This document performs a symmetrical fault analysis on a distribution system with the following key components:
- A 100 MVA transformer with a source impedance of 0.03+j0.99 pu
- Line impedances of 0.0112+j0.0268 pu for a 25kVA transformer and 0.0093+j0.00222 pu for cable C2
- Load impedances of 73.724+j27.221 pu for cable C1 and 17.58+j4.197 pu for cable C2
- A lumped motor impedance of 281.955+j1071.43 pu
The analysis calculates a fault current of 5.744 kA at the 0