Cummins Alternator PDF
Cummins Alternator PDF
5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings
according to the size of each page you wishRedistribution
to print. or publication of this document
by any means, is strictly prohibited.
Service
Manual
L ON 120/240V
Testing Procedures
Repairs
ooip
, p @@@
‘-20A-’ f 120 ONLY 30A L15AJ
I
Wiring Diagrams C
I -5ABGenSet
900-0193
6-82
Printed in U.S.A.
DO NOT fill fuel tankswith the engine runningunlesstanks 0 DO NOT CONNECTTHE GENERATOR SET DIRECTLY
are outside the engine compartment. Fuel contact with hot TO ANY BUILDING ELECTRICAL POWER SYSTEM.
engine or exhaust is a potential fire hazard. Hazardous voltages can flow from the generator set into
the utility line. This creates a potentialfor electrocutionor
DO NOT SMOKE OR ALLOW AN OPEN FLAME near the property damage. Connect only through an approvedde-
generator set or fuel tank. Internal combustion engine fu- vice and after building main switch is open. Consult an
els are highly flammable. electrician in regard to emergency power use.
Fuel lines must be adequately secured and free of leaks. GENERAL SAFETY PRECAUTIONS
Fuel connectionsatthe engine should be made with anap-
proved flexible line. Do not use copper piping on flexible 0 Provide appropriate fire extinguishers and install them in
lines as copper will work harden and become brittle. convenient locations. Consult your local fire department
for the correct type of extinguisher to use. Do not use foam
Be sure that all fuel supplies have a positive shutoff valve. on electrical fires. Use extinguisher rated ABC by NFPA.
DO NOTSMOKEwhile servicing batteries. Lead acid bat- 0 Usedengine oils have been identifiedby some state orfed-
teries emit a highly explosive hydrogen gas that can be ig- era1 agencies as causing cancer or reproductive toxicity.
nited by electrical arcing or by smoking. - -
When checking or changing engine oil, take care not to in-
gest, breathe the fumes, or contact used oil.
EXHAUST GASES ARE DEADLY
Providean adequate exhaust system to properly expel dis- Benzene and lead, found in some gasoline, have been
charged gases. Inspectthe exhaust system daily for leaks identified by some state and federal agencies as causing
per the maintenance schedule. See that exhaust mani- cancer or reproductive toxicity. When checking, draining
folds are secure and are not warped. Do not use exhaust or adding gasoline, take care not to ingest, breathe the
gases to heat a compartment. fumes, or contact gasoline.
Be sure the unit is well ventilated. 0 Make sure that rags are not left on or near the engine.
MOVING PARTS CAN CAUSE SEVERE PERSONAL 0 Remove all unnecessarygrease and oil from the unit. Ac-
INJURY OR DEATH cumulated grease and oil can cause over heating and en-
Keep your hands away from moving parts. gine damage, and present a potentialfire hazard.
Before performing any maintenance on the generator set, Keep the generator set and the surrounding area clean
disconnect the starting battery negative (-) ground lead and free from obstructions. Remove any debris from the
lead first. This will prevent accidental starting. set and keep the floor clean and dry. I
Make sure that fasteners on the generator set are secure, Do notwork on this equipmentwhen mentallyor physically
Tighten supportsandclamps, keepguardsinposition over fatigued, or after consuming any alcohol or drug that
fans, drive belts, etc. makes the operation of equipment unsafe.
