Ethernet Interface in VAMP 321, Configuration Instructions v1.2
Ethernet Interface in VAMP 321, Configuration Instructions v1.2
Ethernet Interface in VAMP 321, Configuration Instructions v1.2
instructions v1.2
1 Overview
This document applies to VAMP 321 Arc flash protection main unit.
The document describes how to set up the Ethernet communications and gives some
general guidelines of connecting the device to the Ethernet network.
VAMP 321 is the main unit of the Arc Flash protection system. The system usually
comprises of VAMP 321 and some I/O units connected to it. Only VAMP 321 main unit is
connected to an Ethernet network. There is internal communication between the VAMP
321 and the I/O units, but this should not be mixed with the external Ethernet
communications.
Figure 1.1. VAMP 321 main unit takes care of the external communications of the Arc Flash protection
system.
1 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2
communication option card “RS-232 + Ethernet RJ-45” for slot 9 and “RS-232” for slot 10
(see figure 2.2.)
Figure 2.1. Explanation of VAMP 321 ordering code – showing the two digits defining the communication
options.
Figure 2.2. Location of the Ethernet port at the back of the device.
3 Configuration
The configuration of the Ethernet port is done with VAMPSET setting tool. VAMPSET can
be connected to the relay either via USB interface to the front panel connector or via the
Ethernet network. The version of VAMPSET that is needed will vary depending on the
AN321.EN002 2
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2
version of the device firmware (for instance, firmware version 10.108 requires VAMPSET
version 2.2.85 or higher).
3.1 Setting the main parameters IP Address, TCP port, and Network Mask
The configuration is started by setting the appropriate values for the IP address (IP
address of the VAMP device), NetMask (Network Mask) and Gateway (IP address of the
gateway).
Please note that the IP address and network mask must be correctly set in reference to
the client system in order to get the communication to work properly. When adding a
device to an existing network, please consult with a network administrator to obtain proper
IP addresses that you are allowed to use.
Also note that by default the devices do not support DHCP, in contrast to PC’s, which are
able to obtain different IP addresses each time they are connected to a network. This may
cause trouble if the communication is tested in an office network. The use of a separate
test network is recommended.
Next, the protocol to be used is activated for one of the two instances of TCP ports. As an
example see Figure 3.1, which show settings when ModBusTCP is used.
Figure 3.1 Ethernet and TCP port instances configuration menu in VAMPSET.
A change of protocols on any port, serial port or TCP port instance, will require a reboot of
the device.
Once the protocol has been activated, the protocol specific parameters will become
selectable in VAMPSET (the list to the left in the VAMPSET window). See figure 3.2 for a
screenshot of this menu in case ModbusTCP is used.
3 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2
The Ethernet network could be described as a network of one or more Ethernet switches,
which are connected to each other. The switches are connected to each other either with
copper cabling (RJ-45 connectors) or with fiber optic cabling. An example is shown in
figure 4.1. VAMP 321 devices are connected to the Ethernet switches of the network.
AN321.EN002 4
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2
Figure 4.1. An example of an Ethernet network and connection of three VAMP 321 devices to it.
Normally the maximum distance that can be used with copper cabling is 100m and
maximum distance with multimode fiber optic cabling is about 1km. With single mode
cabling distances up to tens of kilometers can be reached. The maximum distances that
can be reached with different type of fiber optic cabling depends on the type of the cable,
number of connections on the signal path and type of light transmitters and receivers used
in the Ethernet switches. For more information about switches please read e.g. the
datasheets of the RS900 switch from Ruggedcom.
5 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2
Figure 5.1. The user interface of Simple Tester with ModBus selected as protocol.
AN321.EN002 6
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2
7 AN321.EN002
Ethernet interface in VAMP 321, configuration [ Application note ]
instructions v1.2
Figure 5.1 features an example of reading the Alive Counter (HR 2001) cyclically every
three seconds.
Figure 5.1: Performing a cyclic read on the Alive Counter with Simple Tester.
Figure 5.2 features an example of a write of the value 1 to Virtual Input 1 (holding register
3427).
AN321.EN002 8
[ Application note ] Ethernet interface in VAMP 321, configuration
instructions v1.2
Note that the Event view of Simple Tester now contains an event, corresponding to “Virtual
Input 1 ON”. If there are events in the event buffer when connecting Simple Tester, these
will be listed in the event view. New events triggered by writes done with Simple Tester will
also show up.
Furthermore, a clock synchronisation can be performed with Simple Tester. This is done
by setting the desired behaviour in the Time Controls (see figure 5.1). The two leftmost
fields are used for setting the time manually, but the time can also be taken from the PC,
by checking the PC Time checkbox. The clock synchronisation can also be set to be cyclic,
by checking the Cyclic timesync checkbox. The length of a cycle is set in the rightmost
field (minutes).
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE © 2012 Schneider Electric Industries SAS - All rights reserved.
Electrical equipment should be installed, operated, serviced,
Phone: +33 (0) 1 41 29 70 00 and maintained only by qualified personnel. No responsibility
Fax: +33 (0) 1 41 29 71 00 is assumed by Schneider Electric for any consequences
www.schneider-electric.com arising out of the use of this material.
Publishing: 4/2013
9 AN321.EN002