Distance Protection Testing
Distance Protection Testing
TEST METHOD
P44X/EN TM/A11
Test Method P44x/EN TM/A11
CONTENT
BLANK PAGE
Test Method P44x/EN TM/A11
As you can see, there are no transients created by CMC, but a step change from the
steady state prefault signals to the steady state fault signals. To force currents starting
at 0 deg (possible for single phase and phase-phase faults, for three-phase faults
only in one phase), the fault inception angle has to be set accordingly.
Shot with model constant source impedance, source impedance 9.105 Ohms
64.62°, fault at 6 Ohm, 0°
without dc offset with dc-offset
There is a phase jump between the prefault and fault voltage according to the
network model used.
If dc-offset is selected, the current starts at 0 independently from the fault inception
angle.
If the test is made with identical phase angles for source and fault impedance , no
phase jump in the voltage signals occur:
Fault at 6 Ohm, 64.62°
without dc-offset with dc-offset
Test Method P44x/EN TM/A11
Permissive tolerance
Tolerance of impedances in % and absolute:
The accuracy for the first zone is 5% and 10% for the other zones.
You can set:
Z in % = 10%
Z in Ω = 5% of X3 if X3 ≥ X4
5% of X4 if X3 ≤ X4
with X3: reactance Zone 3 in the P44x menu
X4: reactance Zone 4 in the P44x menu
Tolerance of tripping times in % and absolute:
You can set:
t in % = 10%
t in sec = 30% of (t2 - t1) with a minimum value of 100 ms.
with t1: tripping time of Zone 1 in the P44x menu
t2: tripping time of Zone 2 in the P44x menu
Time reference fault inception
If you do not connect the starting output contact of the protection relay, you must
select “fault inception” as the time reference. So the CMC will display the time
between the fault inception and the protection trip.
Maximum permissible instantaneous tripping time in s
P44x technical data (at 50 Hz):
The maximum tripping time with a Source Impedance Ratio of 30 is ≤ 30 ms.
The maximum tripping time with a Source Impedance Ratio of 40 is ≤ 40 ms.
You must set:
Maximal Tripping Time = 40 ms + T1 (if T1 ≠ 0 ms)
Test current
I test current = 2 x IN
with IN: rating current in the P44x menu
If the overcurrent back-up protection is enabled in the P44x menu, you can set:
Itest current = 1.2 × I>2
with I>2: threshold overcurrent back-up protection
Test line angle
Phi Test = Phi Line
With Phi Line : line angle in the P44x menu
Connection of the voltage transformer
You must choose between „line“ and „busbar“.
If you select ”busbar“, the voltages will be not switched off after the fault simulation.
Test Method P44x/EN TM/A11
Network model
The relay has four negative sequence impedance coefficients kZ1, kZ2, ZP, kZ3-4. The
measurement of impedance for phase-to-ground faults is based on kZ1 for a fault in
zone 1, on kZ2 for a fault in zone 2, etc. You can use them if you have an application
with cable/line between two sub-stations.
During the simulation with the CMC test equipment, you must set the same value for
all negative sequence impedances (kZ1 = kZ2 = Zp = kZ3-4).
Distance Protection Functions
P44x are full scheme protection relays. All digital distance relays work on numerical
measuring principles with simultaneous measurement in all zones and phases. They
are equipped with simultaneous measuring principles consisting of :
⇒ a superimposed measuring technique,
⇒ a conventional measuring technique.
Both techniques are used individually and simultaneously for starting, phase
selection, directional detection and impedance measurement. A parallelogram
characteristic is used for phase and earth fault measuring elements enabling high
fault resistance coverage and proper settings to avoid load encroachment even under
the most adverse conditions.
Measurement of distance to fault and apparent resistance
The P44x distance relays calculate the value of both these parameters of the fault.
To calculate these parameters the following equation is used :
U = XV + RW, where
X = distance to fault from relay equation,
R = apparent resistance,
U = voltage at relay location,
W = fault current image,
V = voltage drop on line per unit of length.
