MG06C702
MG06C702
MG06C702
Programming Guide
VLT® AutomationDrive FC 360
vlt-drives.danfoss.com
Contents Programming Guide
Contents
1 Introduction 3
1.1 How to Read This Programming Guide 3
1.2 Definitions 4
1.3 Electrical Wiring - Control Cables 7
2 Safety 11
2.1 Safety Symbols 11
2.2 Qualified Personnel 11
2.3 Safety Precautions 11
3 Programming 13
3.1 Local Control Panel Operations 13
3.2 Basic Programming 21
4 Parameter Descriptions 24
4.1 Parameters: 0-** Operation and Display 24
4.2 Parameters: 1-** Load and Motor 33
4.3 Parameters: 2-** Brakes 45
4.4 Parameters: 3-** Reference/Ramps 48
4.5 Parameters: 4-** Limits/Warnings 54
4.6 Parameters: 5-** Digital In/Out 57
4.7 Parameters: 6-** Analog In/Out 71
4.8 Parameters: 7-** Controllers 74
4.9 Parameters: 8-** Communications and Options 79
4.10 Parameters: 9-** PROFIdrive 84
4.11 Parameters: 12-** Ethernet 90
4.12 Parameters: 13-** Smart Logic Control 93
4.13 Parameters: 14-** Special Functions 100
4.14 Parameters: 15-** Drive Information 106
4.15 Parameters: 16-** Data Readouts 108
4.16 Parameters: 17-** Feedback Options 112
4.17 Parameters: 18-** Data Readouts 2 112
4.18 Parameters: 21-** Ext. Closed Loop 113
4.19 Parameters: 22-** Application Functions 115
4.20 Parameters: 30-** Special Features 117
4.21 Parameters: 32-** Motion Control Basic Settings 117
4.22 Parameters: 33-** Motion Control Adv. Settings 117
4.23 Parameters: 34-** Motion Control Data Readouts 118
4.24 Parameters: 37-** Application Settings 120
6 Troubleshooting 149
6.1 Warnings and Alarms 149
6.1.1 Alarms 149
6.1.2 Warnings 149
Index 159
1 Introduction 1 1
Coast PM,N
The motor shaft is in free mode. No torque on the motor. Rated motor power (nameplate data in kW or hp).
IVLT,MAX TM,N
Maximum output current. Rated torque (motor).
IVLT,N UM
Rated output current supplied by the frequency converter. Instantaneous motor voltage.
UVLT,MAX UM,N
Maximum output voltage. Rated motor voltage (nameplate data).
Break-away torque
1.2.2 Input Torque
175ZA078.10
Pull-out
Control commands
Start and stop the connected motor with the LCP and
digital inputs.
Functions are divided into 2 groups.
Functions in group 1 have higher priority than functions in
group 2.
Group 1 Coast stop, reset and coast stop, quick stop, DC
braking, stop, and [OFF].
Group 2 Start, latched start, start reversing, jog, freeze
output, and [Hand On].
RPM
Table 1.3 Function Groups
Illustration 1.1 Break-away Torque
1.2.3 Motor
fM Stop command
Motor frequency. A stop command belonging to the control commands in
group 1. See Table 1.3 for more details.
fMAX
Maximum motor frequency.
1.2.4 References
fMIN
Minimum motor frequency. Analog reference
fM,N A signal transmitted to the analog inputs 53 or 54 can be
Rated motor frequency (nameplate data). voltage or current.
IM Binary reference
Motor current (actual). A signal transmitted via the serial communication port.
I1 x cosϕ1 I1 THD
Power factor = = Total harmonic distortion states the total contribution of
IRMS IRMS
The power factor indicates to which extent the frequency harmonic distortion.
converter imposes a load on the mains supply. Thermistor
The lower the power factor, the higher the IRMS for the A temperature-dependent resistor placed where the
same kW performance. temperature is monitored (frequency converter or motor).
130BC438.18
3)
RFI
91 (L1) (U) 96
3 phase 92 (L2) (V) 97
power 93 (L3) (W) 98
input (PE) 99
95 PE
Motor
Switch Mode
Power Supply 1) (-UDC) 88
10 V DC 24 V DC (+UDC) 89 Brake
15 mA 100 mA
resistor
50 (+10 V OUT) + - + -
+10 V DC (BR) 81 5)
0-10 V DC
0/4-20 mA 53 (A IN)
0-10 V DC 54 (A IN)
0/4-20 mA
Relay 1
55 (COM A IN/OUT) 03
250 V AC, 3 A
02
Analog 42 (A OUT)
output
01
0/4-20 mA
45 (A OUT)
12 (+24 V OUT)
Relay 2 2)
P 5-00 06
250 V AC, 3 A
24 V (NPN) 05
18 (D IN) 0 V (PNP)
24 V (NPN) 04
19 (D IN) 0 V (PNP)
20 (COM D IN)
4)
24 V (NPN) ON=Terminated
1 2
ON
RS485
(N RS485) 69 RS485
0V Interface
24 V (NPN) (P RS485) 68
31 (D IN) 0 V (PNP)
0V (COM RS485) 61
24 V (NPN)
32 (D IN) 0 V (PNP) (PNP) = Source
24 V (NPN) (NPN) = Sink
33 (D IN) 0 V (PNP)
A=Analog, D=Digital
1) Built-in brake chopper available from J1–J5.
2) Relay 2 is 2-pole for J1–J3 and 3-pole for J4–J7. Relay 2 of J4–J7 with terminals 4, 5, and 6 has same NO/NC logic as relay 1.
Relays are pluggable in J1–J5 and fixed in J6–J7.
130BD368.11
+24 VDC
0 VDC
result in 50/60 Hz ground loops due to noise from mains NPN (Sink)
Digital input wiring
supply cables. If this occurs, break the shield or insert a
100 nF capacitor between shield and chassis. 12 18 19 27 29 31 32 33 55
12 13 18 19 27 29 32 33 55
Illustration 1.4 NPN (Sink)
NOTICE
Control cables must be shielded/armored.
130BA681.10
Illustration 1.3 PNP (Source)
130BD369.11
130BD370.11
P 5-10 [8]
P 5-12 [0]
P 5 - 10 [9]
P 5 - 12 [6]
+24V
+24 V
12 18 19 27 29 31 32 33 20
12 13 18 19 27 29 32 33
Start/Stop
Speed
Speed
Start
[18]
Terminal 32 = Parameter 5-14 Terminal 32 Digital Parameter 6-19 Terminal 53 mode=[1] Voltage.
Input [22] Speed down.
+10 V/30 mA
130BF873.10
130BF821.10
FC
+24 V 12
Speed
D IN 18 P 6-15 50 53 54 55
D IN 19
D IN 27
D IN 29
D IN 31
D IN 32
Ref. voltage
D IN 33 P 6-11 10V
1 kΩ
+10 V 50
A IN 53
A IN 54 Illustration 1.9 Potentiometer Reference
COM 55
A OUT 42
2 Safety
2 2
2.1 Safety Symbols WARNING
The following symbols are used in this guide: UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
WARNING time. Unintended start during programming, service, or
Indicates a potentially hazardous situation that could repair work can result in death, serious injury, or
result in death or serious injury. property damage. The motor can start via an external
switch, a serial bus command, an input reference signal
Minimum waiting
Voltage Power range
time
[V] [kW (hp)]
2 2
(minutes)
0.37–7.5 kW
380–480 4
(0.5–10 hp)
11–75 kW
380–480 15
(15–100 hp)
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
• Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
• Ensure that only trained and qualified personnel
perform installation, start-up, and maintenance.
• Ensure that electrical work conforms to national
and local electrical codes.
• Follow the procedures in this guide.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
• Ensure that all safety covers are in place and
securely fastened before applying power.
NOTICE
HIGH ALTITUDES
For installation at altitudes above 2000 m (6562 ft),
contact Danfoss regarding PELV.
NOTICE
USE ON ISOLATED MAINS
For details about the use of the frequency converter on
isolated mains, refer to the section RFI Switch in the
design guide.
Follow the recommendations regarding the installation
on IT mains. Use relevant monitoring devices for IT
mains to avoid damage.
3 Programming
The numerical local control panel LCP 21 is divided into 4 Table 3.1 Legend to Illustration 3.1, Section A
functional sections.
130BD135.10
Setup 1234 AHP
A. Numeric display. VkW
srpm
B. Menu key. p5 p4
n1 n2 n3
Hz%
INDEX p3 p2 p1
C. Navigation keys and indicator lights (LEDs). Illustration 3.2 Display Information
D. Operation keys and indicator lights (LEDs).
130BC506.10
1 B. Menu key
To select between Status, Quick Menu, or Main Menu,
press [Menu].
3
A
C. Indicator lights (LEDs) and navigation keys
Setup 1
5 Indicator Light Function
2 ON turns on when the frequency
Status Quick Main converter receives power from the
4 B 10
6 On Green
Menu Menu mains voltage, a DC bus terminal, or a
Menu 24 V external supply.
9 When warning conditions are met, the
C 11 yellow WARN LED turns on, and text
7 Warn Yellow
Back
13 14 15
130BC440.10
Key Function
Setup 1
For moving to the previous step or layer
9 [Back]
in the navigation structure.
For switching between parameter groups,
parameters, and within parameters, or
3 3 10 [▲] [▼] increasing/decreasing parameter values. Setup 1
Key Function
Starts the frequency converter in local control.
Setup 1
• An external stop signal by control input or
13 Hand On serial communication overrides the local
hand on.
Illustration 3.3 Right-key Function
Stops the motor but does not remove power
to the frequency converter, or resets the
14 Off/Reset frequency converter manually after a fault has
been cleared. If in alarm mode, the alarm is
[►] can also be used for moving between parameter
reset if the alarm condition is removed.
groups. When in Main Menu, press [►] to move to the first
parameter in the next parameter group (for example, move
Puts the system in remote operational mode.
from parameter 0-03 Regional Settings [0] International to
15 Auto On • Responds to an external start command by
parameter 1-00 Configuration Mode [0] Open loop).
control terminals or bus communication.
Table 3.4 Legend to Illustration 3.1, Section D 3.1.3 Quick Menu on NLCP
WARNING The Quick Menu gives easy access to the most frequently
used parameters.
HIGH VOLTAGE
Touching the frequency converter after pressing the [Off/ 1. To enter Quick Menu, press [Menu] until the
Reset] key is still dangerous, because the key does not indicator in display is placed above Quick Menu.
disconnect the frequency converter from the mains.
2. Press [▲] [▼] to select either QM1 or QM2, then
press [OK].
• Disconnect the frequency converter from the
mains and wait for the frequency converter to 3. Press [▲] [▼] to browse through the parameters in
fully discharge. See the discharge time in Quick Menu.
Table 2.1. 4. Press [OK] to select a parameter.
5. Press [▲] [▼] to change the value of a parameter
3.1.2 The Right-key Function on NLCP
setting.
Press [►] to edit any of the 4 digits on the display 6. Press [OK] to accept the change.
individually. When pressing [►] once, the cursor moves to 7. To exit, press either [Back] twice (or 3 times if in
the first digit and the digit starts flashing as shown in QM2 and QM3) to enter Status, or press [Menu]
Illustration 3.3. Press the [▲] [▼] to change the value. once to enter Main Menu.
Pressing [►] does not change the value of the digits or
move the decimal point.
QM 1 QM 2 Changes made QM 3 QM 4 QM 5
130BC445.13
Motor
Motor control 1-39 XXXX Motor poles Terminal 32/33
nominal 1-25 XXXX RPM 1-22 XXXX V Motor voltage 1-01 [1] 5-71 [0]
principle encoder direction
speed
Motor cont. Motor thermal
rated torque
1-26 XXXX 1-23 XXXX Hz Motor frequency 1-90 [0] protection
Motor type 1-10 [0]
Stator PM motor Asynchronous motor
Resistance (Rs) 1-30 XXXX 1-24 XXXX A Motor current 2-10 [0] Brake function
Motor
Motor poles 1-39 XXXX Motor 1-24 XXXX A 1-20 XXXX kW Motor power
1-25 XXXX RPM nominal current 4-16 XXXX % Torque limit motor mode
speed
Motor
Back EMF at 1-40 XXXX 1-25 XXXX RPM
nominal 1-22 XXXX V Motor voltage
1000 RPM
Programming Guide
Stator
Resistance (Rs) 1-30 XXXX 1-24 XXXX A Motor current
3-02 XXXX Hz Minimum reference
15
3 3
Programming VLT® AutomationDrive FC 360
After power-up, Status Menu is active. Press [Menu] to The Main Menu gives access to all parameters.
toggle between Status, Quick Menu, and Main Menu.
1. To enter Main Menu, press [Menu] until the
3 3 [▲] and [▼] toggle between the options in each menu. indicator in the display is placed above Main
Menu.
The display indicates the status mode with a small arrow 2. [▲] [▼]: Browse through the parameter groups.
above Status.
3. Press [OK] to select a parameter group.
4. [▲] [▼]: Browse through the parameters in the
130BA466.10
specific group.
5. Press [OK] to select the parameter.
6. [►] and [▲] [▼]: Set/change the parameter value.
7. Press [OK] to accept the value.
8. To exit, press either [Back] twice (or 3 times for
array parameters) to enter Main Menu, or press
[Menu] once to enter Status.
See Illustration 3.6, Illustration 3.7, and Illustration 3.8 for the
Illustration 3.5 Indicating Status Mode principles of changing the value of continuous,
enumerated, and array parameters, respectively. The
actions in the illustrations are described in Table 3.5,
The following 8 parameters can be accessed from NLCP Table 3.6, and Table 3.7.
status menu in auto-on mode:
• Parameter 16-02 Reference [%].
• Parameter 16-09 Custom Readout.
• Parameter 16-10 Power [kW].
• Parameter 16-13 Frequency.
• Parameter 16-14 Motor current.
• Parameter 16-16 Torque [Nm].
• Parameter 16-30 DC Link Voltage.
• Parameter 16-52 Feedback[Unit].
The following 6 parameters can be accessed from NLCP
status menu in [Hand On] mode:
• Parameter 16-09 Custom Readout.
• Parameter 16-10 Power [kW].
• Parameter 16-13 Frequency.
• Parameter 16-14 Motor current.
• Parameter 16-16 Torque [Nm].
• Parameter 16-30 DC Link Voltage.
130BC446.10
Setup 1
12 2 Press [▼] repeatedly to move down to the parameter.
3 Press [OK] to start editing.
OK 1 4 [►]: First digit flashing (can be edited).
Back
11
5 [►]: Second digit flashing (can be edited).
3 3
Setup 1
6 [►]: Third digit flashing (can be edited).
2x 10
7 [▼]: Decreases the parameter value, the decimal point
2 changes automatically.
+ OK Setup 1 8 [▲]: Increases the parameter value.
9 [Back]: Cancel changes, return to 2.
[OK]: Accept changes, return to 2.
OK 3
10 [▲][▼]: Select parameter within the group.
Setup 1
11 [Back]: Removes the value and shows the parameter group.
12 [▲][▼]: Select group.
4
Table 3.5 Changing Values in Continuous Parameters
Setup 1
130BC447.11
OK
Setup 1 Setup 1 7
Back
7 OK 1
Back
6
Setup 1
Setup 1
5
8 OK 2
Setup 1 Back
4 OK
Setup 1
Array parameters function as follows: The GLCP is divided into 4 functional groups (see
Illustration 3.9).
130BC448.10
Setup 1 10
A. Display area.
5x
1 9 B. Display menu keys.
3 3
OK
Back
C. Navigation keys and indicator lights (LEDs).
Setup 1
%
8 D. Operation keys and reset.
INDEX
130BD598.10
OK 2
1 3
Setup 1 Status 1(1)
799 RPM 7.83 A 36.4 kW
Back
% 7
INDEX 2
A
0.000
5
53.2 %
Setup 1 OK
% 4 Auto Remote Ramping
6
INDEX
Back
OK 4 6 9
Quick Main Alarm
B Status Menu Menu Log
Setup 1
% 5
INDEX 7
8
Ca
ck
nc
Ba
11
el
Illustration 3.8 Main Menu Interactions - Array Parameters
10 C
12
On
Info
OK
1 [OK]: Shows parameter numbers and the value in the first 15
Warn.
index.
16 13
2 [OK]: Index can be selected. Alarm
3 [▲][▼]: Select index. 17
130BD532.10
LCP, or select [3] Size indep. from LCP to download
motor size independent parameters from LCP.
4. Press [OK]. A progress bar shows the uploading or
downloading progress.
5. Press [Hand On] or [Auto On] to return to normal
operation.
NOTICE
Risk of losing programming, motor data, localization, and
monitoring records by restoration of default settings. To
provide a back-up, upload data to the LCP before initiali-
zation.
Factory default parameter settings are restored during 2. Select [0] Open Loop in parameter 1-00 Configu-
start-up. This may take slightly longer than normal. ration Mode.
NOTICE
Manual initialization does not reset the following Encoder feedback is not supported for PM motors.
frequency converter information:
• Parameter 0-03 Regional Settings Programming motor data
• Parameter 1-06 Clockwise Direction When the initial programming steps are completed, the PM
motor-related parameters in parameter groups 1-2* Motor
• Parameter 15-00 Operating hours
Data, 1-3* Adv. Motor Data, and 1-4* Adv. Motor Data II are
• Parameter 15-03 Power Up's active.
• Parameter 15-04 Over Temp's The information is on the motor nameplate and in the
motor datasheet.
• Parameter 15-05 Over Volt's
Program the following parameters in the listed order:
• Parameter 15-30 Alarm Log: Error Code
1. Parameter 1-24 Motor Current.
3.2 Basic Programming 2. Parameter 1-26 Motor Cont. Rated Torque.
3.2.1 Asynchronous Motor Set-up 3. Parameter 1-25 Motor Nominal Speed.
4. Parameter 1-39 Motor Poles.
Enter the following motor data in the listed order. Find the
5. Parameter 1-40 Back EMF at 1000 RPM.
information on the motor nameplate.
6. Parameter 1-42 Motor Cable Length.
1. Parameter 1-20 Motor Power. Run a complete AMA using parameter 1-29 Automatic
2. Parameter 1-22 Motor Voltage. Motor Adaption (AMA) and select [1] Enable Complete AMA.
If a complete AMA is not performed successfully, configure
3. Parameter 1-23 Motor Frequency. the following parameters manually.
4. Parameter 1-24 Motor Current.
5. Parameter 1-25 Motor Nominal Speed. 1. Parameter 1-30 Stator Resistance (Rs).
Enter phase common stator winding resistance
For optimum performance in VVC+ mode, extra motor data (Rs). If only phase-to-phase data is available,
is required to set up the following parameters. divide the phase-to-phase value by 2 to achieve
the phase value.
6. Parameter 1-30 Stator Resistance (Rs). It is also possible to measure the value with an
7. Parameter 1-31 Rotor Resistance (Rr). ohmmeter, which also takes the resistance of the
cable into account. Divide the measured value by
8. Parameter 1-33 Stator Leakage Reactance (X1).
2 and enter the result.
9. Parameter 1-35 Main Reactance (Xh).
2. Parameter 1-37 d-axis Inductance (Ld).
The data is found in the motor datasheet (this data is Enter direct axis inductance of the PM motor.
typically not available on the motor nameplate). Run a If only phase-to-phase data is available, divide the
complete AMA using parameter 1-29 Automatic Motor phase-to-phase value by 2 to achieve the phase
Adaption (AMA) [1] Enable Complete AMA or enter the value.
parameters manually. It is also possible to measure the value with an
inductance meter, which also takes the
Application-specific adjustment when running VVC+ inductance of the cable into account. Divide the
VVC+ is the most robust control mode. In most situations, measured value by 2 and enter the result.
it provides optimum performance without further 3. Parameter 1-38 q-axis Inductance (Lq).
adjustments. Run a complete AMA for best performance.
Rotor detection
Adjust the starting torque in parameter 1-66 Min. Current at
This function is the recommended selection for
Low Speed. 100% provides nominal torque as starting
applications where the motor starts from standstill, for
torque.
example pumps or conveyors. For some motors, a sound is
heard when the frequency converter performs the rotor
detection. This sound does not harm the motor. Adjust the
value in parameter 1-46 Position Detection Gain for different
motors. If the frequency converter fails to start, or an
overcurrent alarm occurs when the frequency converter
starts, check if the rotor is blocked or not. If the rotor is
not blocked, set parameter 1-70 Start Mode to [1] Parking
and try again.
NOTICE
The AMA function does not cause the motor to run, and
it does not harm the motor.
4 Parameter Descriptions
[2] Forced stop, Reset the local reference to 0 upon restarting [0] Off This function is not active.
ref=0 the frequency converter. [1] * On This function is active.
0-20 Display Line 1.1 Small 0-21 Display Line 1.2 Small
Select a variable to be shown in line 1, left position. Select a variable to be shown in line 1, middle position.
