0% found this document useful (0 votes)
188 views6 pages

5.slab Design PDF

The document provides a structural design calculation for an underground sewage treatment plant (STP) tank slab panel at a level of 175.50m. It includes calculations for loads, bending moments, required and provided reinforcement, shear strength, and deflection check. The slab has a shorter span of 3.50m and longer span of 6.00m. Calculations show the reinforcement provided of 10mm diameter bars at 200mm c/c meets design requirements for strength and serviceability. The slab design is found to be adequate based on comparisons of calculated and allowable values.

Uploaded by

epe civil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
188 views6 pages

5.slab Design PDF

The document provides a structural design calculation for an underground sewage treatment plant (STP) tank slab panel at a level of 175.50m. It includes calculations for loads, bending moments, required and provided reinforcement, shear strength, and deflection check. The slab has a shorter span of 3.50m and longer span of 6.00m. Calculations show the reinforcement provided of 10mm diameter bars at 200mm c/c meets design requirements for strength and serviceability. The slab design is found to be adequate based on comparisons of calculated and allowable values.

Uploaded by

epe civil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Rev

Project Construction of Sewage Treatmeny Plant of Capacity 375KLD


0
Doc., Designed Checked Approved
19-H20-STP-STR-01
Number VJ GJ DM
Title Structural Design Calculation of Underground STP tank
Design of Slab Panel @ 175.50m Level
Slab name : S1
Data:
Concrete M25 fck = 25 N/mm²
Steel Fe 500 fy = 500 N/mm²

Shorter Span Lx = 3.50 m


Longer Span Ly = 6.00 m
Assuming Depth of Slab D = 150 mm
Assuming Dia of reinf. = 10 mm
Clear Cover = 25 mm
Eff. Depth of Slab d = 120 mm
Eff.Shorter Span lx = 3.62 m
Eff. Longer Span ly = 6.12 m

Load Calculations:
Self weight of slab = 0.15 * 25 = 3.75 kN/m²
Finishing load-50thk. = 0.05 * 24 = 1.20 kN/m²
Live load = 0.75 kN/m²

Total load = 5.70 kN/m²


Load Factor = 1.50
Factored Load = 8.55 kN/m²

Span Ratio 4 ly/lx = 6.12 / 3.62


= 1.69

Bending Moment Calculation: 1


Support Condition 4 Two Adjacent edges Discontinuous
From IS 456-2000 Table 26 2 aNx = 0.082
aPx = 0.061
aNy = 0.047
aPy = 0.035
Shorter Span:
Negative Moment (Support) MNx = aNx x wu x lx²
= 0.082 x 8.55 x 3.62²
= 9.172 kN.m
Positive Moment (Mid span) MPx = aPx x wu x lx²
= 0.061 x 8.55 x 3.62²
= 6.872 kN.m
Longer Span :
Negative Moment (Support) MNy = aNy x wu x lx²
= 0.047 x 8.55 x 3.62²
= 5.266 kN.m
Positive Moment (Mid span) MPy = aPy x wu x lx²
Rev
Project Construction of Sewage Treatmeny Plant of Capacity 375KLD
0
Doc., Designed Checked Approved
19-H20-STP-STR-01
Number VJ GJ DM
Title Structural Design Calculation of Underground STP tank
= 0.035 x 8.55 x 3.62²
= 3.921 kN.m

Mu/ bd2 Values: Pt Values: ( as per SP:16)


Shorter Span
Support 0.64 0.12
Mid span 0.48 0.12
Longer Span
Support 0.37 0.12
Mid span 0.27 0.12

Reinforcement:
Required in Shorter Span Reinf Required Reinf Provided
Support 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c
Mid span 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c
Required in Longer Span
Support 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c
Mid span 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c

Check for Shear:


As per BS:8110 Shear coefficients
Max Shear coeff. for continuous edge in short directiongcx = 0.56

S.F for continuous edge in short direction Vcx = gcx * lx * W


Maximum Shear Force Vu = 0.56 x 3.620 x 8.55
= 17.421 kN
S.F for continuous edge in short direction Vu = 17.421 kN
Design Shear stress tv Vu/bd = 17421 / (1000 x 120)
= 0.145 N/mm²

Reinforcement provided in the slab is - 10Ø @ 200 mm c/c


% of reinforcement provided pt = 0.33
IS:456 Table 19
Allowable shear stress tc = 0.410 N/mm²
As per IS:456 cl. 40.2.1.1 k value for slab - 1.30

Design shear stress for concrete k x tc = 1.30 x 0.410


= 0.532 N/mm²

Actual Shear Stress < Design Shear Stress 0.145 < 0.532 SAFE

CHECK FOR DEFLECTION


Allowable span / depth Ratio l/d = 26
% of Tension reinforcement pt = 0.33
Corresponding Compression reinf. Bar dia = 10 mm
Rev
Project Construction of Sewage Treatmeny Plant of Capacity 375KLD
0
Doc., Designed Checked Approved
19-H20-STP-STR-01
Number VJ GJ DM
Title Structural Design Calculation of Underground STP tank
spacing = 150 mm
% of Compression reinforcement pc = 0.436
(Fig 4 & 5 IS 456 - 2000)
Modification factor for Tension reinf. F1 = 1.18
Modification factor for Comp. reinf. F2 = 1.10