Directional characteristic (angle in the 2nd and angle in the 4th quadrant)
CONVENTIONAL ALGORITHMS :
Simultaneously and in parallel to superimposed algorithms, conventional algorithms
are used for starting, direction detection, phase selection and distance measurement.
Starting and distance measurement are based on the result of fault resistance and
fault distance calculations carried out simultaneously on all six loops. Unfiltered
quantities are used for U (voltage at relay location), V (voltage drop on line per unit
of length) and W (fault current image) for the first few samples after fault detection,
subsequently filtered quantities are used. The fault direction is defined on the basis of
the calculation of the phase shift between the stored voltage and the derivative of a
current. The current and the voltage used are those of the measuring loop(s) defined
by the phase selection. The directional characteristic for the “conventional algorithms”
is fixed by -30° and +150°.
P44x/EN TM/A11 Test Method
+150° FORWARD
REVERSE -30°
P0259ENa
The directional characteristic for the “ high-speed algorithms ” is fixed by +90°± 2.5°
and +270°±2.5° (dead zones between +87.5° and +92.5° AND between +267.5° and
+272.5°).
Fault direction is detected according to the sign of the transition energy characterising
the fault. Transition energy is the energy created by the fault and is given by:
S = S U . I . dt
The sign of the energy is used for detection of fault direction as follows: Considering
the transition network for both forward and reverse faults, as all sources are replaced
by short circuits in the transition network, behind the relay location the network
consists of only passive impedances (resistive inductive or capacitive the total
reactance however cannot be capacitive as no line is compensated over 100%
in series capacitor applications). There, Zs (source impedance) is always positive
and so is:
∆ U = ∆ I . Zs
For forward faults ∆ I is in reverse direction to relay current polarisation.
The power taken through the relay is: P = - ∆ I ². Zs
The energy is: S = - S ∆ I ². Zs. dt, which is always negative.
Similarly, for reverse fault:
∆ U = ∆ I. Zs is positive while ∆ I is in same direction as the relay current polarisation,
hence
P = ∆ I ². Zs and the energy (S = + S ∆ I ². Zs. dt,) is always positive for reverse fault.
Transient energy S is always imported on the relay side and its sign does not depend
on the inductive, capacitive or resistive nature of the network impedance’s, therefore
the directional detection is correctly applicable to all lines’ series compensated or not.
For a three phase network transition, energy is expressed as :
S = S (∆UA . ∆IA + ∆UB . ∆IB + ∆UC . ∆IC ). dt
Which is computed digitally as :
ni
REVERSE FORWARD
R
REVERSE FORWARD
P0260ENa
Z3
Z1
Z4
Tripping at T1
P0261ENa
of the protection relay are taken into account. Each current threshold has a settable
time delay associated with it.
A typical P44x overcurrent back-up protection setting for the CMC OMICRON test is
following:
Threshold I>2 : threshold I>
Direction of I>2 : forward
Direction of I>1 : without direction
I>1, tl>1
t Tripping time
Without direction I>2, tI>2
Z4 Direction Forward
tZ4 Z3
tZ3
Zp
tZp
Z2
tZ2
Z1
tZ1
Z Impedance
P0262ENa
The overcurrent back-up protection will trip if the conventional algorithms are not
active (none of the six measuring loops converges within the distance characteristic)
or if a fuse failure has been detected but is yet unconfirmed. Therefore the time
selectivity can be respected.