Option: Function: Option: Function:
[3450] Actual Position [1669] Pulse output 27 [Hz]
[3456] Track Error [1670] Pulse output 29 [Hz]
[1671] Relay output
0-21 Display Line 1.2 Small
[1672] Counter A
Select a variable to be shown in line 1, middle position. [1673] Counter B
Option: Function: [1679] Analog output 45 [mA] 4 4
[0] None [1680] Fieldbus CTW 1
[37] Display Text 1 [1682] Fieldbus REF 1
[38] Display Text 2 [1684] Comm. Option STW
[39] Display Text 3 [1685] FC Port CTW 1
[748] PCD Feed Forward [1686] FC Port REF 1
[953] Profibus Warning Word [1690] Alarm Word
[1501] Running Hours [1691] Alarm Word 2
[1502] kWh Counter [1692] Warning Word
[1600] Control Word [1693] Warning Word 2
[1601] Reference [Unit] [1694] Ext. Status Word
[1602] Reference [%] [1695] Ext. Status Word 2
[1603] Status Word [1697] Alarm Word 3
[1605] Main Actual Value [%] [1890] Process PID Error
[1609] Custom Readout [1891] Process PID Output
[1610] Power [kW] [1892] Process PID Clamped Output
[1611] Power [hp] [1893] Process PID Gain Scaled Output
[1612] Motor Voltage [2117] Ext. 1 Reference [Unit]
[1613] Frequency [2118] Ext. 1 Feedback [Unit]
[1614] * Motor current [2119] Ext. 1 Output [%]
[1615] Frequency [%] [3401] PCD 1 Write For Application
[1616] Torque [Nm] [3402] PCD 2 Write For Application
[1617] Speed [RPM] [3403] PCD 3 Write For Application
[1618] Motor Thermal [3404] PCD 4 Write For Application
[1622] Torque [%] [3405] PCD 5 Write For Application
[1630] DC Link Voltage [3406] PCD 6 Write For Application
[1633] Brake Energy /2 min [3407] PCD 7 Write For Application
[1634] Heatsink Temp. [3408] PCD 8 Write For Application
[1635] Inverter Thermal [3409] PCD 9 Write For Application
[1636] Inv. Nom. Current [3410] PCD 10 Write For Application
[1637] Inv. Max. Current [3421] PCD 1 Read For Application
[1638] SL Controller State [3422] PCD 2 Read For Application
[1639] Control Card Temp. [3423] PCD 3 Read For Application
[1650] External Reference [3424] PCD 4 Read For Application
[1652] Feedback[Unit] [3425] PCD 5 Read For Application
[1653] Digi Pot Reference [3426] PCD 6 Read For Application
[1657] Feedback [RPM] [3427] PCD 7 Read For Application
[1660] Digital Input [3428] PCD 8 Read For Application
[1661] Terminal 53 Setting [3429] PCD 9 Read For Application
[1662] Analog input 53 [3430] PCD 10 Read For Application
[1663] Terminal 54 Setting [3450] Actual Position
[1664] Analog input 54 [3456] Track Error
[1665] Analog output 42 [mA]
[1666] Digital Output
[1667] Pulse input 29 [Hz]
[1668] Pulse input 33 [Hz]
0-22 Display Line 1.3 Small 0-22 Display Line 1.3 Small
Select a variable to be shown in line 1, right position. Select a variable to be shown in line 1, right position.
Option: Function: Option: Function:
[0] None [1680] Fieldbus CTW 1
[37] Display Text 1 [1682] Fieldbus REF 1
[38] Display Text 2 [1684] Comm. Option STW
[39] Display Text 3 [1685] FC Port CTW 1
[748] PCD Feed Forward [1686] FC Port REF 1
4 4 [953] Profibus Warning Word [1690] Alarm Word
[1501] Running Hours [1691] Alarm Word 2
[1502] kWh Counter [1692] Warning Word
[1600] Control Word [1693] Warning Word 2
[1601] Reference [Unit] [1694] Ext. Status Word
[1602] Reference [%] [1695] Ext. Status Word 2
[1603] Status Word [1697] Alarm Word 3
[1605] Main Actual Value [%] [1890] Process PID Error
[1609] Custom Readout [1891] Process PID Output
[1610] * Power [kW] [1892] Process PID Clamped Output
[1611] Power [hp] [1893] Process PID Gain Scaled Output
[1612] Motor Voltage [2117] Ext. 1 Reference [Unit]
[1613] Frequency [2118] Ext. 1 Feedback [Unit]
[1614] Motor current [2119] Ext. 1 Output [%]
[1615] Frequency [%] [3401] PCD 1 Write For Application
[1616] Torque [Nm] [3402] PCD 2 Write For Application
[1617] Speed [RPM] [3403] PCD 3 Write For Application
[1618] Motor Thermal [3404] PCD 4 Write For Application
[1622] Torque [%] [3405] PCD 5 Write For Application
[1630] DC Link Voltage [3406] PCD 6 Write For Application
[1633] Brake Energy /2 min [3407] PCD 7 Write For Application
[1634] Heatsink Temp. [3408] PCD 8 Write For Application
[1635] Inverter Thermal [3409] PCD 9 Write For Application
[1636] Inv. Nom. Current [3410] PCD 10 Write For Application
[1637] Inv. Max. Current [3421] PCD 1 Read For Application
[1638] SL Controller State [3422] PCD 2 Read For Application
[1639] Control Card Temp. [3423] PCD 3 Read For Application
[1650] External Reference [3424] PCD 4 Read For Application
[1652] Feedback[Unit] [3425] PCD 5 Read For Application
[1653] Digi Pot Reference [3426] PCD 6 Read For Application
[1657] Feedback [RPM] [3427] PCD 7 Read For Application
[1660] Digital Input [3428] PCD 8 Read For Application
[1661] Terminal 53 Setting [3429] PCD 9 Read For Application
[1662] Analog input 53 [3430] PCD 10 Read For Application
[1663] Terminal 54 Setting [3450] Actual Position
[1664] Analog input 54 [3456] Track Error
[1665] Analog output 42 [mA]
0-23 Display Line 2 Large
[1666] Digital Output
[1667] Pulse input 29 [Hz] Select a variable to be shown in line 2.
130BD380.10
Custom Readout (Value)
[11] RPM
P 16-09 [12] Pulse/s
Custom Readout
Unit P 0-30 [20] l/s
Max value
P 0-32 [21] l/min
[22] l/h
w)
flo
nd [23] m³/s
da
ee e)
. Sp ur [24] m³/min
e.g ss
it ( re
Un (P ) [25] m³/h
r nit er
ea U ow
Lin at
ic
t (P [30] kg/s
a dr ni
Min value Qu cU [31] kg/min
bi
Liniar Cu Motor Speed
units only [32] kg/h
P 0-31
0
Motor Speed [33] t/min
High limit
P 4-14 (Hz)
[34] t/h
[40] m/s
Illustration 4.1 Custom Readout [41] m/min
[45] m
[60] °C
The relation depends on the type of unit selected in [70] mbar
parameter 0-30 Custom Readout Unit: [71] bar
[72] Pa
Unit type Speed relation
[73] kPa
Dimensionless
[74] m WG
Speed
[80] kW
Flow, volume
[120] GPM
Flow, mass Linear
[121] gal/s
Velocity
[122] gal/min
Length
[123] gal/h
Temperature
[124] CFM
Pressure Quadratic
[127] ft³/h
Power Cubic
[140] ft/s
Table 4.1 Relation between Unit Type and Speed [141] ft/min
[160] °F
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] HP
Range: Function: [3] Size indep. Copy only the parameters that are
[0 - 0 ] Free text, for example used for the device tag of from LCP independent of the motor size. This selection
fieldbus application. can be used to program several frequency
converters with the same function without
0-38 Display Text 2 disturbing motor data that is already set.
Range: Function:
0-51 Set-up Copy
[0 - 0 ] Free text, for example used for the location tag of
fieldbus application. Option: Function:
[0] * No copy No function.
0-39 Display Text 3 [1] Copy from Copy from set-up 1 to set-up 2.
Range: Function: setup 1
[0 - 0 ] Free text, for example used for the help tag of [2] Copy from Copy from set-up 2 to set-up 1.
fieldbus application. setup 2
[9] Copy from Copy factory setting to programming set-
Factory setup up (selected in parameter 0-11 Programming
4.1.5 0-4* LCP Keypad Set-up).
4.2 Parameters: 1-** Load and Motor 1-01 Motor Control Principle
Option: Function:
4.2.1 1-0* General Settings
parameter 1-55 U/f Characteristic - U and
parameter 1-56 U/f Characteristic - F.
1-00 Configuration Mode
Option: Function:
[1] * VVC+ NOTICE
When parameter 1-10 Motor Construction is
Select the application control principle to be
used when a remote reference (that is, via set to PM-enabled options, only VVC+ option
analog input or fieldbus) is active. is available.
4 4
[0] Open Loop Enables speed control (without feedback signal
Normal running mode, including slip and load
* from motor) with automatic slip compensation
compensations.
for almost constant speed at varying loads.
Compensations are active, but can be disabled
1-03 Torque Characteristics
in parameter group 1-** Load and Motor.
Option: Function:
[1] Speed Enables speed closed-loop control with
Select the torque characteristic required. VT
closed loop feedback. For increased speed accuracy,
and AEO are both energy-saving operations.
provide a feedback signal and set the speed
PID control. The speed control parameters are [0] * Constant Motor shaft output provides constant torque
set in parameter group 7-0* Speed PID Control. torque under variable speed control.
[2] Torque Enables torque closed-loop control with speed [1] Variable Motor shaft output provides variable torque
closed loop feedback. Only possible when option [1] VVC+ Torque under variable speed control. Set the variable
is selected in parameter 1-01 Motor Control torque level in parameter 14-40 VT Level.
Principle. [2] Auto Energy Automatically optimizes energy consumption
[3] Process Enables the use of process control in the Optim. CT by minimizing magnetization and frequency
Closed frequency converter. The process control via parameter 14-41 AEO Minimum Magneti-
Loop parameters are set in parameter group 7-2* sation.
Process Ctrl. Feedback and parameter group 7-3*
Process PID Ctrl. 1-06 Clockwise Direction
Option: Function:
[4] Torque Enables the use of torque open loop in VVC+
open loop mode (parameter 1-01 Motor Control Principle). NOTICE
The torque PID parameters are set in parameter This parameter cannot be adjusted while
group 7-1* Torque PI Control. the motor is running.
[6] Surface Enables the use of surface winder control.
Winder Specific parameters in parameter group 7-2* This parameter defines the term clockwise
Process Ctrl. Feedb. and parameter group 7-3* corresponding to the LCP direction arrow. Used for
Process PID Ctrl. easy change of direction of shaft rotation without
swapping motor wires.
[7] Extended Enables the use of extended PID speed OL.
PID Speed Specific parameters in parameter group 7-2* [0] * Normal The motor shaft turns in clockwise direction when
OL Process Ctrl. Feedb. to parameter group 7-5* Ext. frequency converter is connected U⇒U; V⇒V; and
Process PID Ctrl. W⇒W to motor.
Parameter group for setting general motor data. The parameters cannot be adjusted while the motor is running.
4 4 The active parameters are shown in Table 4.2. x indicates that a particular parameter is active when the option is selected.
Parameter 1-10 Motor Construction [0] Asynchron [1] PM, non salient SPM [3] PM, salient IPM
Parameter 1-00 Configuration Mode x x x
Parameter 1-03 Torque Characteristics x
Parameter 1-06 Clockwise Direction x x x
Parameter 1-08 Motor Control Bandwidth x x x
Parameter 1-14 Damping Gain x x
Parameter 1-15 Low Speed Filter Time Const. x x
Parameter 1-16 High Speed Filter Time Const. x x
Parameter 1-17 Voltage filter time const. x x
Parameter 1-20 Motor Power [kW] x
Parameter 1-22 Motor Voltage x
Parameter 1-23 Motor Frequency x
Parameter 1-24 Motor Current x x x
Parameter 1-25 Motor Nominal Speed x x x
Parameter 1-26 Motor Cont. Rated Torque x x
Parameter 1-29 Automatic Motor Adaption (AMA) x x x
Parameter 1-30 Stator Resistance (Rs) x x x
Parameter 1-31 Rotor Resistance (Rr) x
Parameter 1-33 Stator Leakage Reactance (X1) x
Parameter 1-35 Main Reactance (Xh) x
Parameter 1-37 d-axis Inductance (Ld) x x
Parameter 1-38 q-axis Inductance (Lq) x
Parameter 1-39 Motor Poles x x x
Parameter 1-40 Back EMF at 1000 RPM x x
Parameter 1-42 Motor Cable Length x x x
Parameter 1-43 Motor Cable Length Feet x x x
Parameter 1-44 d-axis Inductance Sat. (LdSat) x
Parameter 1-45 q-axis Inductance Sat. (LqSat) x
Parameter 1-46 Position Detection Gain x x
Parameter 1-48 Current at Min Inductance for d-axis x
Parameter 1-49 Current at Min Inductance for q-axis x
Parameter 1-50 Motor Magnetisation at Zero Speed x
Parameter 1-52 Min Speed Normal Magnetising [Hz] x
Parameter 1-55 U/f Characteristic - U x
Parameter 1-56 U/f Characteristic - F x
Parameter 1-60 Low Speed Load Compensation x
Parameter 1-61 High Speed Load Compensation x
Parameter 1-62 Slip Compensation x
Parameter 1-63 Slip Compensation Time Constant x
Parameter 1-64 Resonance Dampening x
Parameter 1-65 Resonance Dampening Time Constant x
Parameter 1-66 Min. Current at Low Speed x x
Parameter 1-70 PM Start Mode x x
Parameter 1-10 Motor Construction [0] Asynchron [1] PM, non salient SPM [3] PM, salient IPM
Parameter 1-71 Start Delay x x x
Parameter 1-72 Start Function x x x
Parameter 1-73 Flying Start x x x
Parameter 1-80 Function at Stop x x x
Parameter 1-88 AC Brake Gain x
Parameter 1-90 Motor Thermal Protection x x x
Parameter 2-00 DC Hold Current x x x
Parameter 2-01 DC Brake Current
Parameter 2-02 DC Braking Time
x
x
x
x
x
x
4 4
Parameter 2-04 DC Brake Cut In Speed [Hz] x x x
Parameter 2-06 Parking Current x x
Parameter 2-07 Parking Time x x
Parameter 2-10 Brake Function x x x
Parameter 2-16 AC brake Max. Current x
Parameter 2-17 Over-voltage Control x x x
Parameter 4-10 Motor Speed Direction x x x
Parameter 4-14 Motor Speed High Limit [Hz] x x x
Parameter 4-16 Torque Limit Motor Mode x
Parameter 4-17 Torque Limit Generator Mode x
Parameter 4-18 Current Limit x x x
Parameter 4-19 Max Output Frequency x x x
Parameter 4-58 Missing Motor Phase Function x x x
Parameter 14-01 Switching Frequency x x x
Parameter 14-03 Overmodulation x x x
Parameter 14-07 Dead Time Compensation Level x x x
Parameter 14-08 Damping Gain Factor x x x
Parameter 14-09 Dead Time Bias Current Level x x x
Parameter 14-10 Mains Failure x
Parameter 14-11 Mains Voltage at Mains Fault x
Parameter 14-12 Function at Mains Imbalance x x x
Parameter 14-27 Action At Inverter Fault x x x
Parameter 14-40 VT Level x
Parameter 14-41 AEO Minimum Magnetisation x
Parameter 14-50 RFI Filter x x x
Parameter 14-51 DC-Link Voltage Compensation x x x
Parameter 14-55 Output Filter x x x
Parameter 14-64 Dead Time Compensation Zero Current Level x x x
Parameter 14-65 Speed Derate Dead Time Compensation x x x
Parameter 30-22 Locked Rotor Detection x x
Parameter 30-23 Locked Rotor Detection Time [s] x x
[3] PM, salient For permanent magnet (PM) motors with 1-20 Motor Power
IPM interior (salient) magnets. Option: Function:
[2] 0.12 kW - 0.16 hp
1-14 Damping Gain [3] 0.18 kW - 0.25 hp
Range: Function: [4] 0.25 kW - 0.33 hp
120 [0 - The damping gain stabilizes the PM machine. [5] 0.37 kW - 0.5 hp
%* 250 %] The value of damping gain controls the dynamic [6] 0.55 kW - 0.75 hp
performance of the PM machine. High damping [7] 0.75 kW - 1 hp
gain gives high dynamic performance, and low [8] 1.1 kW - 1.5 hp
damping gain gives low dynamic performance. [9] 1.5 kW - 2 hp
The dynamic performance is related to the [10] 2.2 kW - 3 hp
machine data and load type. If the damping gain [11] 3 kW - 4 hp
is too high or low, the control becomes unstable. [12] 3.7 kW - 5 hp
[13] 4 kW - 5.4 hp
1-15 Low Speed Filter Time Const.
[14] 5.5 kW - 7.5 hp
Range: Function: [15] 7.5 kW - 10 hp
Size related* [ 0.01 - 20 This time constant is used below [16] 11 kW - 15 hp
s] 10% rated speed. Obtain quick [17] 15 kW - 20 hp
control through a short damping [18] 18.5 kW - 25 hp
time constant. However, if this value [19] 22 kW - 30 hp
is too short, the control becomes
[20] 30 kW - 40 hp
unstable.
[21] 37 kW - 50 hp
[22] 45 kW - 60 hp
1-16 High Speed Filter Time Const.
[23] 55 kW - 75 hp
Range: Function:
[24] 75 kW - 100 hp
Size related* [ 0.01 - 20 This time constant is used above [25] 90 kW - 120 hp
s] 10% rated speed. Obtain quick
control through a short damping 1-22 Motor Voltage
time constant. However, if this value Range: Function:
is too short, the control becomes
Size [50 - 1000 Enter the nominal motor voltage
unstable.
related* V] according to the motor nameplate
data. The default value corresponds to
1-17 Voltage filter time const. the nominal rated output of the unit.
Range: Function:
Size [ 0.001 - 1 Reduces the influence of high
related* s] frequency ripple and system
resonance in the calculation of supply
voltage. Without this filter, the ripples
in the currents can distort the
calculated voltage and affect the
stability of the system.
Size related* [50 - 60000 Enter the nominal motor speed - Parameter 1-33 Stator Leakage
RPM] value from the motor nameplate Reactance (X1).
data. This data is used for - Parameter 1-35 Main Reactance
calculating automatic motor (Xh).
compensations.
• If [1] PM, non-salient SPM is selected,
the AMA is performed on:
1-26 Motor Cont. Rated Torque
Range: Function: - Parameter 1-30 Stator
Resistance (Rs).
Size [0.1 - Enter the value from the motor
related* 10000.0 nameplate data. The default value - Parameter 1-37 d-axis
Nm] corresponds to the nominal rated output. Inductance (Ld).
This parameter is available when • If [3] PM, salient IPM is selected, the
parameter 1-10 Motor Construction is set AMA is performed on:
to [1] PM, non salient SPM or [3] PM,
- Parameter 1-30 Stator
salient IPM, that is, the parameter is valid
Resistance (Rs).
for PM, non-salient SPM and PM, salient
IPM motors only. - Parameter 1-37 d-axis
Inductance (Ld).
1-29 Automatic Motor Adaption (AMA) - Parameter 1-38 q-axis
Option: Function: Inductance (Lq).
When parameter 1-10 Motor Construction is set to options 1-31 Rotor Resistance (Rr)
that enable permanent motor mode, the only option Range: Function:
available is [1] Enable Complete AMA.
motor. The default setting is calculated
by the frequency converter from the
Activate the AMA function by pressing [Hand On] after motor nameplate data.
selecting [1] Enable Complete AMA or [2] Enable Reduced
AMA. After a normal sequence, the display reads: Press [OK] 1-33 Stator Leakage Reactance (X1)
to finish AMA. After pressing [OK], the frequency converter
Range: Function:
4 4
is ready for operation.
Size [ 0.0 - NOTICE
related* 9999.000
NOTICE Ohm]
This parameter cannot be
adjusted while the motor is
• For the best adaptation of the frequency running.
converter, run AMA on a cold motor.
• AMA cannot be performed while the motor is Set the stator leakage reactance
running. value. Obtain the value from a motor
datasheet or perform an AMA on a
cold motor. The default setting is
NOTICE calculated by the frequency converter
Avoid generating external torque during AMA. from the motor nameplate data.
If an LC filter is used, set the frequency converter to run in 1-35 Main Reactance (Xh)
U/f control mode (recommended), or perform reduced Range: Function:
AMA in VVC+ mode. If an LC filter is not used, perform Size [ 0.0 - NOTICE
complete AMA. related* 9999.00
This parameter cannot be adjusted
Ohm]
while the motor is running.
4.2.4 1-3* Adv. Motor Data I
Set the main reactance of the motor using
Set parameters for advanced motor data. The motor data 1 of these methods:
in parameters 1-30 to 1-39 must match the motor for
• Run an AMA on a cold motor.
optimal performance. If the motor data is not known, The frequency converter
running an AMA is recommended. measures the value from the
1-30 Stator Resistance (Rs) motor.
This parameter is only active when 1-48 Current at Min Inductance for d-axis
parameter 1-10 Motor Construction is set to Range: Function:
options that enable PM (permanent 100 % [ 20 - 200 %] Use this parameter to set the inductance
magnet) motors. saturation point.
NOTICE
When using PM motors, it is
recommended to use brake resistors.
130BA166.10
electronic brake function for quick stop/hold of Par 1-55 [x]
1-55[3]
1-55[1]
1-55[0]
Output Frequency
Par 1-56 [x]
1-50 Motor Magnetisation at Zero Speed Illustration 4.3 Example of U/f Charac-
Range: Function: teristic
100 [0 - Use this parameter along with parameter 1-52 Min
%* 300 % Speed Normal Magnetising [Hz] to obtain a
] different thermal load on the motor when running
at low speed. 4.2.7 1-6* Load Depen. Setting
Enter a value that is a percentage of the rated
magnetizing current. If the setting is too low, the Parameters for adjusting the load-dependent motor
torque on the motor shaft may be reduced. settings.
Magn. current
130BB780.10
1-65 Resonance Dampening Time Constant [1] Parking The parking function applies DC current
Range: Function: across the stator winding and rotates the
rotor to electrical 0 position. This option is
0.005 s* [ 0.001 - Set parameter 1-64 Resonance Dampening
typically for pump and fan applications. If
0.05 s] and parameter 1-65 Resonance Dampening
flystart detects that the motor runs at low
Time Constant to help eliminate high-
speed or has stopped, the frequency
frequency resonance problems. Enter the
converter sends out a DC current to make
time constant that provides the best
the motor park at an angle and then
dampening.
starts the motor from that position.