Modified span/depth ratio = l/d x F1x F2


= 26x1.18x1.1
= 33.75

Actual span/depth ratio = 3620 / 120


= 30.17

Actual span/depth ratio < Modified span/depth ratio 30.17 < 33.75
Rev
Project Construction of Sewage Treatmeny Plant of Capacity 375KLD
0
Doc., Designed Checked Approved
19-H20-STP-STR-01
Number VJ GJ DM
Title Structural Design Calculation of Underground STP tank
Design of Slab Panel @ 175.50m Level
Slab name : S1
Data:
Concrete M25 fck = 25 N/mm²
Steel Fe 500 fy = 500 N/mm²

Shorter Span Lx = 3.50 m


Longer Span Ly = 3.70 m
Assuming Depth of Slab D = 150 mm
Assuming Dia of reinf. = 10 mm
Clear Cover = 25 mm
Eff. Depth of Slab d = 120 mm
Eff.Shorter Span lx = 3.62 m
Eff. Longer Span ly = 3.82 m

Load Calculations:
Self weight of slab = 0.15 * 25 = 3.75 kN/m²
Finishing load-50thk. = 0.05 * 24 = 1.20 kN/m²
Live load = 0.75 kN/m²

Total load = 5.70 kN/m²


Load Factor = 1.50
Factored Load = 8.55 kN/m²

Span Ratio 2 ly/lx = 3.82 / 3.62


= 1.06

Bending Moment Calculation: 1


Support Condition 2 One Short Edge Discontinuous
From IS 456-2000 Table 26 2 aNx = 0.040
aPx = 0.030
aNy = 0.037
aPy = 0.028
Shorter Span:
Negative Moment (Support) MNx = aNx x wu x lx²
= 0.040 x 8.55 x 3.62²
= 4.517 kN.m
Positive Moment (Mid span) MPx = aPx x wu x lx²
= 0.030 x 8.55 x 3.62²
= 3.385 kN.m
Longer Span :
Negative Moment (Support) MNy = aNy x wu x lx²
= 0.037 x 8.55 x 3.62²
= 4.146 kN.m
Positive Moment (Mid span) MPy = aPy x wu x lx²
Rev
Project Construction of Sewage Treatmeny Plant of Capacity 375KLD
0
Doc., Designed Checked Approved
19-H20-STP-STR-01
Number VJ GJ DM
Title Structural Design Calculation of Underground STP tank
= 0.028 x 8.55 x 3.62²
= 3.137 kN.m

Mu/ bd2 Values: Pt Values: ( as per SP:16)


Shorter Span
Support 0.31 0.12
Mid span 0.24 0.12
Longer Span
Support 0.29 0.12
Mid span 0.22 0.12

Reinforcement:
Required in Shorter Span Reinf Required Reinf Provided
Support 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c
Mid span 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c
Required in Longer Span
Support 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c
Mid span 10Ø @ 545mm c/c - 10 dia @ 200 mm c/c

Check for Shear:


As per BS:8110 Shear coefficients
Max Shear coeff. for continuous edge in short directiongcx = 0.38

S.F for continuous edge in short direction Vcx = gcx * lx * W


Maximum Shear Force Vu = 0.38 x 3.620 x 8.55
= 11.655 kN
S.F for continuous edge in short direction Vu = 11.655 kN
Design Shear stress tv Vu/bd = 11655 / (1000 x 120)
= 0.097 N/mm²

Reinforcement provided in the slab is - 10Ø @ 200 mm c/c


% of reinforcement provided pt = 0.33
IS:456 Table 19
Allowable shear stress tc = 0.410 N/mm²
As per IS:456 cl. 40.2.1.1 k value for slab - 1.30

Design shear stress for concrete k x tc = 1.30 x 0.410


= 0.532 N/mm²

Actual Shear Stress < Design Shear Stress 0.097 < 0.532 SAFE

CHECK FOR DEFLECTION


Allowable span / depth Ratio l/d = 26
% of Tension reinforcement pt = 0.33
Corresponding Compression reinf. Bar dia = 10 mm
spacing = 150 mm
Rev
Project Construction of Sewage Treatmeny Plant of Capacity 375KLD
0
Doc., Designed Checked Approved
19-H20-STP-STR-01
Number VJ GJ DM
Title Structural Design Calculation of Underground STP tank
% of Compression reinforcement pc = 0.436
(Fig 4 & 5 IS 456 - 2000)
Modification factor for Tension reinf. F1 = 1.18
Modification factor for Comp. reinf. F2 = 1.10

Modified span/depth ratio = l/d x F1x F2


= 26x1.18x1.1
= 33.75

Actual span/depth ratio = 3620 / 120


= 30.17

Actual span/depth ratio < Modified span/depth ratio 30.17 < 33.75