For the simulation with CMC OMICRON, you must set:
Starting zone: yes
Direction back-up time:
Direction: Forward (direction of I>2)
Time t: tI>2
Time limit: Time t: tI>1 without direction (direction of I>)
ZB I3 ZL
ZB I2 ZL
ZB I1 ZL
V 3N V 2N V 1N V1 V2 V3 R Fault
k B ZB k L ZL
Location
of DR
P0263ENa
Zd
R Fault
Z0 J
V N
Zi
P0264ENa
V1 = Zd ( I1 +k0 IR ) + RFault J
V1 = I1 [ Zd (1+k0 ) + RFault ]
V1
= Zd (1+k0 ) + RFault
I1
with:
V1 : fault voltage
I1 : fault current
Phi1 : fault angle
The P44x measure :
V1 RFault
I1 (1+k0) = Zd +
1+k0
Test Method P44x/EN TM/A11
Xph-grd
RFault/(1+k 0)
Zd
ZFault
Rph-grd
P0265ENa
The CMC OMICRON test equipment cannot simulate the fault resistance and add it
to the line resistance. This means that you must set the following values in the CMC
OMICRON test equipment:
RP44x
ROMICRON = 1+f
R
R01-Rd
fR = = 0.835
3×Rd
X01-Xd
fX = = 0.835
3×Xd
CMC OMICRON phase-to-ground fault characteristic setting for Zone 1
R1 Ph-Grd P44x
R1 OMICRON = = 8.17 Ω
1+fR
V1
I1 = Zd (1 + k0 ) + RFault
with:
V1 : fault voltage
I1 : fault current
Phi1 : fault angle
Test of the resistance phase-to-ground fault for zone 1 :
I1 = 1 A
Phi1 = 0°
V1
I1 = Zd (1 + k0 ) + RFault
Test Method P44x/EN TM/A11
Xph-grd
P0266ENa
with Zd = 0
V1
I1 = ZFault = RFault = R1 Ph-Grd
V1 = I1 x R1 Ph-Grd = 1 x 15 = 15 Volts
Test of the reactance phase-to-ground fault for zone 1 :
I1 = 1 A
Phi1 = 90°
V1
I1
= ZFault (1 + k0 ) + RFault
Xph-grd
RFault /(1+k 0)
ZFault
Z1
Rph-grd
P0267ENa
Xph-grd
ZFault= Z1
Rph-grd
P0268ENa
Xph-grd
RFault /(1+k 0)
Z1
ZFault
Rph-grd
R1h-grd /(1+k 0)
P0269ENa
Z1.sin Phid
With Phi1 = Arctan Z .cos Phi + R / (1+k )
1 d Fault 0
V1
= √ (29.68 x cos 76 x (1 + 0.835) + 15 )² + (29.68 x sin 76 x (1 + 0.835))²)
I1
V1
I1 = 59.89 Ω
V1 = 1 x 59.89 = 59.89 Volts
5.2 Two phase fault : Phase-to-phase fault
5.2.1 Network model
The network model used by the P44X relay is following:
ZB I3 ZL
ZB I2 ZL
R Fault
ZB I1 ZL
V 3N V 2N V 1N V1 V2 V3
Location
of DR
P0270ENa
U12 = I1 . [ 2 . Zd + RFault ]
U12
I1 = 2 . Zd + RFault
with:
U12 : fault voltage phase-to-phase
I1 : fault current
Phi1 : fault angle
The P44x measure :
U12 RFault
2.I1 = Zd + 2
P44x/EN TM/A11 Test Method
Xph-ph
RFault /2
Zd
ZFault
Rph-ph
P0271ENa
The CMC OMICRON test equipment cannot simulate the fault resistance and add it
to the line resistance. That means, you must set the following values in the CMC
OMICRON test equipment:
RP44x
R OMICRON =
2
X OMICRON = ZP44X x sin Phi
Examples :
Rd : positive sequence resistance of the line
Xd : positive sequence reactance of the line