[2] Enabled Enable flying start at every start command. 1-79 Compressor Start Max Time to Trip
Always
Range: Function:
[3] Enabled Enable the frequency converter to catch and
5 s* [0 - The time from the start signal is given until the
Ref. Dir. control a spinning motor. The search is
10 s] speed exceeds the speed set in
performed only in the reference direction.
parameter 1-78 Compressor Start Max Speed [Hz]
[4] Enab. Enable flying start at every start command. The must not exceed the time set in this parameter.
Always Ref. search is performed only in the reference Otherwise, the frequency converter trips with alarm
Dir. direction. 18, Start Failed. Any time set in parameter 1-71 Start
Delay for use of a start function must be executed
within the time limit.
Solution 1:
1. Start the frequency converter with a
0 RPM reference.
Solution 2:
1. Set parameter 1-71 Start Delay to the
premagnetize time (2–4 rotor time
constants).
175HA183.11
(Ω)
4 4
protection warning or trip of the frequency converter is 1330
required.
130BF960.10
+10 V
reset immediately.
42 53 54 50 55
[22] ETR Trip - Calculates the load and stops (trips) the
Extended frequency converter when the motor is
Detection overloaded. Program a warning signal via 1 of OFF
the digital outputs. The signal appears in the 37 38 12 13 18 19 27 29 31 32 33
event of a warning and if the frequency
converter trips (thermal warning). Once the
MOTOR ETR OVER alarm is reported, it can
ON
only reset after parameter 16-18 Motor
PTC / Thermistor <800 Ω >2.9 kΩ R
Thermal decreases to 0.
Illustration 4.5 PTC Thermistor Connection - Digital Input
130BF694.10
+10 V Option: Function:
42 53 54 50 55 [7] Digital input
OFF 31
4 4
ON
R
PTC / Thermistor <800 Ω >2.9 kΩ Use this parameter group to configure DC brake and DC
hold functions.
Illustration 4.6 PTC Thermistor Connection - Analog Input
2-00 DC Hold/Motor Preheat Current
Range: Function:
Input Supply voltage Threshold 50 % [0 - Set the holding current as a percentage of the
digital/analog cutout values * 160 %] rated motor current IM,N parameter 1-24 Motor
Digital 10 V <800 Ω - 2.9 kΩ Current. This parameter holds the motor function
Analog 10 V <800 Ω - 2.9 kΩ (holding torque) or pre-heats the motor. This
parameter is active if [0] DC hold is selected in
Table 4.3 Threshold Cutout Values
parameter 1-72 Start Function, or if [1] DC hold/pre-
heat is selected in parameter 1-80 Function at
NOTICE Stop.
Check that the selected supply voltage follows the
specification of the used thermistor element. NOTICE
The maximum value depends on the rated
motor current. Avoid 100% current for too
1-93 Thermistor Source
long. It may damage the motor.
Option: Function:
NOTICE
2-01 DC Brake Current
This parameter cannot be changed
while the motor is running. Range: Function:
50 [0 - NOTICE
NOTICE %* 150 %
MOTOR OVERHEATING
]
Digital input should be set to [0] PNP The maximum value depends on the rated
- Active at 24 V in motor current.
parameter 5-00 Digital Input Mode. To avoid motor damage caused by
overheating, do not run at 100% for too
Select the input to which the thermistor long.
(PTC sensor) should be connected. If an
analog input in this parameter is set as a Set current as % of rated motor current,
source, it cannot be used for other parameter 1-24 Motor Current. When speed is
purpose, for example, reference, feedback. below the limit set in parameter 2-04 DC Brake Cut
In Speed, or when the DC-brake inverse function is
[0] * None
active (in parameter group 5-1* Digital Inputs set to
[1] Analog Input
[5] DC-brake inverse; or via the serial port), a DC-
53
brake current is applied on a stop command. See
[2] Analog Input
parameter 2-02 DC Braking Time for duration.
54
[3] Digital input
2-02 DC Braking Time
18
Range: Function:
[4] Digital input
19 10 s* [0 - 60 s] Set the duration of the DC-brake current set in
[5] Digital input parameter 2-01 DC Brake Current, once
32 activated.
4 4
is only available for asynchronous
motors. NOTICE
When mechanical brake control output is
selected, but no mechanical brake is
2-17 Over-voltage Control connected, the function does not work by
Option: Function: default setting due to too low motor
Overvoltage control (OVC) reduces the risk of current.
the frequency converter tripping due to an
overvoltage on the DC link caused by
generative power from the load. 2-22 Activate Brake Speed [Hz]
CAUTION Range:
0 s*
Function:
[0 - 5 s] Enter the brake delay time of the coast after
PERSONAL INJURY AND ramp-down time. The shaft is held at 0 speed
EQUIPMENT DAMAGE with full holding torque. Ensure that the
Enabling OVC in hoisting applications mechanical brake has locked the load before the
may lead to personal injuries and motor enters coast mode.
equipment damage.
• DO NOT enable OVC in hoisting
applications.
[1] -Max - For both positive and negative values (both [171] lb/in2
+Max directions), relative to parameter 4-10 Motor [172] in WG
Speed Direction. [173] ft WG
[180] HP
3-01 Reference/Feedback Unit
3-02 Minimum Reference
Option: Function:
Range: Function:
[0] None
0 Reference- [ -4999.0 - Enter the minimum reference. The
[1] %
FeedbackUnit* 4999 minimum reference is the lowest
[2] RPM
ReferenceFeed- value obtainable by summing all
[3] Hz
backUnit] references.
[4] Nm The minimum reference is active
[5] PPM only when
[10] 1/min parameter 3-00 Reference Range is
[12] Pulse/s set to [0] Min.–Max.
[20] l/s
The minimum reference unit
[21] l/min matches:
[22] l/h
• The option in
[23] m³/s parameter 1-00 Configu-
[24] m³/min ration Mode.
[25] m³/h
• The unit selected in
[30] kg/s
parameter 3-01 Reference/
[31] kg/min Feedback Unit.
[32] kg/h
[33] t/min 3-03 Maximum Reference
[34] t/h
Range: Function:
[40] m/s
Size [-4999.0 - 4999 Enter the maximum reference. The
[41] m/min
related* ReferenceFeed- maximum reference is the highest
[45] m backUnit] value obtainable by summing all
[60] °C references.
[70] mbar
The maximum reference unit
[71] bar
matches:
[72] Pa
• The option selected in
[73] kPa
parameter 1-00 Configuration
[74] m WG Mode.
[80] kW
[120] GPM
• The unit selected in
parameter 3-00 Reference
[121] gal/s
Range.
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
130BA059.12
Y
Relative Z Resulting
Option: Function: actual
X Z=X+X*Y/100 reference
[0] * Sum Sum both external and preset reference
sources. Illustration 4.7 Preset Relative Reference
[1] External/ Use either the preset or the external
Preset reference source. Shift between external and
preset via a command or a digital input.
130BA278.10
Z
130BA059.12
Y
33 Relative Z Resulting
actual
X Z=X+X*Y/100 reference
[11] Local bus
reference
[20] Digital pot.meter Illustration 4.9 Resulting Actual
[32] Bus PCD Reference
Hz
[20] Digital pot.meter P 4-14
High-limit
[32] Bus PCD
Reference
P 1-23
Motor
frequency
P 4-12
Low limit
P 3-*2 Time
P 3-*1 Ramp (X)
Ramp (X)Up Down
Time (Acc) Time (Dec)
tacc tdec
[0] * Linear
130BD375.11
Hz
t jog s x ns Hz
Par . 3 − 80 =
Δ jog speed par . 3 − 19 Hz 3-92 Power Restore
3-81 Quick Stop Ramp Time Option: Function:
Range: Function: [0] * Off Reset the digital potentiometer reference to 0% after
Size [0.01 - Enter the quick-stop ramp-down time, power-up.
related* 3600 s] which is the deceleration time from the [1] On Restore the most recent digital potentiometer
synchronous motor speed to 0 Hz. Ensure reference at power-up.
that no resulting overvoltage occurs in the
inverter due to regenerative operation of 3-93 Maximum Limit
the motor required to achieve the given
Range: Function:
ramp-down time. Ensure also that the
100 %* [-200 - Set the maximum permissible value for the
generated current required to achieve the
200 %] resulting reference. This is recommended if
given ramp-down time does not exceed
the digital potentiometer is used for fine-
the current limit (set in
tuning of the resulting reference.
parameter 4-18 Current Limit). Activate quick
stop with a signal on a selected digital
3-94 Minimum Limit
input, or via the serial communication port.
Range: Function:
-100 % [-200 - Set the minimum allowed value for the
130BD376.11
Hz
200 %] resulting reference. This is recommended if
the digital potentiometer is used for fine-
P 4-14 Hz tuning of the resulting reference.
high limit
Qstop
130BA221.10
[2] Analog in 53 [rpm]
[4] Analog in 53 inv
[6] Analog in 54
[8] Analog in 54 inv
Warning 61, Feedback error is active as soon as the value Illustration 4.13 Motor Feedback Speed Error
in parameter 4-31 Motor Feedback Speed Error is
exceeded, regardless of the setting in
parameter 4-32 Motor Feedback Loss Timeout. Alarm 61, 4-32 Motor Feedback Loss Timeout
Feedback error is related to the motor feedback loss
Range: Function:
function.
0.05 s* [0 - 60 Set the timeout value allowing the speed
s] error set in parameter 4-31 Motor Feedback
Speed Error to be exceeded before enabling
the function selected in parameter 4-30 Motor
Feedback Loss Function.
4-61 Bypass Speed From [Hz] [1] Output Define terminal 27 as a digital output.
Range: Function:
5-02 Terminal 29 Mode
0 Hz* [0 - Some systems call for avoiding certain output
500 Hz] speeds due to resonance problems in the
Option: Function:
system. Enter the lower limits of the speeds to [0] * Input Defines terminal 29 as a digital input.
be avoided. [1] Output Defines terminal 29 as a digital output.
The bypass speed from must not exceed the
setting in parameter 4-14 Motor Speed High Limit The digital inputs are used for selecting various functions
[Hz]. in the frequency converter.
5-10 to 5-16 Digital Inputs
4-63 Bypass Speed To [Hz] [0] No No reaction to signals transmitted to the
Range: Function: operation terminal.
0 Hz* [0 - Some systems call for avoiding certain output [1] Reset Resets frequency converter after a TRIP/ALARM.
500 Hz] speeds due to resonance problems in the Not all alarms can be reset.
system. Enter the upper limits of the speeds to [2] Coast Coasting stop, inverted input (NC). The
be avoided. inverse frequency converter leaves the motor in free
mode.
The bypass speed to must not exceed the
Logic 0⇒ coasting stop.
setting in parameter 4-14 Motor Speed High Limit
[3] Coast and Reset and coasting stop inverted input (NC).
[Hz].
reset Leaves motor in free mode and resets
inverse frequency converter.
Logic 0⇒coasting stop.
Logic 1 to Logic 0⇒reset.
[4] Quick stop Inverted input (NC). Generates a stop in
inverse accordance with the quick stop ramp time set
in parameter 3-81 Quick Stop Ramp Time. When
the motor stops, the shaft is in free mode.
Logic 0⇒ Quick-stop.
[5] DC-brake Inverted input for DC braking (NC). Stops the
inverse motor by energizing it with a DC current for a
certain time period. See parameter 2-01 DC [18] Preset ref Same as [16] Preset ref bit 0.
Brake Current to parameter 2-04 DC Brake Cut In bit 2
Speed [Hz]. The function is only active when
the value in parameter 2-02 DC Braking Time is Preset ref. bit 2 1 0
different from 0. Logic 0=>DC braking. Preset ref. 0 0 0 0
[6] Stop NOTICE Preset ref. 1 0 0 1
inverse Preset ref. 2 0 1 0
When the frequency converter is at the
Preset ref. 3 0 1 1
torque limit and has received a stop
[22] Speed Same as [21] Speed up. [56] DigiPot Decrease signal to the digital potentiometer
down decrease function described in parameter group 3-9*
[23] Set-up Select [23] Set-up select bit 0 to select 1 of the 2 Digital Pot. Meter.
select set-ups. Set parameter 0-10 Active Set-up to [9] [57] DigiPot Clear the digital potentiometer reference
bit 0 Multi Set-up. clear described in parameter group 3-9* Digital Pot.
[26] Precise Precise stop inverse function is available for Meter.
stop inv. terminals 18 or 19. [60] Counter A Input for increment counting in the SLC
[28] Catch Increases reference value by percentage (relative) (up) counter.
4 4
up set in parameter 3-12 Catch up/slow Down Value. [61] Counter A Input for decrement counting in the SLC
[29] Slow Reduces reference value by percentage (relative) (down) counter.
down set in parameter 3-12 Catch up/slow Down Value. [62] Reset Input for reset of counter A.
[32] Pulse (Terminal 29 or 33 only) Measures the duration Counter A
input between pulse flanks. This parameter has a higher [63] Counter B Input for increment counting in the SLC
resolution at lower frequencies, but is not as (up) counter.
precise at higher frequencies. This principle has a [64] Counter B Input for decrement counting in the SLC
cut-off frequency, which makes it unsuited for (down) counter.
encoders with low resolutions (for example 30 [65] Reset Input for reset of counter B.
PPR) at low speeds. Counter B
[72] PID error Inverts the resulting error from the process
Speed [rpm] Speed [rpm]
130BB462.10
Timer
Sample time Surface Winder or [7] Extended PID Speed OL.
Time counter
Time Start Read Timer:
20 timer tides
Read Timer:
20 timer tides [74] PID enable This option enables the extended process PID
controller. Equivalent to
Illustration 4.14 Duration Between Pulse Flanks parameter 7-50 Process PID Extended PID.
Available only if parameter 1-00 Configuration
Mode is set to [7] Extended PID Speed OL.
[34] Ramp Enables a selection from the 4 ramps available, [150] Go To The frequency converter moves to the home
bit 0 according to Table 4.6. Home position.
[35] Ramp Same as ramp bit 0. [151] Home Ref. Indicates the status of the home referenced
bit 1 Switch switch. On means that the home position is
reached, off means that the home position is
Preset ramp bit 1 0 not reached.
Ramp 1 0 0 [155] HW Limit The positive hardware position limit is
Ramp 2 0 1 Positive exceeded. This option is active on the falling
Ramp 3 1 0 edge.
Ramp 4 1 1 [156] HW Limit The negative hardware position limit is
Negative exceeded. This option is active on the falling
Table 4.6 Preset Ramp Bits edge.
[157] Pos. Quick Stops the frequency converter during
[45] Latched The motor starts to run reverse when a pulse Stop Inv positioning with the ramp time that is set in
start is applied for minimum 4 ms. The motor stops parameter 32-81 Motion Ctrl Quick Stop Ramp.
reverse when stop commands are given. This option is only effective when
[51] External This function makes it possible to give an parameter 37-00 Application Mode is set to [2]
interlock external fault to the frequency converter. This Position Control.
fault is treated in the same way as an [160] Go To The frequency converter moves to the target
internally generated alarm. Target Pos. position. This option is only effective when
[55] DigiPot Increase signal to the digital potentiometer parameter 37-00 Application Mode is set to [2]
increase function described in parameter group 3-9* Position Control.
Digital Pot. Meter. [162] Pos. Idx Position index bit 0. This option is only
Bit0 effective when parameter 37-00 Application
Mode is set to [2] Position Control.
[163] Pos. Idx Position index bit 1. This option is only 5-10 Terminal 18 Digital Input
Bit1 effective when parameter 37-00 Application
Option: Function:
Mode is set to [2] Position Control.
[8] * Start Functions are described in parameter group 5-1*
[164] Pos. Idx Position index bit 2. This option is only
Digital Inputs.
Bit2 effective when parameter 37-00 Application
Mode is set to [2] Position Control. 5-11 Terminal 19 Digital Input
[165] Core The core diameter source. off means core 1 is Option: Function:
diameter selected, and on means that core 2 is
[10] * Reversing Functions are described in parameter group 5-1*
4 4
source selected. This option is only effective when
Digital Inputs.
parameter 37-00 Application Mode is set to [1]
Center winder. 5-12 Terminal 27 Digital Input
[166] New Configures whether to select partial roll Option: Function:
diameter diameter (off) or core diameter (on). This
[2] * Coast inverse Functions are described in parameter group
select option is only effective when
5-1* Digital Inputs.
parameter 37-00 Application Mode is set to [1]
Center winder. 5-13 Terminal 29 Digital Input
[167] Reset Resets the diameter. This option is only Option: Function:
diameter effective when parameter 37-00 Application
[14] * Jog Functions are described in parameter group
Mode is set to [1] Center winder.
5-1* Digital Inputs.
[168] Winder jog Enables jog forward during center winding.
[32] Pulse input
forward This option is only effective when
parameter 37-00 Application Mode is set to [1] 5-14 Terminal 32 Digital Input
Center winder. Option: Function:
[169] Winder jog Enables jog reverse during center winding.
[0] * No operation Functions are described in parameter
reverse This option is only effective when
group 5-1* Digital Inputs.
parameter 37-00 Application Mode is set to [1]
[82] Encoder input B
Center winder.
[170] Tension on Enables tension PID control. This option is 5-15 Terminal 33 Digital Input
only effective when Option: Function:
parameter 37-00 Application Mode is set to [1]
[0] No operation Functions are described in parameter
Center winder.
group 5-1* Digital Inputs.
[16] * Preset ref bit 0
[32] Pulse input
[81] Enocder input A
4.6.2 5-3* Digital Outputs [16] Below The output speed is lower than the
frequency, low setting in parameter 4-40 Warning Freq.
The 2 solid-state digital outputs are common for terminals Low.
27 and 29. Set the I/O function for terminal 27 in [17] Above The output speed is higher than the
parameter 5-01 Terminal 27 Mode, and set the I/O function frequency, high setting in parameter 4-41 Warning Freq.
for terminal 29 in parameter 5-02 Terminal 29 Mode. High.
[18] Out of The feedback is outside the range set in
Terminals 42 and 45 can also be configured as digital feedback range parameter 4-56 Warning Feedback Low and
4 4
outputs. parameter 4-57 Warning Feedback High.
[19] Below The feedback is below the limit set in
feedback low parameter 4-56 Warning Feedback Low.
NOTICE [20] Above The feedback is above the limit set in
These parameters cannot be adjusted while the motor is
feedback high parameter 4-57 Warning Feedback High.
running.
[21] Thermal The thermal warning turns on when the
warning temperature exceeds the limit in the
5-30 to 5-31 Digital Outputs motor, the frequency converter, the brake
[0] No operation Default for all digital outputs and relay resistor, or the thermistor.
outputs. [22] Ready, no The frequency converter is ready for
[1] Control ready The control card is ready. thermal operation, and there is no overtem-
[2] Drive ready The frequency converter is ready for warning perature warning.
operation and applies a supply signal on [23] Remote, ready, The frequency converter is ready for
the control board. no thermal operation and is in auto-on mode. There
[3] Drive ready / The frequency converter is ready for warning is no overtemperature warning.
remote control operation and is in auto-on mode. [24] Ready, no The frequency converter is ready for
[4] Enable / no Ready for operation. No start or stop overvoltage/ operation and the mains voltage is within
warning command is given (start/disable). No undervoltage the specified voltage range (see General
warnings are active. Specifications section in the design guide).
[5] Running The motor is running and shaft torque is [25] Reverse The motor runs (or is ready to run)
present. clockwise when logic=0 and counter-
[6] Running / no The motor is running and there are no clockwise when logic=1. The output
warning warnings. changes as soon as the reversing signal is
[7] Run in range / The motor is running within the applied.
no warning programmed current and speed ranges [26] Bus OK Active communication (no timeout) via
set in parameter 4-50 Warning Current Low the serial communication port.
to parameter 4-51 Warning Current High. [27] Torque limit Use in performing a coast stop and in
There are no warnings. and stop torque limit condition. If the frequency
[8] Run on The motor runs at reference speed. No converter has received a stop signal and
reference / no warnings. is at the torque limit, the signal is logic 0.
warning [28] Brake, no brake The brake is active and there are no
[9] Alarm An alarm activates the output. warning warnings.
[10] Alarm or An alarm or a warning activates the [29] Brake ready, no The brake is ready for operation and
warning output. fault there are no faults.
[11] At torque limit The torque limit set in [30] Brake fault The output is logic 1 when the brake
parameter 4-16 Torque Limit Motor Mode (IGBT) IGBT is short-circuited. Use this function
or parameter 4-17 Torque Limit Generator to protect the frequency converter if
Mode has been exceeded. there is a fault on the brake modules. Use
[12] Out of current The motor current is outside the range the output/relay to cut out the mains
range set in parameter 4-18 Current Limit. voltage from the frequency converter.
[13] Below current, The motor current is lower than set in [31] Relay 123 The relay is activated when [0] Control
low parameter 4-50 Warning Current Low. Word is selected in parameter group 8-**
[14] Above current, The motor current is higher than set in Communications and Options.
high parameter 4-51 Warning Current High. [32] Mechanical Enables control of an external mechanical
[15] Out of Output frequency is outside the brake control brake. See parameter group 2-2*
frequency frequency range. Mechanical Brake for more details.
range [36] Control word
bit 11
[37] Control word [74] Logic Rule 4 See parameter group 13-4* Logic Rules. If
bit 12 logic rule 4 is evaluated as TRUE, the
[40] Out of ref This option is active when the actual output goes high. Otherwise, it is low.
range speed is outside the settings in [75] Logic Rule 5 See parameter group 13-4* Logic Rules. If
parameter 4-54 Warning Reference Low to logic rule 5 is evaluated as TRUE, the
parameter 4-55 Warning Reference High. output goes high. Otherwise, it is low.
