Cable and Cable Fault Locating - Part 3
Cable and Cable Fault Locating - Part 3
UK
THORNE & DERRICK UK
TEL 0044 191 490 1547 FAX 0044 477 5371
TEL 0044 117 977 4647 FAX 0044 977 5582
WWW.THORNEANDDERRICK.CO.UK
This is the third of a four part series on cable and fault locating technologies that are in common
use today. This installment is on using Time Domain Reflectometers (TDRs).
TDRs have been used in the CATV and Telecommunications industries for many years and are
now growing in popularity for troubleshooting a wide variety of cable problems. They also have
several other uses that can benefit the operations of utility companies. Heat tracing cables can be
inspected with this method, theft of service can be detected, cable lengths can be determined for
inventory purposes. Even metal loss on exposed neutrals can be located!
A TDR is the most convenient tool to find short circuits between conductors and open circuits in
the tested cable where there is no associated path to ground that can be used for 'A-frame' type
ground fault locating. A TDR is usually more accurate for cables in duct where the path to
ground may not be at the point of the fault but rather at an unrelated duct damage (i.e. crack or
joint).
The theory of a TDR is that it transmits a pulse of energy that travels or propagates along a cable.
A portion of the energy will reflect back to the sending end whenever it passes a relative change
in the impedance of the cable. The time the reflections take to return is proportional to the
distance. If we know the approximate speed of the pulse in the cable and multiply it by the time
the reflection takes to return, the distance to the anomaly is easily calculated. Most TDR
The polarity of the reflection also tells you more about the fault. A reflected pulse that increases
in amplitude (as in the above example) tells the user it is an open circuit at the problem. If the
pulse comes back pointing downward, this indicates a lowering of impedance or short circuit.
The speed of the pulse in the cable is not at the speed of light as we might expect but typically
closer to half that value. This speed measurement is usually called either 'Velocity of
Propagation' (VOP) or 'Propagation Velocity Factor (PVF). There are different methods of
expressing the speed, the two most common are as a percentage of the speed of light, the other is
in meters per microsecond. The impedance of a cable limits the speed or velocity of the pulse so
we need to review this topic. Cable impedance is different from resistance; it includes the sum
of all of the reactive resistance we encounter in a cable. The source of this reactance is from four
sources:
The single biggest factor affecting the impedance, and hence speed, is insulation material. For
example, signals in coaxial cable propagate at close to 85% of the speed of light, polyethylene
(PE) results in a speed of around 65%, and cross-linked PE (XLPE) is a little slower yet at
around 54%.
A TDR does require that there are at least two individual conductors in the cable under test,
insulated from each other. Multiple single conductors, not in a common jacket often can’t be
tested as there is too many impedance changes due to changes in the spacing. This may be
overcome by capturing a copy of the traces when the system is new and comparing it to future
results after the cable has failed.
TDRs do have a couple of limitations. The impedance of the fault must be quite different from
the normal impedance. Series faults have to be close to an open circuit, a corroded or 'green'
high-resistance area is often missed. Similarly, a fault to earth or another conductor must be
below approximately 300 ohms. Another is that the accuracy of the distance is very dependent
on the accuracy of the VOP selected. 1% inaccuracy means potentially digging a 5' hole to find
the fault if we are 500' away from the test point. Still another consideration is that a TDR gives a
distance to the fault but it does not locate the cable. For this reason, TDRs may be used in
conjunction with a cable locator and a measuring wheel to find the true path of the cable. Any
cable in slack loops and pole bases, including the 1 meter of depth, must also be accounted for.
Finally, the fault must be 'persistent', that is the fault must be there at low voltages. Arcing faults
that short only when high voltage is applied require the use of a high voltage surge generator also
known as a 'thumper'. Some modern thumpers have the equivalent of a TDR built into them to
reduce the number of surges required and thus reduce the electrical over-voltage stress on the
cables. Their use are covered next month.
Pulse Width is usually adjustable for a couple of reasons. A wider pulse will have more energy
and be able to test longer distances and show up smaller faults. The trade-off is that faults can be
difficult to detect if they are close to the normally occurring reflection caused by the test lead to
cable connection or close behind another fault. Narrow pulses give more useable resolution but
no more accuracy. An additional but less known use of this is that a narrower pulse has a higher
fundamental frequency. A cable that may pass a test with a wider pulse may have problems that
show up when a narrower pulse is used. These problems may affect the performance of upper
channel signal strength on CATV applications but be completely invisible at power frequencies.
Another advanced control is amplification. Control over the vertical amplification of the
displayed trace allows smaller faults with weak reflections to still be detected. Faults can be as
small as a pinch on coax and still show up.
A screen zoom function is desirable to allow more accurate placement of a cursor when
measuring distances. The resolution of the LCD screen will affect the accuracy of cursor
placement and the ability to zoom in to improve the resolution will give greater accuracy.
Two channels and/or memory settings give additional trouble-shooting ability. Due to their
design, or environment (temperature and moisture for example), some cables may show a 'noisy'
trace that is difficult to interpret. Comparing a trace on a bad phase to the equally difficult trace
on a phase known to be operational will often allow the fault to be detected. TDRs that can show
both traces at the same time or even better, mathematically subtracting one trace from the other,
make many faults show up very well.
Training. The best equipment manufactured can still not give the needed information if the
operators don't understand how to effectively use it. Make sure training and applications support
is available, included, and utilized when purchasing test equipment.
The uses of a TDR are just about limitless. Technicians and engineers in any industry using
cables can usually find ways of detecting and locating their problems. This includes fire
suppression and detection systems; aircraft, shipboard power and communications cables,
underground primary and secondary cable, street lighting, mine cables, heat tracing cable and
more.
A typical TDR application can be to locate an open circuit in a three conductor power cable in
duct. Because of the duct, there is no path to ground to use an a-frame. The graph below shows
two traces; one channel on the known good phase shows an open circuit at approximately 1200
meters, the other wire is open circuit at 629.6 meters thus easily showing the fault. Up to the
point of the fault the cable exhibit several reflections that when laid on top of one another are
easily diagnosed as being normal.
Next month we will be covering cable fault locating using a high voltage surge generator.
If anyone has cable or cable fault locating questions, please e-mail me at the address below and I
will send you a reply. With your permission, I would like to share some of these situations in
future articles.
World Technical Servicing Training
leaders support and repair
Radiodetection is a proud member Radiodetection equipment Radiodetection has a team of Product training for your
of the SPX group of companies, users have easy access to factory-trained service technicians operators and training personnel
which provide technical products technical support. A call to your and dedicated service facilities. is available on your site, or at
and service solutions worldwide. regional representative, or the Turnaround is fast, and costs are Radiodetection’s headquarters.
Radiodetection head office, will put very competitive. Training is with qualified
Radiodetection and its associated
you in contact with our team of instructors and each trainee
companies specialize in the design
field-experienced technical experts. receives a certificate to confirm
and manufacture of products for
they have received the training.
the location and maintenance of
underground pipes and cables. Our
aim is to be viewed as the supplier
of choice of ‘high performance’
quality equipment using advanced
product technologies. We are
also committed to both design
innovation and customer support.
WWW.THORNEANDDERRICK.CO.UK