ss-7
-
Spec J 60 Hz Models Only
Models . I Watts I Volts I Amps
RESIDENTIAL MODELS
I wire I . Phase I RPM 1
-
Spec H 50 Hz Models Only
1.8PE-53AP 2.7PL-53AP 3.1PF-53AP 4.1PK-53AP 4.1PK-53AE 5.4PM-53AP - 5.4PW-53AE
I 4.1PK-53BP I
~
Amperes
53A , 1417.0 18/9.0 27A3.5 31115.5 I 41f20.5 I 41120.5 I 54127 54127
(Code) 538 12.716.3 16.4/8.2 24.5112.3 28.2f14.1 I 37.3118.6 I 37.3118.6 I 49124.5 I 49f24.5 1
PI
,
-
Spec J 50 Hz Models Only
Generator Set 1.4PE-53AP 1.8PE-53AP I I 2.7PL-53AP I 3.1PP-53AP I 3.1PFI-53AP I 4.1PN-53AP I 4.1PN-53AE 1 4.1PKI-53AP
Model Nom 1.4PE-53BP I 1.8PE-53BP I 2.7PL-53BP 1 3.1 PP-53BP I 3.1 PFI-53BP I 4.1 PN-53BP 1 4.1 PN-53BE I 4.1PKI-53BP
1.4PE-53CP 1.8PE-53CP 2.7PL-53CP 3.1 PP-53CP 3.1 PFI-53CP 4.1 PN-53CP 4.1 PN-53CE 4.1 PKI-53CP
Watts 1400 1800 2700 3100 3100 4100 4100 4100
53A 14/7.0 18/9.0 27/13.5 31/15 ’ 31/15.5 41/20.5 41/20.5 4V20.5
Amperes 538 12.7/6.3 16.418.2 24.611 2.3 28.2114.1 2a.2114.i 37.2178.6 37.2/18.6 37.2/18.6
53C 11.6/5.8 1517.5 22111 25.8112.9 25.811 2.9 34117 34.2117.1 34.2117.1
53A 1001200 1001200 1001200 100/200 1001200 1001200 1001200 100/200
Voltage 5381 1101220 1101220 I I 1101220 1 1101220 I 110/220 I 1101220 I 110/220 I 1101220
53Cl120/240 120/240 I I 1201240 I 1201240 I 1201240 I 120/240 I 1201240 I 1201240
RPM I3000 I3000 I 3000 I 3000 I 3000 I 3000 I 3000 I 3000
-
Single-phase, ** 50-Hertz Models Spec A Through C Only
* * Three-phase, 50-hz, 127/220 and 2201380-volt models are available by special order only.
4
Redistribution or publication of this document
by any means, is strictly prohibited.
Alternator Specifications
Design: Revolving field, two pole, compound wound Rotor: Laminated steel stack, press fitted to shaft.
for improved voltage regulation. Self-excited. Drip Heavy polyester with insulated copper wire field
proof construction. Connected directly to the engine coils. Balanced.
and permanently aligned. Stator: Laminated electrical steel welded stack.
Bearing: Prelubricated, double-sealed needle Machine wound and laced AC windings in class Fslot
bearing. liners.
Exciter: Isolated exciter winding, solicon diodes or Brushes: Electrographitic. Long life, easily serviced.
bridge rectifier, no commutator. Collector rings and Collector Rings: Sintered copper alloy, concentric
brushes carry only rectified excitation current to the annular rings molded in phenolic.
field coils.
Frequency Regulation: 3 hertz maximum, no load to
Insulation: Class F per NEMA MG1-1.65 definition. rated load.
Insulating varnish conforms to MIL-1-24092. Type M,
Voltage Regulation: k 5%.
Class 155.
Battery Charging Circuit: A separate alternator wind-
Ternperafure Rise: Temperature rise at rated load is
ing internally wired to an insulated terminal inside the
within NEMA MGl-22.40 definition.
generator end bell. This simplifies installation of the
Cooling: Direct drive centrifugal blower. Air required optional, customer installed battery charging kit.
67-cf m . Output is 12 volts only at 5-8 amperes of continuous
charging current.
6
Redistribution or publication of this document
by any means, is strictly prohibited.
FIGURE 2. OPTIONAL RECEPTACLE PANEL
EM263
I, j 0
WITH VOLTMETER
(SPEC A AND B ONLY) ES-1266
FIGURE 5. STANDARD RECEPTACLE BOX
FOR 120 VOLT MODELS
(SPEC J ONLY)
0
240V ;@ 12OV
ON 120/240V
ES-1264
ES-1265
M-1326
1 L ES-1268
8
Redistribution or publication of this document
by any means, is strictly prohibited.
The 150-1667 ldlematic kit (Optional in Spec C I NlTIAL LINKAGE ADJUSTMENT
through F ONLY) or 150-1763 ldlematic kit (Optional
in Spec H ONLY); are obsolete and no longer availa- 1. Push solenoid plunger completely into solenoid
ble. Both kits are superseded by Replacement P.C. case (by hand) until plunger is completely bot-
Board kit 150-1905. When servicing any ldlematic tomed out (seated). See Figure 11 or 12.
equipped unit in Spec C through H that requires 2. Depresssolenoid plunger until fully seated. If low
replacement of the original printed circuit board: speed throttle stop screw on engine carburetor
order kit 150-1905. does not touch throttle stop on carburetor,
loosen jam nut on the solenoid plunger to allow
If asked to install a complete ldlematic kit on any for additional travel as required. Be careful not to
4
Spec H or J model, order kit 150-1904. All electrical stretch linkage spring.
components in these kits (except the on/off switch) 3. Adjust inside jam nut (closest to plunger) until it
are installed inside the control (receptacle) panel. touches the solenoid linkage spring. See Figure
11 or 12.