[41] Below This option is active when the actual [80] SL Digital See parameter 13-52 SL Controller Action.
reference low speed is below the speed reference Output A The output goes high whenever the
4 4
setting. smart logic action [38] Set dig. out. A high
[42] Above This option is active when the actual is executed. The output goes low
reference high speed is above the speed reference whenever the smart logic action [32] Set
setting. dig. out. A low is executed.
[45] Bus Ctrl Controls output via fieldbus. The state of [81] SL Digital See parameter 13-52 SL Controller Action.
the output is set in parameter 5-90 Digital Output B The input goes high whenever the smart
& Relay Bus Control. The output state is logic action [39] Set dig. out. B high is
retained in the event of fieldbus timeout. executed. The input goes low whenever
[46] Bus Ctrl On at Controls output via fieldbus. The state of the smart logic action [33] Set dig. out. B
timeout the output is set in parameter 5-90 Digital low is executed.
& Relay Bus Control. When bus timeout [82] SL Digital See parameter 13-52 SL Controller Action.
occurs, the output state is set high (On). Output C The input goes high whenever the smart
[47] Bus Ctrl Off at logic action [40] Set dig. out. C high is
timeout executed. The input goes low whenever
[55] Pulse output the smart logic action [34] Set dig. out. C
[56] Heat sink low is executed.
cleaning [83] SL Digital See parameter 13-52 SL Controller Action.
warning, high Output D The input goes high whenever the smart
[60] Comparator 0 See parameter group 13-1* Comparators. If logic action [41] Set dig. out. D high is
comparator 0 is evaluated as TRUE, the executed. The input goes low whenever
output goes high. Otherwise, it is low. the smart logic action [35] Set dig. out. D
[61] Comparator 1 See parameter group 13-1* Comparators. If low is executed.
comparator 1 is evaluated as TRUE, the [160] No alarm The output is high when no alarm is
output goes high. Otherwise, it is low. present.
[62] Comparator 2 See parameter group 13-1* Comparators. If [161] Running The output is high when the frequency
comparator 2 is evaluated as TRUE, the reverse converter is running counterclockwise
output goes high. Otherwise, it is low. (the logical product of the status bits
[63] Comparator 3 See parameter group 13-1* Comparators. If Running AND Reverse).
comparator 3 is evaluated as TRUE, the [165] Local reference
output goes high. Otherwise, it is low. active
[64] Comparator 4 See parameter group 13-1* Comparators. If [166] Remote ref
comparator 4 is evaluated as TRUE, the active
output goes high. Otherwise, it is low. [167] Start command The output is high when there is an
[65] Comparator 5 See parameter group 13-1* Comparators. If active active start command, and no stop
comparator 5 is evaluated as TRUE, the command is active.
output goes high. Otherwise, it is low. [168] Drive in hand The output is high when the frequency
[70] Logic Rule 0 See parameter group 13-4* Logic Rules. If mode converter is in hand-on mode.
logic rule 0 is evaluated as TRUE, the [169] Drive in auto The output is high when the frequency
output goes high. Otherwise, it is low. mode converter is in auto-on mode.
[71] Logic Rule 1 See parameter group 13-4* Logic Rules. If [170] Homing The homing operation is completed. This
logic rule 1 is evaluated as TRUE, the Completed option is only effective when
output goes high. Otherwise, it is low. parameter 37-00 Application Mode is set to
[72] Logic Rule 2 See parameter group 13-4* Logic Rules. If [2] Position Control.
logic rule 2 is evaluated as TRUE, the [171] Target Position The target position is reached. This option
output goes high. Otherwise, it is low. Reached is only effective when
[73] Logic Rule 3 See parameter group 13-4* Logic Rules. If parameter 37-00 Application Mode is set to
logic rule 3 is evaluated as TRUE, the [2] Position Control.
output goes high. Otherwise, it is low. [172] Position A fault occurred in the positioning
Control Fault process. Refer to parameter 37-18 Pos. Ctrl
Fault Reason for details about the fault. 4.6.3 5-4* Relays
This option is only effective when
parameter 37-00 Application Mode is set to Parameters for configuring the timing and the output
[2] Position Control. functions for the relays.
[173] Position Mech Selects mechanical control for positioning.
Brake This option is only effective when The parameter is an array parameter representing 2 relays:
parameter 37-00 Application Mode is set to Array [2] (Relay 1 [0], Relay 2 [1]).
[2] Position Control.
5-40 Function Relay
4 4
[174] TLD indicator Indicates whether the tension is out of
limit (on) during center winding. This Option: Function:
option is only effective when [0] No operation Default setting for all digital and relay
parameter 37-00 Application Mode is set to outputs.
[1] Center winder.
[1] Control Ready The control card is ready.
[175] Running on Indicates whether tension PID control is
tension active (on) or inactive (off). This option is [2] Drive ready The frequency converter is ready to
only effective when operate. Mains and control supplies are
parameter 37-00 Application Mode is set to OK.
[1] Center winder. [3] Drive rdy/rem ctrl The frequency converter is ready for
[176] Ready to run The center winder control is ready to run. operation, and is in auto-on mode.
This option is only effective when
[4] Stand-by / no Ready for operation. No start or stop
parameter 37-00 Application Mode is set to
warning commands have been applied. No
[1] Center winder.
warnings are active.
[177] End of roll The diameter limit is reached. This option
is only effective when [5] Running The motor is running and a shaft
parameter 37-00 Application Mode is set to torque is present.
[1] Center winder.
[6] Running / no The motor is running and no warnings
[193] Sleep mode The frequency converter/system has warning are present.
entered sleep mode. See parameter group
22-4* Sleep Mode. [7] Run in range/no The motor is running within the
warn programmed current ranges set in
[194] Broken belt A broken belt condition has been
parameter 4-50 Warning Current Low.
detected. See parameter group 22-4* Sleep
Mode. [8] Run on ref/no The motor runs at reference speed. No
warn warnings.
5-30 Terminal 27 Digital Output
[9] Alarm An alarm activates the output.
Option: Function:
[0] * No operation Functions are described in parameter group [10] Alarm or warning An alarm or warning activates the
5-3* Digital Outputs. output.
Range: Function: [13] Below current, The motor current is lower than set in
0.01 s* [0 - 600 s] low parameter 4-50 Warning Current Low.
130BA172.10
Option: Function:
Selected
parameter 37-00 Application Mode is set Event
to [2] Position Control.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
Illustration 4.15 On Delay, Relay
4 4
Input) to [32] Pulse input. If terminal 29 is used as an input, parameter 5-13 Terminal 29 Digital
then set parameter 5-02 Terminal 29 Mode to [0] Input. Input=applicable value).
130BD377.10
Ref.
130BA089.11
[106] Power
[107] Speed
[109] Max Out Freq
High output
value [113] PID Clamped Output
P 5-60(term27)
P 5-63(term29) 5-65 Pulse Output Max Freq 29
Range: Function:
5000 Hz* [4 - 32000 Set the maximum frequency for terminal
Hz] 29 corresponding to the output variable
set in parameter 5-63 Terminal 29 Pulse
Output Variable.
High freq. Output
P 5-62(term27) (Hz)
P 5-65(term29)
4.6.6 5-7* 24 V Encoder Input
Illustration 4.18 Configuration of Pulse Outputs
+24 V DC
5-70 Term 32/33 Pulses Per Revolution
130BD366.12
GND
Range: Function:
A
B
1024* [1 - 4096 ] Set the encoder pulses per revolution on the
12 18 19 27 29 32 33 20
motor shaft. Read the correct value from the
encoder.
Illustration 4.19 24 V or 10–30 V Encoder Connection This parameter group selects digital and relay outputs via a
fieldbus setting.
CW Range: Function:
A
0* [0 - 0xFFFFFFFF ] This parameter holds the state of the bus-
controlled digital outputs and relays.
B
A logical 1 indicates that the output is
high or active.
A logical 0 indicates that the output is
low or inactive.
130BD378.11
Parameter group for setting up the analog I/O configu-
ration and the digital output. Par 6-xx
High Ref./ 50
Feedb. Value'
40
The frequency converter provides 2 analog inputs:
• Terminal 53. 30
• Terminal 54. 20
4 4 Range: Function:
6-23 Terminal 54 High Current
Size [-4999 - Enter the reference or feedback value
related* 4999 ] that corresponds to the voltage or Range: Function:
current set in parameter 6-11 Terminal 20 mA* [0 - 20 Enter the high current value corresponding
53 High Voltage to mA] to the high reference/feedback value set in
parameter 6-13 Terminal 53 High parameter 6-25 Terminal 54 High Ref./Feedb.
Current. Value.
6-16 Terminal 53 Filter Time Constant 6-24 Terminal 54 Low Ref./Feedb. Value
Range: Function: Range: Function:
0.01 s* [0.01 - 10 Enter the time constant. This constant is a 0* [-4999 - Enter the reference or feedback value that
s] first-order digital low-pass filter time 4999 ] corresponds to the voltage or current set in
constant for suppressing electrical noise in parameter 6-21 Terminal 54 High Voltage/
terminal 53. A high time constant value parameter 6-22 Terminal 54 Low Current.
improves dampening, but also increases the
time delay through the filter. 6-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
6-19 Terminal 53 mode
Size [-4999 - Enter the reference or feedback value
Option: Function: related* 4999 ] that corresponds to the voltage or
Select whether terminal 53 is used for current set in parameter 6-21 Terminal
current or voltage input. 54 High Voltage/
parameter 6-23 Terminal 54 High
[0] Current mode
Current.
[1] * Voltage mode
6-93 Terminal 42 Output Min Scale 7-00 Speed PID Feedback Source
Range: Function: Option: Function:
0 %* [0 - Scale for the minimum output (0 mA or 4 mA) [20] * None
200 %] of the analog signal at terminal 42. Set the
value to be the percentage of the full range of
7-02 Speed PID Proportional Gain
the variable selected in parameter 6-91 Terminal Range: Function:
42 Analog Output. 0.015* [0 - Enter the speed controller proportional gain. The
1] proportional gain amplifies the error (that is the
20
8 [2 - Enter the speed controller integral time, which
ms* 20000 determines the time the internal PID control
ms] takes to correct errors. The greater the error,
the more quickly the gain increases. The
0/4
integral time causes a delay of the signal, and
0% Analog Analog 100% Variable
output Output for therefore a dampening effect, and can be used
Min Scale Max Scale output to eliminate steady-state speed error. Obtain
par. 6-93 par. 6-94 example:
Power quick control through a short integral time,
though if the integral time is too short, the
Illustration 4.22 Output Scale versus Current process becomes unstable. An excessively long
integral time disables the integral action,
leading to major deviations from the required
reference, since the process regulator takes too
6-96 Terminal 42 Output Bus Control
long to regulate errors. This parameter is used
Range: Function: with [1] Speed closed loop control set in
0* [0 - 16384 ] Hold the analog output at terminal 42 if parameter 1-00 Configuration Mode.
controlled by bus. This parameter is N2 format.
7-04 Speed PID Differentiation Time
4.8 Parameters: 7-** Controllers Range: Function:
30 [0 - Enter the speed controller differentiation time.
4.8.1 7-0* Speed PID Ctrl.
ms* 200 ms] The differentiator does not react to constant
error. It provides gain proportional to the rate
7-00 Speed PID Feedback Source of change of the speed feedback. The quicker
Option: Function: the error changes, the stronger the gain from
NOTICE the differentiator. The gain is proportional with
the speed at which errors change. Setting this
This parameter cannot be
parameter to 0 disables the differentiator. This
changed while the motor is
parameter is used with parameter 1-00 Configu-
running.
ration Mode [1] Speed closed loop control.
7-06 Speed PID Lowpass Filter Time 7-06 Speed PID Lowpass Filter Time
Range: Function: Range: Function:
10 [1 - NOTICE Feedback
175ZA293.11
ms* 6000
Severe filtering can be detrimental to
Disturbed feedback signal
ms]
dynamic performance.
130BA871.10
1024 5 ms
n1 n2
2048 2 ms
4096 1 ms Motor
Range: Function:
100 %* [0 - 500 %] Enter the proportional gain value for the 4.8.4 7-3* Process PID Ctrl.
torque controller. Selection of a high value
7-30 Process PID Normal/ Inverse Control
4 4
makes the controller react faster. Too high
a setting leads to controller instability. Option: Function:
Normal and inverse controls are implemented by
7-13 Torque PID Integration Time
introducing a difference between the reference
Range: Function: signal and the feedback signal.
0.020 s* [0.002 - 2 s] Enter the integration time for the torque
[0] * Normal Set process control to increase the output
controller. The lower the integration time,
frequency.
the faster the controller reacts. However,
too low a setting leads to controller [1] Inverse Set process control to decrease the output
instability. frequency.
7-35 Process PID Differentiation Time 4.8.5 7-4* Advanced Process PID Ctrl.
Range: Function:
0 s* [0 - 20 s] Enter the PID differentiation time. The differen-
This parameter group is only used if parameter 1-00 Config-
tiator does not react to a constant error, but
uration Mode is set to [7] Extended PID speed CL.
provides a gain only when the error changes. 7-40 Process PID I-part Reset
The shorter the PID differentiation time, the
Option: Function:
stronger the gain from the differentiator.
[0] * No
4 4
[1] Yes Select [1] Yes to reset the I-part of the process PID
7-36 Process PID Diff. Gain Limit
controller. The selection automatically returns to [0]
Range: Function:
No. Resetting the I-part makes it possible to start from
5* [1 - 50] Enter a limit for the differentiator gain. If there is a well-defined point after changing something in the
no limit, the differentiator gain increases when process, for example changing a textile roll.
there are fast changes. To obtain a pure differen-
tiator gain at slow changes and a constant 7-41 Process PID Output Neg. Clamp
differentiator gain where fast changes occur, limit
Range: Function:
the differentiator gain.
-100 %* [ -100 - 100 %] Enter a negative limit for the process
PID controller output.
7-38 Process PID Feed Forward Factor
Range: Function:
7-42 Process PID Output Pos. Clamp
0 %* [0 - Enter the PID feed forward (FF) factor. The FF
Range: Function:
200 %] factor sends a constant fraction of the reference
100 %* [ -100 - 100 %] Enter a positive limit for the process
signal to bypass the PID control, so the PID
PID controller output.
control only affects the remaining fraction of the
control signal. Any change to this parameter
7-43 Process PID Gain Scale at Min. Ref.
affects the motor speed. When the FF factor is
activated, it provides less overshoot, and high Range: Function:
dynamics when changing the setpoint. 100 %* [0 - Enter a scaling percentage to apply to the
Parameter 7-38 Process PID Feed Forward Factor is 100 %] process PID output when operating at the
active when parameter 1-00 Configuration Mode minimum reference. The scaling percentage is
is set to [3] Process. adjusted linearly between the scale at
minimum reference (parameter 7-43 Process PID
7-39 On Reference Bandwidth Gain Scale at Min. Ref.) and the scale at
Range: Function: maximum reference (parameter 7-44 Process
PID Gain Scale at Max. Ref.).
5 %* [0 - Enter the on-reference bandwidth. When the
200 %] PID control error (the difference between the
7-44 Process PID Gain Scale at Max. Ref.
reference and the feedback) is less than the
value of this parameter, the on-reference Range: Function:
status bit is 1. 100 %* [0 - Enter a scaling percentage to apply to the
100 %] process PID output when operating at the
maximum reference. The scaling percentage is
adjusted linearly between the scale at
minimum reference (parameter 7-43 Process PID
Gain Scale at Min. Ref.) and the scale at
maximum reference (parameter 7-44 Process
PID Gain Scale at Max. Ref.).
7-45 Process PID Feed Fwd Resource 7-51 Process PID Feed Fwd Gain
Option: Function: Range: Function:
Select which frequency converter input 1* [0 - The feed forward is used to obtain the gain, based
is used as the feed forward factor. The 100 ] on a well-known signal available. The PID controller
FF factor is added directly to the then only takes care of the smaller part of the
output of the PID controller. This control, necessary because of unknown characters.
parameter can increase dynamic The standard feed-forward factor in
performance. parameter 7-38 Process PID Feed Forward Factor is
7-46 Process PID Feed Fwd Normal/ Inv. Ctrl. 7-53 Process PID Feed Fwd Ramp down
Option: Function: Range: Function:
[0] * Normal Select [0] Normal to set the feed-forward factor to 0.01 s* [0.01 - 100 s] Control the dynamics of the feed-forward
treat the FF resource as a positive value. signal when ramping down.
[17] [1618] Motor Thermal [0] Digital Activate coasting command via a digital input.
[18] [1630] DC Link Voltage input
[19] [1634] Heatsink Temp. [1] Bus Activate coasting command via the serial
[20] [1635] Inverter Thermal communication port or fieldbus option.
[21] [1638] SL Controller State [2] Logic AND Activate coasting command via the fieldbus/
[22] [1650] External Reference serial communication port and 1 extra digital
[23] [1652] Feedback [Unit] input.
[24] [1660] Digital Input
[3] * Logic OR Activate coasting command via the fieldbus/
18,19,27,33
serial communication port or via 1 of the
[25] [1661] Terminal 53 Switch
digital inputs.
Setting
[26] [1662] Analog input 53 8-51 Quick Stop Select
[27] [1663] Terminal 54 Switch
Option: Function:
Setting
[0] Digital Activate quick stop command via a digital
[28] [1664] Analog input 54
input input.
[29] [1665] Analog output 42
[mA] [1] Bus Activate quick stop command via the serial
[30] [1671] Relay output communication port or fieldbus option.
[31] [1672] Counter A [2] Logic AND Activate quick stop command via the fieldbus/
[32] [1673] Counter B serial communication port and additionally via
[33] [1690] Alarm Word 1 of the digital inputs.
[34] [1692] Warning Word
[3] * Logic OR Activate quick stop command via the fieldbus/
[35] [1694] Ext. Status Word
serial communication port or via 1 of the
[38] [1622] Torque [%] digital inputs.
[41] [1657] Feedback [RPM]
When parameter 1-10 Motor Construction is [3] * Logic OR The fieldbus/serial communication port or a
set to [1] PM non-salient SPM, only digital input triggers the set-up selection.
4 4
selection [0] Digital input is available.
8-56 Preset Reference Select
[0] Digital Activate DC brake command via a digital input. Option: Function:
input Select the trigger for the preset reference
[1] Bus Activate DC brake command via the serial selection.
communication port or fieldbus option.
[0] Digital A digital input triggers the preset reference
[2] Logic Activate DC brake command via the fieldbus/ input selection.
AND serial communication port and additionally via 1
[1] Bus A serial communication port or the fieldbus
of the digital inputs.
triggers the preset reference selection.
[3] * Logic OR Activate DC brake command via the fieldbus/
[2] Logic AND The fieldbus/serial communication port and a
serial communication port or via 1 of the digital
digital input trigger the preset reference
inputs.
selection.
[0] Digital A digital input triggers the reversing function. 8-58 Profidrive OFF3 Select
input Select control of the frequency converter OFF3 selection via the
[1] Bus A serial communication port or the fieldbus terminals (digital input) and/or via the fieldbus. This parameter is
triggers the reversing function. active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word, and parameter 8-10 Control Word Profile is set to [1]
[2] Logic AND The fieldbus/serial communication port and a
Profidrive profile.
digital input trigger the reversing function.
Option: Function:
[3] * Logic OR The fieldbus/serial communication port or a
[0] Digital input
digital input triggers the reversing function.
[1] Bus
[2] Logic AND
8-55 Set-up Select
[3] * Logic OR
Select the trigger for the set-up selection.
Option: Function:
[0] Digital input A digital input triggers the set-up selection.
8-79 Protocol Firmware version Use the parameter group to configure the bus feedback.
Range: Function: 8-90 Bus Jog 1 Speed
Size related* [0 - 65535 ] Firmware revision: FC is in index 0; Range: Function:
Modbus is in index 1; indexes 2–4
100 RPM* [ 0 - 1500 Enter the jog speed. This is a fixed
are reserved.
RPM] jog speed activated via the serial
4 4
port or fieldbus option.
4.9.7 8-8* FC Port Diagnostics
8-91 Bus Jog 2 Speed
These parameters are used for monitoring the bus Range: Function:
communication via the frequency converter port. 200 RPM* [ 0 - 1500 Enter the jog speed. This value is a
RPM] fixed jog speed activated via the
8-80 Bus Message Count
serial port or fieldbus option.
Range: Function:
0* [0 - 4294967295 ] This parameter shows the number of
valid telegrams detected on the bus.
9-00 Setpoint
[696]
[733]
Terminal 42 Output Bus Control
Process PID Proportional Gain
Range: Function: [734] Process PID Integral Time
0* [0 - This parameter receives cyclic reference from a [735] Process PID Differentiation Time
65535 ] master class 2. If the control priority is set to [748] PCD Feed Forward
master class 2, the reference for the frequency [890] Bus Jog 1 Speed
converter is taken from this parameter, whereas [891] Bus Jog 2 Speed
the cyclic reference is ignored. [1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
9-07 Actual Value [3401] PCD 1 Write For Application
Range: Function: [3402] PCD 2 Write For Application
0* [0 - 65535 ] This parameter delivers the MAV for a master [3403] PCD 3 Write For Application
class 2. The parameter is valid if the control [3404] PCD 4 Write For Application
priority is set to master class 2. [3405] PCD 5 Write For Application
[3406] PCD 6 Write For Application
9-15 PCD Write Configuration [3407] PCD 7 Write For Application
Select the parameters to be assigned to PCD 3–10 of the [3408] PCD 8 Write For Application
telegrams. The number of available PCDs depends on the [3409] PCD 9 Write For Application
telegram type. Values in PCD 3–10 are written to the selected [3410] PCD 10 Write For Application
parameters as data. For standard PROFIBUS telegrams, see
parameter 9-22 Telegram Selection. 9-16 PCD Read Configuration
Option: Function: Select the parameters to be assigned to PCD 3–10 of the
telegrams. The number of available PCDs depends on the
[0] None
telegram type. Values in PCD 3–10 contain the actual data values
[302] Minimum Reference
of the selected parameters.
