Diesel Fire Pump Controller Series Fd4
Diesel Fire Pump Controller Series Fd4
Controllers are completely wired, assembled, and tested at the factory before shipment and
ready for immediate installation.
Data Logging
The controller includes two (2) separate data logs for Each event or alarm recorded in the event log shall have the
storing system data that is readable through the OID or following data recorded with the event/alarm:
copied to a computer equipped with an SD card reader. • Time and Date of Event or Alarm • Charger 1 Status
The 2 data logs are as follows: • System Pressure • Charger 2 Status
• Descriptive Text Message of • Battery 1 Status
Pressure Log: The pressure log provides a the Event/Alarm • Battery 2 status
continuous pressure record for 30 days. The pressure • System Auto Mode Status
log samples shall be time and date stamped and • Engine Running Status
stored in permanent non-volatile SD memory card.
The pressure log can be searched by each sample, by
minute, or by hour through the OID.
Options
Event Log: The event log is also stored on the SD Option H: Space Heater
memory card. It will hold a maximum of 3000 events. If the ambient atmosphere is especially damp, a space
These events can include, any of the following events/ heater rated at 100 watts may be supplied to reduce
alarms: moisture in the cabinet. A thermostat is supplied
as standard with this option. A humidistat may be
• BATTERY 1 FAULT • SYSTEM AUTO MODE substituted if specified.
• BATTERY 2 FAULT • ENGINE LOCKOUT SIGNAL
• BATTERY 1 LOW VOLTAGE • SYSTEM AUTO MODE
• BATTERY 2 LOW VOLTAGE • SYSTEM MANUAL MODE
Option N: Step-Down Transformer
• CHARGER 1 FAULT • SYSTEM OFF MODE When AC voltage exceeds 240 VAC single phase, and
• CHARGER 2 FAULT • SYSTEM TEST RUN integral transformer may be provided for operation
• AC POWER FAIL • ALARM RESET from 380 to 600 VAC 50/60 Hz input. Exact voltage
• ENGINE OVERSPEED • LOW PRESSURE CONDITION and frequency must be specified when ordering.
• ENGINE FAILED TO START • LOW PRESSURE START
• ENGINE QUIT • DELUGE START
• ENGINE LOW OIL PRESSURE • REMOTE START Option W: 24 Inch (609.6 mm) Legs
• ENGINE HIGH WATER TEMP • AC POWER FAIL START Provided for free standing installations when wall
• PRESSURE DROP • HORN SILENCED mounting is not practical. If specified, lifting eyes may
• STOP PUSHBUTTON • PRESSURE TRANSDUCER also be supplied.
PRESSED FAULT
• SPEED SWITCH FAILURE • CONTACTOR COIL FAILURE
• CLOGGED WATER • ECM FAILURE Enclosure
STRAINER • ECM WARNING NEMA type 4X (Painted Cold Rolled Steel) and 4X
• FUEL INJECTION FAULT • ECM SWITCH IN ALT (304 or 316 Stainless Steel) enclosures are also
• FUEL TANK LEAK available.
Example: FD4-H-24VDC-NEG-120VAC-60HZ
FD4 -- Model Type
- X -- Option Designation(s)
- xVDC -- DC Voltage: 24VDC or 12VDC
- NEG -- Ground Polarity (available only in negative ground)
- xxxVAC -- AC Voltage: 120 - 600
- xxHZ -- Frequency: 50 or 60
Information required with order: 1) Engine Manufacturer and Model Number, if engine is not UL Listed/FM Approved
2) Engine Battery (12 or 14 VDC) 3) Available Single Phase Voltage 4) Options, if any (complete description)
General Controller Description »» The system status data shall be displayed on The internal logic of the controller shall be
The Fire Pump Controller shall be factory the OlD. The displayed items shall include: capable of operation in a temperature range
assembled, wired and tested as a unit and Speed Switch Failure, Contactor Coil Failure, of 4.4ºC to 50ºC and high, non-condensing,
shall conform to all requirements of the System pressure, Battery 1 Voltage, Battery humidity levels.
latest edition of NFPA 20 and be Third Party 2 Voltage, Battery 1 Charger Amps, Battery
Listed by Underwriters Laboratories (UL) 2 Charger Amps, Current time and date, Controllers shall be manufactured by Metron -
and Approved by Factory Mutual (FM). The Number of starts, Total engine run hours, A Division of Hubbell Industrial Controls, Inc.
controller shall be available for either 12VDC Displayed countdown timers for:
or 24VDC systems Sequential engine start and engine stop,
and Time until AC Power fail start, Status of
Controller Equipment Features Automatic Stop Setting. LED indication of
The controller shall include the following Loss of DC Power. Audible horn with horn
standard features: silence feature for silenceable alarms.
»» NEMA Type 4 watertight metal wall mount »» Lamp test feature
enclosure »» English or Spanish languages selectable
through the OlD
»» Dual Battery chargers, 10 amp
»» Microprocessor based logic with real time/
microprocessor temperature compensated
date
with integral volt/amp digital display and
»» Audible horn with horn silence feature for
integral LEDs for indication of AC Power
silenceable alarms.
On and Battery Power On.
»» Lamp test feature.
»» Two outer door mounted crank pushbuttons
and two inner panel mounted battery on/off »» English or Spanish languages selectable
switches through the OlD.
»» Outer door mounted key operated AUTO, »» Microprocessor based logic with real time/
OFF, MANUAL, mode selector switch date clock capable of running a minimum
of 14 days without DC power connected to
»» Operator Interface Device (OID) with 4 lines
controller and non-volatile flash memory to
by 20 character display with large character
permanently store the continuous pressure
backlit LCD capable of being read in both
log, event log, alarm log and all user
direct sunlight or dark lighting conditions
changeable set points and system data.
»» 12 pushbuttons for easy screen navigation, Battery backup of any kind not allowed.
alarm reset, and horn silencing
»» Input and output status LED’s to provide
»» Multicolored LED’s for alarm and mode visual indication of each discrete input’s or
annunciation. output’s on/off status.
»» LEDs shall be labeled with removable »» One RS485 Serial Port.
labels to allow for easy field modification if
»» MODBUS Communication Protocol via
additional alarms and/or language changes
RS485 port.
»» All controller settings shall be
»» All wiring terminals on PCB’s shall be
programmable through the OlD and shall
removable type.
be protected by two password levels
»» 600 PSI rated.
»» All features shall be enabled or disabled
through the OlD, no jumpers or external
wires shall be needed or allowed to activate
or deactivate a feature.
www.metroninc.com
FD4 0815 © Hubbell Incorporated. All rights reserved. Specifications subject to change without notice. Printed in USA.
METRON OID100
METRON OID202
1 2 3
SYSTEM SYSTEM CHANGE/
CONFIG PILOT
STATUS LOGS ENTER
SILENCE/
RESET/
AUTO MANUAL TEST LAMP
ESC
TEST
METRON
A Division of:
Hubbell ICD, Inc.
4301 Cheyenne Dr., Archdale, NC 27263
METRON
A Division of:
Hubbell ICD, Inc.
4301 Cheyenne Dr., Archdale, NC 27263