Ups
Ups
Ups
380/400/415 V
Technical Specifications
01/2016
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
380/400/415 V
Table of Contents
Important Safety Information .....................................................................5
Safety Precautions .....................................................................................6
Technical Data .............................................................................................8
Model List ..................................................................................................8
Symmetra PX 96 kW 400 V ...................................................................8
Symmetra PX 160 kW 400 V..................................................................9
Input Power Factor ...................................................................................10
Efficiency (TÜV certified)...........................................................................10
Efficiency Curves ................................................................................10
Derating due to Load Power Factor ............................................................10
Batteries .................................................................................................. 11
Efficiency DC to AC............................................................................. 11
Battery Runtimes – Schneider Electric Battery Solutions ........................ 11
Battery Runtimes — Third Party Classic Battery Solution .......................15
Battery Discharge Current ...................................................................17
End of Discharge Voltage at 100% Load ...............................................17
Electrolyte Values ...............................................................................17
Communication and Management .............................................................17
Features ............................................................................................17
EPO and Input/Output Contacts ...........................................................18
Compliance..............................................................................................20
Regulatory Approvals..........................................................................20
Facility Planning ........................................................................................21
Input Specifications ..................................................................................21
Bypass Specifications ...............................................................................21
Output Specifications ................................................................................21
Modular Battery Specifications ..................................................................22
Classic Battery Specifications....................................................................22
DC Power Levels for Battery Sizing with Output Power Factor =
1........................................................................................................23
DC Power Levels for Battery Sizing with Output Power Factor =
0.8 .....................................................................................................23
Maximum Current with Battery at End of Discharge (A) ..........................23
Recommended Cable Sizes ......................................................................23
Recommended Upstream and Downstream Protection................................23
Single and Dual Mains Systems ...........................................................23
Physical ...................................................................................................24
Weights and Dimensions .....................................................................24
Shipping Weights and Dimensions .......................................................24
Clearance Symmetra PX 96 and 160 kW ..............................................24
Environmental ..........................................................................................24
Heat Dissipation .................................................................................25
Drawings ....................................................................................................26
Symmetra PX Single System with PDU with Modular Batteries.....................27
Options .......................................................................................................28
Hardware Options.....................................................................................28
Modular Battery Cabinets ....................................................................28
990–3879C-001 3
380/400/415 V
4 990–3879C-001
Important Safety Information 380/400/415 V
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990–3879C-001 5
380/400/415 V Important Safety Information
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream circuit breakers, battery circuit
breakers, cabling, etc.) and environmental requirements. No responsibility is
assumed by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The UPS System must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection against
overcurrent), or
• NEC NFPA 70
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Install the UPS system in a temperature controlled area free of conductive
contaminants and humidity.
• Install the UPS system on a non-inflammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant
heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
6 990–3879C-001
Important Safety Information 380/400/415 V
WARNING
HAZARD OF OVERHEATING
Respect the space requirements around the UPS system and do not cover the
product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
HAZARD OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
990–3879C-001 7
380/400/415 V Technical Data
Technical Data
Model List
Symmetra PX 96 kW 400 V
Symmetra PX 96 kW
8 990–3879C-001
Technical Data 380/400/415 V
990–3879C-001 9
380/400/415 V Technical Data
Efficiency Curves
10 990–3879C-001
Technical Data 380/400/415 V
Batteries
Efficiency DC to AC
96 kW 160 kW
Load kW
Number of bat shelves 16 32 48 64 80 96
9 68 29 17 11 8 6
990–3879C-001 11
Technical Data 380/400/415 V
96 kW 160 kW
I bat at bat nominal , 100% load 265 441
Electrolyte Values
Audible alarm Alarm when on battery : distinctive low battery alarm : configurable
delays
990–3879C-001 17
380/400/415 V Technical Data
18 990–3879C-001
Technical Data 380/400/415 V
990–3879C-001 19
380/400/415 V Technical Data
Compliance
Regulatory Approvals
• EN 50091-1.
• EN/IEC 62040–1: Uninterruptible Power Systems (UPS). General and safety
requirements for UPS, 2008 Operator access area.
• EN/IEC 62040–2: 2006 Uninterruptible Power Systems (UPS) Part 2.
Electromagnetic compatibility (EMC) requirements. Class C1–UPS.
• EN/IEC 62040–3: 2011 Uninterruptible Power Systems (UPS). Method of
specifying the performance and test requirements, 2001 Classifications; VFI-
SS-111.