[303] Maximum Reference
[311] Jog Speed [Hz] Option: Function:
[312] Catch up/slow Down Value [0] None
[341] Ramp 1 Ramp Up Time [1500] Operating hours
[342] Ramp 1 Ramp Down Time [1501] Running Hours
[351] Ramp 2 Ramp Up Time [1502] kWh Counter
[352] Ramp 2 Ramp Down Time [1600] Control Word
[380] Jog Ramp Time [1601] Reference [Unit]
[381] Quick Stop Ramp Time [1602] Reference [%]
[412] Motor Speed Low Limit [Hz] [1603] Status Word
[414] Motor Speed High Limit [Hz] [1605] Main Actual Value [%]
[416] Torque Limit Motor Mode [1609] Custom Readout
[417] Torque Limit Generator Mode [1610] Power [kW]
[553] Term. 29 High Ref./Feedb. Value [1611] Power [hp]
[558] Term. 33 High Ref./Feedb. Value [1612] Motor Voltage
[590] Digital & Relay Bus Control [1613] Frequency
[593] Pulse Out 27 Bus Control [1614] Motor current
[595] Pulse Out 29 Bus Control [1615] Frequency [%]
[615] Terminal 53 High Ref./Feedb. [1616] Torque [Nm]
Value [1617] Speed [RPM]
[625] Terminal 54 High Ref./Feedb. [1618] Motor Thermal
Value [1622] Torque [%]
4 4
subindexes is defined and shown in Table 4.9.
individual master (cyclic, acyclic MCL1, 1st
Index Content Value acyclic MCL2, 2nd acyclic MCL2, 3rd acyclic
0 Manufacturer 128 MCL2).
1 Device type 1 [1] Set-up 1
2 Version xxyy [2] Set-up 2
3 Firmware date year yyyy [9] * Active Set-
4 Firmware date ddmm up
month
5 No. of axes Variable 9-71 Profibus Save Data Values
6 Vendor specific: PB xxyy Option: Function:
Version Parameter values changed via RS485 are not
7 Vendor specific: xxyy automatically stored in a non-volatile memory.
Database Version Use this parameter to activate a function that
8 Vendor specific: xxyy stores parameter values in the EEPROM non-
AOC Version volatile memory, so changed parameter values
9 Vendor specific: xxyy are retained at power-down.
MOC Version [0] * Off Deactivates the non-volatile storage function.
Table 4.9 Device Identification 1st Subindex [1] Store all Stores all parameter values in the set-up selected
Assignment setups in parameter 9-70 Edit Set-up in the non-volatile
memory. The selection returns to [0] Off when all
values are stored.
9-65 Profile Number
Range: Function: 9-72 ProfibusDriveReset
0* [0 - 0 ] NOTICE Option: Function:
This parameter is not visible via LCP. NOTICE
Resets the VLT® PROFIBUS DP MCA
This parameter contains the profile identification. 101 option only.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
[0] * No action
[1] Power-on reset Resets the frequency converter after
9-67 Control Word 1
power-up, as for power cycle.
Range: Function:
[2] Power-on reset
0* [0 - 65535 ] This parameter accepts the control word from a
prep
master class 2 in the same format as PCD 1.
[3] Comm option When reset, the frequency converter
reset disappears from the fieldbus, which may
9-68 Status Word 1
cause a communication error from the
Range: Function: master.
0* [0 - 65535 ] This parameter delivers the status word for a
master class 2 in the same format as PCD 2. 9-75 DO Identification
Range: Function:
0* [0 - 65535 ] Provides information about the DO (drive
object). This parameter is for PROFINET only.
4 4
[0] Disabled Disables the auto-crossover function.
4.11.3 12-8* Other Ethernet Services [1] * Enabled Enables the auto-crossover function.
Example:
12-90 Cable Diagnostic
OFF means that the filter is disabled - all broadcast
Option: Function: messages are passed through. The value 0% means
Enables/disables advanced cable diagnosis that no broadcast messages are passed through. A
function. If enabled, the distance to cable errors value of 10% means that 10% of the total
can be read out in parameter 12-93 Cable Error bandwidth is allowed for broadcast messages. If
Length. The parameter resumes to the default the amount of broadcast messages exceeds the
setting [0] Disable after the diagnostics have 10% threshold, they are blocked.
finished.
The cable diagnostics function is only Applies to parameter 12-94 Broadcast Storm Protection, if the
issued on ports where there is no link (see broadcast storm protection also includes multicast telegrams.
parameter 12-10 Link Status). Option: Function:
[0] * Broadcast only
[0] * Disabled [1] Broadcast & Multicast
[1] Enabled
130BA062.14
event P13-01
actions (see parameter 13-52 SL Controller Action) executed
by the SLC when the associated user-defined event (see State 1
13-51.0
parameter 13-51 SL Controller Event) is evaluated as true by 13-52.0 State 2
Stop 13-51.1
the SLC. event P13-02 13-52.1
130BB671.13
Stop
SL Controller Event SL Controller Action event P13-02
Illustration 4.26 Events and Actions
Running Coast
Warning Start timer
Torque limit Set Do X low
Digital input X 30/2 Select set-up 2 Starting and stopping the SLC
... ... Start and stop the SLC by selecting [1] On or [0] Off in
parameter 13-00 SL Controller Mode. The SLC always starts
Par. 13-43
Logic Rule Operator 2 in state 0 (where it evaluates event [0]). The SLC starts
when the Start Event (defined in parameter 13-01 Start
Event) is evaluated as true (provided that [1] On is selected
in parameter 13-00 SL Controller Mode). The SLC stops when
...
the stop event (parameter 13-02 Stop Event) is true.
...
Parameter 13-03 Reset SLC resets all SLC parameters and
Par. 13-11 starts programming from scratch.
Comparator Operator
NOTICE
= SLC is only active in auto-on mode, not hand-on mode.
TRUE longer than..
...
...
[0] Less Than (<) The result of the evaluation is true when the
Par. 13-11
130BB672.10
Comparator Operator variable selected in
Par. 13-10 parameter 13-10 Comparator Operand is
Comparator Operand
=
smaller than the fixed value in 4 4
parameter 13-12 Comparator Value. The result
Par. 13-12 TRUE longer than.
Comparator Value ... is false if the variable selected in
... parameter 13-10 Comparator Operand is
greater than the fixed value in
Illustration 4.27 Comparators parameter 13-12 Comparator Value.
130BB673.10
Logic Rule Operator 1 Logic Rule Operator 2 [35] Digital input DI27
Par. 13-40
Logic Rule Boolean 1 [36] Digital input DI29
Par. 13-42 [39] Start command
Logic Rule Boolean 2 ...
... ...
[40] Drive stopped
... [42] Auto Reset Trip
Par. 13-44 [50] Comparator 4
Logic Rule Boolean 3 [51] Comparator 5
Illustration 4.28 Logic Rules [60] Logic rule 4
[61] Logic rule 5
[70] SL Time-out 3
Priority of calculation [71] SL Time-out 4
The results of parameter 13-40 Logic Rule Boolean 1, [72] SL Time-out 5
parameter 13-41 Logic Rule Operator 1, and [73] SL Time-out 6
parameter 13-42 Logic Rule Boolean 2 are calculated first.
[74] SL Time-out 7
The outcome (true/false) of this calculation is combined
[83] Broken Belt
with the settings of parameter 13-43 Logic Rule Operator 2
and parameter 13-44 Logic Rule Boolean 3, yielding the final 13-41 Logic Rule Operator 1
result (true/false) of the logic rule. Option: Function:
13-40 Logic Rule Boolean 1 Select the 1st logical operator to use on the
Option: Function: boolean inputs from parameter 13-40 Logic
Rule Boolean 1 and parameter 13-42 Logic Rule
Select the 1st boolean (true or false)
Boolean 2.
input for the selected logic rule. See
parameter 13-01 Start Event ([0]–[61]) [0] * Disabled Ignore parameter 13-42 Logic Rule Boolean 2,
and parameter 13-02 Stop Event ([70]– parameter 13-43 Logic Rule Operator 2, and
[74]) for further description. parameter 13-44 Logic Rule Boolean 3.
[0] * False [1] AND Evaluate the expression [13-40] AND [13-42].
[1] True [2] OR Evaluate the expression [13-40] OR [13-42].
[2] Running
[3] AND NOT Evaluate the expression [13-40] AND NOT
[3] In range
[13-42].
[4] On reference
[7] Out of current range [4] OR NOT Evaluate the expression [13-40] OR NOT
[8] Below I low [13-42].
[9] Above I high [5] NOT AND Evaluate the expression NOT [13-40] AND
[16] Thermal warning [13-42].
[17] Mains out of range
[6] NOT OR Evaluate the expression NOT [13-40] OR
[18] Reversing
[13-42].
[19] Warning
[7] NOT AND Evaluate the expression NOT [13-40] AND
[20] Alarm (trip)
NOT NOT [13-42].
[21] Alarm (trip lock)
[22] Comparator 0 [8] NOT OR Evaluate the expression NOT [13-40] OR NOT
[23] Comparator 1 NOT [13-42].
[24] Comparator 2
[15] Select preset Selects preset reference 5. If the active [39] Set digital Any output with SL output B is high.
ref 5 preset reference is changed, it merges with out B high
other preset reference commands coming [40] Set digital Any output with SL output C is high.
from either the digital inputs, or via a out C high
fieldbus. [41] Set digital Any output with SL output D is high.
out D high
[16] Select preset Selects preset reference 6. If the active
[60] Reset Resets Counter A to zero.
ref 6 preset reference is changed, it merges with
Counter A
other preset reference commands coming
[61] Reset Resets Counter B to zero.
from either the digital inputs, or via a
Counter B
fieldbus.
[70] Start Timer 3 See parameter 13-20 SL Controller Timer for
[17] Select preset Selects preset reference 7. If the active further description.
ref 7 preset reference is changed, it merges with
[71] Start Timer 4 See parameter 13-20 SL Controller Timer for
other preset reference commands coming
further description.
from either the digital inputs, or via a
fieldbus. [72] Start Timer 5 See parameter 13-20 SL Controller Timer for
further description.
[18] Select ramp 1 Selects ramp 1.
[73] Start Timer 6 See parameter 13-20 SL Controller Timer for
[19] Select ramp 2 Selects ramp 2.
further description.
[22] Run Issues a start command to the frequency
[74] Start Timer 7 See parameter 13-20 SL Controller Timer for
converter.
further description.
[23] Run reverse Issues a start reverse command to the
frequency converter.
[1] Ran5 5 kHz true random PWM (white noise 4.13.2 14-1* Mains On/Off
modulation).
[2] 2.0 kHz Parameters for configuring mains failure monitoring and
[3] 3.0 kHz handling. If a mains failure appears, the frequency
[4] 4.0 kHz converter tries to continue in a controlled way until the
[5] 5.0 kHz power in the DC link is exhausted.
[6] 6.0 kHz 14-10 Mains Failure
[7] 8.0 kHz Option: Function:
[8] 10.0 kHz
[9] 12.0 kHz
NOTICE
Parameter 14-10 Mains Failure cannot be
[10] 16.0 kHz
changed while the motor is running.
14-03 Overmodulation
Option: Function: Parameter 14-10 Mains Failure is typically used
[0] Off To avoid torque ripple on the motor shaft, select [0] where short mains interruptions (voltage dips) are
Off for no overmodulation of the output voltage. This present. At 100% load and a short voltage
feature may be useful for applications such as grinding interruption, the DC voltage on the main
machines. capacitors drops quickly. For larger frequency
converters, it only takes a few milliseconds before
[1] * On Select [1] On to enable the overmodulation function
the DC level is down to about 373 V DC and the
for the output voltage. Select this setting when it is
IGBTs cut off and lose control of the motor. When
required that the output voltage is >95% of the input
mains is restored, and the IGBTs start again, the
voltage (typical when running oversynchronously). The
output frequency and voltage vector do not
output voltage is increased according to the degree of
correspond to the speed/frequency of the motor,
overmodulation.
and the result is normally an overvoltage or
NOTICE overcurrent, mostly resulting in a trip lock.
Overmodulation leads to increased torque Parameter 14-10 Mains Failure can be programmed
ripple as harmonics are increased. to avoid this situation.
A B C DE A
UDC [V]
relatively high level on the DC-link during ramp
UDC
down.
14-11*1.35
n [RPM] t [S]
130BC920.10
A B C D
UDC [V]
Ref
790 V
t [S] UDC
14-11*1.35
n [RPM] t [S]
A Normal operation
Ref
B Mains failure
C Kinetic back-up 0
t [S]
D Mains return
E Normal operation: Ramping A Normal operation
B Mains failure
Illustration 4.29 Kinetic Back-up C Kinetic back-up
D Trip
The DC-level during [4] Kinetic back-up is Illustration 4.30 Kinetic Back-up Trip
parameter 14-11 Mains Fault Voltage Level x 1.35.
[14] Reset at power- [0] Trip Disable the protection filters and trips at the first
up fault.
4 4
or regenerative operation, the frequency converter tries to
Range: Function:
reduce torque below the preset torque limits as quickly as
possible without losing control of the motor. 100 [0 - This parameter is available only when
%* 200 %] parameter 1-10 Motor Construction is set to [3]
14-30 Current Lim Ctrl, Proportional Gain PM, salient IPM.
Range: Function:
Normally, VVC+ PM control automatically
100 %* [0 - 500 %] Enter the proportional gain value for the optimizes d-axis demagnetizing current based on
current limit controller. Selection of a high d-axis and q-axis settings. When
value makes the controller react faster. Too parameter 1-10 Motor Construction is set to [3]
high a setting leads to controller PM, salient IPM, use this parameter to
instability. compensate the saturation effect at high load.
Usually, decreasing this value improves the
14-31 Current Lim Ctrl, Integration Time efficiency. However, 0% means no optimization
Range: Function: and the d-axis current is 0 (not recommended).
0.020 s* [0.002 - 2 s] Control the current limit control
integration time. Setting it to a lower
4.13.6 14-5* Environment
value makes it react faster. A setting too
low leads to control instability.
NOTICE
14-32 Current Lim Ctrl, Filter Time Perform a power cycle after changing any of the
Range: Function: parameters in parameter group 14-5* Environment.
5 ms* [1 - 100 ms] Set a time constant for the current limit
controller low-pass filter. These parameters help the frequency converter to operate
under special environmental conditions.
Range: Function:
15-98 Drive Identification
0* [0 - 10 ] View the frequency converter serial number.
Range: Function:
15-53 Power Card Serial Number 0* [0 - 56 ] This parameter contains data used by MCT-10 Set-
up Software.
Range: Function:
0* [0 - 19 ] View the power card serial number.
15-99 Parameter Metadata
Range: Function:
4.14.4 15-6* Option Indent. 0* [0 - 9999 ] This parameter contains data used by MCT-10
Set-up Software.
This read-only parameter group contains information about
the hardware and software configuration of the options
installed in slots A, B, C0, and C1.
Range: Function:
16-52 Feedback[Unit]
0 V* [0 - 65535 V] View a measured value. The value is filtered
Range: Function:
with a 128 ms time constant.
0 [-4999 - 4999 View the feedback unit
16-33 Brake Energy Average ProcessCtrlUnit* ProcessCtrlUnit] resulting from the selection
of unit and scaling in
Range: Function:
parameter 3-00 Reference
0 kW* [0 - 10000 View the brake power transmitted to an
Range,
kW] external brake resistor. The mean power is
parameter 3-01 Reference/
calculated on an average level based on
Feedback Unit,
the latest 120 s.
parameter 3-02 Minimum
Reference, and
16-34 Heatsink Temp. parameter 3-03 Maximum
Range: Function: Reference.
0 °C* [-128 - View the frequency converter heat sink
127 °C] temperature. The cutout limit is 90 ±5 °C 16-53 Digi Pot Reference
[194 °F], and the motor cuts back in at 60 Range: Function:
±5 °C [140 °F].
0* [-200 - 200 ] View the contribution of the digital potenti-
ometer to the actual reference.
16-35 Inverter Thermal
Range: Function:
0 %* [0 - 255 %] View the percentage load on the inverter.
4.16 Parameters: 17-** Feedback Options 4.16.3 17-6* Monitoring and App.
4.16.1 17-1* Inc.Enc.Interface 17-60 Feedback Direction
Option: Function:
17-10 Signal Type
[0] * Clockwise
Select the incremental type (A/B channel) of the encoder in use. [1] Counter clockwise
Find the information on the encoder datasheet.
Option: Function: 17-61 Feedback Signal Monitoring
4.19 Parameters: 22-** Application 4. When the error between reference and feedback
Functions is greater than parameter 22-44 Wake-Up Ref./FB
Diff, and the condition lasts more than
22-02 Sleepmode CL Control Mode parameter 22-41 Minimum Sleep Time, the
frequency converter is out of sleep mode.
This parameter is used to set whether feedback is detected for
entering sleep mode in process closed loop. 5. The frequency converter reverts to closed-loop
Option: Function: control.
[0] * Normal Detect feedback together NOTICE
with other parameters. Sleep mode is not active when local reference is active 4 4
[1] Simplified Do not detect feedback. (set speed manually with navigation keys on the LCP).
Only check sleep speed and Does not work in hand-on mode. Auto set-up in open
time. loop must be carried out before setting input/output in
closed loop.
4.20 Parameters: 30-** Special Features 32-67 Max. Tolerated Position Error
Range: Function:
4.20.1 30-2* Adv. Start Adjust
2000000* [1 - This parameter defines the
2147483648 ] maximum error allowed between
30-20 High Starting Torque Time [s] the actual position and the
Range: Function: calculated command position. If
Size related* [0 - 60 s] High starting torque time for PM the actual error exceeds the value
motors in VVC+ mode without set in this parameter, the position-
feedback. control-fault alarm is triggered.
4 4
30-21 High Starting Torque Current [%] 32-80 Maximum Allowed Velocity
Range: Function: Range: Function:
Size related* [ 0 - 200.0 %] High starting torque current for PM 1500 RPM* [1 - 30000 RPM] This parameter defines the
motors in VVC+ mode without maximum velocity in RPM during
feedback. motion control.
30-22 Locked Rotor Protection 32-81 Motion Ctrl Quick Stop Ramp
Option: Function: Range: Function:
[0] * Off 1000 ms* [50 - 3600000 This parameter defines the quick-
[1] On The locked rotor protection for PM motors. ms] stop ramp time from the
maximum allowed velocity to 0
30-23 Locked Rotor Detection Time [s] for motion control.
Range: Function:
4.22 Parameters: 33-** Motion Control Adv.
0.10 s* [0.05 - 1 s] The locked rotor detection time for PM
motors.
Settings
33-00 Homing Mode
4.21 Parameters: 32-** Motion Control Basic
Select the homing mode.
Settings
Option: Function:
32-11 User Unit Denominator [0] * Not forced
Range: Function: [1] Forced manual homing
1* [1 - All target positions are made in user units and [2] Forced automated homing
65535 ] are converted to quad-counts internally. By
33-01 Home Offset
selecting scaling units, it is possible to work
Range: Function:
with any measurement unit (for example mm).
This factor consists of a numerator and 0* [-1073741824 - Use this parameter to set an offset of
denominator. 1073741824 ] 0 (home position) compared to the
position after homing.
32-12 User Unit Numerator
33-02 Home Ramp Time
Range: Function:
Range: Function:
1* [1 - All target positions are made in user units and
65535 ] are converted to quad-counts internally. By 10 ms* [1 - 1000 This parameter defines the ramp time (in
selecting scaling units, it is possible to work ms] ms) from standstill to the value set in
with any measurement unit (for example mm). parameter 32-80 Maximum Allowed Velocity.
This factor consists of a numerator and
denominator. 33-03 Homing Velocity
Range: Function:
100 [-1500 - This parameter defines the velocity of
RPM* 1500 RPM] homing. It must not exceed the
parameter 32-80 Maximum Allowed
Velocity.
Parameters for readout of fieldbus data sent to the fieldbus Readout of process data for motion control.
master.
34-50 Actual Position
34-21 PCD 1 Read For Application Range: Function:
Range: Function: 0* [-1073741824 - The actual position in user
0* [0 - 65535 ] Value sent in PCD1 of fieldbus telegram. 1073741824 ] unit.
4.24 Parameters: 37-** Application Settings 37-06 Pos. Ramp Down Time
Range: Function:
4.24.1 37-0* Application Mode
5000 [50 - It is defined as the time in milliseconds
ms* 100000 ms] that it takes to ramp from
37-00 Application Mode parameter 32-80 Maximum Allowed
Option: Function: Velocity to standstill.
[0] * Drive mode
[1] Center winder 37-07 Pos. Auto Brake Ctrl
4 4 [2]
[3]
Position Control
Synchronization
When the automatic brake control function is disabled, the
frequency converter controls the application also at standstill.
When the automatic brake control function is enabled, the
mechanical brake is automatically activated every time the
4.24.2 37-1* Position Control
application is at standstill for a time period specified in
parameter 37-08 Pos. Hold Delay.
37-01 Pos. Feedback Source
Option: Function:
Select position feedback source.
