Programming: Menu Structure
Programming: Menu Structure
Menu structure
Two menu levels are provided.
"Advanced level"
Access to dedicated parameters which define the characteristics of the motor protections, interface, communication,…
This selection will add some menus and, in the particular case of Monitoring menu, it will add some parameters.
Note: A parameter value becomes valid and takes effect immediately upon changing its value. If ESC is pressed, the value previously stored
in the EEPROM is restored.
Menu description
Easy start up level Advanced level
AdJ Advanced
adjustments
SEt2 Advanced
Settings
PrO Advanced
protections
IO Advanced
I/O
COP Advanced
communication
UtIL Utility
(1) Status displays the state of the soft starter: rdY nrdY rUn.
See next page for Status menu.
46 BBV51330 08/2012
Programming
ACC
LCr1 Current phase 1 display, value in Amp
USF
nrdY
rdY
rUN LCr2 Current phase 2 display, value in Amp
Note: When the soft starter is inside delta connection, LCr1, LCr2, LCr3 values are current inside the windings.
The line current = LCr x 3.
Status Description
ACC During acceleration
tbS The soft starter has tripped in SnbF, too many starts, see Diagnostics/Troubleshooting page 76.
dEC During deceleration
nrdY A stop command is present, with line and control power on
LI1 = 0 and LI2 = 1 in 2-wire control
LI1 = 1 and LI2 = 1 at power up in 3-wire control
Or main power is switched off
rdY Soft starter is ready to start
rUn Steady state, the bypass contactor is closed
For the trip codes, see chapter Diagnostics / Troubleshooting page 75.
BBV51330 08/2012 47
List of parameters
(1) Only available when Advanced mode LAC page 50 is set (2) Accessible, except motor in run state, using the key shortcut
to On
ESC +
48 BBV51330 08/2012