Complete ldlematic kits are no longer available for 4. While holding solenoid plunger, linkage spring
any Spec A through C generator sets. and inside jam nut from rotating, torque outside
jam nut to 8 inch pounds. See Figure 11 or 12.
IDLEMATIC CONTROL OPTION
(1.7 Through 6.5 kW Proper solenoid adjustment is
critical for speed control to
Briggs 8t Stratton Powered Models Only) function. If linkage spring is too taut, engine
The operating characteristics, initial linkage and car- solenoid will not remain seated in idle mode of
buretor throttle stop screw adjustments are critical in operation.
diagnosing proper operation or troubleshooting and
repair of any Spec H or J models equipped with the CARBURETOR THROTTLE STOP SCREW
150-1904 kit. Any Spec C through H modelsequipped
with an obsolete 300-1801 printed circuit board and ADJUSTMENT
solid wire throttle linkage MUST be converted to the Start the generator set and place the Idlematic on/off
new linkage and 300-2298 printed circuit board sup- switch in “off” (down) position with no load con-
plied in the 150-1905 kit. nected to set. Connect an accurate AC voltmeter to
any 120 volt duplex receptacle. Manually over-ride
IDLEMATIC CONTROL OPERATION engine governor by holding the throttle stop screw
against stop on carburetor at idle speed. Adjust throt-
When a load is placed on thealternator, the ldlematic tle stop screw for 75 volts AC output. Release gover-
control senses the load and opens the throttle so the nor and allow engine to come up to governed RPM.
set runs at 3600 RPM. A toggle switch mounted on the
receptacle panel turns the ldlematic on or off. Turning throttle stop screw inward (clockwise) increasesvoltage
and backing screw out (counter-clockwise) decreases the output
Using the Idlematic Control: Place the ldlematic voltage.
switch in the Off (down) position and start the gener-
ator set. place the switch in the ON (up) position with Torque locknut on throttle stop screw of carburetor
no load connected to the generator set. Within 30 to 20-24 inch pounds (2.3-2.7 Nom) to hold the proper
seconds, the engine RPM should drop from full load adjustment.
speed to idle speed. Connecting a load of at least 30
watts or more will cause the engine RPM to increase Place the ldlematic switch in “on” (up) position and
I
’
immediately to full load speed. After the first load/no within 30 seconds RPM should drop from full load
load cycle, time delay from full load speed to idle speed to idle speed with no load connected to the set.
speed is approximately 15 seconds. Remove load and
t place ldlematic switch in OFF position prior to stop-
ping the generator set.
If unit is operated with the ldlematic circuit inoperative, place the
ldlematic on/off switch in “off” (down) position to protect circuits
from any further electrical damage.
from full load speed to no load speed is approxi- tinuously. AC output voltage (no load) MUST be
mately 15 seconds after load is removed. adjusted for 75 volts AC by adjusting throttle stop
screw o n carburetor to obtain this voltage.
An electrical load less than 30 watts If control does not reduce set speed at all, stop unit, remove
will not be sensed by the Idlematic receptacle panel and recheck all wiring step by step for proper and
control. Application of such a small load will result in tight connections. If all connections are correct, check one amp
improper engine speed fluctuations. fuse on printed circuit board which controls solenoid operation. If
speed control still does not operate and external governor linkage
is not binding and throttle stop screw is properly adjusted for 75
If the unit idle speed is not stable, but the output volts AC, replace printedcircuit board with a known good 300-2298
voltage is correct (75volts AC at idle without load and .P.C. Board.
throttle held on idle stop); the engine solenoid
plunger was not fully seated during initial linkage
spring adjustment. Loosen jam nuts on plunger rod
and readjust spring setting on plunger. rod per
instructions under INITIAL LINKAGE ADJUST-
MENT Section. Then repeat steps3and 4and besure
locknut is tightened properly to hold this adjustment.