[0] Disable
Option: Function:
[1] * Enable
[0] * 24V Encoder
[1] MCB102 37-08 Pos. Hold Delay
[2] MCB103 Range: Function:
0 ms* [0 - 10000 To be used with the automatic brake
37-02 Pos. Target
ms] control function. The hold delay is a
Range: Function: waiting period in which the brake is not
0* [-1073741824 If parameter 37-03 Pos. Type is set to [0] activated even though the application is at
- 1073741824 ] Absolute, the target position is an absolute standstill.
position (relative to home position). If the
parameter 37-03 Pos. Type is set to [1] Relative 37-09 Pos. Coast Delay
and the last position was obtained through
Range: Function:
jogging, the target position is relative to that
200 ms* [0 - 1000 To be used with the automatic brake
position. If the last position was reached as a
ms] control function. The coast delay is the
result of a positioning command, then the
delay from activating the mechanical
target position is relative to the last target
brake to disabling the controller and
position regardless of being reached or not.
coasting the frequency converter.
37-36 Tension Set Point Input 37-43 Diameter Calculator Min Speed
Set the source of the tension setpoint. Range: Function:
Option: Function: 0 %* [0 - Set the minimum line speed to be achieved
[0] * Par.3721 100 %] before the diameter calculator is activated. At
[1] Input53(0~10 VDC or 0~20 mA ) low line speeds, the resolution of the line and
winder speed are too low for the diameter to
[2] Input54(0~10 VDC or 0~20 mA )
be accurately calculated.
37-37 Taper Set Point Input
Set the source of the taper setpoint. 37-44 Line Acceleration Feed Forward
Range: Function:
4 4
Option: Function:
[0] * Par.3722 0* [-20 - 20 ] Set the feed forward speed that helps
[1] Input53(0~10 VDC or 0~20 mA ) compensate for tension changes caused by line
speed acceleration and deceleration.
[2] Input54(0~10 VDC or 0~20 mA )
5 Parameter Lists
Par. No. # Parameter description Default value 2-set-up Change Conversion Type
during index
operation
0-0* Basic Settings
0-01 Language [0] English 1 set-up TRUE – Uint8
0-03 Regional Settings [0] International 1 set-up FALSE – Uint8
0-04 Operating State at Power-up [0] Resume All set-ups TRUE – Uint8
5 5 0-06
0-07
GridType
Auto DC Braking
ExpressionLimit
[1] On
1 set-up
1 set-up
FALSE
FALSE
–
–
Uint8
Uint8
0-1* Set-up Operations
0-10 Active Set-up [1] Set-up 1 1 set-up TRUE – Uint8
0-11 Programming Set-up [9] Active Set-up 1 set-up TRUE – Uint8
0-12 Link Setups [20] Linked All set-ups FALSE – Uint8
0-14 Readout: Edit Set-ups/Channel 0 N/A All set-ups TRUE 0 Int32
0-16 Application Selection [0] None All set-ups FALSE – Uint8
0-2* LCP Display
0-20 Display Line 1.1 Small 1602 All set-ups TRUE – Uint16
0-21 Display Line 1.2 Small 1614 All set-ups TRUE – Uint16
0-22 Display Line 1.3 Small 1610 All set-ups TRUE – Uint16
0-23 Display Line 2 Large 1613 All set-ups TRUE – Uint16
0-24 Display Line 3 Large 1502 All set-ups TRUE – Uint16
0-3* LCP Custom Readout
0-30 Custom Readout Unit [1] % 1 set-up TRUE – Uint8
0-31 Custom Readout Min Value 0 CustomReadoutUnit 1 set-up TRUE -2 Int32
0-32 Custom Readout Max Value 100 CustomReadoutUnit 1 set-up TRUE -2 Int32
0-37 Display Text 1 [] 1 set-up TRUE 0 VisStr[21]
0-38 Display Text 2 [] 1 set-up TRUE 0 VisStr[26]
0-39 Display Text 3 [] 1 set-up TRUE 0 VisStr[26]
0-4* LCP Keypad
0-40 [Hand on] Key on LCP [1] Enabled All set-ups TRUE – Uint8
0-42 [Auto on] Key on LCP [1] Enabled All set-ups TRUE – Uint8
0-44 [Off/Reset] Key on LCP [1] Enabled All set-ups TRUE – Uint8
0-5* Copy/Save
0-50 LCP Copy [0] No copy 1 set-up FALSE – Uint8
0-51 Set-up Copy [0] No copy 1 set-up FALSE – Uint8
0-6* Password
0-60 Main Menu Password 0 N/A 1 set-up TRUE 0 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
1-0* General Settings
1-00 Configuration Mode [0] Open Loop All set-ups TRUE – Uint8
1-01 Motor Control Principle [1] VVC+ All set-ups FALSE – Uint8
1-03 Torque Characteristics [0] Constant torque All set-ups FALSE – Uint8
1-06 Clockwise Direction [0] Normal 1 set-up FALSE – Uint8
1-08 Motor Control Bandwidth ExpressionLimit All set-ups FALSE – Uint8
1-1* Motor Selection
1-10 Motor Construction [0] Asynchron All set-ups FALSE – Uint8
5 5
1-14 Damping Gain 120% All set-ups TRUE 0 Int16
1-15 Low Speed Filter Time Const. ExpressionLimit All set-ups TRUE -2 Uint16
1-16 High Speed Filter Time Const. ExpressionLimit All set-ups TRUE -2 Uint16
1-17 Voltage filter time const. ExpressionLimit All set-ups TRUE -3 Uint16
1-2* Motor Data
1-20 Motor Power ExpressionLimit All set-ups FALSE – Uint8
1-22 Motor Voltage ExpressionLimit All set-ups FALSE 0 Uint16
1-23 Motor Frequency ExpressionLimit All set-ups FALSE 0 Uint16
1-24 Motor Current ExpressionLimit All set-ups FALSE -2 Uint32
1-25 Motor Nominal Speed ExpressionLimit All set-ups FALSE 67 Uint16
1-26 Motor Cont. Rated Torque ExpressionLimit All set-ups FALSE -1 Uint32
1-29 Automatic Motor Adaption (AMA) [0] Off All set-ups FALSE – Uint8
1-3* Adv. Motor Data I
1-30 Stator Resistance (Rs) ExpressionLimit All set-ups FALSE -3 Uint32
1-31 Rotor Resistance (Rr) ExpressionLimit All set-ups FALSE -3 Uint32
1-33 Stator Leakage Reactance (X1) ExpressionLimit All set-ups FALSE -3 Uint32
1-35 Main Reactance (Xh) ExpressionLimit All set-ups FALSE -2 Uint32
1-37 d-axis Inductance (Ld) ExpressionLimit All set-ups FALSE -3 Int32
1-38 q-axis Inductance (Lq) ExpressionLimit All set-ups FALSE -6 Int32
1-39 Motor Poles ExpressionLimit All set-ups FALSE 0 Uint8
1-4* Adv. Motor Data II
1-40 Back EMF at 1000 RPM ExpressionLimit All set-ups FALSE 0 Uint16
1-42 Motor Cable Length 50 m All set-ups FALSE 0 Uint8
1-43 Motor Cable Length Feet 164 ft All set-ups FALSE 0 Uint16
1-44 d-axis Inductance Sat. (LdSat) ExpressionLimit All set-ups FALSE -3 Int32
1-45 q-axis Inductance Sat. (LqSat) ExpressionLimit All set-ups FALSE -3 Int32
1-46 Position Detection Gain 100% All set-ups TRUE 0 Uint16
1-48 Current at Min Inductance for d-axis 100% All set-ups TRUE 0 Uint16
1-49 Current at Min Inductance for q-axis 100% All set-ups TRUE 0 Uint16
1-5* Load Indep. Setting
1-50 Motor Magnetisation at Zero Speed 100% All set-ups TRUE 0 Uint16
1-52 Min Speed Normal Magnetising [Hz] 1 Hz All set-ups TRUE -1 Uint16
1-55 U/f Characteristic - U ExpressionLimit All set-ups FALSE -1 Uint16
1-56 U/f Characteristic - F ExpressionLimit All set-ups FALSE -1 Uint16
1-6* Load Depen. Setting
1-60 Low Speed Load Compensation 100% All set-ups TRUE 0 Int16
1-61 High Speed Load Compensation 100% All set-ups TRUE 0 Int16
1-62 Slip Compensation ExpressionLimit All set-ups TRUE 0 Int16
1-63 Slip Compensation Time Constant 0.1 s All set-ups TRUE -2 Uint16
1-64 Resonance Dampening 100% All set-ups TRUE 0 Uint16
1-65 Resonance Dampening Time Constant 0.005 s All set-ups TRUE -3 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
1-66 Min. Current at Low Speed 50% All set-ups TRUE 0 Uint32
1-7* Start Adjustments
1-70 PM Start Mode [0] Rotor Detection All set-ups TRUE – Uint8
1-71 Start Delay 0s All set-ups TRUE -1 Uint8
1-72 Start Function [2] Coast/delay time All set-ups TRUE – Uint8
1-73 Flying Start ExpressionLimit All set-ups TRUE – Uint8
1-75 Start Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-76 Start Current ExpressionLimit All set-ups TRUE -2 Uint32
5 5 1-78
1-79
Compressor Start Max Speed [Hz]
Compressor Start Max Time to Trip
0 Hz
5s
All set-ups
All set-ups
TRUE
TRUE
-1
-1
Uint16
Uint8
1-8* Stop Adjustments
1-80 Function at Stop [0] Coast All set-ups TRUE – Uint8
1-82 Min Speed for Function at Stop [Hz] 0 Hz All set-ups TRUE -1 Uint16
1-9* Motor Temperature
1-90 Motor Thermal Protection [0] No protection All set-ups TRUE – Uint8
1-93 Thermistor Source [0] None All set-ups FALSE – Uint8
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
2-0* DC-Brake
2-00 DC Hold/Motor Preheat Current 50% All set-ups TRUE 0 Uint16
2-01 DC Brake Current 50% All set-ups TRUE 0 Uint16
2-02 DC Braking Time 10 s All set-ups TRUE -1 Uint16
2-04 DC Brake Cut In Speed 0 Hz All set-ups TRUE -1 Uint16
2-06 Parking Current 100% All set-ups TRUE 0 Uint16
2-07 Parking Time 3s All set-ups TRUE -1 Uint16
2-1* Brake Energy Funct.
2-10 Brake Function [0] Off All set-ups FALSE – Uint8
2-11 Brake Resistor (ohm) ExpressionLimit All set-ups FALSE -1 Uint16
2-12 Brake Power Limit (kW) ExpressionLimit All set-ups TRUE 0 Uint32
2-14 Brake voltage reduce 0V All set-ups FALSE 0 Uint16
2-16 AC Brake, Max current 100% All set-ups TRUE -1 Uint16
2-17 Over-voltage Control [0] Disabled All set-ups TRUE – Uint8
2-19 Over-voltage Gain 100% All set-ups TRUE 0 Uint16
2-2* Mechanical Brake
2-20 Release Brake Current 0A All set-ups TRUE -2 Uint32
2-22 Activate Brake Speed [Hz] 0 Hz All set-ups TRUE -1 Uint16
2-23 Activate Brake Delay 0.0 s All set-ups TRUE -1 Uint8
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
3-0* Reference Limits
3-00 Reference Range [0] Min - Max All set-ups TRUE – Uint8
3-01 Reference/Feedback Unit ExpressionLimit All set-ups TRUE – Uint8
3-02 Minimum Reference 0 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
3-03 Maximum Reference ExpressionLimit All set-ups TRUE -3 Int32
3-04 Reference Function [0] Sum All set-ups TRUE – Uint8
3-1* References
3-10 Preset Reference 0% All set-ups TRUE -2 Int16
5 5
3-11 Jog Speed [Hz] 5 Hz All set-ups TRUE -1 Uint16
3-12 Catch up/slow Down Value 0% All set-ups TRUE -2 Int16
3-14 Preset Relative Reference 0% All set-ups TRUE -2 Int16
3-15 Reference 1 Source [1] Analog Input 53 All set-ups TRUE – Uint8
3-16 Reference 2 Source [2] Analog Input 54 All set-ups TRUE – Uint8
3-17 Reference 3 Source [11] Local bus reference All set-ups TRUE – Uint8
3-18 Relative Scaling Reference Resource [0] No function All set-ups TRUE –- Uint8
3-4* Ramp 1
3-40 Ramp 1 Type [0] Linear All set-ups TRUE – Uint8
3-41 Ramp 1 Ramp Up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-42 Ramp 1 Ramp Down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-5* Ramp 2
3-50 Ramp 2 Type [0] Linear All set-ups TRUE – Uint8
3-51 Ramp 2 Ramp Up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-52 Ramp 2 Ramp Down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-6* Ramp 3
3-60 Ramp 3 Type [0] Linear All set-ups TRUE – Uint8
3-61 Ramp 3 Ramp up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-62 Ramp 3 Ramp down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-7* Ramp 4
3-70 Ramp 4 Type [0] Linear All set-ups TRUE – Uint8
3-71 Ramp 4 Ramp up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-72 Ramp 4 Ramp Down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-8* Other Ramps
3-80 Jog Ramp Time ExpressionLimit All set-ups TRUE -2 Uint32
3-81 Quick Stop Ramp Time ExpressionLimit 1 set-up TRUE -2 Uint32
3-9* Digital Pot.Meter
3-90 Step Size 0.10% All set-ups TRUE -2 Uint16
3-92 Power Restore [0] Off All set-ups TRUE – Uint8
3-93 Maximum Limit 100% All set-ups TRUE 0 Int16
3-94 Minimum Limit -100% All set-ups TRUE 0 Int16
3-95 Ramp Delay 1000 ms All set-ups TRUE -3 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
4-1* Motor Limits
4-10 Motor Speed Direction [2] Both directions All set-ups FALSE – Uint8
4-12 Motor Speed Low Limit [Hz] 0 Hz All set-ups FALSE -1 Uint16
4-14 Motor Speed High Limit [Hz] 65 Hz All set-ups FALSE -1 Uint16
4-16 Torque Limit Motor Mode ExpressionLimit All set-ups TRUE 0 Uint16
4-17 Torque Limit Generator Mode 100% All set-ups TRUE 0 Uint16
5 5 4-18
4-19
Current Limit
Max Output Frequency
ExpressionLimit
ExpressionLimit
All set-ups
All set-ups
TRUE
FALSE
0
-1
Uint16
Uint16
4-2* Limit Factors
4-20 Torque Limit Factor Source [0] No function All set-ups TRUE – Uint8
4-21 Speed Limit Factor Source [0] No function All set-ups TRUE – Uint8
4-22 Break Away Boost [0] Off All set-ups FALSE – Uint8
4-3* Motor Fb Monitor
4-30 Motor Feedback Loss Function [0] Disabled All set-ups TRUE – Uint8
4-31 Motor Feedback Speed Error 20 Hz All set-ups TRUE 0 Uint16
4-32 Motor Feedback Loss Timeout 0.05 s All set-ups TRUE -2 Uint16
4-4* Adj. Warnings 2
4-40 Warning Freq. Low ExpressionLimit All set-ups TRUE -1 Uint16
4-41 Warning Freq. High ExpressionLimit All set-ups TRUE -1 Uint16
4-42 Adjustable Temperature Warning 0 N/A All set-ups TRUE 0 Uint8
4-5* Adj. Warnings
4-50 Warning Current Low 0A All set-ups TRUE -2 Uint32
4-51 Warning Current High ExpressionLimit All set-ups TRUE -2 Uint32
4-54 Warning Reference Low -4999 N/A All set-ups TRUE -3 Int32
4-55 Warning Reference High 4999 N/A All set-ups TRUE -3 Int32
4-56 Warning Feedback Low -4999 ProcessCtrlUnit All set-ups TRUE -3 Int32
4-57 Warning Feedback High 4999 ProcessCtrlUnit All set-ups TRUE -3 Int32
4-58 Missing Motor Phase Function [1] On All set-ups FALSE – Uint8
4-6* Speed Bypass
4-61 Bypass Speed From [Hz] 0 Hz All set-ups TRUE -1 Uint16
4-63 Bypass Speed To [Hz] 0 Hz All set-ups TRUE -1 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
5-0* Digital I/O mode
5-00 Digital I/O Mode [0] PNP 1 set-up FALSE – Uint8
5-01 Terminal 27 Mode [0] Input All set-ups TRUE – Uint8
5-02 Terminal 29 Mode [0] Input All set-ups TRUE – Uint8
5-1* Digital Inputs
5-10 Terminal 18 Digital Input [8] Start All set-ups TRUE – Uint8
5-11
5-12
Terminal 19 Digital Input
Terminal 27 Digital Input
[10] Reversing
ExpressionLimit
All set-ups
All set-ups
TRUE
TRUE
–
–
Uint8
Uint8
5 5
5-13 Terminal 29 Digital Input [14] Jog All set-ups TRUE – Uint8
5-14 Terminal 32 Digital Input [0] No operation All set-ups TRUE – Uint8
5-15 Terminal 33 Digital Input [16] Preset ref bit 0 All set-ups TRUE – Uint8
5-16 Terminal 31 Digital Input [0] No operation All set-ups TRUE – Uint8
5-3* Digital Outputs
5-30 Terminal 27 Digital Output [0] No operation All set-ups TRUE – Uint8
5-31 Terminal 29 Digital Output [0] No operation All set-ups TRUE – Uint8
5-34 On Delay, Digital Output 0.01 s All set-ups TRUE -2 Uint16
5-35 Off Delay, Digital Output 0.01 s All set-ups TRUE -2 Uint16
5-4* Relays
5-40 Function Relay ExpressionLimit All set-ups TRUE – Uint8
5-41 On Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-42 Off Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-5* Pulse Input
5-50 Term. 29 Low Frequency 4 Hz All set-ups TRUE 0 Uint32
5-51 Term. 29 High Frequency 32000 Hz All set-ups TRUE 0 Uint32
5-52 Term. 29 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
5-53 Term. 29 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
5-55 Term. 33 Low Frequency 4 Hz All set-ups TRUE 0 Uint32
5-56 Term. 33 High Frequency 32000 Hz All set-ups TRUE 0 Uint32
5-57 Term. 33 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
5-58 Term. 33 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
5-6* Pulse Output
5-60 Terminal 27 Pulse Output Variable [0] No operation All set-ups TRUE – Uint8
5-62 Pulse Output Max Freq 27 5000 Hz All set-ups TRUE 0 Uint32
5-63 Terminal 29 Pulse Output Variable [0] No operation All set-ups TRUE – Uint8
5-65 Pulse Output Max Freq 29 5000 Hz All set-ups TRUE 0 Uint32
5-7* 24 V Encoder Input
5-70 Term 32/33 Pulses Per Revolution 1024 N/A All set-ups FALSE 0 Uint16
5-71 Term 32/33 Encoder Direction [0] Clockwise All set-ups FALSE – Uint8
5-9* Bus Controlled
5-90 Digital & Relay Bus Control 0 N/A All set-ups TRUE 0 Uint32
5-93 Pulse Out 27 Bus Control 0% All set-ups TRUE -2 Uint16
5-94 Pulse Out 27 Timeout Preset 0% 1 set-up TRUE -2 Uint16
5-95 Pulse Out 29 Bus Control 0% All set-ups TRUE -2 Uint16
5-96 Pulse Out 29 Timeout Preset 0% 1 set-up TRUE -2 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8
6-01 Live Zero Timeout Function [0] Off All set-ups TRUE – Uint8
6-1* Analog Input 53
6-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Uint16
6-11 Terminal 53 High Voltage 10 V All set-ups TRUE -2 Uint16
5 5 6-12
6-13
Terminal 53 Low Current
Terminal 53 High Current
4 mA
20 mA
All set-ups
All set-ups
TRUE
TRUE
-5
-5
Uint16
Uint16
6-14 Terminal 53 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
6-15 Terminal 53 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-16 Terminal 53 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16
6-19 Terminal 53 mode [1] Voltage mode 1 set-up TRUE – Uint8
6-2* Analog Input 54
6-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Uint16
6-21 Terminal 54 High Voltage 10 V All set-ups TRUE -2 Uint16
6-22 Terminal 54 Low Current 4 mA All set-ups TRUE -5 Uint16
6-23 Terminal 54 High Current 20 mA All set-ups TRUE -5 Uint16
6-24 Terminal 54 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
6-25 Terminal 54 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-26 Terminal 54 Filter Time Constant 0.01 s All set-ups TRUE -2 Uint16
6-29 Terminal 54 mode [1] Voltage mode 1 set-up TRUE – Uint8
6-7* Analog/Digital Output 45
6-70 Terminal 45 Mode [0] 0-20 mA All set-ups TRUE – Uint8
6-71 Terminal 45 Analog Output [0] No operation All set-ups TRUE – Uint8
6-72 Terminal 45 Digital Output [0] No operation All set-ups TRUE – Uint8
6-73 Terminal 45 Output Min Scale 0% All set-ups TRUE -2 Uint16
6-74 Terminal 45 Output Max Scale 100% All set-ups TRUE -2 Uint16
6-76 Terminal 45 Output Bus Control 0 N/A All set-ups TRUE 0 Uint16
6-9* Analog/Digital Output 42
6-90 Terminal 42 Mode [0] 0-20 mA All set-ups TRUE – Uint8
6-91 Terminal 42 Analog Output [0] No operation All set-ups TRUE – Uint8
6-92 Terminal 42 Digital Output [0] No operation All set-ups TRUE – Uint8
6-93 Terminal 42 Output Min Scale 0% All set-ups TRUE -2 Uint16
6-94 Terminal 42 Output Max Scale 100% All set-ups TRUE -2 Uint16
6-96 Terminal 42 Output Bus Control 0 N/A All set-ups TRUE 0 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
7-0* Speed PID Ctrl.
