Ethernet Interface in VAMP 321, Configuration Instructions v1.2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

[ Application note ] Ethernet interface in VAMP 321, configuration

instructions v1.2

Ethernet interface in VAMP 321, configuration


instructions v1.2

1 Overview
This document applies to VAMP 321 Arc flash protection main unit.
The document describes how to set up the Ethernet communications and gives some
general guidelines of connecting the device to the Ethernet network.

VAMP 321 is the main unit of the Arc Flash protection system. The system usually
comprises of VAMP 321 and some I/O units connected to it. Only VAMP 321 main unit is
connected to an Ethernet network. There is internal communication between the VAMP
321 and the I/O units, but this should not be mixed with the external Ethernet
communications.

Figure 1.1. VAMP 321 main unit takes care of the external communications of the Arc Flash protection
system.

2 Communication interface in VAMP 321


VAMP 321 can be ordered with different types of communication options. The
communication option cards are in slots 9 and 10 at the back of the device. The type of
the option is defined in the ordering code. The different possibilities are shown in figure
2.1. For example ordering code VAMP 321 ABAAA-AAACB-A1 defines the

1 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2

communication option card “RS-232 + Ethernet RJ-45” for slot 9 and “RS-232” for slot 10
(see figure 2.2.)

Figure 2.1. Explanation of VAMP 321 ordering code – showing the two digits defining the communication
options.

Figure 2.2. Location of the Ethernet port at the back of the device.

3 Configuration
The configuration of the Ethernet port is done with VAMPSET setting tool. VAMPSET can
be connected to the relay either via USB interface to the front panel connector or via the
Ethernet network. The version of VAMPSET that is needed will vary depending on the

AN321.EN002 2
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2

version of the device firmware (for instance, firmware version 10.108 requires VAMPSET
version 2.2.85 or higher).

3.1 Setting the main parameters IP Address, TCP port, and Network Mask
The configuration is started by setting the appropriate values for the IP address (IP
address of the VAMP device), NetMask (Network Mask) and Gateway (IP address of the
gateway).
Please note that the IP address and network mask must be correctly set in reference to
the client system in order to get the communication to work properly. When adding a
device to an existing network, please consult with a network administrator to obtain proper
IP addresses that you are allowed to use.
Also note that by default the devices do not support DHCP, in contrast to PC’s, which are
able to obtain different IP addresses each time they are connected to a network. This may
cause trouble if the communication is tested in an office network. The use of a separate
test network is recommended.
Next, the protocol to be used is activated for one of the two instances of TCP ports. As an
example see Figure 3.1, which show settings when ModBusTCP is used.

Figure 3.1 Ethernet and TCP port instances configuration menu in VAMPSET.

A change of protocols on any port, serial port or TCP port instance, will require a reboot of
the device.

Once the protocol has been activated, the protocol specific parameters will become
selectable in VAMPSET (the list to the left in the VAMPSET window). See figure 3.2 for a
screenshot of this menu in case ModbusTCP is used.

3 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2

Figure 3.2. Protocol specific parameters for ModbusTCP.

Figure 3.3. Examples of ModbusTCP data mapping shown by VAMPSET.

4 Connection to Ethernet network

The Ethernet network could be described as a network of one or more Ethernet switches,
which are connected to each other. The switches are connected to each other either with
copper cabling (RJ-45 connectors) or with fiber optic cabling. An example is shown in
figure 4.1. VAMP 321 devices are connected to the Ethernet switches of the network.

AN321.EN002 4
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2

Figure 4.1. An example of an Ethernet network and connection of three VAMP 321 devices to it.

Normally the maximum distance that can be used with copper cabling is 100m and
maximum distance with multimode fiber optic cabling is about 1km. With single mode
cabling distances up to tens of kilometers can be reached. The maximum distances that
can be reached with different type of fiber optic cabling depends on the type of the cable,
number of connections on the signal path and type of light transmitters and receivers used
in the Ethernet switches. For more information about switches please read e.g. the
datasheets of the RS900 switch from Ruggedcom.

5 Testing Ethernet connection with SimpleTester


5.1 Simple Tester overview
Simple Tester is a basic protocol testing tool (for PC) that supports several different
protocols, including ModbusTCP. Simple Tester can be used to test reading data from
holding registers, writing to holding registers, viewing events and performing clock
synchronization from the PC. The user interface of Simple Tester with Modbus selected as
protocol is shown and explained in figure 5.1.

5 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2

Figure 5.1. The user interface of Simple Tester with ModBus selected as protocol.

5.2 Connecting with Modbus TCP


To connect a device with Modbus TCP, the device Ethernet port and TCP port instances
must be configured as described in the previous sections of this document. Also, an
Ethernet connection (physical) to the relay from the PC running Simple Tester must be
made.

To connect follow these steps:

1. Select “ModBus” in the Protocol selector.


2. In the Connection type selection, mark TCP Connection and set the Host to the IP
address set on the device.
3. Set the Port to the same TCP IP port as configured on the device. (“IP port for
protocol”).
4. Set the Slave ID in the Modbus Slave ID selector.
5. Press “GO”.
6. A successful connection is indicated by an “OK” in the rightmost connection status
indicator furthest down in the Simple Tester window. An example of a successful
connection is shown in 5.2.

AN321.EN002 6
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2

Figure 5.2. Simpe Tester with ModbusTCP connection.

5.3 Reading data


To read data, follow these steps.
1. Set Type of data, (HR = Holding register).
2. Select which Index to read, to read some data item from a VAMP device (refer to
the data mapping provided by VAMPSET).
3. The Count value indicates how many consecutive indices are to be read. For
instance, setting Index to 2001 and Count to 2 will display the values of Index 2001
and Index 2002 in the Values-box.
4. Press the Read button to manually initiate a read. Reads can also be done
cyclically, by checking the Cyclic read box. The length of one cycle can be changed
by setting a value in the Cycles field (seconds).

7 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2

Figure 5.1 features an example of reading the Alive Counter (HR 2001) cyclically every
three seconds.

Figure 5.1: Performing a cyclic read on the Alive Counter with Simple Tester.

5.4 Writing data


To write data, follow these steps:
1. Set Type of data to be written. (HR = Holding register).
2. Select which Index to write to.
3. Set Value to be written.
4. Press the Write button.
5. The Status field will indicate if the operation is successful.

Figure 5.2 features an example of a write of the value 1 to Virtual Input 1 (holding register
3427).

AN321.EN002 8
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2

Figure 5.2: Simple Tester after write to Virtual Input 1.

Note that the Event view of Simple Tester now contains an event, corresponding to “Virtual
Input 1 ON”. If there are events in the event buffer when connecting Simple Tester, these
will be listed in the event view. New events triggered by writes done with Simple Tester will
also show up.

Furthermore, a clock synchronisation can be performed with Simple Tester. This is done
by setting the desired behaviour in the Time Controls (see figure 5.1). The two leftmost
fields are used for setting the time manually, but the time can also be taken from the PC,
by checking the PC Time checkbox. The clock synchronisation can also be set to be cyclic,
by checking the Cyclic timesync checkbox. The length of a cycle is set in the rightmost
field (minutes).
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE © 2012 Schneider Electric Industries SAS - All rights reserved.
Electrical equipment should be installed, operated, serviced,
Phone: +33 (0) 1 41 29 70 00 and maintained only by qualified personnel. No responsibility
Fax: +33 (0) 1 41 29 71 00 is assumed by Schneider Electric for any consequences
www.schneider-electric.com arising out of the use of this material.

Publishing: 4/2013

9 AN321.EN002

You might also like