- SOLENOID PLUNGER
RETAINER BRACKET
PLUNGER
SPRING
/
PLUNGER b< 0
-PLUNGER
ROD
LINKAGE COUPLING
SPRING
4-BEAD CHAIN
ENGINE GOVERNOR
ARM
-
GOVERNOR BRACKET
(CUT-AWAY)
FS-1241
- -~
A-,,,A
/.
---Y
GENERATOR
t i t N t K A IUK
ADAPTER
.IF..
bHAP I
ADAPTER
P
.--R
/ \
STI
TPa
CONNE CTO R
LOCAT ION P 1-E I-A
RECEPTACLE
CAPACITOR COVER
ES-1270
\
\
NUT
-1-
-
\ A - lERAToR
GENERATOR
GENERATOR
SHAFT
ADAPTER ADAPTER
WIRE
CONNECTORS
sTA'v, BRUSH
GUIDE
LOCAT ION
PIN
BRUSH
CAPACITOR GROUNDING
TERMINAL
RECEPTACLE
ES-1271
14
Redistribution or publication of this document
by any means, is strictly prohibited.
\
15-1272
-
SYMPTOM POSSIBLE CAUSE(S) I CORRECTIVE ACTION *
-
No Output 1. Open fuse(s) or circuit breaker (s) 1. Replace C
i n receptacle box (if used).
2. Faulty receptacle. (60 Hz only) 2. Replace D
3. Brushes worn excessively. 3. Replace A
4. Brushes sticking or broken spring. 4. Replace A
5. Loss of residual. 5. See Troubleshooting Procedures E
6. Dirty collector rings. 6. Clean or replace A
7. Loose or broken wire. 7. Repair B
8. One or both diodes shorted or 8. Replace F
defective bridge rectifier (if used).
9. Faulty capacitor. 9. Replace G
10. Faulty rotor. 10. Replace H
11. Faulty stator. 11. Replace . J
-
Low output 1. Alternator speed too low. 1. Speed should be 3600 rpm. (3000 rF I
(Requires Frequent 2. Engine low on power. 2. See Engine Manual. 50 Hz)
Field Flashing) 3. Worn brushes. 3. Replace A
4. One open diode. 4. Replace F
5. Open Capacitor. 5. Replace F
6. Rotor windings shorted. 6. Replace H
7. Stator windings shorted. 7. Replace J
8. Loss of Residual. 8. See Troubleshooting Procedures E
Alternator 1. Overloaded. 1. Remove part of load.. C
Overheats 2. Alternator air intake plugged, 2. Clean
with dirt, leaves, etc.
3. Windings covered with dirt or '3. Clean .
oil.
ALTERNATOR TROUBLESHOOTING
There are four main items to check if generator out-
put does not build up to nameplate rating.
[AI
ALTERNATOR BRUSHES
To inspect the brushes, refer to Figure 16 using the
following procedures:
I
1. Remove receptacle cover plate, receptacle box or
receptacle panel (NOT wrap around sheet metal
e
housing) from end bell.
Some modelswill have duplex receptacles,a ground terminal
strip ora bridge rectifier mounted in the end bell. These items NEW REPLACE
will not interfere with brush removal and replacement. ALTERNATOR BRUSH WEAR LIMITS
ES-1273
2. Unfasten brush mounting (Phillips) screws.
3. Slide brushes out of their holders. FIGURE 16. BRUSH REMOVAL AND REPLACEMENT
4. Replace if worn to 5/16 inch or less as shown in (ALL MODELS)
Figure 16.
17
Redistribution or publication of this document
by any means, is strictly prohibited.
BROKEN WIRE OR LOOSE CONNECTION FAULTY RECEPTACLE(S)
Check all internal wiring for loose or broken connec- Receptacles mounted on or within the end bell can be
tions or terminals. Check especiallyaround all recep- removed and replaced without removing the end bell
tacles and switches, terminal strip or circuit board from the generator. Remove the receptacle cover
connections, stator output leads (T1 through T4), plate or receptacle box from endbell, then remove
ground connections, etc. mounting screws of each individual receptacle. On
larger size 120/240 volt models, remove the side
mounting screws which secure the receptacle panel
to the sheetmetal wrap around housing. Pull the
FUSES receptacle panel out as far as the interconnecting
wiring allows. Each receptacle can now be removed
Some models with separate receptacle boxes are by disconnecting wiresand removing screw(s) which
equipped with fuses. If fuse is open or blown, turn secure receptacle to panel. Mark all wires for easier
fuse cover counterclockwise and replace (Figure 17) replacement before disconnecting.
with an identical fuse. Blown fuses are caused by too
much load on the receptacle, or an external short
Do NOT attempt to remove any
circuit. recep tacles with unit running.
