Short Circuit Per Unit Method

This document performs a symmetrical fault analysis on a distribution system with the following key components: - A 100 MVA transformer with a source impedance of 0.03 + j0.99 pu - Line impedances of 0.0112 + j0.0268 pu and 17.58 + j4.197 pu - A lumped motor load modeled as an impedance of 281.955 + j1071.43 pu - The calculated fault current is 5.744 kA

Uploaded by

I'am Phil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views1 page

Short Circuit Per Unit Method

This document performs a symmetrical fault analysis on a distribution system with the following key components: - A 100 MVA transformer with a source impedance of 0.03 + j0.99 pu - Line impedances of 0.0112 + j0.0268 pu and 17.58 + j4.197 pu - A lumped motor load modeled as an impedance of 281.955 + j1071.43 pu - The calculated fault current is 5.744 kA

Uploaded by

I'am Phil
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SHORT CIRCUIT ANALYSIS - SYMMETRICAL FAULT

KVA Base = 100,000KVA E E


KV Base = 0.230KV
ASSUMED:
MVAsc = 100MVA
Zu = 100000
X/R = 30 100000 = 1 pu Z1 = Zu + Ztx + ZC1
Zth
X/R = 30; ɸ=88.09° Z1 = Zu + Ztx + ZC1
Zu = 0.03+j0.99 p.u. Z1 = 73.77 + j28.238 p.u. Z1 Z2 F1
Ztx = (%Z/100)(kVA Base/KVA-tx)
Ztx = 0.029 pu.; X/R = 2.4;∠67.38 Z2 = ZC2 + ZMU
25KVA,13.8KV-0.230KV
%Z = 2.6
R =0.0112 Z2 = 299.54 + j1075.62 p.u Z1 0.230kV, BUS
X/R = 2.4 X =0.0268
Ztx = 0.0112 + j0.0268 p.u. Zth = Z1 // Z2
Zth = 75.69∠24.07°
C1 C1 = 50mm2
50mm2 R of 50mm2 @ 100m = 0.039 Calculation for the fault current F1
100m
F1 X of 50mm2 @ 100m = 0.0144
1/ph Z = 0.039+j0.0144 F1 = MVA Base / (kV x Zth)
Convert to per unit impedance;
0.230kV, BUS ZC1 = 73.724+j27.221 p.u. F1 = 100/ 0.230 x 75.69
C2 F1 = 5.744kA
#2 AWG
C2
15m
R of #2 AWG @ 15m = 0.0093 USE: 10K AIC, CIRCUIT BREAKER
1/ph
X of #2 AWG @ 15m = 0.00222
LUMP SUM MOTORS Z = 0.0093+j0.00222 Z2
14KVA Convert to per unit impedance
M1 X"d =15% ZC2 = 17.58 + j4.197 p.u.
V=230V
X/R = 3.8 M1
NOTE: Xmu = (15/100)(100,000 14) = 1071.43 p.u.
Rmu = 281.955
M1 - LUMP SUM MOTORS
Zmu = 281.955 + j1071.43 p.u.

F SHORT CIRCUIT ANALYSIS & IMPEDANCE DIAGRAM


EE 01 SCALE NTS