LS81X Dual Aviation Obstruction Light
LS81X Dual Aviation Obstruction Light
LS81X Dual Aviation Obstruction Light
Applications
Applying to tower(power transportation, telecom, GSM), smokestacks(power plant, coking plant,
chemical plant), high buildings, bridge, harbor machinery, construction machinery, wind turbine etc
for aircraft warning.
Specification
Compliant to the
Standard ICAO(Aerodromes Annex 14) Vertical degree ≥10°
and FAA-L810
Light source High luminance LED Horizontal degree 360°
30FPM/40FPM/60F
Wiring diagram red(other color can be PM/ steady
Light color Flashing rate
AC110-240V wiring customized) burning can be
adjusted
Operating
AC110-240V/DC48V/DC12V Flashing duration 150±20ms
voltage
Power
4W LED lifetime ≥100,000h
consumption
Operating
-40˚C ~ +70˚C IP protection IP65
temperature
Relative
10% ~ 95% (no condensing) Weight 2.2kg
Remarks:For customized product,please humidity
1/2
LS81X Dual aviation obstruction light LS81X-E1-V10
Flashing rate adjustment:
• If the lamp is with photocell, please do not put photocell direct to nearby light. Meanwhile
AC110-240V
ensure that the photocell is not obstructed by nearby object.
• Open the connection box and connect the power wire, signal wire according to marking.
Then remount the connection box.
• Switch on the power after check up. The light begins to work.
S1
ON
ON
1 2
1=OFF,2=OFF:Work model is in dual light way (Lead light + standby light. When and if
lead light fails, standby light will switch on automatically.)
1=ON,2=OFF:Work model is in two lights way. (Two lights work at the same time)
Application
• Power on, the light will work as your setting.
DC48V/DC12V:
• Switch off the power.
• Switch to SWITCH condition, and the corresponding woke mode as below:
SWITCH without jumper cap connect:the dual lights work with one host and the other one
standby.
SWITCH with jumper cat connect: the dual lights work together.
• After cable connected well and close the junction box, power on, then lamp can be work
normally.
Notice
•When the lamp works, temperature rising is normal phenomenon.
•Please do not open any components except professional serviceman.
•The product is a sealed structure. Do not be tampered by anyone other than registered
installer.
2/2