MVS

DIN rail electronic fan speed controller


The MVS series control the speed of single-phase voltage controllable electric motors
(230 VAC / 50—60 Hz) according to a standard input control signal. They are equipped
with Modbus RTU communication and provide a wide range of functionalities: remote
control options, adjustable off level, min. and max. output voltage settings, and time-
limited motor operation initiated by a logic or switch signal.

Key features
• Invertible analog input signal: 0—10 / 10—0 VDC or 0—20 / 20—0 mA

• Minimum and maximum output voltage setting via trimmers or Modbus

• Off-level value setting via trimmer or Modbus

• Modbus RTU (RS485) communication

• Kick start or soft start

• Remote control input with selectable functionality (normal or timer)

• Analog input (normal or logic functionality - only for the timer start)

• 1 regulated output for the motor

• 1 unregulated output (230 VAC / max. 2 A) for 3-wire motor connection or


voltage supply

• 1 low voltage supply output (+12 VDC / 1 mA) for external 10 kΩ potentiometer

• DIN rail mounted

• Green LED operating indication

Technical specifications
Power supply, Us 230 VAC ±10 % / 50—60 Hz

Regulated output 30—100 % Us

Max. load Max. load depends on the version Article codes


Unregulated output 230 VAC / max. 2 A Fuse rating
Article Max. rated current [A]
Analog input 0—10 / 10—0 VDC or 0—20 / 20—0 mA Fuse 1 Fuse 2
Logic input Timer start (min. 2,5 VDC > 30 ms) F 3,15 A H 250 V
MVS-1-15CDM 1,5
(5*20 mm)
Minimum output voltage
30—70 % Us
setting, Umin F 5,0 A H 250 V
MVS-1-30CDM 3,0 F 0,315 A H 250 V (5*20 mm)
Maximum output voltage
75—100 % Us (5*20 mm)
setting, Umax F 10,0 A H 250 V
MVS-1-60CDM 6,0
(5*20 mm)
0—4 VDC / 0—8 mA  for ascending mode
Off level
10—6 VDC / 20—12 mA for descending mode F 16,0 A H 250 V
MVS-1100CDM 10,0
(6,3*32 mm)
Supply output +12 VDC / 1 mA

Protection Overvoltage and overcurrent

Enclosure PA- UL94 V0, green RAL 6017 Area of use


Protection standard IP20 (according to EN 60529) • Fan speed control in ventilation systems

Temperature -20—40 °C • For indoor use only


Ambient conditions
Rel. humidity 0—80 % rH (non-condensing)

Modbus registers
Standards
The Sensistant Modbus configurator allows you to easily
• Low Voltage Directive 2014/35/EC monitor and/or configure Modbus parameters. Designed to
be used in combination with PDM or DPOM modules.
• EMC Directive 2014/35/EC The parameters of the unit can be monitored / configured
through the 3SModbus software platform. You can download
• WEEE Directive 2012/19/EC it from the following link:
https://www.sentera.eu/3SMCenter/Index/ENG/
• DIN rail EN 50022
 ou can find register maps in the  mounting instructions.
Y
Download them from:
• RoHs Directive 2011/65/EC https://www.sentera.eu/Product/Index/

S.3.2.D.1 www.sentera.eu DS-MVS-EN-002 - 27 / 04 / 18


MVS
DIN rail electronic fan speed controller

Settings
1 - DIP switch settings

ON – Descending mode:
5 Ascending / descending
ON
10—0 VDC / 20—0 mA
input mode selection
7 (DIP switch, position 1) OFF – Ascending mode:
4 1 2 3 4
0—10 VDC / 0—20 mA

3 ON ON - enabled
OFF level selection
(DIP switch, position 2)
1 2 3 4 OFF - disabled

ON ON – Kick start enabled


1 Kick start selection
(DIP switch, position 3)
6 1 2 3 4 OFF – Soft start enabled

2 ON – Current mode (0—20 mA /


ON
20—0 mA)
Input mode selection (DIP
switch, position 4)
1 2 3 4 OFF – Voltage mode (0—10 VDC
/ 10—0 VDC)

2 - Network bus resistor


*  MVS is the first or last unit
jumper (NBT)
Wiring and connections
VR1
L Supply voltage 230 VAC ±10 % / 50—60 Hz Adjusts the maximum output voltage
7 3 - Max. speed trimmer from 175 VAC (left) to 230 VAC
N Neutral (right)

L1 Unregulated output (230 VAC / max. 2 A)


VR2
Adjusts the minimum output voltage
U1, U2 Regulated output to the motor
4 - Min. speed trimmer from 69 VAC (left) to
161 VAC (right)
SW Remote control switch / timer start switch

+V Supply output +12 VDC / 1 mA Ascending mode

Ai Analog input 0—10 VDC / 0—20 mA Off-level value from 0 VDC (left) to
4 VDC (right) in voltage mode
GND Ground
VR3 Off-level value from 0 mA (left) to
A Modbus RTU (RS485) signal A 8 mA (right) in current mode
5 - Off level trimmer Descending mode
/B Modbus RTU (RS485) signal /B
Off-level value from 10 VDC (left) to
Connections Cable cross section: max. 2,5 mm2 6 VDC (right) in descending and
voltage mode
Caution: If an AC power supply is used with any of the units on a Modbus network, the GND
terminal should NOT BE CONNECTED to other units on the network or via the CNVT-USB-RS485 Off-level value from 20 mA (left) to
converter. This may cause permanent damage to the communication semiconductors and / or 12 mA (right) in descending and
the computer! current mode

6 - Modbus communication
Blinking green Transmitting / receiving
indication

7 - Operating LED Solid on Normal operation


indication Blinking green Stand-by mode

*
indicates closed position of the jumper.

