852 PDF
852 PDF
852 PDF
ELECTRIC
DIESEL
MOST COMMON TYPES OF
FIRE PUMPS
ELECTRIC
Electric driven fire pumps are
more compact.
Simple to design and maintain.
Less of Environmental
headache.
No need for external fuel
storage facilities. But,
Entirely infrastructure
dependent.
DIESEL
Requires combustible liquid fueling /
refueling area.
Requires a dedicated fuel storage for
its operational sustainability (5.07
liter/Kw or 1 gal/HP plus 10% - NFPA
20). However,
Diesel fire pump can operate
anywhere as long as there is fuel.
When is a Fire Pump
Required?
When is a Fire Pump Required?
Where:
Cmil – is the conductor size in circular mils
K – is the conductor constant 12.9 ohms for copper
I – is the current through the conductor
D – is the distance of the pump from the source in
feet to controller or motor terminal
VD – is the allowable voltage drop
Note:
1 circular mil is approximately equal to:
5.067×10−4 square millimetres
Section 6.951.14 (e) & (f) Wiring Methods
Conductor runs shall be protected, either run
outside the building or in Rigid Steel conduit or
intermediate conduit encased in 50mm (2’’)
concrete when run inside the building .
All wiring from motor controllers to the pump
motors shall be in:
• rigid metal conduit or
• intermediate metal conduit or
• liquid tight flexible metal conduit or
• liquid tight flexible non-metallic conduit type LFNC-B or
• fire resistant cables (MI – mineral insulated) – can be
used to add to the reliability of the fire pump wiring.
1 hour fire rating is required for Fire pump
wiring.
C. Overcurrent protection for individual
sources must comply with 6.95.1.4(a) or (b):
(1) Individual Sources. The OCPD(s) must be
selected or set
Also, the trip point for the circuit breaker must not be
field adjustable.
Sizing the automatic transfer switch
1. Initially, size the ampere rating of the transfer switch to be equal to or next
size greater than the required feeder conductors.
2. Verify that the over current device used on the utility line side, CB1, does
not exceed the maximum allowable circuit breaker or fuse size allowed for
the transfer switch. If it does, increase the transfer switch rating to one that
includes CB1 as an allowable upstream breaker.