7-00 Speed PID Feedback Source [20] None All set-ups FALSE – Uint8
7-02 Speed PID Proportional Gain 0.015 N/A All set-ups TRUE -3 Uint16
7-03 Speed PID Integral Time 8 ms All set-ups TRUE -4 Uint32
7-04 Speed PID Differentiation Time 30 ms All set-ups TRUE -4 Uint16
7-05 Speed PID Diff. Gain Limit 5 N/A All set-ups TRUE -1 Uint16
7-06
7-07
Speed PID Lowpass Filter Time
Speed PID Feedback Gear Ratio
10 ms
1 N/A
All set-ups
All set-ups
TRUE
FALSE
-4
-4
Uint16
Uint32
5 5
7-08 Speed PID Feed Forward Factor 0% All set-ups FALSE 0 Uint16
7-1* Torque PID Ctrl.
7-12 Torque PID Proportional Gain 100% All set-ups TRUE 0 Uint16
7-13 Torque PID Integration Time 0.020 s All set-ups TRUE -3 Uint16
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource [0] No function All set-ups TRUE – Uint8
7-22 Process CL Feedback 2 Resource [0] No function All set-ups TRUE – Uint8
7-3* Process PID Ctrl.
7-30 Process PID Normal/ Inverse Control [0] Normal All set-ups TRUE – Uint8
7-31 Process PID Anti Windup [1] On All set-ups TRUE – Uint8
7-32 Process PID Start Speed 0 RPM All set-ups TRUE 67 Uint16
7-33 Process PID Proportional Gain 0.01 N/A All set-ups TRUE -2 Uint16
7-34 Process PID Integral Time 9999 s All set-ups TRUE -2 Uint32
7-35 Process PID Differentiation Time 0s All set-ups TRUE -2 Uint16
7-36 Process PID Diff. Gain Limit 5 N/A All set-ups TRUE -1 Uint16
7-38 Process PID Feed Forward Factor 0% All set-ups TRUE 0 Uint16
7-39 On Reference Bandwidth 5% All set-ups TRUE 0 Uint8
7-4* Adv. Process PID I
7-40 Process PID I-part Reset [0] No All set-ups TRUE – Uint8
7-41 Process PID Output Neg. Clamp -100 % All set-ups TRUE 0 Int16
7-42 Process PID Output Pos. Clamp 100% All set-ups TRUE 0 Int16
7-43 Process PID Gain Scale at Min. Ref. 100% All set-ups TRUE 0 Int16
7-44 Process PID Gain Scale at Max. Ref. 100% All set-ups TRUE 0 Int16
7-45 Process PID Feed Fwd Resource [0] No function All set-ups TRUE – Uint8
7-46 Process PID Feed Fwd Normal/ Inv. Ctrl. [0] Normal All set-ups TRUE – Uint8
7-48 PCD Feed Forward 0 N/A All set-ups TRUE 0 Uint16
7-49 Process PID Output Normal/ Inv. Ctrl. [0] Normal All set-ups TRUE – Uint8
7-5* Adv. Process PID II
7-50 Process PID Extended PID [1] Enabled All set-ups TRUE – Uint8
7-51 Process PID Feed Fwd Gain 1 N/A All set-ups TRUE -2 Uint16
7-52 Process PID Feed Fwd Ramp up 0.01 s All set-ups TRUE -2 Uint32
7-53 Process PID Feed Fwd Ramp down 0.01 s All set-ups TRUE -2 Uint32
7-56 Process PID Ref. Filter Time 0.001 s All set-ups TRUE -3 Uint16
7-57 Process PID Fb. Filter Time 0.001 s All set-ups TRUE -3 Uint16
7-6* Feedback Conversion
7-60 Feedback 1 Conversion [0] Linear All set-ups TRUE – Uint8
7-62 Feedback 2 Conversion [0] Linear All set-ups TRUE – Uint8
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
8-0* General Settings
8-01 Control Site [0] Digital and ctrl.word All set-ups TRUE – Uint8
8-02 Control Source ExpressionLimit All set-ups TRUE – Uint8
8-03 Control Timeout Time 1s 1 set-up TRUE -1 Uint16
8-04 Control Timeout Function [0] Off 1 set-up TRUE – Uint8
8-07 Diagnosis Trigger [0] Disable 1 set-up TRUE – Uint8
Par. No. # Parameter description Default value 2-set-up Change Conversion Type
during index
operation
9-00 Setpoint 0 N/A All set-ups TRUE 0 Uint16
9-07 Actual Value 0 N/A All set-ups FALSE 0 Uint16
9-15 PCD Write Configuration ExpressionLimit 1 set-up TRUE – Uint16
9-16 PCD Read Configuration ExpressionLimit 1 set-up TRUE – Uint16
9-18 Node Address 126 N/A 1 set-up TRUE 0 Uint8
9-19 Drive Unit System Number 1037 N/A All set-ups TRUE 0 Uint16
9-22
9-23
Telegram Selection
Parameters for Signals
[100] None
0
1 set-up
All set-ups
TRUE
TRUE
–
–
Uint8
Uint16
5 5
9-27 Parameter Edit [1] Enabled 1 set-up FALSE – Uint16
9-28 Process Control [1] Enable cyclic master 1 set-up FALSE – Uint8
9-44 Fault Message Counter 0 N/A All set-ups TRUE 0 Uint16
9-45 Fault Code 0 N/A All set-ups TRUE 0 Uint16
9-47 Fault Number 0 N/A All set-ups TRUE 0 Uint16
9-52 Fault Situation Counter 0 N/A All set-ups TRUE 0 Uint16
9-53 PROFIBUS Warning Word 0 N/A All set-ups TRUE 0 V2
9-63 Actual Baud Rate [255] No baudrate found All set-ups TRUE – Uint8
9-64 Device Identification 0 N/A All set-ups TRUE 0 Uint16
9-65 Profile Number 0 N/A All set-ups TRUE 0 OctStr[0]
9-67 Control Word 1 0 N/A All set-ups TRUE 0 V2
9-68 Status Word 1 0 N/A All set-ups TRUE 0 V2
9-70 Programming Set-up [9] Active Set-up 1 set-up TRUE – Uint8
9-71 PROFIBUS Save Data Values [0] Off All set-ups TRUE – Uint8
9-72 PROFIBUSDriveReset [0] No action 1 set-up FALSE – Uint8
9-75 DO Identification 0 N/A All set-ups TRUE 0 Uint16
9-80 Defined Parameters (1) 0 N/A All set-ups FALSE 0 Uint16
9-81 Defined Parameters (2) 0 N/A All set-ups FALSE 0 Uint16
9-82 Defined Parameters (3) 0 N/A All set-ups FALSE 0 Uint16
9-83 Defined Parameters (4) 0 N/A All set-ups FALSE 0 Uint16
9-84 Defined Parameters (5) 0 N/A All set-ups FALSE 0 Uint16
9-90 Changed Parameters (1) 0 N/A All set-ups FALSE 0 Uint16
9-91 Changed Parameters (2) 0 N/A All set-ups FALSE 0 Uint16
9-92 Changed Parameters (3) 0 N/A All set-ups FALSE 0 Uint16
9-93 Changed Parameters (4) 0 N/A All set-ups FALSE 0 Uint16
9-94 Changed Parameters (5) 0 N/A All set-ups FALSE 0 Uint16
9-99 PROFIBUS Revision Counter 0 N/A All set-ups TRUE 0 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversion Type
during index
operation
12-0* IP Settings
12-00 IP Address Assignment [10] DCP 1 set-up TRUE – Uint8
12-01 IP Address 0 N/A 1 set-up TRUE 0 OctStr[4]
12-02 Subnet Mask 0 N/A 1 set-up TRUE 0 OctStr[4]
12-03 Default Gateway 0 N/A 1 set-up TRUE 0 OctStr[4]
12-04 DHCP Server 0 N/A 1 set-up TRUE 0 OctStr[4]
5 5 12-05
12-06
Lease Expires
Name Servers
0 N/A
0 N/A
All set-ups
1 set-up
TRUE
TRUE
0
0
TimD
OctStr[4]
12-07 Domain Name 0 N/A 1 set-up TRUE 0 VisStr[48]
12-08 Host Name 0 N/A 1 set-up TRUE 0 VisStr[48]
12-09 Physical Address 0 N/A 1 set-up TRUE 0 VisStr[17]
12-1* Ethernet Link Parameters
12-10 Link Status [0] No Link 1 set-up TRUE – Uint8
12-11 Link Duration ExpressionLimit All set-ups TRUE 0 TimD
12-12 Auto Negotiation [1] On 1 set-up TRUE – Uint8
12-13 Link Speed [0] None 1 set-up TRUE – Uint8
12-14 Link Duplex [1] Full Duplex 1 set-up TRUE – Uint8
12-8* Other Ethernet Services
12-80 FTP Server [0] Disabled 1 set-up TRUE – Uint8
12-81 HTTP Server [0] Disabled 1 set-up TRUE – Uint8
12-82 SMTP Service [0] Disabled 1 set-up TRUE – Uint8
12-89 Transparent Socket Channel Port 4000 N/A 1 set-up TRUE 0 Uint16
12-9* Advanced Ethernet Services
12-90 Cable Diagnostic [0] Disabled 1 set-up TRUE – Uint8
12-91 Auto Cross Over [1] Enabled 1 set-up TRUE – Uint8
12-92 IGMP Snooping [1] Enabled 1 set-up TRUE – Uint8
12-93 Cable Error Length 0 N/A 1 set-up TRUE 0 Uint16
12-94 Broadcast Storm Protection -1 % 1 set-up TRUE 0 Int8
12-95 Broadcast Storm Filter [0] Broadcast only 1 set-up TRUE – Uint8
12-96 Port Config ExpressionLimit 1 set-up TRUE – Uint8
12-98 Interface Counters 4000 N/A All set-ups TRUE 0 Uint32
12-99 Media Counters 0 N/A All set-ups TRUE 0 Uint32
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
13-0* SLC Settings
13-00 SL Controller Mode [0] Off 1 set-up TRUE – Uint8
13-01 Start Event [39] Start command 1 set-up TRUE – Uint8
13-02 Stop Event [40] Drive stopped 1 set-up TRUE – Uint8
13-03 Reset SLC [0] Do not reset SLC 1 set-up TRUE – Uint8
13-1* Comparators
13-10
13-11
Comparator Operand
Comparator Operator
[0] Disabled
[1] Approx.Equal (~)
1 set-up
1 set-up
TRUE
TRUE
–
–
Uint8
Uint8
5 5
13-12 Comparator Value 0 N/A 1 set-up TRUE -3 Int32
13-2* Timers
13-20 SL Controller Timer 0s 1 set-up TRUE -2 Uint32
13-4* Logic Rules
13-40 Logic Rule Boolean 1 [0] False 1 set-up TRUE – Uint8
13-41 Logic Rule Operator 1 [0] Disabled 1 set-up TRUE – Uint8
13-42 Logic Rule Boolean 2 [0] False 1 set-up TRUE – Uint8
13-43 Logic Rule Operator 2 [0] Disabled 1 set-up TRUE – Uint8
13-44 Logic Rule Boolean 3 [0] False 1 set-up TRUE – Uint8
13-5* States
13-51 SL Controller Event [0] False 1 set-up TRUE – Uint8
13-52 SL Controller Action [0] Disabled 1 set-up TRUE – Uint8
Par. No. # Parameter description Default value 4-set-up Change during Conversion Type
operation index
14-0* Inverter Switching
14-01 Switching Frequency ExpressionLimit All set-ups TRUE - Uint8
14-03 Overmodulation [1] On All set-ups FALSE - Uint8
14-07 Dead Time Compensation Level ExpressionLimit All set-ups FALSE 0 Uint8
14-08 Damping Gain Factor ExpressionLimit All set-ups TRUE 0 Uint8
14-09 Dead Time Bias Current Level ExpressionLimit All set-ups FALSE 0 Uint8
14-1* Mains On/Off
5 5 14-10
14-11
Mains Failure
Mains Voltage at Mains Fault
[0] No function
342 V
All set-ups
All set-ups
FALSE
TRUE
-
0
Uint8
Uint16
14-12 Function at Mains Imbalance [0] Trip 1 set-up TRUE - Uint8
14-15 Kin. Backup Trip Recovery Level ExpressionLimit All set-ups TRUE -3 Uint32
14-2* Reset Functions
14-20 Reset Mode [0] Manual reset All set-ups TRUE - Uint8
14-21 Automatic Restart Time 10 s All set-ups TRUE 0 Uint16
14-22 Operation Mode [0] Normal operation 1 set-up TRUE - Uint8
14-24 Trip Delay at Current Limit 60 s All set-ups TRUE 0 Uint8
14-25 Trip Delay at Torque Limit 60 s All set-ups TRUE 0 Uint8
14-27 Action At Inverter Fault [1] Warning All set-ups TRUE - Uint8
14-28 Production Settings [0] No action 1 set-up FALSE - Uint8
14-29 Service Code 0 N/A 1 set-up TRUE 0 Uint32
14-3* Current Limit Ctrl.
14-30 Current Lim Ctrl, Proportional Gain 100% All set-ups TRUE 0 Uint16
14-31 Current Lim Ctrl, Integration Time 0.020 s All set-ups TRUE -3 Uint16
14-32 Current Lim Ctrl, Filter Time 5 ms All set-ups TRUE -4 Uint16
14-4* Energy Optimising
14-40 VT Level 66% All set-ups FALSE 0 Uint8
14-41 AEO Minimum Magnetisation 66% All set-ups FALSE 0 Uint8
14-44 d-axis current optimization for IPM 100% All set-ups TRUE 0 Uint8
14-5* Environment
14-50 RFI Filter [2] Grid Type 1 set-up FALSE - Uint8
14-51 DC-Link Voltage Compensation [1] On All set-ups FALSE - Uint8
14-52 Fan Control [5] Constant-on mode 1 set-up TRUE - Uint8
14-55 Output Filter [0] No Filter 1 set-up FALSE - Uint8
14-6* Auto Derate
14-61 Function at Inverter Overload [0] Trip All set-ups TRUE - Uint8
14-63 Min Switch Frequency [2] 2.0 kHz 1 set-up FALSE - Uint8
Dead Time Compensation Zero
14-64 Current Level [0] Disabled All set-ups FALSE - Uint8
Speed Derate Dead Time Compen-
14-65 sation ExpressionLimit All set-ups FALSE 0 Uint16
14-8* Options
[0] Protect Option
14-89 Option Detection Config. 1 set-up TRUE - Uint8
14-9* Fault Settings
14-90 Fault Level [3] Trip Lock All set-ups TRUE - Uint8
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
15-0* Operating Data
15-00 Operating hours 0h 1 set-up TRUE 74 Uint32
15-01 Running Hours 0h 1 set-up TRUE 74 Uint32
15-02 kWh Counter 0 kWh 1 set-up TRUE 75 Uint32
15-03 Power Up's 0 N/A 1 set-up TRUE 0 Uint32
15-04 Over Temp's 0 N/A 1 set-up TRUE 0 Uint16
15-05
15-06
Over Volt's
Reset kWh Counter
0 N/A
[0] Do not reset
1 set-up
1 set-up
TRUE
TRUE
0
–
Uint16
Uint8
5 5
15-07 Reset Running Hours Counter [0] Do not reset 1 set-up TRUE – Uint8
15-3* Alarm Log
15-30 Alarm Log: Error Code 0 N/A 1 set-up TRUE 0 Uint8
15-31 InternalFaultReason 0 N/A 1 set-up TRUE 0 Int16
15-4* Drive Identification
15-40 FC Type 0 N/A 1 set-up FALSE 0 VisStr[7]
15-41 Power Section 0 N/A 1 set-up FALSE 0 VisStr[20]
15-42 Voltage 0 N/A 1 set-up FALSE 0 VisStr[20]
15-43 Software Version 0 N/A 1 set-up FALSE 0 VisStr[20]
15-44 Ordered TypeCode 0 N/A 1 set-up FALSE 0 VisStr[41]
15-45 Actual Typecode String 0 N/A All set-ups FALSE 0 VisStr[40]
15-46 Drive Ordering No 0 N/A 1 set-up FALSE 0 VisStr[9]
15-48 LCP Id No 0 N/A 1 set-up FALSE 0 VisStr[21]
15-49 SW ID Control Card 0 N/A 1 set-up FALSE 0 VisStr[21]
15-50 SW ID Power Card 0 N/A 1 set-up FALSE 0 VisStr[21]
15-51 Drive Serial Number 0 N/A 1 set-up FALSE 0 VisStr[13]
15-53 Power Card Serial Number 0 N/A 1 set-up FALSE 0 VisStr[21]
15-6* Option Ident
15-60 Option Mounted ExpressionLimit All set-ups FALSE 0 VisStr[30]
15-61 Option SW Version ExpressionLimit All set-ups FALSE 0 VisStr[20]
15-62 Option Ordering No ExpressionLimit All set-ups FALSE 0 VisStr[8]
15-63 Option Serial No ExpressionLimit All set-ups FALSE 0 VisStr[18]
15-70 Option in Slot A 0 N/A All set-ups FALSE 0 VisStr[30]
15-71 Slot A Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
15-9* Parameter Info
15-92 Defined Parameters 0 N/A 1 set-up TRUE 0 Uint16
15-97 Application Type 0 N/A 1 set-up TRUE 0 Uint32
15-98 Drive Identification 0 N/A 1 set-up FALSE 0 VisStr[56]
15-99 Parameter Metadata 0 N/A 1 set-up FALSE 0 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversion Type
during index
operation
16-0* General Status
16-00 Control Word 0 N/A 1 set-up TRUE 0 Uint16
16-01 Reference [Unit] 0 ReferenceFeedbackUnit 1 set-up TRUE -3 Int32
16-02 Reference [%] 0% 1 set-up TRUE -1 Int16
16-03 Status Word 0 N/A 1 set-up TRUE 0 Uint16
16-05 Main Actual Value [%] 0% 1 set-up TRUE -2 Int16
Par. No. # Parameter description Default value 2-set-up Change Conversion Type
during index
operation
16-8* Fieldbus & FC Port
16-80 Fieldbus CTW 1 0 N/A 1 set-up TRUE 0 Uint16
16-82 Fieldbus REF 1 0 N/A 1 set-up TRUE 0 Int16
16-84 Comm. Option STW 0 N/A 1 set-up TRUE 0 Uint16
16-85 FC Port CTW 1 1084 N/A 1 set-up FALSE 0 uint16
16-86 FC Port REF 1 0 N/A 1 set-up TRUE 0 Int16
16-9* Diagnosis Readouts
16-90 Alarm Word 0 N/A 1 set-up TRUE 0 Uint32
16-91
16-92
Alarm Word 2
Warning Word
0 N/A
0 N/A
1 set-up
1 set-up
TRUE
TRUE
0
0
Uint32
Uint32
5 5
16-93 Warning Word 2 0 N/A 1 set-up TRUE 0 Uint32
16-94 Ext. Status Word 0 N/A 1 set-up TRUE 0 Uint32
16-95 Ext. Status Word 2 0 N/A 1 set-up TRUE 0 Uint32
16-97 Alarm Word 3 0 N/A 1 set-up TRUE 0 Uint32
Par. No. # Parameter description Default value 2-set-up Change Conversion Type
during index
operation
17-1* Inc.Enc.Interface
17-10 Signal Type [1] RS422 (5 V TTL) All set-ups FALSE – Uint8
17-11 Resolution (PPR) 1024 N/A All set-ups FALSE 0 Uint16
17-5* Resolver Interface
17-50 Poles 2 N/A 1 set-up FALSE 0 Uint8
17-51 Input Voltage 7V 1 set-up FALSE -1 Uint8
17-52 Input Frequency 10 kHz 1 set-up FALSE 2 Uint8
17-53 Transformation Ratio 0.5 N/A 1 set-up FALSE -1 Uint8
17-56 Encoder Sim. Resolution [0] Disabled 1 set-up FALSE – Uint8
17-59 Resolver Interface [0] Disabled All set-ups FALSE – Uint8
17-6* Monitoring and App.
17-60 Feedback Direction [0] Clockwise All set-ups FALSE – Uint8
17-61 Feedback Signal Monitoring [1] Warning All set-ups TRUE – Uint8
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
22-4* Sleep Mode
22-40 Minimum Run Time 10 s All set-ups TRUE 0 Uint16
22-41 Minimum Sleep Time 10 s All set-ups TRUE 0 Uint16
22-43 Wake-Up Speed [Hz] 10 N/A All set-ups TRUE -1 Uint16
22-44 Wake-Up Ref./FB Diff 10% All set-ups TRUE 0 Uint8
22-45 Setpoint Boost 0% All set-ups TRUE 0 Int8
22-46
22-47
Maximum Boost Time
Sleep Speed [Hz]
60 s
0 N/A
All set-ups
All set-ups
TRUE
TRUE
0
-1
Uint16
Uint16
5 5
22-6* Broken Belt Detection
22-60 Broken Belt Function [0] Off All set-ups TRUE – Uint8
22-61 Broken Belt Torque 10% All set-ups TRUE 0 Uint8
22-62 Broken Belt Delay 10 s All set-ups TRUE 0 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s] ExpressionLimit All set-ups TRUE -2 Uint16
30-21 High Starting Torque Current [%] ExpressionLimit All set-ups TRUE -1 Uint32
30-22 Locked Rotor Protection [0] Off All set-ups TRUE - Uint8
30-23 Locked Rotor Detection Time [s] 0.10 s All set-ups TRUE -2 Uint8
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
32-11 User Unit Denominator 1 N/A 1 set-up TRUE 0 Uint32
32-12 User Unit Numerator 1 N/A 1 set-up TRUE 0 Uint32
32-67 Max. Tolerated Position Error 2000000 N/A 1 set-up TRUE 0 Uint32
32-81 Motion Ctrl Quick Stop Ramp 1000 ms 1 set-up TRUE -3 Uint32
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
33-00 Force Home [0] Home not forced 1 set-up TRUE – Uint8
33-01 Home Offset 0 N/A 1 set-up TRUE 0 Int32
33-02 Home Ramp Time 10 ms 1 set-up TRUE -3 Uint16
33-03 Homing Velocity 100 RPM 1 set-up TRUE 67 Int16
33-04 Homing Type [1] Reverse no index 1 set-up TRUE – Uint8
33-41 Negative Software Limit -500000 N/A 1 set-up TRUE 0 Int32
5 5 33-42 Positive Software Limit 500000 N/A 1 set-up TRUE 0 Int32
33-43 Negative Software Limit Active [0] Inactive 1 set-up TRUE – Uint8
33-44 Positive Software Limit Active [0] Inactive 1 set-up TRUE – Uint8
33-47 Target Position Window 0 N/A 1 set-up TRUE 0 Uint16
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
34-0* PCD Write Par.