Phi : line angle
RP44X : fault resistance setting in the P44x relay
ZP44X : zone setting in the P44x relay
With :
Rd = 8.975 Ω
Xd = 35.998 Ω
Phid = 76°
Z1 P44X = 29.68 Ω (impedance for zone 1)
Z2 P44X = 44.52 Ω (impedance for zone 2)
ZP P44X = 55.65 Ω (impedance for zone 3)
Z3 P44X = 74.19 Ω (impedance for zone 4)
Z4 P44X = 18.54 Ω (impedance for zone 5)
R1 Ph-Ph = 10 Ω (resistance phase-to-phase fault for zone 1)
R2 Ph-ph = 20 Ω (resistance phase-to-phase and phase-to-phase fault for zone 2)
RP Ph-ph = 25 Ω (resistance phase-to-phase and phase-to-phase fault for zone P)
Test Method P44x/EN TM/A11
U12
I1
= 2 . Zd + RFault
with:
U12 : fault voltage phase-to-phase
I1 : fault current
Phi1 : fault angle
Test of the resistance phase-to-phase fault for zone 1 :
I1 = I2 = 1 A
Phi1 = 0°
U12
= 2 . Zd + RFault
I1
P44x/EN TM/A11 Test Method
Xph-ph
P0272ENa
with Zd = 0
U12
I1 = ZFault = RFault = R1 Ph-Ph
U12 = I1 x R1 Ph-Ph = 1 x 10 = 10 Volts
Test of the reactance phase-to-phase fault for zone 1 :
I1 = I2 = 1 A
Phi1 = 90°
U12
I1 = 2 . Zd + RFault
Xph-ph
RFault /2
X1
ZFault
Z1
Rph-ph
P0273ENa
Xph-ph
X1
ZFault= Z1
Rph-ph
P0274ENa
Xph-ph
RFault /2
X1
Z1
ZFault
Rph-ph
R1Ph-ph /2
P0275ENa
U12
I1 = √ (2 . Z1 . cos Phid + R1 Ph-Ph )² + (2 . Z1 . sin Phid )²)
U12
I1 = √ (2 x 29.68 x cos 76 + 10 )² + (2 x 29.68 x sin 76)²)
U12
= 62.53 Ω
I1
U12 = 1 x 62.53 = 62.53 Volts
5.3 Three phase fault
5.3.1 Network model
The network model used by the relay is as follows:
ZB I3 ZL
R Fault
ZB I2 ZL
R Fault
ZB I1 ZL
V 3N V 2N V 1N V1 V2 V3
Location
of DR
P0276ENa
RFault
V1 = I1 . [Zd +
2 ]
V1 RFault
= Zd +
I1 2
with:
V1 : fault voltage
I1 : fault current
Phi1 : fault angle
The P44x measure :
V1 RFault
= Zd+
I1 2
V1 RFault
I1 = Zd + 2
with:
V1 : fault voltage
I1 : fault current
Phi1 : fault angle
Test of the resistance phase-to-phase fault for zone 1 :
I1 = I2 = I3 = 1 A
Phi1 = 0°
V1 RFault
I1 = Zd+
2
P44x/EN TM/A11 Test Method
Xph-ph
P0277ENa
with Zd = 0
V1 R1 Ph-Ph
I1 = ZFault = RFault = 2
R1 Ph-Ph
V1 = V2 = V3 = I1 x
2 = 1 x 10/2 = 5 Volts
Xph-ph
RFault /2
X1
ZFault
Z1
Rph-ph
P0278ENa
V1 RFault
= X1 . sin Phid + R1 . cos Phid + = X1 . sin Phid
I1 2
V1 = V2 = V3 = I1 . X1 = 1 x 28.80 = 28.20 Volts
Test of the impedance for zone 1 :
I1 = I2 = I3 = 1 A
Phi1 = Line angle = 76°
V1 RFault
I1 = Zd + 2
Xph-ph
X1
ZFault= Z1
Rph-ph
P0279ENa
Xph-ph
RFault /2
X1
Z1
ZFault
Rph-ph
R1Ph-ph /2
P0280ENa
Z1.sin Phid
With Phi1 = Arctan
(Z1.cos Phid = RFault/2)
Zd = Z1 and RFault = R1 Ph-Ph
29.68 x sin 76
Phi1 = Arctan (29.68 x cos 76 + 10/2)