Protocol: Device ID: Baud Rate: Parity: Stop Bits: Addressing Convention Modbus Coils

The document describes Modbus communication parameters and data for monitoring diesel generators. It specifies a Modbus RTU protocol over serial communication with a device ID of 10, baud rate of 19200, no parity, and 1 stop bit. Modbus coils and holding registers are defined to provide read-only access to parameters like generator run status, power output, and frequency in various data formats like integers and floating point values.

Uploaded by

machineman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views2 pages

Protocol: Device ID: Baud Rate: Parity: Stop Bits: Addressing Convention Modbus Coils

The document describes Modbus communication parameters and data for monitoring diesel generators. It specifies a Modbus RTU protocol over serial communication with a device ID of 10, baud rate of 19200, no parity, and 1 stop bit. Modbus coils and holding registers are defined to provide read-only access to parameters like generator run status, power output, and frequency in various data formats like integers and floating point values.

Uploaded by

machineman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Modbus Communication Parameters

Protocol: Modbus RTU (Serial)


Device ID: 10
Baud rate: 19200
Parity: None
Stop bits: 1
Addressing 0
convention

Modbus Coils
Address Description Access
100 Start Request from Scrubber (from Network) R/W
101 Request Response / Start Permit R
102 Diesel Generator No1 RUN R
103 Diesel Generator No2 RUN R
104 Diesel Generator No3 RUN R

Modbus Holding Registers


Address Description Access Data Type Units Range
100 Request Response / Start Permit R Integer16 - 0 or 1
101 Diesel Generator No1 RUN R Integer16 - 0 or 1
102 Diesel Generator No2 RUN R Integer16 - 0 or 1
103 Diesel Generator No3 RUN R Integer16 - 0 or 1
104 Diesel Generator No1 Power (Raw Value) R Integer16 kW x 10 0..2000
105 Diesel Generator No2 Power (Raw Value) R Integer16 kW x 10 0..2000
106 Diesel Generator No3 Power (Raw Value) R Integer16 kW x 10 0..2000
107 Diesel Generator No1 Frequency (Raw Value) R Integer16 Hz x 10
108 Diesel Generator No2 Frequency (Raw Value) R Integer16 Hz x 10
109 Diesel Generator No3 Frequency (Raw Value) R Integer16 Hz x 10
110 Diesel Generator No1 Power R Float32 kW 0..1300
112 Diesel Generator No2 Power R Float32 kW 0..1300
114 Diesel Generator No2 Power R Float32 kW 0..1300
116 Diesel Generator No1 Frequency R Float32 Hz 42..70
118 Diesel Generator No2 Frequency R Float32 Hz 42..70
120 Diesel Generator No3 Frequency R Float32 Hz 42..70