20 990–3879C-001
Facility Planning 380/400/415 V
Facility Planning
Input Specifications
96 kW 160 kW
380 V 400 V 415 V 380 V 400 V 415 V
Connection type 3PH + N + PE
Bypass Specifications
96 kW 160 kW
380 V 400 V 415 V 380 V 400 V 415 V
Connection type 3PH + N + PE
Output Specifications
96 kW 160 kW
380 V 400 V 415 V 380 V 400 V 415 V
Connection type 3PH + N + PE
2. Input current is based on nominal voltage and rated load, batteries fully charged
3. Input current is based on nominal voltage, rated load and full battery charge current.
4. Integrated electronic current limitation functionality.
5. The following options can be selected: 40–60 Hz, 47–53 Hz, 49.9–50.1 Hz.
990–3879C-001 21
380/400/415 V Facility Planning
96 kW 160 kW
380 V 400 V 415 V 380 V 400 V 415 V
Total harmonic < 2% linear
distortion < 5% non-linear
(THDU)
End of discharge voltage at full load (VDC) +/- 154 (96 cells at 1.6 V)
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Do not mix battery types in the same installation.
Failure to follow these instructions can result in equipment damage.
6. Input current limit may lower charging capability in some line and load conditions.
7. 15 min 1.60 VDC 25 °C W/block
8. C10 1.80 VDC 25 °C Ah
22 990–3879C-001
Facility Planning 380/400/415 V
DC power in kW
DC Power Levels for Battery Sizing with Output Power Factor = 0.8
DC power in kVA
Static bypass input Q5 160 A gL type fuse 160 250 A gL type fuse 250
UPS output Q2 160 A gL type fuse 160 250 A gL type fuse 250
990–3879C-001 23
380/400/415 V Facility Planning
Physical
Weights and Dimensions
Environmental
Operation Storage
Temperature 0 to 40 °C -15 to 40 °C
24 990–3879C-001
Facility Planning 380/400/415 V
Heat Dissipation
NOTE: Full load heat loss at nominal mains and fully charged batteries.
Heat dissipation 1.68 (5748) 3.37 (11496) 5.05 (17244) 6.73 (22992) 8.42 (28741)
kWh (BTU/hr)
990–3879C-001 25
380/400/415 V Drawings
Drawings
NOTE: A comprehensive set of drawings is available on the engineering website at
engineer.apc.com.
NOTE: These drawings are for reference ONLY — subject to change without
notice.
26 990–3879C-001
Drawings 380/400/415 V
990–3879C-001 27
380/400/415 V Options
Options
Hardware Options
Modular Battery Cabinets
High-performance battery module for 400V Symmetra PX 48/96/160KW & 208V SYBT9–B4
Symmetra PX 100 KW
High-performance long-lige battery module for 400V Symmetra PX 48/96/160KW & SYBT9–B4LL
208V Symmetra PX 100 KW
Symmetra PX Modular battery cabinet for 400V PX 96/160kW & 208V PX 100kW for SYCFXR9
9 Battery Modules
Symmetra PX Modular battery cabinet for 400V PX 96/160kW & 208V PX 100kW with SYCFXR9–9
9 Battery Modules & Startup
Symmetra PX Modular battery cabinet for 400V PX 96/160kW & 208V PX 100kW for SYCFXR9–S
9 Battery Modules & Startup
Symmetra PX 96/160kW Classic battery cabinet with classic batteries A10 SYPBV96K160HA
Symmetra PX 96/160kW Classic battery cabinet with classic batteries B10 SYPBV96K160HB
Symmetra PX 96/160kW Classic battery cabinet (empty) for third party batteries10 SYPBV96K160H
Power Module
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 1080cm PDX316IEC-1080
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 120cm PDX316IEC-120
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 1200cm PDX316IEC-1200
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 240cm PDX316IEC-240
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 360cm PDX316IEC-360
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 480cm PDX316IEC-480
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 600cm PDX316IEC-600
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 720cm PDX316IEC-720
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 840cm PDX316IEC-840
Modular IT Power Distribution Cable Extender 3 Wire 16A IEC309 960cm PDX316IEC-960
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 1080cm PDX332IEC-1080
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 120cm PDX332IEC-120
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 1200cm PDX332IEC-1200
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 240cm PDX332IEC-240
28 990–3879C-001
Options 380/400/415 V
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 360cm PDX332IEC-360
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 480cm PDX332IEC-480
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 600cm PDX332IEC-600
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 720cm PDX332IEC-720
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 840cm PDX332IEC-840
Modular IT Power Distribution Cable Extender 3 Wire 32A IEC309 960cm PDX332IEC-960
IT Power Distribution Module 3x1 Pole 3 Wire 16A 3xIEC309 300cm, 360cm, 420cm PDM1316IEC-3P
IT Power Distribution Module 3x1 Pole 3 Wire 32A 3xIEC309 300cm, 360cm, 420cm PDM1332IEC-3P
IT Power Distribution Module 3x1 Pole 3 Wire 32A 3xIEC309 480cm, 540cm, 600cm PDM1332IEC-3P-2
IT Power Distribution Module 3x1 Pole 3 Wire 32A 3xIEC309 660cm, 720cm, 780cm PDM1332IEC-3P-3
Power Dist. Mod. 3x1 POLE 3 WIRE RCD 32A 3xIEC309 300CM, 360CM, 420CM PDM2332IEC-3P30R-
1
Power Dist. Mod. 3x1 POLE 3 Wire RCD 32A 3xIEC309 480CM, 540CM, 600CM PDM2332IEC-3P30R-
2