Touching “live” wires or terminals could cause
Don’t exceed c u r r e n t rating serious injury or death.
stamped belowreceptacles. Be sure
to replace with the correct rated fuse to avoid damage
to power tools. [El
LOSS OF RESIDUAL MAGNETISM
(Flashing the Field)
20 A M P FUSE If there is a loss of residual magnetism (voltage will
not build up), it may be necessary to flash the field.
18
Redistribution or publication of this document
by any means, is strictly prohibited.
BRUSHES
10 OHM, 10 WATT 120 AMP (DC)
RESISTOR 300 VOLT DIODE
I TOGETHER
CAPACITOR OUTSIDEVIEW
OF ENDBELL
(RECEPTACLE PANEL
REMOVED)
C:ITOR
6 VOLT DRY
ELL BATTERY
[FI
DIODES (Spec A and B Models ONLY)
. Diodes can be tested without removal from end bell
or unsoldering wire leads. Disconnect plug between
' stator and end bell located underneath end bell.
0 Diodes and connector plug are shown in Figure 19.
Using an accurate ohmmeter, connect one lead to
LEAD
each end of each diode and observe reading. Reverse
ohmmeter leads and again observe resistance read-
ings as shown in Figure 19.
19
Redistribution or publication of this document
by any means, is strictly prohibited.
POSiTlVE TERMINAL
POSiTlVE TERMINAL
I FIGURE 22. BRIDGE RECTIFIER LOCATION ON
120/240 VOLT MODELS IN SPEC H ONLY
e - *
. .
. . . . ES-1281
FIGURE 23. BRIDGE RECTIFIER LOCATION
ON SPEC J MODELS .
..
' [GI
CAPACITOR
If it is necessary t o flash the field daily or each time
the alternator is used, the problem is probably a
defective capacitor. Capacitor is located in end bell
(Figure 20). If generator set is running at a constant
speed (no fluctuation) but voltage rises and falls, the
capacitor may also be defective. If suspecting a
ES-1279
defective capacitor, replace with one known to be
FIGURE 21. BRIDGE RECTIFIER LOCATION ON good.
120 VOLT MODELS IN SPEC H ONLY
20
Redistribution or publication of this document
by any means, is strictly prohibited.
Replacing the Capacitor 5. Install the capacitorinto position with themount-
To replace the capacitor: ing bracket-
1. Remove the screw that secures the capacitor 6. Fasten the screw through the mounting bracket
mounting bracket t o the end bell. Remove the t o the end bell. Be sure the grounding wire is in
bracket. See Figure 20. position.
2. Free the capacitor from its position.
3. Slide the two terminal wires off the terminal posts
at the bottom of the capacitor.
CHI
TESTING ROTOR WINDINGS
4. Connect terminal wires onto the terminal posts of
the new capacitor. Be sure to attach the ground- Measuring Rotor Winding Resistance
ing wire (white) to the unpainted terminal post. Use an accurate ohmmeter for this test. Connect
The black wire attaches to the terminal post with meter leads to each collector ring (Figure 24). Resist-
the red marking. ances should be within the values specified in Table
1. Readings are taken at 68F (20C).
81 -Orange
xo -Black
X2 - Lt. Blue
x3 - Ll. Blue
T1 -Blue
T2 -Black
T3 -Red
T4 -Yellow
ES-1282
[JI 81 XO X 2 X3 T4 T3 T2 T1
81 -Orange
XO -Black
X2 - L l . Blue
X3 - L I Blue
T1 -Blue
T2 -Black
TD -Red
T4 -Yellow
61 XO X 2 X3 T4 T3 T2 T1
ALL MODELS BEGINNING SPEC C
AND LATER
A
A
W
m
I
I
I
I
I
I
I
I
I 240V, 15A RECEPTACLE
I
I
I
I 6 6
T2
818
I RECEPTACLE
T3 I BOX
2
T4
4
3----
-
-
I-
1
5 .
I
I
I I
1 1 -
-- -- CR1
I ROTOR
I
MAGNETO ASSY.