34-01 PCD 1 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-02 PCD 2 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-03 PCD 3 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-04 PCD 4 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-05 PCD 5 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-06 PCD 6 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-07 PCD 7 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-08 PCD 8 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-09 PCD 9 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-10 PCD 10 Write For Application 0 N/A All set-ups TRUE 0 Uint16
34-2* PCD Read Par.
34-21 PCD 1 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-22 PCD 2 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-23 PCD 3 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-24 PCD 4 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-25 PCD 5 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-26 PCD 6 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-27 PCD 7 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-28 PCD 8 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-29 PCD 9 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-30 PCD 10 Read For Application 0 N/A All set-ups TRUE 0 Uint16
34-5* Process Data
34-50 Actual Position 0 N/A All set-ups TRUE 0 Int32
34-56 Track Error 0 N/A All set-ups TRUE 0 Int32
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
Par. No. # Parameter description Default value 2-set-up Change Conversio Type
during n index
operation
37-43 Diameter Calculator Min Speed 0% 1 set-up TRUE 0 Uint16
37-44 Line Acceleration Feed Forward 0 N/A 1 set-up TRUE -3 Int16
37-45 Line Speed Source [0] No function 1 set-up FALSE – Uint8
37-46 Winder Speed Match Scale 1 N/A 1 set-up FALSE -3 Uint32
37-47 Tension PID Profile 0% 1 set-up TRUE -2 Uint16
37-48 Tension PID Proportional Gain 0 N/A 1 set-up TRUE -2 Uint16
37-49 Tension PID Derivate Time 0s 1 set-up TRUE -2 Uint16
37-50 Tension PID Integral Time 501 s 1 set-up TRUE -2 Uint32
5 5 37-51
37-52
Tension PID Out Limit
Tension PID Der Gain Limit
0%
5 N/A
1 set-up
1 set-up
TRUE
TRUE
-3
-1
Uint32
Uint16
37-53 Tension PID Anti Windup [1] Enabled 1 set-up TRUE – Uint8
37-54 Winder Jog Reverse [0] No Function 1 set-up TRUE – Uint8
37-55 Winder Jog Forward [0] No function 1 set-up TRUE – Uint8
37-56 New Diameter Select [0] Core diameter 1 set-up FALSE – Uint8
37-57 Tension On/Off [0] Off 1 set-up TRUE – Uint8
37-58 Core Select [0] Core1 diameter 1 set-up FALSE – Uint8
37-59 Diameter Reset [0] Off 1 set-up FALSE – Uint8
6 Troubleshooting
6.1.2 Warnings A trip lock is an action when an alarm occurs which can
damage the frequency converter or connected equipment.
During a warning, the frequency converter remains Power is removed from the motor. A trip lock can only be
operational, although the warning flashes for as long as reset after a cycling power has cleared the condition. Once
the condition exists. The frequency converter could, the problem has been rectified, only the alarm continues
however, reduce the warning condition. For example, if the flashing until the frequency converter is reset.
warning shown was warning 12, Torque Limit, the frequency
converter would reduce speed to compensate for the
The warnings and alarms are explained in Table 6.2.
overcurrent condition. Sometimes, if the condition is not
corrected or worsens, an alarm condition is activated and
the frequency converter stops output to the motor
terminals. Line 1 identifies the warning in plain language,
and line 2 identifies the warning number.
Numb
Description Warning Alarm Trip lock Cause
er
Signal on terminal 53 or 54 is less than 50% of value set
in parameter 6-10 Terminal 53 Low Voltage,
2 Live zero error X X – parameter 6-12 Terminal 53 Low Current,
parameter 6-20 Terminal 54 Low Voltage, and
parameter 6-22 Terminal 54 Low Current.
No motor has been connected to the output of the
3 No motor X – –
frequency converter, or 1 motor phase is missing.
Missing phase on supply side, or the voltage imbalance is
4 Mains phase loss1) X X X
too high. Check the supply voltage.
7 DC overvoltage1) X X – Intermediate circuit voltage exceeds limit.
Intermediate circuit voltage drops below the voltage
8 DC undervoltage1) X X –
warning low limit.
6 6 9
10
Inverter overloaded
X
X
X
–
–
More than 100% load for too long.
Motor is too hot due to more than 100% load for too
long.
Motor thermistor overtem-
11 X X – Thermistor or thermistor connection is disconnected.
perature
Torque exceeds value set in either parameter 4-16 Torque
12 Torque limit X X – Limit Motor Mode or parameter 4-17 Torque Limit Generator
Mode.
Inverter peak current limit is exceeded. For J1–J6 units, if
13 Overcurrent X X X this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.
14 Earth fault – X X Discharge from output phases to ground.
Short circuit in motor or on motor terminals. For J7 units,
16 Short circuit – X X if this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.
17 Control word timeout X X – No communication to frequency converter.
18 Start failed – X – –
Brake resistor is short-circuited, thus the brake function is
25 Brake resistor short-circuited – X X
disconnected.
The power transmitted to the brake resistor over the last
26 Brake overload X X – 120 s exceeds the limit. Possible corrections: Decrease
brake energy via lower speed or longer ramp time.
Brake IGBT/Brake chopper short- Brake transistor is short-circuited, thus brake function is
27 – X X
circuited disconnected.
28 Brake check – X – Brake resistor is not connected/working.
30 U phase loss – X X Motor phase U is missing. Check the phase.
31 V phase loss – X X Motor phase V is missing. Check the phase.
32 W phase loss – X X Motor phase W is missing. Check the phase.
34 Fieldbus fault X X – PROFIBUS communication issues have occurred.
35 Option fault – X – Fieldbus or option B detects internal faults.
This warning/alarm is only active if the supply voltage to
the frequency converter is less than the value set in
36 Mains failure X X – parameter 14-11 Mains Fault Voltage Level, and
parameter 14-10 Mains Failure is NOT set to [0] No
Function.
38 Internal fault – X X Contact the local Danfoss supplier.
Check the load connected to terminal 27 or remove
40 Overload T27 X – –
short-circuit connection.
Check the load connected to terminal 29 or remove
41 Overload T29 X – –
short-circuit connection.
46 Gate drive voltage fault – X X –
Numb
Description Warning Alarm Trip lock Cause
er
47 24 V supply low X X X 24 V DC may be overloaded.
50 AMA calibration – X – –
51 AMA check Unom and Inom – X – Wrong setting for motor voltage and/or motor current.
52 AMA low Inom – X – Motor current is too low. Check the settings.
The power size of the motor is too large for the AMA to
53 AMA big motor – X –
operate.
The power size of the motor is too small for the AMA to
54 AMA small motor – X –
operate.
The parameter values of the motor are outside of the
55 AMA parameter range – X –
acceptable range. AMA does not run.
56 AMA interrupt – X – The AMA is interrupted.
57 AMA timeout – X – –
58 AMA internal – X – Contact Danfoss.
6 6
59 Current limit X X – Frequency converter overload.
60 External Interlock – X – –
61 Feedback error X X – –
Actual motor current has not exceeded release brake
63 Mechanical brake low – X –
current within start delay time window.
The cutout temperature of the control card is 80 °C
65 Control card temp X X X
(176 °F).
69 Power card temp X X X –
70 Illegal FC config – X X –
Frequency converter initialized
80 – X – All parameter settings are initialized to default settings.
to default value
Occurs in IT mains when the frequency converter coasts
and the DC voltage are higher than 830 V. Energy on DC-
87 Auto DC brake X – –
link is consumed by the motor. This function can be
enabled/disabled in parameter 0-07 Auto DC Braking.
90 Feedback monitor X X – A feedback fault is detected by option B.
95 Broken belt X X – –
99 Locked rotor – X – –
Flow/pressure information
101 – X X –
missing
120 Position control fault – X – –
124 Tension limit – X – –
126 Motor rotating – X – –
Try to start PM motor which is rotating in an abnormal
127 Back EMF too high2) X – –
high speed.
250 New spare part – X X –
251 New type code – X X –
For diagnosis, read out the alarm words, warning words, and extended status words.
000000
0 1 Brake check Reserved Reserved Reserved Reserved Ramping Off
01
000000 Pwr. card Gate drive Pwr. card
1 2 Reserved Reserved AMA tuning Hand/Auto
02 temp voltage fault temp
6 6 2
000000
04
4 Earth fault Reserved Reserved Reserved Reserved Start CW/CCW
PROFIBUS OFF1
active
000000 Ctrl. card PROFIBUS OFF2
3 8 Reserved Reserved Ctrl. card temp Reserved Slowdown
08 temp active
000000 Ctrl. word Illegal FC PROFIBUS OFF3
4 16 Reserved Ctrl. word TO Reserved Catch up
10 TO config active
000000
5 32 Overcurrent Reserved Reserved Overcurrent Reserved Feedback high Reserved
20
000000
6 64 Torque limit Reserved Reserved Torque limit Reserved Feedback low Reserved
40
000000 Motor Th. Output current
7 128 Reserved Reserved Motor Th. over Reserved Control ready
80 over high
000001 Motor ETR Motor ETR Output current Frequency converter
8 256 Broken belt Reserved Broken belt
00 over over low ready
000002 Inverter Output freq.
9 512 Reserved Reserved Inverter overld. Reserved Quick stop
00 overld. high
000004 DC Output freq.
10 1024 Start failed Reserved DC undervolt. Reserved DC brake
00 undervolt. low
000008
11 2048 DC overvolt. Reserved Reserved DC overvolt. Reserved Brake check OK Stop
00
000010 External
12 4096 Short circuit Reserved Reserved Reserved Braking max Latched
00 interlock
000020
13 8192 Reserved Reserved Reserved Reserved Reserved Braking Reserved
00
000040 Mains ph.
14 16384 Reserved Reserved Mains ph. loss Reserved Reserved Freeze output
00 loss
000080
15 32768 AMA not OK Reserved Reserved No motor Auto DC brake OVC active Reserved
00
000100 Live zero
16 65536 Reserved Reserved Live zero error Reserved AC brake Jog
00 error
000200
17 131072 Internal fault Reserved Reserved Reserved Reserved Reserved Reserved
00
000400 Brake Brake resistor
18 262144 Reserved Reserved Reserved Reserved Start
00 overload power limit
000800
19 524288 U phase loss Reserved Reserved Reserved Reserved Reference high Reserved
00
001000 Option
20 1048576 V phase loss Reserved Reserved Overload T27 Reference low Start delay
00 detection
002000
21 2097152 W phase loss Option fault Reserved Reserved Reserved Reserved Sleep
00
004000 Fieldbus
22 4194304 Locked rotor Reserved Fieldbus fault Reserved Reserved Sleep boost
00 fault
008000 24 V supply Position ctrl. 24 V supply
23 8388608 Reserved Reserved Reserved Running
00 low fault low
010000 Tension
24 16777216 Mains failure Reserved Mains failure Reserved Reserved Bypass
00 Limit
25
020000
00
33554432 Reserved Current limit Reserved Current limit Reserved Reserved Reserved 6 6
040000 Brake
26 67108864 Reserved Reserved Reserved Reserved Reserved External interlock
00 resistor
080000 13421772
27 Brake IGBT Reserved Reserved Reserved Reserved Reserved Reserved
00 8
100000 26843545 Option Feedback
28 Reserved Encoder loss Reserved Reserved FlyStart active
00 6 change fault
Frequency
200000 53687091 Back EMF too Heat sink clean
29 converter Encoder loss Reserved Reserved Reserved
00 2 high warning
initialized
400000 10737418
30 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
00 24
800000 21474836 Mech. brake
31 Reserved Reserved Reserved Reserved Database busy Reserved
00 48 low
Table 6.3 Description of Alarm Word, Warning Word, and Extended Status Word
WARNING/ALARM 2, Live zero error • Show the thermal frequency converter load on
This warning or alarm only appears if programmed in the LCP and monitor the value. When running
parameter 6-01 Live Zero Timeout Function. The signal on 1 above the frequency converter continuous
of the analog inputs is less than 50% of the minimum current rating, the counter increases. When
value programmed for that input. Broken wiring or faulty running below the frequency converter
device sending the signal can cause this condition. continuous current rating, the counter decreases.
Troubleshooting WARNING/ALARM 10, Motor overload temperature
• Check connections on all the analog input According to the electronic thermal protection (ETR), the
terminals. Control card terminals 53 and 54 for motor is too hot. Select whether the frequency converter
signals, terminal 55 common. issues a warning or an alarm when the counter reaches
100% in parameter 1-90 Motor Thermal Protection. The fault
• Check that the frequency converter programming
occurs when the motor runs with more than 100%
and switch settings match the analog signal type.
overload for too long.
• Perform the input terminal signal test.
Troubleshooting
6 6 WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
• Check for motor overheating.
voltage imbalance is too high. This message also appears • Check if the motor is mechanically overloaded.
for a fault in the input rectifier. Options are programmed in • Check that the motor current set in
parameter 14-12 Function at Mains Imbalance. parameter 1-24 Motor Current is correct.
Troubleshooting • Ensure that motor data in parameters 1-20 to 1-25
• Check the supply voltage and supply currents to is set correctly.
the frequency converter.
• Running AMA in parameter 1-29 Automatic Motor
WARNING/ALARM 7, DC overvoltage Adaptation (AMA) tunes the frequency converter
If the DC-link voltage exceeds the limit, the frequency to the motor more accurately and reduces
converter trips after a time. thermal loading.
Troubleshooting WARNING/ALARM 11, Motor thermistor over temp
• Extend the ramp time. Check whether the thermistor is disconnected. Select
whether the frequency converter issues a warning or an
• Change the ramp type.
alarm in parameter 1-90 Motor Thermal Protection.
WARNING/ALARM 8, DC under voltage
Troubleshooting
If the DC-link voltage (DC-link) drops below the
undervoltage limit, the frequency converter trips after a • Check for motor overheating.
fixed time delay. The time delay varies with unit size. • Check if the motor is mechanically overloaded.
Troubleshooting • When using terminal 53 or 54, check that the
• Check that the supply voltage matches the thermistor is connected correctly between either
frequency converter voltage. terminal 53 or 54 (analog voltage input) and
terminal 50 (+10 V supply). Also check that the
• Perform the input voltage test.
terminal switch for 53 or 54 is set for voltage.
• Perform the soft charge circuit test. Check that parameter 1-93 Thermistor Resource
WARNING/ALARM 9, Inverter overload selects terminal 53 or 54.
The frequency converter is about to cut out because of an • When using terminal 18, 19, 31, 32, or 33 (digital
overload (too high current for too long). The counter for inputs), check that the thermistor is connected
electronic, thermal inverter protection issues a warning at correctly between the digital input terminal used
90% and trips at 100%, while giving an alarm. The (digital input PNP only) and terminal 50. Select
frequency converter cannot be reset until the counter is the terminal to use in parameter 1-93 Thermistor
below 0%. Resource.
The fault occurs when the frequency converter has run
WARNING/ALARM 12, Torque limit
with more than 100% overload for too long.
The torque has exceeded the value in
Troubleshooting parameter 4-16 Torque Limit Motor Mode or the value in
• Compare the output current shown on the LCP parameter 4-17 Torque Limit Generator Mode.
with the frequency converter rated current. Parameter 14-25 Trip Delay at Torque Limit can change this
• Compare the output current shown on the LCP warning from a warning-only condition to a warning
with measured motor current. followed by an alarm.
• Remove power to the frequency converter and WARNING/ALARM 28, Brake check failed
repair the short circuit. The brake resistor is not connected or not working.
WARNING/ALARM 34, communication fault The option is not Check if the product supports
6144
supported this option.
6 6 The fieldbus on the communication option card is not
working. 6400
The option
Remove the option.
combination error
ALARM 38, Internal fault
Power cycle the frequency
When an internal fault occurs, a code number is shown.
converter. If the alarm occurs
Other Other internal faults
Troubleshooting again, contact a Danfoss
See Table 6.4 for the causes and solutions for different supplier.
internal faults. If the fault persists, contact the Danfoss
supplier or service department for assistance. Table 6.4 Internal Fault List
ALARM 54, AMA motor too small WARNING/ALARM 65, Control card over temperature
The motor is too small for the AMA to operate. The cutout temperature of the control card has exceeded
the upper limit.
ALARM 55, AMA parameter out of range
The parameter values of the motor are outside of the Troubleshooting
acceptable range. The AMA does not run. • Check that the ambient operating temperature is
within the limits.
ALARM 56, AMA interrupted by user
The AMA is manually interrupted. • Check the fan operation.
ALARM 57, AMA internal fault • Check the control card.
Try to restart the AMA again. Repeated restarts can ALARM 67, Option module configuration has changed
overheat the motor. One or more options have either been added or removed
ALARM 58, Internal fault since the last power-down. Check that the configuration
Contact a Danfoss supplier. change is intentional and reset the unit.
WARNING 59, Current limit ALARM 68, Safe stop activated
The current is higher than the value in
parameter 4-18 Current Limit.
Safe Torque Off (STO) is activated. If STO is in manual
restart mode (default), to resume normal operation, apply
6 6
24 V DC to terminals 37 and 38 and initiate a reset signal
Troubleshooting
(via fieldbus, digital I/O, or [Reset]/[Off Reset] key). If STO is
• Ensure that motor data in parameters 1-20 to 1-25 in automatic restart mode, applying 24 V DC to terminals
is set correctly.
37 and 38 automatically resumes the frequency converter
• Possibly increase the current limit. to normal operation.
• Be sure that the system can operate safely at a ALARM 69, Power card temperaturePower card
higher limit. temperature
ALARM 60, External interlock The cutout temperature of the power card has exceeded
A digital input signal indicates a fault condition external to the upper limit.
the frequency converter. An external interlock has Troubleshooting
commanded the frequency converter to trip. • Check that the ambient operating temperature is
Troubleshooting within limits.
• Clear the external fault condition. • Check fan operation.
• To resume normal operation, apply 24 V DC to • Check the power card.
the terminal programmed for external interlock.
ALARM 80, Drive initialised to default value
• Reset the frequency converter. Parameter settings are initialized to default settings after a
WARNING/ALARM 61, Feedback error manual reset.
An error between calculated speed and speed Troubleshooting
measurement from feedback device. • To clear the alarm, reset the unit.
Troubleshooting WARNING 87, Auto DC-Braking
• Check the settings for warning/alarm/disabling in Occurs in IT mains when the frequency converter coasts,
parameter 4-30 Motor Feedback Loss Function. and the DC voltage is higher than 830 V for 400 V units
• Set the tolerable error in parameter 4-31 Motor and 425 V for 200 V units. The motor consumes energy on
Feedback Speed Error. the DC link. This function can be enabled/disabled in
parameter 0-07 Auto DC Braking.
• Set the tolerable feedback loss time in
parameter 4-32 Motor Feedback Loss Timeout. ALARM 88, Option detection
A new option configuration has been detected. Set
ALARM 63, Mechanical brake low
parameter 14-89 Option Detection to [1] Enable Option
The actual motor current has not exceeded the release
Change, and power cycle the frequency converter to
brake current within the start delay time window.
accept the new configuration.
ALARM 95, Broken belt
Torque is below the torque level set for no load, indicating
a broken belt. Parameter 22-60 Broken Belt Function is set
for alarm.
Troubleshooting
• Troubleshoot the system and reset the frequency
converter after clearing the fault.
D
J
Data readout........................................................................................ 108
Jog................................................................................................................ 4
DC brake current................................................................................... 45
DC brake cut-in speed........................................................................ 46
L
DC braking time.................................................................................... 45
LCP.................................................................................................. 4, 5, 149
Default setting............................................................................. 20, 125
LCP copy/save........................................................................................ 32
Digital Input............................................................................................ 57
Leakage current.................................................................................... 12
Discharge time...................................................................................... 11
LED.......................................................................................................... 149
Live zero................................................................................................... 71
E
Load compensation............................................................................. 33
Electrical wiring....................................................................................... 7
Load sharing................................................................................. 11, 102
Electronic thermal relay........................................................................ 5
Terminal 53
Terminal 53 filter time constant.................................................. 72
Terminal 53 high current............................................................... 71
Terminal 53 high voltage.............................................................. 71
Terminal 53 low current................................................................. 71
Terminal 53 low voltage................................................................ 71
Terminal 53 mode............................................................................ 72
Terminal 54
Terminal 54 filter time constant.................................................. 72
Terminal 54 high current............................................................... 72
Terminal 54 high voltage.............................................................. 72
Terminal 54 low current................................................................. 72
Terminal 54 low voltage................................................................ 72
Terminal 54 mode............................................................................ 72
Terminals
Control terminal............................................................................... 19
Input terminal................................................................................. 154
Thermal load................................................................................. 40, 109
Thermistor................................................................................................. 6
Timer......................................................................................................... 95
Torque
Limit.................................................................................................... 154
[%]....................................................................................................... 109
Trip................................................................................................................ 6
Trip condition...................................................................................... 149
Trip lock................................................................................................. 149
U
Unintended start......................................................................... 11, 102
V
Voltage imbalance............................................................................. 154
VVC+............................................................................................................ 6
W
Warning and alarm list..................................................................... 151
Warning current high.......................................................................... 56
Warning current low............................................................................ 56
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MG06C702*