has stabilized, insert the TS sensor in
the ice bath and let both sensors stabilize for a few minutes. Stir the
mixture occasionally. Monitor the readings of both the reference
sensor and the TS sensor (by TCAL) and note when stabilized.
5. Input your reference T value in PWD by entering the TCAL
command with the value (for example, 0,0) as the parameter
>TCAL 0.0
TEMPERATURE SCALES
TS 1 1.0000 TS 0 -0.02 TS -0.0
If TS shows the temperature of the reference, the adjustment has
succeeded. The difference of +/-0.1 °C is acceptable.
6. Dry the TS probe and the reference probe and let the sensors
stabilize for at least five minutes. Repeat steps 5 and 6 described in
Checking TS Sensor Temperature on page 116.
7. Insert the TS sensor back to its original place. Note that right after
the TS sensor is inserted back it may show a slightly higher
temperature than the reference.
If the ice bath is prepared carefully, the ice bath method is accurate
enough and the TS sensor can be adjusted even without a reference
meter. However, if possible, Vaisala recommends that you use a
reference meter.
Vaisala recommends that you use the ice bath method for calibration and
adjusting. However, if it is not possible, you can calibrate with water
and/or isopropyl alcohol.
Instead of inserting the probe in ice bath, immerse the reference probe
and the TS sensor in a water container and let them stabilize for a few
minutes. Monitor the readings and note when they are stabilized.
*M210543EN*