I--
I
, CHARGER I
i--A
- (OPTIONAL)
SPARK
PLUG ~1
RECONNECTION CHART
12ov, 2w 120/240, 3W
REF
c1
IQTY
I 1
I
I CAPACITOR
DESCRIPTION
II
CR1,2 2 RECTIFIER - DIODE
T3 El SPARK PLUG
G1 MAGNETO ASSY.
T4
J1 1 CONNECTOR
P1 1 CONNECTOR
s1 -
SWITCH STOP
RECEPTACLE
I ROTOR
- SPARK
PLUG
-
NOTE:
T2 MUST BE GROUNDED
RECONNECTION CHART
X Y
2W, 50 Hz 3W, 50 Hz 2W, 50 Hz
120v 120/24ov 240V
11ov 11OI22OV 220v
1oov 100/200v 200v
i:-T
T4
T1
T4
..
t
c
t
T3
T1
f Y
I
--
Redistribution or publication of this document
27 by any means, is strictly prohibited.
601-0212
(SPEC A-C)
iI T1
I
' BLUE
-- r --
RECEPTACLE
-- - I
BOX
T2 BLACK (OPTIONAL)
-
- REF
DES
QTY DESCRIPTION
c1 1 CAPACITOR (REF)
CR1 1 BRDIGE-RECTIFIER (REF)
El 1 SPARKPLUG
G1 1 MAGNETO
-
1- CONTROL - GEN SET s1
S2
1
1
SWITCH-ON OFF (WHEN USED)
SWITCH-STOP (WHEN USED)
T4
:I* I
v
F1
52
rw7
F2
r'
I
DESCRIPTION I
I
I
/i 1 I~/SONNECTOR I
F1 I 1 lFUSE-30AMP
1 -
F2
F3 1
1 IFUSE 15 AMP
-
1 IFUSE 20 AMP I
-
1 RCPT LOCKING (30A, 225V)
-
1 RCPT DUPLEX (15A, 125V)
-
1 RCPT TWIST LOCK (20A. 250V)
PI I 1 JCONNECTOR
I 1 RECEPTACLE
BOX ASSY WIFUSE .
-
CB
ZOA
20A
15A
--
CB
25A
30A -
251
323-1052
max W @
120v
3750 CSA 323-1061
:El Y2:
3750 3750 CSA 323-1051 CSA 323-1045
-
STD HOME STANDBY: CANADA BLANK PANEL STD CONTRACTORS PANEL
STD HOME STANDBY: USA
n
WITH FULL PWR AT 120 VOLT SWITCH
15A 20A 15A 30A
125V 125f250V 125V 125l25OV 30A 1SA 20A .
I 125V 125V '250V
CB
w
0
20A
323-1063
15A
30A
323-1062 301-4331
C t
323-1066
I
15A,250V
30A,125V
181 1
G o w
6-15R
L5-30R
a0
15A
30A
20A
20A
323-1073
601-0211
SHEET 1 OF 2
-
CONTROL GEN SET (W ~RlNGDIAGRAM)
SPEC F OF LY
(T2) BLK
(T3) RED
(T4) Y E S
f
- **
- 240V
T21BLz>-
*FOR 2 WIRE UNGROUNDED USE 332-1556
(Tl) BLUE t
(TZ) ELK> 4
-
(T3) RED
(Tl) BLUE
(T3) RED
(T3) RED
L12ov
(T4)YEL 20A (T4)YEL 30A
If,
t
*FOR 2 WIRE UNGRDUNDED USE 332-1556
STATOR -- END BELL
L__
PLUG CONTROL GEM SET - 601-0211
(WIRING DIAGRAM) SHEET 2 OF 2
SPEC F ONLY Redistribution or publication of this document
by any means, is strictly prohibited.
