SAIC-Q-1013 Rev 7 (Final)
SAIC-Q-1013 Rev 7 (Final)
SAIC-Q-1013 Rev 7 (Final)
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
FBE Reinforcing Steel, Embedded Items, and
Form Closure Inspection
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
Various
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
25/01/2018; 10:00 AM 25/01/2018; 10:00 AM SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT
REQUIRED?
SATIP-Q-001-02 MP 3.3
SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL YES
H H
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
All reinforcing steel and other embedded items/materials have been duly
received and documented prior to installation as per requirements of
Schedule Q, Att.
A1 SAIC-Q-1007 (FBE Rebar & Embedments Receiving Inspection), signed
IV, Sec. 3.3
copies of which are available during reinforcing steel installation
inspection
Anchor Bolts, Nuts & Washers for Structural Connections have been
duly received and documented prior to installation as per requirements
Schedule Q, Att.
A2 of SAIC-M-2021, (Receiving Inspection - Bolts, Nuts & Washers for
IV, Sec. 3.3
Structural Connections), signed copies of which are available during
anchor bolt installation inspection
Forms are inspected and checked before the reinforcing steel is placed
SAES-Q-001
B1 to the dimensions and locations on the structural plans.
Sec. 8.0
(ACI 347-04, Sec. 3.2.4.1)
Use of welded wire fabrics shall conform to SASO SSA 224, (cold drawn) SAES-Q-001
B4
wire with minimum yield strength of 422 Mpa (60.0 Ksi). Sec. 5.3
SAES-Q-001
B5 Galvanized welded wire fabric shall conform to ASTM A767.
Sec. 5.4
Coated wire and welded wire fabric used for reinforcement shall be SAES-Q-001
B7
fusion bonded epoxy in accordance with ASTM A884. Sec. 5.4
All field cut ends of rebar are coated with approved Epoxy Coating SAES-Q-001
B8
Material. (ASTM A775/ A775M-2007, Sec. 11.4) Sec. 5.6
Page 1 of 7
Damaged coated steel reinforcing bars are repaired with the approved SAES-Q-001
B9
patching material. (ASTM A 775/A 775M-07, Sec. 11.2) Sec. 5.6
Page 2 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13
SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED RFI NUMBER
NSH -
NBC-CIVIL-1396
FBE Reinforcing Steel, Embedded Items, and Form
SAIC-Q-1013 30-Apr-13 CIVIL-
Closure Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
The minimum concrete cover shall be measured from the outer most
rebar (tie bar), that shall be provided for reinforcement of cast-in-
place concrete structures as follows:
Table 2-Minimum Concrete Cover
Concrete Structure Minimum Cover (mm)
Concrete cast against and permanently
exposed to earth (including foundations
over a sub-slab) 75
Formed concrete exposed to earth or weather
Supporting Process Equipment 75
SAES-Q-001
B10 Buildings, walkway platforms, stairs, AC pads 50
Sec. 5.8
Concrete not exposed to weather nor in contact with
ground (which can be inspected from all sides):
Beams, Columns 50
Slabs, Walls, Joists 25
Concrete exposed to sea water, raw water or sewage 75
Between reinforcement and anchor flange/pipe within
pipeline anchor blocks 100
Concrete slab over 50 mm sub-slab 50
Reinforcing steel lap splice lengths for each bar size shall be as
B13 IFC Drawings
detailed for each size as shown on the IFC Drawings.
All wire bar supports, spacers, and tying wire shall be coated with
SAES-Q-001
B14 dielectric material, for example, an epoxy-coated or plastic coated
Sec. 5.6
material. (ASTM A 775/A 775M-2007, Appendix X1.3.13)
The diameter of reinforcing bar bends, other than stirrups or ties, for
SAES-Q-001
B17 sizes No. 29 through No. 36 shall be 8 bar diameters.
Sec. 5.6
(ACI 318-2011, Sec. 7.2.3, Table 7.2)
The diameter of reinforcing bar bends, other than stirrups or ties, for
SAES-Q-001
B18 sizes No. 43 through No. 57 shall be 10 bar diameters.
Sec. 5.6
(ACI 318-2011, Sec. 7.2.3, Table 7.2)
The inside diameter of bends for stirrups and ties shall be no less
than 4 bar diameter for sizes 5 and smaller, all other sizes shall be SAES-Q-001
B19
bent in accordance with items 16, 17 and 18 above. (ACI 318-2011, Sec. 5.6
Se. 7.2.2)
SAES-Q-001
B20 Welded wire fabric shall be located as shown on IFC Drawings.