S.3.2.D.1 www.sentera.eu DS-MVS-EN-002 - 27 / 04 / 12


18
MVS
DIN rail electronic fan speed controller

Operational diagrams
Operating modes
Off level disabled Off level enabled

Uout,[%] Uout, [%]


100 100
Umax Off level
Umax
range Umax range Umax

75 75
70
70
Umin
Umin 2 range Umin
range Umin 2
30
30
0
10 VDC Ai,
0 20 mA [VDC] /
10 VDC Ai, Off level
Off level range
range [mA]
20 mA [VDC]/[mA]

Ai (
Descending mode calculation formula Uout = Umax - Aimax Umax - Umin) Descending calculation formula
Ai - Off level
Uout = Umax - Aimax (Umax - Umin)
- Off level
Ai (
Uout = Umin + Aimax Umax - Umin)
Ascending mode calculation formula Ai - Offlevel
Ascending calculation formula Uout = Umin + Aimax (Umax - Umin)
- Offlevel

Ascending / Descending input mode


Note: The operational diagrams for Descending mode are mirror images of the diagrams above for Ascending mode.

Kick start enabled Soft start enabled

Uout, [%] Uout, [%]

100 100
Ai, 10 VDC / 20 mA Ai, 10 VDC / 20 mA
Umax
range

Umax Umax Umax


Umax

0 VDC / 0 mA 0 VDC / 0 mA
range

range Umax range

75 75

70 70
2 1
range
range

Umin

Umin
Umin

Umin Umin
range Umin OFF Level
Ai, 10 VDC / 20 mA range
1 0 VDC / 0 mA
30 30
Ai, 10 VDC / 20 mA
2 0 VDC / 0 mA
0 0
Kick starttime
Kickstart time t [s] Soft starttime
Softstart time t [s]

Kick start & off level Soft start & off level

Uout,[%]
Uout, [%]

100 100
Ai, 10 VDC / 20 mA Ai, 10 VDC / 20 mA
Umax
range

Umax
range

Umax 0 VDC / 0 mA Umax Umax 0 VDC / 0 mA


range Umax range

75 75

70 70
2 1
range
range

Umin
Umin

Umin Umin Umin


OFF Level OFF Level
range Umin range

30 30
Ai, 10 VDC / 20 mA
1 Ai, 10 VDC / 20 mA
2 0 VDC / 0 mA
0 VDC / 0 mA 0
0
Soft start time
Softstart time t [s]
Kick start time
Kickstart time t [s] Softstart time

1 - Descending mode Note: You can find more details about the control functionalities of MVS in our mounting instructions published on our website.
Please follow the link: https://www.sentera.eu/Product/Index/ENG/?ArticleID=1330055
2 - Ascending mode

S.3.2.D.1 www.sentera.eu DS-MVS-EN-002 - 27 / 04 / 13


18
MVS
DIN rail electronic fan speed controller

Operational diagrams
Timer mode Logic mode
Kick start enabled Switch control signal

Remote
Uout, [%] Switch,
[VDC]
100
5 VDC
Umax
range Voltage
amplitude
75 range

2,5 VDC

0
t, [s]
0
Kick start time Operation timer Controller t [s]
is off
Stand-by Operate

Soft start enabled

Switch control signal Ai control signal

Ai>2,4 VDC min. 30 ms min. 30 ms


SW

ON OFF ON OFF t
ON OFF ON OFF t

Soft
start Soft
start

t
Holding Holding t Holding Holding
register register register register
18 18 18 18
Timer
Timer

t
Holding t Holding Holding
register register register
21 21 21
Output
Umax Output
Umax

Soft start Operation Stop Start Soft start Operation Stopt


Start Soft start Operation Stop Start Soft start Stop t Start duration timer duration timer
duration timer duration

S.3.2.D.1 www.sentera.eu DS-MVS-EN-002 - 27 / 04 / 14


18
MVS
DIN rail electronic fan speed controller

Fixing and dimensions Packaging

L W

H H

MVS-1-60CDM MVS-1-15CDM
MVS-1100CDM MVS-1-30CDM

Length Width Height Net Gross


Article Packaging
[mm] [mm] [mm] weight weight

L Unit (1 pc.) 220 130 110 0,36 kg 0,46 kg


MVS-1-15CDM
DIN Box (15 pcs.) 590 380 280 5,40 kg 7,70 kg
rail
Unit (1 pc.) 220 130 110 0,36 kg 0,46 kg
MVS-1-30CDM
W Box (15 pcs.) 590 380 280 5,40 kg 7,70 kg

Unit (1 pc.) 220 130 110 0,49 kg 0,59 kg


MVS-1-60CDM
Articles Height [mm] Length [mm] Width [mm] Box (15 pcs.) 590 380 280 7,35 kg 9,65 kg
MVS-1-15CDM,
112 Unit (1 pc.) 220 130 110 0,50 kg 0,60 kg
MVS-1-30CDM
96 127 MVS-1100CDM
MVS-1-60CDM, Box (15 pcs.) 590 380 280 7,50 kg 9,80 kg
128
MVS-1100CDM

S.3.2.D.1 www.sentera.eu DS-MVS-EN-002 - 27 / 04 / 15


18