- “Ty Mott MacDonald am Fon Uo Tato seca Can Gent ec 6 eCopt a QATAR POWER TRANSMISSION SYSTEM EXPANSION PHASE XI CONTRACT CONTRACT NO.GTC/488G/2012 ADDENDUM-S14 EQUIPMENT POWER TRANSFORMER-| | DOCREF | PHIL-8G-10-25-006 [REV [A D SITE LOCATION 6611 KV AL KHALDIYAH sis |PATE __loulos| 2016. PAGENO | of 2 SITE ACCEPTANCE TEST FORMS FOR 66/11kV 40MVA POWER TRANSFORMER 5. Vector Group Test (Applicable Standard - LEC 60076-1:2011- Clause 11.3) Test Set Up es Test procedure * Do the connections as shown in the fig * Select the normal tap * Isolate primary/secondary/neutral earth. * Short R-r, Apply 3 phase 415V to R-Y-B HV side of the terminals. ‘* Measure the voltages given below table, + From the measured voltages check the following conditions Condition to check for Dyn B-b=B-y Y-y< Yo Y-y [Tuo | Bb una] Bm [asp ‘Compare the Values for the Following Combinations 1. Bb=By 2.Y-y< Yor 3. Y-y