Power Dist. Mod. 3x1 POLE 3 Wire RCD 32A 3xIEC309 660CM, 720CM, 780CM PDM2332IEC-3P30R-
3
Power Dist. Mod. 3 Pole 5 Wire RCD 16A 30mA IEC309 1040CM PDM316IEC-30R-1040
Power Dist. Mod. 3 Pole 5 Wire RCD 16A 30mA IEC309 140CM PDM316IEC-30R-140
Power Dist. Mod. 3 Pole 5 Wire RCD 16A 30mA IEC309 320CM PDM316IEC-30R-320
Power Dist. Mod. 3 Pole 5 Wire RCD 16A 30mA IEC309 500CM PDM316IEC-30R-500
Power Dist. Mod. 3 Pole 5 Wire RCD 16A 30mA IEC309 680CM PDM316IEC-30R-680
Power Dist. Mod. 3 Pole 5 Wire RCD 16A 30mA IEC309 860CM PDM316IEC-30R-860
Power Dist. Mod. 3 Pole 5 Wire RCD 32A 30mA IEC309 1040CM PDM332IEC-30R-1040
Power Dist. Mod. 3 Pole 5 Wire RCD 32A 30mA IEC309 140CM PDM332IEC-30R-140
Power Dist. Mod. 3 Pole 5 Wire RCD 32A 30mA IEC309 320CM PDM332IEC-30R-320
Power Dist. Mod. 3 Pole 5 Wire RCD 32A 30mA IEC309 500CM PDM332IEC-30R-500
Power Dist. Mod. 3 Pole 5 Wire RCD 32A 30mA IEC309 680CM PDM332IEC-30R-680
Power Dist. Mod. 3 Pole 5 Wire RCD 32A 30mA IEC309 860CM PDM332IEC-30R-860
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 1040cm PDM3516IEC-1040
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 140cm PDM3516IEC-140
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 200cm PDM3516IEC-200
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 260cm PDM3516IEC-260
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 320cm PDM3516IEC-320
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 380cm PDM3516IEC-380
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 440cm PDM3516IEC-440
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 500cm PDM3516IEC-500
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 560cm PDM3516IEC-560
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 620cm PDM3516IEC-620
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 680cm PDM3516IEC-680
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 740cm PDM3516IEC-740
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 80cm PDM3516IEC-80
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 800cm PDM3516IEC-800
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 860cm PDM3516IEC-860
IT Power Distribution Module 3 Pole 5 Wire 16A IEC309 920cm PDM3516IEC-920
990–3879C-001 29
380/400/415 V Options
UPS Network Management Card with Environmental Monitoring and Out of Band AP9618
Management
30 990–3879C-001
Options 380/400/415 V
Configuration Options
• Unity power factor corrected
• TÜV-verified high efficiency (95% at 30% load)
• Internal N+1 redundancy
• Swappable battery and power modules
• Main and redundant intelligence modules
• Service
• Automatic internal bypass
• Dual mains input
• Top or bottom feed
• Line-up/remote modular battery cabinets
• Extended battery runtime available
• Service included
• Generator compatible
• Network manageable
• StruxureWare Central compatible
• Secondary network management card
• SmartSlot device management cards
• Optional modular PDU with maintenance bypass and power distribution
modules
990–3879C-001 31
Schneider Electric Limited Factory
380/400/415 V Warranty
Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-
remanufactured.
Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by “You” or “Your”) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.
Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned “AS IS” and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.
Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (“Specifications”). It is understood that the
Specifications are not warranties of performance and not warranties of fitness for a
particular purpose.
32 990–3879C-001
Schneider Electric Limited Factory
Warranty 380/400/415 V
Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was
caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage or
connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, start-up by non-Schneider Electric designated personnel, a
change in location or operating use, exposure to the elements, Acts of God, fire,
theft, or installation contrary to Schneider Electric recommendations or
specifications or in any event if the Schneider Electric serial number has been
altered, defaced, or removed, or any other cause beyond the range of the intended
use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF
LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED
UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER
ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER
ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,
SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE
CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER’S
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE
NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC
HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY
COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,
LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.
WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED
BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.SCHNEIDER ELECTRIC.com/support/contact/. Select your
country from the country selection pull-down menu. Open the Support tab at the
top of the web page to obtain contact information for customer support in your
region.
990–3879C-001 33