:RONT VIEW OF PANEL CONTROL GEN SET-
15A. 15A
(WIRING DIAGRAM)
15A 15A . 15A
240V 120v 12ov 120v SPEC H ONLY
0 0
0
(30
rl NOTES:
1. FUSES AND SWITCHES SHOWN ON
PANEL
3KW TO 5 K W 120v
1.7KW TO 3DKW 120V e240V 3 K W TO 5KW 240V r; 2 BEARING C
0 0
w
h)
. a (n"O)
00
4 . 4
E r n
\
3 K W TO 6.5KW 240V r
,IE
r
2 BEARING ( [ 1.7KW TO 2.2KW 120v 3.0 KW 240V
CONTRACTORS PANEL CONTRACTORS PANEL
WITH FULL POWER AT 120V RATING WITH FULL POWER AT 120v RATING
2OA 30A 15A 20A S A 15A
I
240V 120v 120v 240V 120v 120v
I I I
601-0214
3.2KW TO 6.5KW c 3.2KW T O 6.5KW r 200,220,240 V
1.4KW TO 5.4KW Id, SoHz SHEET 1 OF 2
r 5EE
NOTE I
t
TZfBLKl
TJLRED)
t
T4(YEL) T4(YEU T 4 Y EL)
1.7 KW TO 2.2 KW 120V 3KW 2 4 0 V 3KW TO 5KW 240V p 3 K H TO 5 K W 120V 3KW TO 6 S K W 2 4 0 V
TII
15A 15A
l20V I20V
I I I 1 I
T4(YEL)
1.7KW g 2 2 K W 120V 6.5 KW 240V H IJI
NOTES
1. IF NO BREAKER IS IN THE CONTROL
THE LEADS GO DIRECTLY TO THE LOAD.
2. 50 HZ GENERATORS: GROUND TERMINAL 2,
DO NOT GROUND TERMINAL 1.
CONTROL GEN SET -
(WIRING DIAGRAM)
SPEC H ONLY
3.2KW-6.5KW 240V
CUSTOMER
CONNECTION
601-0214
SHEET 2 OF 2
Redistribution or publication of this document
by any means, is strictly prohibited.
15A 15A
15A 15A 120v 12ov
12ov IZOV
F
(o.o)(o.o) 00
30 A
200/240v
i
I
2.2F€I-IPIIJ
3.2PFI- 3 P l l J
3.7 PFI-3PIIJ
-
F
5.0 PKI 3P/ IJ m
.E .
. -. .- .-. .
I
I
15A I5A
12ov l2OV 30A 3OA ISA
240V I20V 12ov
'
CONTROL GENSET
(WIRING DIAGRAM)
-
SPEC J ONLY
601-021 5
ISHEET 1 OF 2
5 T I (BWEI
17
. KW TO 2.2 KW 12OV 3KW 12OV 1-10
i-
3 KW 120/240V -
20 A
120/240V
T I (BLUE)
T 2 (BLKI
T3 (REO1
E N
T 4 (YELI
SEE NOTE 6
3.W3.7 KW 120/240V
T4 ( Y E L I
3.7/5.0 KW 120/240V
6.5 KW 120/240V
3.7/5.OKW 120/240V ( 23 0 A )
idKW 120/240V SAME AS ABOVE E X C E T m d
ENGIFE WlRNG DIAGRAM ENGINE WIRING DIAGRAM --_- STATOR-- END BELL _______-
RECEPTACLE BOX I
A
NOTE: SI IN
RECEPTACLE
PANEL
i 5. [ -1 DENOTES BREAKER LOCATIONWHEN USED.
4 0 SWITCH ~
6. USE BLANK CONTROL PANEL
~ ~ ~
SI -STOP SWITCH OR START-STOP
SP-VACUUM SWITCH
SI-LOPKO
KI -START SOLENOID
81 -STARTER 601-0215
SHEET 2 OF 2
Redistribution or publication of this document
by any means, is strictly prohibited.
DICTIONARY OF BASIC ELECTRICAL TERMS
ALTERNATING CURRENT - Electricity that flows INSULATOR - Any material which has a very high
in one direction, then in the reversedirection through resistance to current flow. .L
kconductors. The current reverses at regular inter-
.
vals as each wire becomes positive then negative, .KILOWATT - 1000 Watts.
reversing polarity typically 60 times per second.
FUSE - A ribbon of fusible metal that burns and VOLTAGE DROP - The voltage required to force :
opens its associated circuit on detecting excess current through the resistance of line wires or the
current. power consuming device.
GROUNDING WIRE - Usually green in color and is WATT - A unit of measurement of electrical power
used to ground electrical equipment to prevent supplied to the circuit when one volt is forcing one <
electrical shock. ampere through one ohm resistance.
36
Redistribution or publication of this document
by any means, is strictly prohibited.
Redistribution or publication of this document
by any means, is strictly prohibited.
Onan Corporation
1400 73rd Avenue N. E.
Minneapolis,MN 55432
612-574-5000
Telex: 275477
Fax: 612-574-8087
Onan is a registered trademark of Onan Corporation