Sec. 5.6
Page 3 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13
SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED RFI NUMBER
NSH -
NBC-CIVIL-1396
FBE Reinforcing Steel, Embedded Items, and Form
SAIC-Q-1013 30-Apr-13 CIVIL-
Closure Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
Anchor bolt set in a foundation pedestal should never extend below SAES-Q-005
C3
the bottom of the pedestal into the footing. Sec. 4.8.3
Minimum clear distance from anchor bolts or anchor bolt sleeves to SAES-Q-005
C4
edge of concrete shall be 100mm. Sec. 4.8.8
SAES-Q-005
C5 Metallic anchor bolt sleeves are not permitted.
Sec. 4.8.8
Anchor bolts and embedded items shall be set accurately, using SAES-Q-005
C10
templates. Sec. 4.8.2
The bottom of the anchor bolts are secured to prevent movement or SAES-Q-005
C11
tilting of the anchor bolts during concrete placement. Sec. 4.8.2.
Page 4 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13
SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED RFI NUMBER
NSH -
NBC-CIVIL-1396
FBE Reinforcing Steel, Embedded Items, and Form
SAIC-Q-1013 30-Apr-13 CIVIL-
Closure Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
The thread length required at the top of the anchor bolt must be
sufficient to accommodate two nuts and about ½ of the anchor bolt SASD AA-
C14
diameter projecting above the top nut. The thread length for Types 2 036322
& 3 anchor bolt is 4 bolt diameters.
The thread length required for Type 1 anchor bolt is as specified in SASD AA-
C15
Table 1 of SASD AA-036322, Rev.8. 036322
The spacing, embedment and edge distance of the anchor bolts SASD AA-
C16
shall comply with SASD AA-036322. 036322
Projecting steel items which are attached to the formwork and cast at
SAES-Q-001
C23 the concrete surface shall be either hot dip galvanized or coated with
Sec 6.3
a zinc rich epoxy primer (APCS 1C).
Conduits, pipes and other items made from aluminum shall not be
SAES-Q-001
C24 embedded in structural concrete unless effectively coated to prevent
Sec. 6.5
aluminum-concrete reaction.
Page 5 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13
SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED RFI NUMBER
NSH -
NBC-CIVIL-1396
FBE Reinforcing Steel, Embedded Items, and Form
SAIC-Q-1013 30-Apr-13 CIVIL-
Closure Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
Wedges used for final alignment before concrete placement shall be SAES-Q-001
D2
secured before placing concrete. (ACI 347-04, Sec. 3.6.1.2) Sec. 3.2
If needed, access holes in wall forms or other high, narrow forms are SAES-Q-001
D8
provided to facilitate concrete placement. (ACI 347-04, Sec. 3.2.1.7) Sec. 3.2
Page 6 of 7
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - March 2013) Rev 7 31-Mar-13
SAUDI ARAMCO INSPECTION CHECKLIST SAIC NUMBER DATE APPROVED RFI NUMBER
NSH -
NBC-CIVIL-1396
FBE Reinforcing Steel, Embedded Items, and Form
SAIC-Q-1013 30-Apr-13 CIVIL-
Closure Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM RE-INSP
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A
No. DATE
REMARKS:
REFERENCE DOCUMENTS:
1- SAES-Q-001 -- Criteria for Design and Construction of Concrete Structures, 15 May 2010
2- SAES-Q-005 -- Concrete Foundations, 28 January 2009
3- SASD AA - 036322 -- Anchor Bolt Details Rev. 8
4- Schedule Q
Contractor / Third-Party Saudi Aramco
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I
QC Record Reviewed Work Verified
Name, Initials and Witnessed
Name, Initials and Date: Mr. JOHN Date:
Mr. HORNDAOA
QC Inspector PID Representative
T&I
Performed Inspection Work / Rework May Proceed QC Record Reviewed Work Verified
Name, Initials and Witnessed
Name, Initials and Date:
Date:
Mr. RENJITH V R Mr. SAID AMEER
QC Supervisor Proponent and Others
T&I
Quality Record Approved: QC Record Reviewed Work Verified
Name, Organization, Witnessed
Name, Sign and Date:
Initials and Date:
Page 7 of 7